Bulletin 700-P (10A), 700DC-P (10A), 700-PL (10A), 700-PT (10A), 700-PK (20A), 700DC-PK (20A),
700-PH (35A), 700DC-PH (35A), 700-CP1, 700-CPM, 700-CPR, 700-CPH
Industrial Control Relay and Accessory Installation Instructions
ATTENTION: To prevent electrical shock, disconnect from power source before installing or servicing. Install in suitable enclosure.
Keep free from contaminants.
It is necessary to adhere to the torque values listed for proper operation.
Relay Installation
6 - 45/64
Panel Mounting (170.10)
5 - 25/64
B (136.75)
2-1/4 AC
(57.2) 4 - 5/64
(103.43)
3 - 17/32
(89.7)
3 - 1/8
(79.4)
4-3/4
C Provision for 2 - #8 (M4) (120.49)
Mtg. Screws DC
6-1/16
(153.83)
7-3/8
(187.17)
2-1/4
(57.1)
1/2
(12.7)
in 2
(mm) #8 (M4)
14-20 lb-in
(1.6-2.3 N-m)
199-DR1
700-DRA CLICK
Wire Installation X
A4
X
A3 X Contact Arrangement and Markings
A2
X B4
E X
A1
X B3 X A1X A2X A3X A4X
X C4 K1
B2 3X 4 - Pole
X C
B1 X Relay
C2
X K2
C1 A1Y A2Y A3Y A4Y
B1X B2X B3X B4X
12 - Pole
Y
A4 Relay
3Y Y
Y
A B4 C1Y C2Y C3Y C4Y
A2 B3
Y Y
1Y Y C4
F
A B2 C3
Y
Y
B1 C2
Y
Y
C1
A
Contact Cartridges Cat. No. Contact Ratings
Continuous
Contact Ratings
Make / Break
600V AC 600V DC 600V AC 600V DC
8 -12 lb-in
Standard 700-CP1 Lt. Grey 10 A 5A NEMA NEMA
(.9 - 1.4 N-m) A600 P600
Overlap 700-CP11Z Black 10 A 5A NEMA NEMA
A600 P600
Master 700-CPM Lt. Grey 20 A 10 A (2) X NEMA (2) X NEMA
A600 P600
Tandem (2 Masters) 700-CPH Lt. Grey 35 A 20 A (2) X NEMA (2) X NEMA
A600 P600
Any combination of N.O. & N.C. ATTENTION: Do not install the logic reed cartridge in a relay, timer or latch unit that is located next to a
red cartridges must be used. Bulletin 700 Type R, RM, RTC sealed contact relay or other device with a strong magnrtic leakage field.
Do not use in Timers or Latches. As erratic contact action could result. Because the logic reeds require very little force to operate. At least
2 standard cartridges are required in the relay to provide maximum mechanical life.
Remove contact
3 cartridge.
7 Tighten terminal
screw(s).
Convert contacts
5 N.O. N.C.
7 - 14 lb-in
(.8 - 1.6 N-m)
14 - 18 lb-in
(1.6 - 2.0 N-m)
E 4 Loosen screw(s).
Install drive
Install contact 8 bar
6 cartridge.
#10 AWG
35A Jumper Kit Installation
7 - 14 lb-in
(.8 - 1.6 N-m)
ATTENTION: Both cartridges must be of the same configuration (N.O. or N.C.) (4 N.C. or 6 N.O.
Jumper Kits Maximum per AC or DC Relay) . If a kit is added to the third deck of an AC Relay, be
sure the enclosure is a 700-N31 Series B which has an electrical tape added inside the cover.
Because of a high inner barrier, Jumper Kits should be used on Series B 700-PT pneumatic timers.
2
18 - 25 lb-in
F (2.0 - 2.82 N-m)
#10 AWG
(2)
A
Adder Deck Installation
Install contact
B 4 cartridges
as required. 7 Install terminal shield.
Install cross bar
5 with longer drive
screw.
6 Install top
cover.
CLICK
CLICK
8 -12 lb-in
(.9 -1.4 N-m) 8 - 12 lb-in
(.9 - 1.4 N-m)
14 - 18 lb-in
(1.6 - 2.0 N-m)
Coil Replacement
8 - 12 lb-in
AC Coil (.9 - 1.4 N-m)
DC Coil
8 - 12 lb-in
(.9 - 1.4 N-m)
18 - 22 lb-in
(2.0 - 2.5 N-m) 18 - 22 lb-in
(2.0 - 2.5 N-m)
18 - 22 lb-in
(2.0 - 2.5 N-m)
18 - 22 lb-in
(2.0 - 2.5 N-m) 18 - 22 lb-in 18 - 22 lb-in
(2.0 - 2.5 N-m) (2.0 - 2.5 N-m)
CLICK
A
Latch Attachment Contact
Cartridges Reconfiguration
8 - 12 lb-in
(.9 - 1.4 N-m)
B
Install contact
4 cartridge.
1 Remove cover.
Remove terminal
1 covers.
Remove crossbar
1 screw.
D
8 - 12 lb-in
(.9 - 1.4 N-m)
OFF Delay
8 - 12 lb-in
(.9 - 1.4 N-m)
1 Remove cover.
4
Install contact
cartridge.
F
PN-15096