Earthing Transformer is for connecting to 22kV, 3 phase 3 wire, 1250 Amp, Isc-25kA.
22kV bus Upstream is connected to 40MVA 230/22kV YNd1 Transformer.
Maximum line fault current is 400 Amp for 30 Sec.
Ig= 400; %A
t= 30; %seg
V=22000; %V zigzag