DV-5a Automatic Water Control Valve


Deluge Fire Protection Systems
1-1/2 Inch to 8 Inch (DN40 to DN200)
General
Description
The TYCO DV-5 a Automatic Water
Control Valves are diaphragm type
valves that can be used in deluge fire
protection systems. When properly
trimmed, the double seat design of the
DV-5a Valve also provides actuation of
fire alarms upon system operation.
The diaphragm style design of the
DV-5a Valve allows external resetting,
providing for easy resetting of a deluge
system without having to open a valve
handhole cover to manually reposition
a clapper and/or latch mechanism.
Simply re-pressurizing the diaphragm
chamber resets the valve.
The DV-5a features internal and exter-
nal coating of the valve to provide
corrosion resistance. The external cor-
rosion resistance of the epoxy coating
permits the use of the DV-5a in cor- Available End Connections and Weights — lb/(kg)
rosive atmospheres associated with
many types of industrial processing Nominal Valve Size
plants and outdoor installations. End Connection ANSI Inches
The DV-5a Valves are offered with the (DN)
DV-5a Valve and separately ordered 1-1/2 2 3 4 6 8
Inlet Outlet
semi-assembled trim shown in Figures (40) (50) (80) (100) (150) (200)
7, 8, and 9, or, for ease of installa- 26 25
tion, with the DV-5a Valve completely Thread Thread N/A N/A N/A N/A
(11,8) (11,3)
trimmed with or without a System Main
Control Valve. 25 25 60 95 177 327
Groove Groove (11,3) (11,3) (27,2) (43,1) (80,3) (148,3)
NOTICE Flange Groove N/A N/A 66 106 190 346
(30,0) (48,1) (86,2) (157,0)
The DV-5 a Valves described herein
must be installed and maintained in Flange Flange N/A N/A 72 116 204 365
compliance with this document, as (32,7) (52,6) (92,5) (165,6)
well as with the applicable standards
of the NATIONAL FIRE PROTECTION The owner is responsible for main-
ASSOCIATION (NFPA), in addition to taining their fire protection system
the standards of any other authorities and devices in proper operating con-
having jurisdiction. Failure to do so dition. Contact the installing contrac-
may impair the performance of these tor or product manufacturer with any
devices. questions.

IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.

Page 1 of 34 MARCH 2020 TFP1306


TFP1306
Page 2 of 34

Nominal Valve Size ANSI Inch (DN)


Item Description Qty. 1-1/2 (DN40) 2 (DN50) 3 (DN80) 4 (DN100) 6 (DN150) 8 (DN200)
P/N P/N P/N P/N P/N P/N
1 Valve Body 1 N/R N/R N/R N/R N/R N/R
2 Diaphragm 1 545000020 545000020 545000030 545000040 545000060 545000080
3 Diaphragm Cover 1 N/R N/R N/R N/R N/R N/R
4 Hex Bolt, Short 2a 545100001 545100001 545100002 545100003 545100004 545100003
5 Hex Bolt, Long 2 545100011 545100011 545100012 545100013 545100014 545100015
6 Lift Washer 2 b
N/A N/A 545100021 545100022 545100023 545100022
7 Hex Nut 2 545100031 545100031 545100032 545100033 545100034 545100033
8 Hoist Ring 2 545100041 545100041 545100041 545100041 545100041 545100041
9 Flat Washer 2 N/A N/A 545100024 545100025 545100026 545100025
NOTES: c. N/R = Not Replaceable
a. Hex Bolt, Short, Qty. 6 in 6 and 8 inch (DN150 and DN200) assemblies d. Order replacements parts only via Part Numbers given, do not replace
b. Lift Washer not used in 1-1/2 and 2 inch (DN40 and DN50) assemblies Hex Bolt, Hex Nut, Lift Washer or Hoist Ring with common hardware parts

1
1
3
2
7 5
5 3 1-1/2 AND 2 INCH
9 VALVES ONLY
6

3
7 1
4
8

6
4
9 7 5
6 AND 8 INCH
1 2
VALVES ONLY
FIGURE 1
DV-5 a VALVE ASSEMBLY AND REPLACEMENT PARTS

Flange Drilling Specification Dim. A


Nominal Bolt Circle
Valve Nominal Dimensions in Inches and (mm) Diameter
Size
ANSI ANSI B16.1a ISO 7005-2 JIS B 2210 AS 2129 Dim. B
Inches (Class 125) (PN16)b (10K) (Table E)
(DN) Bolt Hole
Diameter
A B N A B N A B N A B N

3 6.00 0.75 6.30 0.75 5.90 0.59 5.75 0.71 Qty. N


4 (160,0) 8 (150,0) 8 (146,0) 4 Number of
(80) (152,4) (19,0) (19,0) (15,0) (18,0)
Bolt Holes
4 7.50 0.75 7.09 0.75 6.89 0.60 7.00 0.71
8 (180,0) 8 (175,0) 8 178,0) 8
(100) (190,5) (19,0) (19,0) (15,0) (18,0) NOTES:
a. Same drilling as for
6 9.50 0.88 9.45 0.91 9.45 0.75 9.25 0.87 ANSI B16.5 (Class 150) and
8 (240,0) 8 (240,0) 8 (235,0) 8
(150) (241,3) (22,2) (23,0) (19,0) (22,0) ANSI B16.42 (Class 150)
b. Same drilling as for
8 11.75 0.88 11.61 0.91 12 11.42 0.75 12 11.50 0.87
8 (295,0) 8 BS 4504 Section 3.2 (PN16)
(200) (298,5) (22,2) (23,0) (290,0) (19,0) (292,0) (22,0)
and DIN 2532 (PN16)
TABLE A
FLANGE DRILLING SPECIFICATIONS
TFP1306
Page 3 of 34

Port Sizes, NPT Inch per ANSI B1.20.1


Port Port Description 1-1/2 2 3 4 6 8
(DN40) (DN50) (DN80) (DN100) (DN150) (DN200)
P1 Diaphragm Chamber Supply 1/2 1/2 1/2 1/2 1/2 1/2
P2 Water Supply Pressure & Alarm Test 1/2 1/2 1/2 1/2 1/2 1/2
P3 Alarm Actuation 3/4 3/4 3/4 3/4 3/4 3/4
P4 Automatic Drain Valve 1/2 1/2 1/2 1/2 1/2 1/2
P5 System Drain 3/4 3/4 3/4 3/4 3/4 3/4
P6 Main Drain 3/4 3/4 1-1/4 2 2 2
P7 System Air Supply Not Used for Deluge 1/2 1/2 1/2 1/2 1/2 1/2
SYSTEM OPEN TO ATMOSPHERE WATERFLOW TO SYSTEM

VALVE AIR SUPPLY


WATERWAY PLUGGED FOR
DIAPHRAGM DELUGE SYSTEMS
SEAT
VALVE
WATERWAY ALARM PORT
DIAPHRAGM WATERFLOW
CHAMBER TO ALARM
DIAPHRAGM
CHAMBER
OPEN TO
AUTOMATIC ATMOSPHERE
DRAIN VALVE AUTOMATIC
OPEN TO DRAIN VALVE
DIAPHRAGM
DIAPHRAGM ATMOSPHERE CLOSED
RETRACTS
CHAMBER
OPENING
SUPPLY
VALVE
FROM
WATERWAY
UPSTREAM WATER SUPPLY
SIDE OF PRESSURE &
SHUT-OFF ALARM TEST
VALVE
WATER SUPPLY WATERFLOW FROM WATER SUPPLY
FIGURE 2A FIGURE 2B
SET CONDITION OPERATED CONDITION

DRAIN FROM SYSTEM RESIDUAL DRAIN FROM SYSTEM

VALVE
WATERWAY
DIAPHRAGM
SEAT

VALVE DIAPHRAGM
WATERWAY AUTOMATICALLY
SYSTEM FLEXES TO SYSTEM
DRAIN ITS SEATED DRAIN
DIAPHRAGM OPEN OPEN
CHAMBER POSTION
OPEN TO
ATMOSPHERE

DIAPHRAGM
CHAMBER
SUPPLY
FROM
UPSTREAM
MAIN SIDE OF MAIN
DRAIN SHUT-OFF DRAIN
OPEN VALVE CLOSED
WATER SUPPLY SHUT OFF WATER SUPPLY SHUT OFF
FIGURE 2C FIGURE 2D
SYSTEM DRAIN CONDITION RESIDUAL DRAIN CONDITION
FIGURE 2
DV-5 a VALVE OPERATION, DELUGE SYSTEMS
TFP1306
Page 4 of 34

DIMENSIONS SHOWN
ARE APPLICABLE TO
Technical Pressure Loss
Refer to Graph A
ALL END CONNECTION
CONFIGURATIONS Data Detection System
Refer to subsections Wet Pilot Actua-
AVAILABLE PER Approvals tion, Dry Pilot Actuation, or Electric
VALVE SIZE UL and C-UL Listed Actuation, as necessary.
FM Approved

10-3/16"
VdS Approved*
LPCB Approved Materials of
(260 mm) Listings and Approvals are based
on DV-5 a Valve being trimmed as
Construction
described in Figures 7, 8, and 9 (i.e., Valve Body
Wet Pilot, Dry Pilot, and Electric Epoxy coated ductile iron per ASTM
1-1/2 Inch (DN40)
Actuation). A536-77, Grade 65-45-12
For local EMEA regional approvals, Diaphragm Cover
consult with your local distributor. Epoxy coated ductile iron per ASTM
* VdS approval is additionally based on installing the VdS
A536-77, Grade 65-45-12
10-3/16" required column prevention drain components provided
(260 mm) with assemblies per Table J in the Ordering Procedure
Diaphragm
section. Polyester fabric reinforced, TEFLON
coated, EPDM rubber per ASTM D2000
DV-5A Valve
2 Inch (DN50) Components for the 1-1/2 in. to 8 in. Diaphragm Cover Fasteners
(DN40 to DN200) DV-5a Valves are Aluminum zinc coated steel
shown in Figure 1. The DV-5a Valves Common Hardware Trim
are for vertical installations. They are • Common hardware pipe fittings are
rated for use at a service pressures of galvanized or black as required and
13-3/4" 20 psi to 300 psi (1,4 bar to 20,7 bar). are malleable per ASME B16.3.
(349 mm) The take-out dimensions are shown • Common hardware pipe nipples are
in Figure 3, and the flanged connec- galvanized or black as required and
tions are available drilled per ANSI, ISO, are Schedule 40 per ASTM A53 or
AS, and JIS specifications (Ref. Table A135.
3 Inch (DN80) A). Threaded inlet and port connec-
tions are available in NPT or ISO 7/1. • Common hardware compression
Threaded port connections are NPT fittings are brass per ASTM B16.
threaded. • Common hardware tubing is Type L
NOTE: PN16 flanges are pressure rated copper per ASTM B88.
16-3/4" to 16 bar.
(425 mm)
Valve Trim Operation
The maximum pressure rating is as
follows: The TYCO DV-5a Valve is a diaphragm
style valve that depends upon water
4 Inch (DN100) • Wet Pilot Actuation Trim is 300 psi pressure in the Diaphragm Chamber
(20,7 bar) (Ref. Figure 2A) to hold the Diaphragm
• Dry Pilot Actuation Trim is 250 psi closed against the water supply
(17,2 bar) pressure.
• Electric Actuation Trim is dependent When the DV-5a Valve is set for service,
on separately ordered solenoid the Diaphragm Chamber is pressurized
22-3/8" valve per Technical Data Sheet through the trim connections from the
(569 mm) TFP2180 inlet side of the system’s main control
valve.
When the system pressure is greater
than 175 psi (12,1 bar), provision is to be Opening an actuation device, for
6 Inch (DN150) made to replace the standard order 300 example the solenoid valve in the
psi (20,7 bar) Water Pressure Gauges Electric Actuation Trim (Ref. Figure 6),
with separately ordered 600 psi trips the Model MRA-1 Manual Reset
(41,4 bar) Water Pressure Gauges. Actuator. Tripping the MRA-1 releases
water from the DV-5 a Diaphragm
If the addition of an Alarm Control Valve Chamber faster than it can be replen-
is desired or required by the local AHJ, ished through a 1/8 in. (3,2 mm) restric-
27-7/16" the Alarm Control Valve noted as Item H tion located in the diaphragm chamber
(697 mm) in Figures 16, 17, and 18 is to be a sepa- supply connection. Release of water
rately ordered electronically supervised through the MRA-1 results in a rapid
normally open valve. pressure loss in the DV-5a Diaphragm
External trim connections are NPT Chamber. The force differential applied
8 Inch (DN200) threaded. EMEA trim is provided with through the Diaphragm to hold the
NPT x ISO 7/1 thread adapters. Diaphragm in the set position is then
FIGURE 3
reduced below the valve trip point. The
DV-5 a VALVE
water supply pressure then forces the
TAKE-OUT DIMENSIONS
TFP1306
Page 5 of 34

FLOW RATE IN LITERS PER MINUTE (LPM)


(1 GPM = 3,785 LPM)
200 400 600 1000 2000 3000 5000 7000 10000 15000
9.0 0,600
8.0
7.0 0,500
NOMINAL PRESSURE DROP IN POUNDS PER SQUARE INCH (PSI)

6.0 0,400
5.0
0,300
)
40

4.0
DN
H(

NOMINAL PRESSURE DROP IN BAR


INC

)
3.0 50
0,200
DN
/2
1-1

H(

(1 PSI = 0,06895 BAR)


)
80
NC

DN
2I

2.0
H(

0)
NC

10
DN
3I

0,100
H(

0)
NC 0,090

15
0,080

DN
4I

H(

0)
1.0 0,070

20
NC
0.9

DN
0,060
0.8 6I

H(
0,050

NC
0.7

8I
0.6 0,040
0.5
0,030
0.4

0,022
0.3
50 100 200 400 600 1000 2000 3000 4000
FLOW RATE IN GALLONS PER MINUTE (GPM)
GRAPH A
DV-5 a VALVE
NOMINAL PRESSURE LOSS VERSUS FLOW

Diaphragm open permitting water to Refer to the following three sections for
flow into the system piping, as well as additional information regarding actua-
through the Alarm Port to actuate the tion options:
system alarms (Ref. Figure 2B). • Wet Pilot Actuation
Upon opening of the DV-5a Valve, the • Dry Pilot Actuation
Model MRA-1 Manual Reset Actuator,
which is described in Technical Data • Electric Actuation
Sheet TFP1387, opens to constantly
vent the DV-5a Diaphragm Chamber
to hydraulically latch the DV-5a in the
tripped position until manually reset.
TFP1306
Page 6 of 34

SYSTEM PIPING WITH OPEN NOZZLES OR SPRINKLERS - NORMALLY DRY INSPECTOR'S


TEST CONNECTION
(AT MOST HYDRAULICALLY
DEMANDING LOCATION OF
WET PILOT LINE)

REMOTE
WET PILOT SPRINKLER MANUAL
DETECTION SYSTEM CONTROL
(MINIMUM 1/2" PIPE AND DRAIN STATION DRAIN
AUTOMATIC SPRINKLERS) (WHEN
SPECIFIED)

WATERFLOW SYSTEM DRAIN VALVE


DV-5A (NORMALLY CLOSED)
PRESSURE VALVE
ALARM
SWITCH MAIN
DRAIN VALVE
DIAPHRAGM CHAMBER (NORMALLY
DRAIN CLOSED)
PRESSURE GAUGE

LOCAL
RESTRICTION DRAIN MANUAL
DRAIN CONTROL
MANUAL RESET WATER SUPPLY STATION DRAIN
ACTUATOR PRESSURE
GAUGE MAIN
DIAPHRAGM CONTROL VALVE
CHAMBER SUPPLY (NORMALLY
CONTROL VALVE WATER SUPPLY SHUT-OFF DIAPHRAGM CHAMBER WATER OPEN)
(NORMALLY OPEN) (NORMALLY OPEN) SUPPLY CONNECTION SUPPLY
FIGURE 4
DV-5 a VALVE
DELUGE WET PILOT ACTUATION SCHEMATIC DIAGRAM

Wet Pilot Pilot sprinklers are to be minimum


5.6 K-factor (80 K-factor) orifice
Provision must be made for install-
ing a 5.6 K-factor (80 K-factor) orifice,
Actuation approved automatic sprinklers. Manual
Control Stations are to be the Model
Inspector’s Test Connection at the
most hydraulically demanding location
The Wet Pilot Actuation Trim forms a MC-1 described in Technical Data of a wet pilot line (usually adjacent to
part of the laboratory approval of the Sheet TFP1382. the highest and most remote wet pilot
DV-5a Valves and is necessary for their sprinkler or manual control station).
The maximum height of a wet pilot
proper operation. line above the DV-5a Valve must not NOTES: Wet Pilot Lines must be main-
With Reference to Figure 4, the Wet exceed the limitations shown in Table tained at a minimum temperature of
Pilot Actuation Trim provides for con- B as a function of the minimum water 40°F (4°C).
nection of a detection system consist- supply pressure to the DV-5a Valve for At a minimum, it is recommended that
ing of wet pilot line sprinklers (heat an equivalent length (pipe plus fittings) internally galvanized pipe and fittings
detectors) and manual control sta- of the pilot line up to 500 ft (150 meters) be used for wet pilot lines.
tions interconnected with minimum to the most remote pilot sprinkler.
1/2 in. (DN15) steel pipe. The pilot
line is connected to the Wet Pilot Line
Connection.
Dimensions are provided in Figure 13.
TFP1306
Page 7 of 34

SYSTEM PIPING WITH OPEN NOZZLES OR SPRINKLERS - NORMALLY DRY INSPECTOR'S


TEST CONNECTION
(AT MOST REMOTE
LOCATION FROM
DV-5A VALVE)

LOW REMOTE
PRESSURE DRY PILOT SPRINKLER MANUAL
ALARM DRY PILOT DETECTION SYSTEM CONTROL
SWITCH ACTUATOR (MINIMUM 1/2" PIPE AND DRAIN STATION DRAIN
AUTOMATIC SPRINKLERS) (WHEN
SPECIFIED)

DRAIN SYSTEM DRAIN VALVE


WATERFLOW DV-5A
PRESSURE (NORMALLY CLOSED)
VALVE
ALARM
AUTOMATIC SWITCH MAIN
AIR/NITROGEN
DRAIN VALVE
MAINTENANCE
DIAPHRAGM CHAMBER (NORMALLY
DEVICE DRAIN
PRESSURE GAUGE CLOSED)

LOCAL
RESTRICTION DRAIN MANUAL
DRAIN CONTROL
MANUAL RESET WATER SUPPLY STATION DRAIN
ACTUATOR PRESSURE
GAUGE MAIN
DIAPHRAGM CONTROL VALVE
CHAMBER SUPPLY (NORMALLY
CONTROL VALVE WATER SUPPLY SHUT-OFF DIAPHRAGM CHAMBER WATER OPEN)
(NORMALLY OPEN) (NORMALLY OPEN) SUPPLY CONNECTION SUPPLY
FIGURE 5
DV-5 a VALVE
DELUGE DRY PILOT ACTUATION SCHEMATIC DIAGRAM

Dry Pilot The Dry Pilot Actuation Trim is pro-


vided with a Model DP-1 Dry Pilot
Supervision of the pressure in the dry
pilot actuation system and an alarm
Actuation Actuator, which is described in Tech-
nical Data Sheet TFP1380. The Actua-
that separately indicates operation of
the detection system is provided by
The Dry Pilot Actuation Trim forms a tor is rated for use at a maximum pilot a low pressure alarm switch set as
part of the laboratory approval of the service pressure of 50 psi (3,4 bar) and follows:
DV-5a Valves and is necessary for their a maximum water supply service pres- • Low pressure alarm setting at
proper operation. sure of 250 psi (17,2 bar). approximately 6 psi (0,4 bar) below
With reference to Figure 5, the Dry Pilot Graph B shows the minimum pilot line the minimum pilot line service pres-
Actuation Trim provides for installation service pressure as a function of the sure requirement shown in Graph B
of a detection system consisting of pilot water supply pressure. The pressure in • Fire alarm setting at approximately
sprinklers (heat detectors) and manual the dry pilot actuation system must be 15 psi (1,0 bar) below the minimum
control stations interconnected with automatically maintained using one of pilot line service pressure require-
a minimum length of 56 ft (17,1 m) of the following maintenance devices, as ment shown in Graph B
1/2 in. (DN15) steel pipe equivalent to appropriate:
The Pressure Relief Valve provided
207 in.3 (3400 cm3). The dry pilot line, • Model AMD-1 Air Maintenance in the trim is factory set to relieve
which is to be pressurized with air or Device (pressure reducing type), refer at a pressure of approximately
nitrogen, is connected to the Dry Pilot to Technical Data Sheet TFP1221 45 psi (3,1 bar); however, it may be
Line Connection.
• Model AMD-2 Air Maintenance field adjusted to a lower pressure, if
Dimensions are provided in Figure 14. Device (compressor control type), required.
Pilot sprinklers are to be minimum 5.6 refer to Technical Data Sheet The dry pilot line is to be provided with
K-factor (80 K-factor) orifice approved TFP1231 low point drains to enable draining of
automatic sprinklers. Manual Control • Model AMD-3 Nitrogen Maintenance condensate.
Stations are to be the Model MC-1 Device (high pressure reducing NOTE: At a minimum, it is recom-
described in Technical Data Sheet type), refer to Technical Data Sheet mended that internally galvanized pipe
TFP1382. TFP1241 and cast iron fittings be used for dry
Provision must be made for installing pilot lines.
a 5.6 K-factor (80 K-factor) Inspector's
Test Connection at the most remote
location on the dry pilot line.
TFP1306
Page 8 of 34

SYSTEM PIPING WITH OPEN NOZZLES OR SPRINKLERS - NORMALLY DRY

ELECTRIC DETECTION SYSTEM


(TYPICALLY 24 VOLTS DC)
HEAT DETECTORS, SMOKE DETECTORS,
MANUAL PULL STATIONS, ETC.
DELUGE VALVE SOLENOID
RELEASING PANEL VALVE
(AUTOMATIC (TYPICALLY
CONTROL UNIT 24 VOLTS DC)
WITH BATTERY
BACK-UP)
WATERFLOW SYSTEM DRAIN VALVE
DV-5A DRAIN (NORMALLY CLOSED)
PRESSURE VALVE
POWER ALARM
SUPPLY SWITCH MAIN
(TYPICALLY DRAIN VALVE
120 VOLTS AC) DIAPHRAGM CHAMBER (NORMALLY
DRAIN CLOSED)
PRESSURE GAUGE

LOCAL
RESTRICTION DRAIN MANUAL
DRAIN CONTROL
MANUAL RESET WATER SUPPLY STATION DRAIN
ACTUATOR PRESSURE
GAUGE MAIN
DIAPHRAGM CONTROL VALVE
CHAMBER SUPPLY (NORMALLY
CONTROL VALVE WATER SUPPLY SHUT-OFF DIAPHRAGM CHAMBER WATER OPEN)
(NORMALLY OPEN) (NORMALLY OPEN) SUPPLY CONNECTION SUPPLY
FIGURE 6
DV-5 a VALVE
DELUGE ELECTRIC ACTUATION SCHEMATIC DIAGRAM

Electric NOTES: The normally closed, de-


energized, Solenoid Valve is separately
to energize the Solenoid Valve to
open. After the ten minute duration, at
Actuation ordered and selected based on the
required laboratory approval accept-
which point should the Solenoid Valve
become de-energized and close (espe-
The Electric Actuation Trim forms a part able to the authority having jurisdiction. cially while operating under battery
of the laboratory approval of the DV-5a Refer to Technical Data Sheet TFP2180 back-up), the MRA-1 will have already
Valves and is necessary for their proper for specific laboratory approvals. automatically opened, thereby pre-
operation. venting the DV-5a Diaphragm Chamber
Consult with the applicable standards
from becoming re-pressurized, and
The Electric Actuation Trim is required of the Approval agency regarding
preventing an inadvertent closing of
for electric operation of the DV-5a Valve installation criteria pertaining to elec-
tric actuation circuitry. the DV-5a during a fire event.
by a detection system consisting of
electrical devices such as heat sen- Due to the functionality of the Model
sitive thermostats, smoke detectors, MRA-1 Manual Reset Actuator, the
and/or electric manual pull stations as release circuit of the releasing panel
shown in Figure 6. need only provide the typical ten
Dimensions are provided in Figure 15. minutes of alarm condition intended
TFP1306
Page 9 of 34

45 NOTES:
URE The dew point of the pilot line air pressure must be maintained
IR PRESS below the lowest ambient temperature to which the dry pilot
EM A
AIR PRESSURE IN PSI

YST actuation system will be exposed. Accumulation of water in the


UM S
30 MINIM pilot line connection to the Actuator will lower the air pressure
at which the actuator will open and possibly prevent proper
SURE
ING PRES operation. Also, introduction of moisture into the pilot lines
OPEN exposed to freezing temperatures can create an ice buildup
TOR
CTUA that could prevent proper operation of the Actuator.
15 E OF A
RANG An air dryer must be installed where the moisture content
of the air supply is not properly controlled at less than the
required value.
0 It is recommended that an AMD-3 Nitrogen Maintenance
Device be utilized in dry pilot actuation system applications
20 60 100 140 180 200 250
where the dew point must be maintained below -20°F (-29°C).
Refer to Technical Data Sheet TFP1241.
WATER SUPPLY PRESSURE IN PSI
GRAPH B
DV-5 a VALVE
DRY PILOT LINE AIR PRESSURE REQUIREMENTS

Maximum Pilot Height 2


Supply Pressure Feet
psi (Meters)
(bar)1 1-1/2 2 3 4 6 8
(DN40) (DN50) (DN80) (DN100) (DN150) (DN200)
20 13 13 4 9 12 15
(1,4) (4) (4) (1) (3) (4) (5)
40 34 34 29 33 27 23
(2,8) (10) (10) (9) (10) (8) (7)
60 55 55 54 57 42 31
(4,1) (17) (17) (16) (17) (13) (9)
80 76 76 79 81 57 39
(5,5) (23) (23) (24) (25) (17) (12)
100 97 97 103 105 73 46
(6,9) (30) (30) (31) (32) (22) (14)
120 118 118 128 129 88 54
(8,3) (36) (36) (39) (39) (27) (16)
140 139 139 153 153 103 62
(9,7) (42) (42) (47) (47) (31) (19)
160 160 160 178 177 118 70
(11,0) (49) (49) (54) (54) (36) (21)
175 172 172 188 195 131 75
(12,1) (52) (52) (57) (59) (40) (23)
200 201 201 203 224 152 84
(13,8) (61) (61) (62) (68) (48) (26)
225 226 226 219 254 173 92
(15,5) (69) (69) (67) (77) (53) (28)
250 252 252 235 284 195 100
(17,2) (77) (77) (72) (87) (59) (30)
275 277 277 247 308 212 107
(19,0) (84) (84) (75) (94) (65) (33)
300 303 303 266 347 237 124
(20,7) (92) (92) (81) (106) (72) (38)
Notes:
1. If supply pressure is variable, assume minimum expected value.
2. Maximum pilot height for up to 500 ft (150 m) of equivalent length of pilot line (pipe plus fittings).
3. Interpolation between data points is permitted.

TABLE B
DV-5A VALVE
WET PILOT DESIGN CRITERIA FOR UP TO
500 FEET (150 METERS) OF EQUIVALENT LENGTH OF 1/2 INCH (DN15) PILOT LINE
(PIPE PLUS FITTINGS)
TFP1306
Page 10 of 34

Installation The DV-5a Valve is to be installed in


accordance with the following criteria:
Step 9. An Air Maintenance Device,
as described in the Dry Pilot Actuation
The TYCO DV-5a Valve is to be installed section, must be provided for Dry Pilot
Step 1. All nipples, fittings, and devices
in accordance with this section. Actuation.
must be clean and free of scale and
burrs before installation. Use pipe Step 10. A desiccant dryer, when
NOTICE thread sealant sparingly on male pipe specified for Dry Pilot Actuation, is to
threads only. be installed between a drip leg and the
DV-5A Automatic Water Control Valves
Air Maintenance Device.
are designed to be used in freshwa- Step 2. The DV-5a Valve must be
ter systems. When the supply is from trimmed in accordance with one of the Step 11. The Low Pressure Alarm
an alternative source such as brackish trim illustrations shown in Figures 7, 8, Switch for Dry Pilot Actuation is to be
water, saltwater, or contains additives and 9, as applicable. adjusted as follows:
such as foam, the limited warranty is Note: If the addition of an Alarm Control • Low pressure alarm setting at
reduced to one year from the time of Valve is desired or required by the local approximately 6 psi (0,4 bar) below
installation. An increase in frequency of AHJ, the Alarm Control Valve noted as the minimum pilot line service pres-
inspections is required when the valve Item H in Figures 16, 17, and 18 is to sure requirement shown in Graph B
is exposed to such supplies and other be a separately ordered electronically
corrosive conditions or chemicals that • Fire alarm setting at approximately
supervised normally open valve.
could impact valve materials or the 15 psi (1,0 bar) below the minimum
operation of the assembly. The system Step 3. Care must be taken to ensure pilot line service pressure require-
and all components must be designed that check valves, strainers, globe ment shown in Graph B
accordingly for the increased demand. valves, etc. are installed with the flow Step 12. Unused Pressure Alarm
It is required to thoroughly flush the arrows in the proper direction. Switch connections must be plugged.
valve and trim assembly with freshwa- Step 4. Drain tubing to the Drip Funnel
ter and reset to the set condition after Step 13. The Pressure Relief Valve pro-
must be installed with smooth bends
each operation. vided with the Dry Pilot Actuation Trim
that will not restrict flow. is factory set to relieve at a pressure
Proper operation of the DV-5a Valves Step 5. The Main Drain and Drip Funnel of approximately 45 psi (3,1 bar), which
depends upon their trim being installed Drain may be interconnected provided can typically be used for a maximum
in accordance with the instructions a check valve is located at least 12 in. dry pilot actuation system pressure of
given in this technical data sheet. (300 mm) below the Drip Funnel. 40 psi (2,8 bar). The Pressure Relief
Failure to follow the appropriate trim Valve may be reset; however, it must
diagram may prevent the DV-5a Valve Step 6. Suitable provision must be
be reset to relieve at a pressure which
from functioning properly, as well as made for disposal of drain water. Drain-
is in accordance with the requirements
void approvals and the manufacturer’s age water must be directed such that
of the authority having jurisdiction.
warranties. it will not cause accidental damage to
property or danger to persons. To reset the Pressure Relief Valve, first
The DV-5a Valve must be installed in a loosen the jam nut and then adjust the
readily visible and accessible location. Step 7. Connect the Diaphragm Supply
cap accordingly, clockwise for a higher
Valve to the inlet side of the System
The DV-5a Valve, associated trim, and pressure setting or counter clockwise
Main Control Valve in order to facili-
wet pilot lines must be maintained at for a lower pressure setting. After ver-
tate setting of the DV-5a Valve. Refer
a minimum temperature of 40°F (4°C). ifying the desired pressure setting,
to Figures 16, 17, and 18 as applicable.
tighten the jam nut.
Heat tracing of the DV-5a Valve or its Step 8. An Inspector’s Test Connec-
associated trim is not permitted. Heat Step 14. Conduit and electrical con-
tion, as described in the Wet Pilot Actu-
tracing can result in the formation of nections are to be made in accordance
ation and Dry Pilot Actuation sections,
hardened mineral deposits that are with the applicable standards of the
must be provided for Wet or Dry Pilot
capable of preventing proper operation. approval agency.
Actuation systems.
Always open the system control valves Step 15. Before a system hydrostatic
slowly to avoid a sudden rush of water test is performed, the DV-5a Diaphragm
entering the system. Chamber is to be depressurized, the
Automatic Drain Valve is to be tem-
porarily replaced with a plug, and the
Diaphragm Cover Bolts must be uni-
formly and securely tightened using a
cross-draw sequence. After tighten-
ing, double-check to make certain that
all of the Diaphragm Cover Bolts are
securely tightened. Refer to Table C in
the Care and Maintenance section for
torque specifications.
TFP1306
Page 11 of 34

D
C

F
P4 E
P7
A2
A
P5

C2 C4 P6
C6
H P3 A1
J C3
B
P1 C5
P2
G
A4
K
A3

A4 C1

A5 Assemble in order
1-1/2" (DN40) AND 2" (DN50)
VALVES ONLY
from A to K
A6

A8
A7

Notes:
1. Port Connections P1 through P7 are described in Figure 2.
2. External Trim Connections C1 through C6 are described in Figure 16.
3. When ordering pre-assembled "DV-5A Valve with Galvanized Valve Trim" or pre-assembled "DV-5A Valve with Galvanized Valve Trim and Butterfly Valve",
Items A1 through A8 are provided, as applicably related to valve size.
4. When ordering DV-5A Trim separately from the DV-5A Valve, Items A1 through A8 are separately ordered, as applicably related to valve size. Water
Pressure Gauges for EMEA valve trim are also separately ordered.

FIGURE 7
DV-5A VALVE
DELUGE WET PILOT ACTUATION TRIM
SEMI-ASSEMBLED
TFP1306
Page 12 of 34

D
C

F
P4 E
P7
A2 A3
A
P5
C3
C6
C2 C5 P6
C8
H P3 A1
J
B C4
P1 C7
P2
G
L
A5
K
A4

A5 C1

A6 Assemble in order
1-1/2" (DN40) AND 2" (DN50)
VALVES ONLY
from A to L
A7

A9
A8

Notes:
1. Port Connections P1 through P7 are described in Figure 2.
2. External Trim Connections C1 through C8 are described in Figure 17.
3. When ordering pre-assembled "DV-5A Valve with Galvanized Valve Trim" or pre-assembled "DV-5A Valve with Galvanized Valve Trim and Butterfly Valve",
Items A1 through A9 are provided, as applicably related to valve size.
4. When ordering DV-5A Trim separately from the DV-5A Valve, Items A1 through A9 are separately ordered, as applicably related to valve size. Water
Pressure Gauges for EMEA valve trim are also separately ordered.

FIGURE 8
DV-5A VALVE
DELUGE DRY PILOT ACTUATION TRIM
SEMI-ASSEMBLED
TFP1306
Page 13 of 34

D
C

F
P4 E
P7
A2
A
P5

C2 C3 P6
C5 A6

H P3 A1
J
B
P1 C4
P2
G
A4
K
A3

A4 C1

A5 Assemble in order
1-1/2" (DN40) AND 2" (DN50)
VALVES ONLY
from A to K
A7

A9
A8

Notes:
1. Port Connections P1 through P7 are described in Figure 2.
2. External Trim Connections C1 through C5 are described in Figure 18.
3. When ordering pre-assembled "DV-5A Valve with Galvanized Valve Trim" or pre-assembled "DV-5A Valve with Galvanized Valve Trim and Butterfly Valve",
Items A1 through A9 are provided, as applicably related to valve size, and Item A9 is provided as P/N 52-287-1-124 described in Technical Data Sheet
TFP2180.
4. When ordering DV-5A Trim separately from the DV-5A Valve, Items A1 through A9 are separately ordered. Water Pressure Gauges for EMEA valve trim are
also separately ordered.

FIGURE 9
DV-5A VALVE
DELUGE ELECTRIC ACTUATION TRIM
SEMI-ASSEMBLED
TFP1306
Page 14 of 34

V2 42 24
V3 23
(GREEN
TINT) 43

V1 19 34
VdS APPROVAL
ONLY, SEE P4
NOTE 5 40
P7 17 25
A2 P5 46
C3
C4 11
10 4 Notes:
C2 1. Port Connections P1
P6 45 17 21
27 through P7 are described
44 13 in Figure 2.
36 A1 28 35 31
P3 2. External Trim Connec-
20 12 32 tions C1 through C6 are
27 P1 C6 25 described in Figure 16.
P2 C5 3. When ordering pre-
39 9 assembled "DV-5A Valve
49 3
16 41 A4 30 with Galvanized Valve Trim"
21 48 or pre-assembled "DV-5A
33 5 38 Valve with Galvanized Valve
47
26 A3 8 47 Trim and Butterfly Valve",
29 30 15 Items A1 through A8 are
provided, as applicably
22 2 related to valve size.
24 1 18 7 4. When ordering DV-5A Trim
30 24 separately from the DV-5A
6 37
16 14 Valve, Items A1 through
30 A8 are separately ordered,
A4 as applicably related to
C1 6 valve size. Water Pressure
A5 Gauges for EMEA valve
trim are also separately
A8 ordered.
A6 A7
5. V1 through V3 Water
Column Prevention Drain
1-1/2" (DN40) AND 2" (DN50) Components are required
VALVES ONLY for VdS Approval.
ITEM QTY. DESCRIPTION CH 1-1/2 IN. (DN40) 2 IN. (DN50) 3 IN. (DN80) 4 IN. (DN100) 6 IN. (DN150) 8 IN. (DN200)
1 1 1/4" GAUGE TEST VALVE 460051003 460051003 460051003 460051003 460051003 460051003
2 1 MRA-1 MANUAL RESET ACTUATOR 545001000 545001000 545001000 545001000 545001000 545001000
3 1 MC-2 MANUAL CONTROL STATION 545002000 545002000 545002000 545002000 545002000 545002000
4 1 AD-3 AUTOMATIC DRAIN VALVE 547932004 547932004 547932004 547932004 547932004 547932004
5 1 PRIMING SUPPLY RESTRICTION 545100051 545100051 545100051 545100051 545100051 545100051
6 2 1/2" BALL VALVE 460501004 460501004 460501004 460501004 460501004 460501004
7 1 1/2" SPRING LOADED CHECK VALVE 923221003 923221003 923221003 923221003 923221003 923221003
8 1 1/2" Y-STRAINER 523531006 523531006 523531006 523531006 523531006 523531006
9 1 3/4" ANGLE VALVE 460481010 460481010 460481010 460481010 460481010 460481010
10 1 ANGLE VALVE 460481010 460481010 460481011 460481012 460481012 460481012
11 1 DRIP FUNNEL BRACKET CONNECTOR 922111005 922111005 922111005 922111005 922111005 922111005
12 1 DRIP FUNNEL BRACKET 922111003 922111003 922111003 922111003 922111003 922111003
13 1 DRIP FUNNEL 923431007 923431007 923431007 923431007 923431007 923431007
14 1 COMP. FITTING 90° 1/2" MNPT x 1/2" OD TUBE ✓ — — — — — —
15 1 COMP. FITTING 90° 1/2" FNPT x 1/2" OD TUBE ✓ — — — — — —
16 2 FLARE FITTING 90° 1/2" NPT x 1/2" TUBE 545100062 545100062 545100062 545100062 545100062 545100062
17 2 FLARE FITTING 3/4" NPT x 3/4" TUBE 545100063 545100063 545100063 545100063 545100063 545100063
18 1 PIPE PLUG ✓ 1/4" 1/4" 1/4" 1/4" 1/4" 1/4"
19 1 PIPE PLUG, SOCKET HEAD ✓ 1/2" 1/2" 1/2" 1/2" 1/2" 1/2"
20 1 PIPE PLUG ✓ 3/4" 3/4" 3/4" 3/4" 3/4" 3/4"
21 2 UNION ✓ 1/2" 1/2" 1/2" 1/2" 1/2" 1/2"
22 1 STREET ELBOW ✓ 1/4" x 90° 1/4" x 90° 1/4" x 90° 1/4" x 90° 1/4" x 90° 1/4" x 90°
23 1 ELBOW ✓ 1/2" x 45° 1/2" x 45° 1/2" x 45° 1/2" x 45° 1/2" x 45° 1/2" x 45°
24 3 ELBOW ✓ 1/2" x 90° 1/2" x 90° 1/2" x 90° 1/2" x 90° 1/2" x 90° 1/2" x 90°
25 2 TEE ✓ 1/2" 1/2" 1/2" 1/2" 1/2" 1/2"
26 1 REDUCING TEE ✓ 1/2" x 1/2" x 1/4" 1/2" x 1/2" x 1/4" 1/2" x 1/2" x 1/4" 1/2" x 1/2" x 1/4" 1/2" x 1/2" x 1/4" 1/2" x 1/2" x 1/4"
27 2 REDUCING TEE ✓ 3/4" x 1/2" x 3/4" 3/4" x 1/2" x 3/4" 3/4" x 1/2" x 3/4" 3/4" x 1/2" x 3/4" 3/4" x 1/2" x 3/4" 3/4" x 1/2" x 3/4"
28 1 REDUCING TEE ✓ 3/4" x 3/4" x 3/4" 3/4" x 3/4" x 3/4" 1-1/4" x 1-1/4" x 3/4" 2" x 2" x 3/4" 2" x 2" x 3/4" 2" x 2" x 3/4"
29 1 PIPE NIPPLE ✓ 1/4" x 1-1/2" 1/4" x 1-1/2" 1/4" x 1-1/2" 1/4" x 1-1/2" 1/4" x 1-1/2" 1/4" x 1-1/2"
30 4 PIPE NIPPLE ✓ 1/2" x 1-1/2" 1/2" x 1-1/2" 1/2" x 1-1/2" 1/2" x 1-1/2" 1/2" x 1-1/2" 1/2" x 1-1/2"
31 1 PIPE NIPPLE ✓ 1/2" x 2-1/2" 1/2" x 2-1/2" 1/2" x 2-1/2" 1/2" x 2-1/2" 1/2" x 2-1/2" 1/2" x 2-1/2"

FIGURE 10 (1 OF 2)
DV-5 a VALVES — DELUGE WET PILOT ACTUATION TRIM — EXPLODED VIEW
TFP1306
Page 15 of 34

ITEM QTY. DESCRIPTION CH 1-1/2 IN. (DN40) 2 IN. (DN50) 3 IN. (DN80) 4 IN. (DN100) 6 IN. (DN150) 8 IN. (DN200)
32 1 PIPE NIPPLE ✓ 1/2" x 4-1/2" 1/2" x 4-1/2" 1/2" x 4-1/2" 1/2" x 4-1/2" 1/2" x 4-1/2" 1/2" x 4-1/2"
33 1 PIPE NIPPLE ✓ 1/2" x 2" 1/2" x 2" 1/2" x 2" 1/2" x 2" 1/2" x 2" 1/2" x 2"
34 1 PIPE NIPPLE ✓ 1/2" x 5" 1/2" x 5" 1/2" x 5" 1/2" x 5" 1/2" x 5" 1/2" x 5"
35 1 PIPE NIPPLE ✓ 3/4" x 1-1/2" 3/4" x 1-1/2" 3/4" x 1-1/2" 3/4" x 1-1/2" 3/4" x 1-1/2" 3/4" x 1-1/2"
36 1 PIPE NIPPLE ✓ 3/4" x 4-1/2" 3/4" x 4-1/2" 3/4" x 4-1/2" 3/4" x 4-1/2" 3/4" x 4-1/2" 3/4" x 4-1/2"
37 1 TUBING, MRA-1 DRAIN 545100065 545100065 545100066 535002140 535002160 535002180
38 1 TUBING, MC-2 DRAIN 535000220 535000220 535000230 535000240 535000260 535000280
39 1 TUBING ASSY, ALARM TEST INTERCONNECT 535000320 535000320 535000330 535000340 535000360 535000380
40 1 TUBING ASSY, SYSTEM DRAIN 535000420 535000420 535000430 535000440 535000460 535000480
41 1 PIPE NIPPLE ✓ 1/2" x 3-1/2" 1/2" x 3-1/2" 1/2" x 4-1/2" 1/2" x 5-1/2" 1/2" x 5-1/2" 1/2" x 6-3/4"
42 1 PIPE NIPPLE ✓ 1/2" x 5" 1/2" x 5" 1/2" x 5-1/2" 1/2" x 5-1/2" 1/2" x 5-1/2" 1/2" x 6-1/2"
43 1 PIPE NIPPLE ✓ 1/2" x 5" 1/2" x 5" 1/2" x 4-1/2" 1/2" x 5" 1/2" x 7-1/2" 1/2" x 9-1/2"
44 1 PIPE NIPPLE ✓ 3/4" x 5" 3/4" x 5" 3/4" x 6" 3/4" x 7" 3/4" x 9" 3/4" x 11-1/2"
45 1 PIPE NIPPLE ✓ 3/4" x 4-1/2" 3/4" x 4-1/2" 1-1/4" x 3-1/4" 2" x 3" 2" x 3" 2" x 3"
46 1 PIPE NIPPLE ✓ 3/4" x 6-1/2" 3/4" x 6-1/2" 1-1/4" x 5-1/2" 2" x 5" 2" x 6" 2" x 8"
WATER PRESSURE GAUGE, 300 PSI / 2000 kPa
2 923431005 923431005 923431005 923431005 923431005 923431005
(AMER/APAC)
47
WATER PRESSURE GAUGE, 20 bar / 2000 kPa
2 025500013 025500013 025500013 025500013 025500013 025500013
(EMEA)
48 1 LABEL 545003001 545003001 545003001 545003001 545003001 545003001
49 1 LABEL WIRE — — — — — —
A1 1 DV-5A Valve REFER TO TABLE F FOR DV-5A VALVE PART NUMBERS
WATERFLOW PRESSURE ALARM SWITCH,
1 25710 25710 25710 25710 25710 25710
PS10-2 (AMER/APAC)
A2
WATERFLOW PRESSURE ALARM SWITCH,
1 0260 0260 0260 0260 0260 0260
PS10-1 (EMEA)
1 BUTTERFLY VALVE, 1-1/2" G x G 51024A 51021A — — — —
A3
1 BFV-300 BUTTERFLY VALVE, G x G — — 59300G030WS 59300G040WS 59300G060WS 59300G080WS
2 FIGURE 577 RIGID GROOVED COUPLING 57715ACP 57720ACP — — — —
A4
1 FIGURE 577 RIGID GROOVED COUPLING — — 57730ACP 57740ACP 57760ACP 57780ACP
A5 1 GROOVE x THREADED OUTLET WELDED TEE 545004000 545004001 — — — —
A6 1 INVERTED FLARE SHUT-OFF VALVEa 545100100 545100100 545100099 545100100 545100100 545100100
A7 1 FLARE FITTING 90° 1/2" NPT x 1/2" TUBE 545100062 545100062 545100062 545100062 545100062 545100062
A8 1 TUBING ASSY, DIAPHRAGM CHAMBER SUPPLY 540000015 540000020 540000030 540000040 540000060 540000080
V1 1 REDUCING BUSHING ✓ 1/2" x 1/4" 1/2" x 1/4" 1/2" x 1/4" 1/2" x 1/4" 1/2" x 1/4" 1/2" x 1/4"
V2 1 3/32" VENT FITTING 920321002 920321002 920321002 920321002 920321002 920321002
V3 1 TUBING, VENT TRIM DRAIN 923041035 923041035 923041035 923041035 923041035 923041035

NOTE:
a. Not VdS Approved
CH - Common Hardware - Refer to Materials of Construction section for specifications.

FIGURE 10 (2 OF 2)
DV-5 a VALVES — DELUGE WET PILOT ACTUATION TRIM — EXPLODED VIEW
TFP1306
Page 16 of 34

A3
C3
7
35
C6 29
V2 50 27
V3 26 35
(GREEN 56
51 35
TINT) 33 9
28
V1 22 41 35
VdS APPROVAL 1 28
ONLY, SEE P4 29 C4
NOTE 5 48 18
P7 20 28 21 36
A2 P5 54 39
5
C5 14 35
13 4
C2
P6 53 20 24 46
31 Notes:
52 16 1. Port Connections P1
43 A1 32 42 38
P3 through P7 are described
23 15 40 in Figure 2.
31 C8 28
P1 2. External Trim Connec-
P2 C7 tions C1 through C8 are
47 12 described in Figure 17.
58 3 3. When ordering pre-
19 49 A5 36
24 57 assembled "DV-5A Valve
37 6 45 with Galvanized Valve Trim"
55 55 or pre-assembled "DV-5A
30 A4 11
34 36 18 Valve with Galvanized Valve
Trim and Butterfly Valve",
25 2 Items A1 through A9 are
27 1 21 10 provided, as applicably
36 27 related to valve size.
8 44
17 4. When ordering DV-5A Trim
19
36 separately from the DV-5A
A5 Valve, Items A1 through
C1 8 A9 are separately ordered,
as applicably related to
A6 valve size. Water Pressure
A9 Gauges for EMEA valve
A7 A8
trim are also separately
ordered.
1-1/2" (DN40) AND 2" (DN50) 5. V1 through V3 Water
VALVES ONLY Column Prevention Drain
Components are required
for VdS Approval.
ITEM QTY. DESCRIPTION CH 1-1/2 IN. (DN40) 2 IN. (DN50) 3 IN. (DN80) 4 IN. (DN100) 6 IN. (DN150) 8 IN. (DN200)
1 2 1/4" GAUGE TEST VALVE 460051003 460051003 460051003 460051003 460051003 460051003
2 1 MRA-1 MANUAL RESET ACTUATOR 545001000 545001000 545001000 545001000 545001000 545001000
3 1 MC-2 MANUAL CONTROL STATION 545002000 545002000 545002000 545002000 545002000 545002000
4 1 AD-3 AUTOMATIC DRAIN VALVE 547932004 547932004 547932004 547932004 547932004 547932004
5 1 DP-1 DRY PILOT ACTUATOR 522801001 522801001 522801001 522801001 522801001 522801001
6 1 PRIMING SUPPLY RESTRICTION 545100051 545100051 545100051 545100051 545100051 545100051
7 1 1/4" PRESSURE RELIEF VALVE 923431020 923431020 923431020 923431020 923431020 923431020
8 2 1/2" BALL VALVE 460501004 460501004 460501004 460501004 460501004 460501004
9 1 1/2" GLOBE VALVE 460471005 460471005 460471005 460471005 460471005 460471005
10 1 1/2" SPRING LOADED CHECK VALVE 923221003 923221003 923221003 923221003 923221003 923221003
11 1 1/2" Y-STRAINER 523531006 523531006 523531006 523531006 523531006 523531006
12 1 3/4" ANGLE VALVE 460481010 460481010 460481010 460481010 460481010 460481010
13 1 ANGLE VALVE 460481010 460481010 460481011 460481012 460481012 460481012
14 1 DRIP FUNNEL BRACKET CONNECTOR 922111005 922111005 922111005 922111005 922111005 922111005
15 1 DRIP FUNNEL BRACKET 922111003 922111003 922111003 922111003 922111003 922111003
16 1 DRIP FUNNEL 923431007 923431007 923431007 923431007 923431007 923431007
17 1 COMP. FITTING 90° 1/2" MNPT x 1/2" OD TUBE ✓ — — — — — —
18 2 COMP. FITTING 90° 1/2" FNPT x 1/2" OD TUBE ✓ — — — — — —
19 2 FLARE FITTING 90° 1/2" NPT x 1/2" TUBE 545100062 545100062 545100062 545100062 545100062 545100062
20 2 FLARE FITTING 3/4" NPT x 3/4" TUBE 545100063 545100063 545100063 545100063 545100063 545100063
21 2 PIPE PLUG ✓ 1/4" 1/4" 1/4" 1/4" 1/4" 1/4"
22 1 PIPE PLUG, SOCKET HEAD ✓ 1/2" 1/2" 1/2" 1/2" 1/2" 1/2"
23 1 PIPE PLUG ✓ 3/4" 3/4" 3/4" 3/4" 3/4" 3/4"
24 2 UNION ✓ 1/2" 1/2" 1/2" 1/2" 1/2" 1/2"
25 1 STREET ELBOW ✓ 1/4" x 90° 1/4" x 90° 1/4" x 90° 1/4" x 90° 1/4" x 90° 1/4" x 90°

FIGURE 11 (1 OF 2)
DV-5 a VALVES — DELUGE DRY PILOT ACTUATION TRIM — EXPLODED VIEW
TFP1306
Page 17 of 34

ITEM QTY. DESCRIPTION CH 1-1/2 IN. (DN40) 2 IN. (DN50) 3 IN. (DN80) 4 IN. (DN100) 6 IN. (DN150) 8 IN. (DN200)
26 1 ELBOW ✓ 1/2" x 45° 1/2" x 45° 1/2" x 45° 1/2" x 45° 1/2" x 45° 1/2" x 45°
27 3 ELBOW ✓ 1/2" x 90° 1/2" x 90° 1/2" x 90° 1/2" x 90° 1/2" x 90° 1/2" x 90°
28 4 TEE ✓ 1/2" 1/2" 1/2" 1/2" 1/2" 1/2"
29 2 REDUCING TEE ✓ 1/2" x 1/4" x 1/2" 1/2" x 1/4" x 1/2" 1/2" x 1/4" x 1/2" 1/2" x 1/4" x 1/2" 1/2" x 1/4" x 1/2" 1/2" x 1/4" x 1/2"
30 1 REDUCING TEE ✓ 1/2" x 1/2" x 1/4" 1/2" x 1/2" x 1/4" 1/2" x 1/2" x 1/4" 1/2" x 1/2" x 1/4" 1/2" x 1/2" x 1/4" 1/2" x 1/2" x 1/4"
31 2 REDUCING TEE ✓ 3/4" x 1/2" x 3/4" 3/4" x 1/2" x 3/4" 3/4" x 1/2" x 3/4" 3/4" x 1/2" x 3/4" 3/4" x 1/2" x 3/4" 3/4" x 1/2" x 3/4"
32 1 REDUCING TEE ✓ 3/4" x 3/4" x 3/4" 3/4" x 3/4" x 3/4" 1-1/4" x 1-1/4" x 3/4" 2" x 2" x 3/4" 2" x 2" x 3/4" 2" x 2" x 3/4"
33 1 PIPE NIPPLE ✓ 1/4" x CLOSE 1/4" x CLOSE 1/4" x CLOSE 1/4" x CLOSE 1/4" x CLOSE 1/4" x CLOSE
34 1 PIPE NIPPLE ✓ 1/4" x 1-1/2" 1/4" x 1-1/2" 1/4" x 1-1/2" 1/4" x 1-1/2" 1/4" x 1-1/2" 1/4" x 1-1/2"
35 5 PIPE NIPPLE ✓ 1/2" x CLOSE 1/2" x CLOSE 1/2" x CLOSE 1/2" x CLOSE 1/2" x CLOSE 1/2" x CLOSE
36 5 PIPE NIPPLE ✓ 1/2" x 1-1/2" 1/2" x 1-1/2" 1/2" x 1-1/2" 1/2" x 1-1/2" 1/2" x 1-1/2" 1/2" x 1-1/2"
37 1 PIPE NIPPLE ✓ 1/2" x 2" 1/2" x 2" 1/2" x 2" 1/2" x 2" 1/2" x 2" 1/2" x 2"
38 1 PIPE NIPPLE ✓ 1/2" x 2-1/2" 1/2" x 2-1/2" 1/2" x 2-1/2" 1/2" x 2-1/2" 1/2" x 2-1/2" 1/2" x 2-1/2"
39 1 PIPE NIPPLE ✓ 1/2" x 3" 1/2" x 3" 1/2" x 3" 1/2" x 3" 1/2" x 3" 1/2" x 3"
40 1 PIPE NIPPLE ✓ 1/2" x 4-1/2" 1/2" x 4-1/2" 1/2" x 4-1/2" 1/2" x 4-1/2" 1/2" x 4-1/2" 1/2" x 4-1/2"
41 1 PIPE NIPPLE ✓ 1/2" x 5" 1/2" x 5" 1/2" x 5" 1/2" x 5" 1/2" x 5" 1/2" x 5"
42 1 PIPE NIPPLE ✓ 3/4" x 1-1/2" 3/4" x 1-1/2" 3/4" x 1-1/2" 3/4" x 1-1/2" 3/4" x 1-1/2" 3/4" x 1-1/2"
43 1 PIPE NIPPLE ✓ 3/4" x 4-1/2" 3/4" x 4-1/2" 3/4" x 4-1/2" 3/4" x 4-1/2" 3/4" x 4-1/2" 3/4" x 4-1/2"
44 1 TUBING, MRA-1 DRAIN 545100065 545100065 545100066 535002140 535002160 535002180
45 1 TUBING, MC-2 DRAIN 535000220 535000220 535000230 535000240 535000260 535000280
46 1 TUBING, DP-1 DRAIN 535000520 535000520 535000530 535000540 535000560 535000580
47 1 TUBING ASSY, ALARM TEST INTERCONNECT 535000320 535000320 535000330 535000340 535000360 535000380
48 1 TUBING ASSY, SYSTEM DRAIN 535000420 535000420 535000430 535000440 535000460 535000480
49 1 PIPE NIPPLE ✓ 1/2" x 3-1/2" 1/2" x 3-1/2" 1/2" x 4-1/2" 1/2" x 5-1/2" 1/2" x 5-1/2" 1/2" x 6-3/4"
50 1 PIPE NIPPLE ✓ 1/2" x 5" 1/2" x 5" 1/2" x 5-1/2" 1/2" x 5-1/2" 1/2" x 5-1/2" 1/2" x 6-1/2"
51 1 PIPE NIPPLE ✓ 1/2" x 5" 1/2" x 5" 1/2" x 4-1/2" 1/2" x 5" 1/2" x 7-1/2" 1/2" x 9-1/2"
52 1 PIPE NIPPLE ✓ 3/4" x 5" 3/4" x 5" 3/4" x 6" 3/4" x 7" 3/4" x 9" 3/4" x 11-1/2"
53 1 PIPE NIPPLE ✓ 3/4" x 4-1/2" 3/4" x 4-1/2" 1-1/4" x 3-1/4" 2" x 3" 2" x 3" 2" x 3"
54 1 PIPE NIPPLE ✓ 3/4" x 6-1/2" 3/4" x 6-1/2" 1-1/4" x 5-1/2" 2" x 5" 2" x 6" 2" x 8"
WATER PRESSURE GAUGE, 300 PSI / 2000 kPa
2 923431005 923431005 923431005 923431005 923431005 923431005
(AMER/APAC)
55
WATER PRESSURE GAUGE, 20 bar / 2000 kPa
2 025500013 025500013 025500013 025500013 025500013 025500013
(EMEA)
AIR PRESSURE GAUGE, 80 PSI / 550 kPa
56 1 923431012 923431012 923431012 923431012 923431012 923431012
RETARDED TO 250PSI / 1750 kPa
57 1 LABEL 545003001 545003001 545003001 545003001 545003001 545003001
58 1 LABEL WIRE — — — — — —
A1 1 DV-5A Valve REFER TO TABLE F FOR DV-5A VALVE PART NUMBERS
WATERFLOW PRESSURE ALARM SWITCH,
1 25710 25710 25710 25710 25710 25710
PS10-2 (AMER/APAC)
A2
WATERFLOW PRESSURE ALARM SWITCH,
1 0260 0260 0260 0260 0260 0260
PS10-1 (EMEA)
LOW AIR PRESSURE ALARM SWITCH, PS40-2
1 25730 25730 25730 25730 25730 25730
(AMER/APAC)
A3
LOW AIR PRESSURE ALARM SWITCH, PS40-1
1 0262 0262 0262 0262 0262 0262
(EMEA)
1 BUTTERFLY VALVE, G x G 51024A 51021A — — — —
A4
1 BFV-300 BUTTERFLY VALVE, G x G — — 59300G030WS 59300G040WS 59300G060WS 59300G080WS
2 FIGURE 577 RIGID GROOVED COUPLING 57715ACP 57720ACP — — — —
A5
1 FIGURE 577 RIGID GROOVED COUPLING — — 57730ACP 57740ACP 57760ACP 57780ACP
A6 1 GROOVE x THREADED OUTLET WELDED TEE 545004000 545004001 — — — —
A7 1 INVERTED FLARE SHUT-OFF VALVEa 545100100 545100100 545100099 545100100 545100100 545100100
A8 1 FLARE FITTING 90° 1/2" NPT x 1/2" TUBE 545100062 545100062 545100062 545100062 545100062 545100062
A9 1 TUBING ASSY, DIAPHRAGM CHAMBER SUPPLY 540000015 540000020 540000030 540000040 540000060 540000080
V1 1 REDUCING BUSHING ✓ 1/2" x 1/4" 1/2" x 1/4" 1/2" x 1/4" 1/2" x 1/4" 1/2" x 1/4" 1/2" x 1/4"
V2 1 3/32" VENT FITTING 920321002 920321002 920321002 920321002 920321002 920321002
V3 1 TUBING, VENT TRIM DRAIN 923041035 923041035 923041035 923041035 923041035 923041035

NOTE:
a. Not VdS Approved
CH - Common Hardware - Refer to Materials of Construction section for specifications.

FIGURE 11 (2 OF 2)
DV-5 a VALVES — DELUGE DRY PILOT ACTUATION TRIM — EXPLODED VIEW
TFP1306
Page 18 of 34

V2 44 24
V3 23
(GREEN
TINT) 45

V1 19 35 40
VdS APPROVAL 14
ONLY, SEE P4
42 A6
NOTE 5
P7 17 25
A2 P5 48
Notes:
C3 11 30 1. Port Connections P1
10 4 through P7 are described
C2 in Figure 2.
P6 47 17 21
27 2. External Trim Connec-
46 13 tions C1 through C5 are
37 A1 28 36 33
P3 described in Figure 18.
20 12 34 3. When ordering pre-
27 P1 C5 25 assembled "DV-5A Valve
P2 C4 with Galvanized Valve Trim"
41 9 or pre-assembled "DV-5A
51 3
16 43 A4 31 Valve with Galvanized Valve
21 50 Trim and Butterfly Valve",
32 5 39 Items A1 through A9 are
49
26 A3 8 49 provided, as applicably
29 31 15 related to valve size, and
Item A6 is provided as
22 2 P/N 52-287-1-124
24 1 18 7 described in Technical
31 24 Data Sheet TFP2180.
6 38
16 14 4. When ordering DV-5A Trim
31 separately from the DV-5A
A4 Valve, Items A1 through
C1 6 A9 are separately ordered.
A5 Water Pressure Gauges for
EMEA valve trim are also
A9 separately ordered.
A7 A8
5. V1 through V3 Water
Column Prevention Drain
1-1/2" (DN40) AND 2" (DN50) Components are required
VALVES ONLY for VdS Approval.
ITEM QTY DESCRIPTION CH 1-1/2 IN. (DN40) 2 IN. (DN50) 3 IN. (DN80) 4 IN. (DN100) 6 IN. (DN150) 8 IN. (DN200)
1 1 1/4" GAUGE TEST VALVE 460051003 460051003 460051003 460051003 460051003 460051003
2 1 MRA-1 MANUAL RESET ACTUATOR 545001000 545001000 545001000 545001000 545001000 545001000
3 1 MC-2 MANUAL CONTROL STATION 545002000 545002000 545002000 545002000 545002000 545002000
4 1 AD-3 AUTOMATIC DRAIN VALVE 547932004 547932004 547932004 547932004 547932004 547932004
5 1 PRIMING SUPPLY RESTRICTION 545100051 545100051 545100051 545100051 545100051 545100051
6 2 1/2" BALL VALVE 460501004 460501004 460501004 460501004 460501004 460501004
7 1 1/2" SPRING LOADED CHECK VALVE 923221003 923221003 923221003 923221003 923221003 923221003
8 1 1/2" Y-STRAINER 523531006 523531006 523531006 523531006 523531006 523531006
9 1 3/4" ANGLE VALVE 460481010 460481010 460481010 460481010 460481010 460481010
10 1 ANGLE VALVE 460481010 460481010 460481011 460481012 460481012 460481012
11 1 DRIP FUNNEL BRACKET CONNECTOR 922111005 922111005 922111005 922111005 922111005 922111005
12 1 DRIP FUNNEL BRACKET 922111003 922111003 922111003 922111003 922111003 922111003
13 1 DRIP FUNNEL 923431007 923431007 923431007 923431007 923431007 923431007
14 2 COMP. FITTING 90° 1/2" MNPT x 1/2" OD TUBE ✓ — — — — — —
15 1 COMP. FITTING 90° 1/2" FNPT x 1/2" OD TUBE ✓ — — — — — —
16 2 FLARE FITTING 90° 1/2" NPT x 1/2" TUBE 545100062 545100062 545100062 545100062 545100062 545100062
17 2 FLARE FITTING 3/4" NPT x 3/4" TUBE 545100063 545100063 545100063 545100063 545100063 545100063
18 1 PIPE PLUG ✓ 1/4" 1/4" 1/4" 1/4" 1/4" 1/4"
19 1 PIPE PLUG, SOCKET HEAD ✓ 1/2" 1/2" 1/2" 1/2" 1/2" 1/2"
20 1 PIPE PLUG ✓ 3/4" 3/4" 3/4" 3/4" 3/4" 3/4"
21 2 UNION ✓ 1/2" 1/2" 1/2" 1/2" 1/2" 1/2"
22 1 STREET ELBOW ✓ 1/4" x 90° 1/4" x 90° 1/4" x 90° 1/4" x 90° 1/4" x 90° 1/4" x 90°
23 1 ELBOW ✓ 1/2" x 45° 1/2" x 45° 1/2" x 45° 1/2" x 45° 1/2" x 45° 1/2" x 45°
24 3 ELBOW ✓ 1/2" x 90° 1/2" x 90° 1/2" x 90° 1/2" x 90° 1/2" x 90° 1/2" x 90°
25 2 TEE ✓ 1/2" 1/2" 1/2" 1/2" 1/2" 1/2"
26 1 REDUCING TEE ✓ 1/2" x 1/2" x 1/4" 1/2" x 1/2" x 1/4" 1/2" x 1/2" x 1/4" 1/2" x 1/2" x 1/4" 1/2" x 1/2" x 1/4" 1/2" x 1/2" x 1/4"
27 2 REDUCING TEE ✓ 3/4" x 1/2" x 3/4" 3/4" x 1/2" x 3/4" 3/4" x 1/2" x 3/4" 3/4" x 1/2" x 3/4" 3/4" x 1/2" x 3/4" 3/4" x 1/2" x 3/4"
28 1 REDUCING TEE ✓ 3/4" x 3/4" x 3/4" 3/4" x 3/4" x 3/4" 1-1/4" x 1-1/4" x 3/4" 2" x 2" x 3/4" 2" x 2" x 3/4" 2" x 2" x 3/4"
29 1 PIPE NIPPLE ✓ 1/4" x 1-1/2" 1/4" x 1-1/2" 1/4" x 1-1/2" 1/4" x 1-1/2" 1/4" x 1-1/2" 1/4" x 1-1/2"
30 1 PIPE NIPPLE ✓ 1/2" x CLOSE 1/2" x CLOSE 1/2" x CLOSE 1/2" x CLOSE 1/2" x CLOSE 1/2" x CLOSE
31 4 PIPE NIPPLE ✓ 1/2" x 1-1/2" 1/2" x 1-1/2" 1/2" x 1-1/2" 1/2" x 1-1/2" 1/2" x 1-1/2" 1/2" x 1-1/2"

FIGURE 12 (1 OF 2)
DV-5 a VALVES — DELUGE ELECTRIC ACTUATION TRIM — EXPLODED VIEW
TFP1306
Page 19 of 34

ITEM QTY DESCRIPTION CH 1-1/2 IN. (DN40) 2 IN. (DN50) 3 IN. (DN80) 4 IN. (DN100) 6 IN. (DN150) 8 IN. (DN200)
32 1 PIPE NIPPLE ✓ 1/2" x 2" 1/2" x 2" 1/2" x 2" 1/2" x 2" 1/2" x 2" 1/2" x 2"
33 1 PIPE NIPPLE ✓ 1/2" x 2-1/2" 1/2" x 2-1/2" 1/2" x 2-1/2" 1/2" x 2-1/2" 1/2" x 2-1/2" 1/2" x 2-1/2"
34 1 PIPE NIPPLE ✓ 1/2" x 4-1/2" 1/2" x 4-1/2" 1/2" x 4-1/2" 1/2" x 4-1/2" 1/2" x 4-1/2" 1/2" x 4-1/2"
35 1 PIPE NIPPLE ✓ 1/2" x 5" 1/2" x 5" 1/2" x 5" 1/2" x 5" 1/2" x 5" 1/2" x 5"
36 1 PIPE NIPPLE ✓ 3/4" x 1-1/2" 3/4" x 1-1/2" 3/4" x 1-1/2" 3/4" x 1-1/2" 3/4" x 1-1/2" 3/4" x 1-1/2"
37 1 PIPE NIPPLE ✓ 3/4" x 4-1/2" 3/4" x 4-1/2" 3/4" x 4-1/2" 3/4" x 4-1/2" 3/4" x 4-1/2" 3/4" x 4-1/2"
38 1 TUBING, MRA-1 DRAIN 545100065 545100065 545100066 535002140 535002160 535002180
39 1 TUBING, MC-2 DRAIN 535000220 535000220 535000230 535000240 535000260 535000280
40 1 TUBING, SOLENOID DRAIN 535001020 535001020 535000630 535000640 535000660 535000680
41 1 TUBING ASSY, ALARM TEST INTERCONNECT 535000320 535000320 535000330 535000340 535000360 535000380
42 1 TUBING ASSY, SYSTEM DRAIN 535000420 535000420 535000430 535000440 535000460 535000480
43 1 PIPE NIPPLE ✓ 1/2" x 3-1/2" 1/2" x 3-1/2" 1/2" x 4-1/2" 1/2" x 5-1/2" 1/2" x 5-1/2" 1/2" x 6-3/4"
44 1 PIPE NIPPLE ✓ 1/2" x 5" 1/2" x 5" 1/2" x 5-1/2" 1/2" x 5-1/2" 1/2" x 5-1/2" 1/2" x 6-1/2"
45 1 PIPE NIPPLE ✓ 1/2" x 5" 1/2" x 5" 1/2" x 4-1/2" 1/2" x 5" 1/2" x 7-1/2" 1/2" x 9-1/2"
46 1 PIPE NIPPLE ✓ 3/4" x 5" 3/4" x 5" 3/4" x 6" 3/4" x 7" 3/4" x 9" 3/4" x 11-1/2"
47 1 PIPE NIPPLE ✓ 3/4" x 4-1/2" 3/4" x 4-1/2" 1-1/4" x 3-1/4" 2" x 3" 2" x 3" 2" x 3"
48 1 PIPE NIPPLE ✓ 3/4" x 6-1/2" 3/4" x 6-1/2" 1-1/4" x 5-1/2" 2" x 5" 2" x 6" 2" x 8"
WATER PRESSURE GAUGE, 300 PSI / 2000 kPa
2 923431005 923431005 923431005 923431005 923431005 923431005
(AMER/APAC)
49
WATER PRESSURE GAUGE, 20 bar / 2000 kPa
2 025500013 025500013 025500013 025500013 025500013 025500013
(EMEA)
50 1 LABEL 545003001 545003001 545003001 545003001 545003001 545003001
51 1 LABEL WIRE — — — — — —
A1 1 DV-5A Valve REFER TO TABLE F FOR DV-5A VALVE PART NUMBERS
WATERFLOW PRESSURE ALARM SWITCH,
A2 1 25710 25710 25710 25710 25710 25710
PS10-2 (AMER/APAC)
WATERFLOW PRESSURE ALARM SWITCH,
A2 1 0260 0260 0260 0260 0260 0260
PS10-1 (EMEA)
A3 1 BUTTERFLY VALVE, G x G 51024A 51021A — — — —
A3 1 BFV-300 BUTTERFLY VALVE, G x G — — 59300G030WS 59300G040WS 59300G060WS 59300G080WS
A4 2 FIGURE 577 RIGID GROOVED COUPLING 57715ACP 57720ACP — — — —
A4 1 FIGURE 577 RIGID GROOVED COUPLING — — 57730ACP 57740ACP 57760ACP 57780ACP
A5 1 GROOVE x THREADED OUTLET WELDED TEE 545004000 545004001 — — — —
A6 1 SOLENOID VALVE, NORMALLY CLOSED SEE TFP2180 SEE TFP2180 SEE TFP2180 SEE TFP2180 SEE TFP2180 SEE TFP2180
A7 1 INVERTED FLARE SHUT-OFF VALVEa 545100100 545100100 5545100099 545100100 545100100 545100100
A8 1 FLARE FITTING 90° 1/2" NPT x 1/2" TUBE 545100062 545100062 545100062 545100062 545100062 545100062
A9 1 TUBING ASSY, DIAPHRAGM CHAMBER SUPPLY 540000015 540000020 540000030 540000040 540000060 540000080
V1 1 REDUCING BUSHING ✓ 1/2" x 1/4" 1/2" x 1/4" 1/2" x 1/4" 1/2" x 1/4" 1/2" x 1/4" 1/2" x 1/4"
V2 1 3/32" VENT FITTING 920321002 920321002 920321002 920321002 920321002 920321002
V3 1 TUBING, VENT TRIM DRAIN 923041035 923041035 923041035 923041035 923041035 923041035

NOTE:
a. Not VdS Approved
CH - Common Hardware - Refer to Materials of Construction section for specifications.

FIGURE 12 (2 OF 2)
DV-5 a VALVES — DELUGE ELECTRIC ACTUATION TRIM — EXPLODED VIEW
TFP1306
Page 20 of 34

Nominal
Valve Inches
Size (mm)
ANSI
Inches A B C D E F G H J
(DN)
1-1/2 2.8 9.7 10.4 12.7 16.2 7.3 10.2 8.0 1.2
(40) (71) (246) (264) (323) (411) (185) (259) (203) (31)
2 2.8 9.7 10.4 12.7 16.2 7.3 10.2 3.8 2.9
(50) (71) (246) (264) (323) (411) (185) (259) (97) (74)
3 3.0 10.9 12.0 12.6 17.9 5.8 13.8 3.9 3.6
(80) (76) (277) (305) (320) (455) (147) (351) (99) (91)
4 3.0 12.2 13.1 14.1 19.6 5.1 16.8 4.5 4.3
(100) (76) (310) (333) (358) (498) (130) (427) (114) (109)
6 4.5 13.6 15.0 16.4 22.3 3.4 22.4 5.9 5.7
(150) (114) (345) (381) (417) (566) (86) (569) (150) (145)
8 5.3 16.3 17.2 19.5 27.5 2.9 27.5 5.2 6.7
(200) (135) (414) (437) (495) (699) (74) (699) (132) (170)
Notes:
1. Dimensions based on drain valves being open.
2. Dimensions do not provide installation clearance.

J B C D
A

E
G

H F

FIGURE 13
DV-5 a VALVE
DELUGE WET PILOT ACTUATION TRIM ASSEMBLY
NOMINAL DIMENSIONS
TFP1306
Page 21 of 34

Nominal
Valve Inches
Size (mm)
ANSI
Inches A B C D E F G H J
(DN)
1-1/2 2.8 9.7 10.4 16.5 19.3 7.3 10.2 8.0 1.2
(40) (71) (246) (264) (419) (490) (185) (259) (203) (31)
2 2.8 9.7 10.4 16.5 19.3 7.3 10.2 3.8 2.9
(50) (71) (246) (264) (419) (490) (185) (259) (97) (74)
3 3.0 11.4 12.0 16.5 21.2 5.8 13.8 3.9 3.6
(80) (76) (290) (305) (419) (539) (147) (350) (99) (91)
4 3.0 12.7 13.1 16.5 22.7 5.1 16.8 4.5 4.3
(100) (76) (323) (333) (419) (577) (130) (427) (114) (109)
6 4.5 14.0 15.0 16.5 25.4 3.4 22.4 5.9 5.7
(150) (114) (356) (381) (419) (645) (86) (568,96) (150) (145)
8 5.3 16.8 17.2 19.5 28.0 2.9 27.5 5.2 6.7
(200) (135) (427) (437) (495) (711) (74) (699) (132) (170)
Notes:
1. Dimensions based on drain valves being open.
2. Dimensions do not provide installation clearance.

J B C D

H F

FIGURE 14
DV-5 a VALVE
DELUGE DRY PILOT ACTUATION TRIM ASSEMBLY
NOMINAL DIMENSIONS
TFP1306
Page 22 of 34

Nominal
Valve Inches
Size (mm)
ANSI
Inches A B C D E F G H J
(DN)
1-1/2 2.8 9.7 10.4 12.7 16.2 7.3 10.2 8.0 1.2
(40) (71) (246) (264) (323) (412) (185) (259) (203) (31)
2 2.8 9.7 10.4 12.7 16.2 7.3 10.2 3.8 2.9
(50) (71) (246) (264) (323) (412) (185) (259) (97) (74)
3 3.0 10.9 12.0 12.6 17.9 5.8 13.8 3.9 3.6
(80) (76) (277) (305) (320) (455) (147) (351) (99) (91)
4 3.0 12.2 13.1 14.1 19.6 5.1 16.8 4.5 4.3
(100) (76) (310) (333) (358) (498) (129) (427) (114) (109)
6 4.5 13.6 15.0 16.4 22.3 3.4 22.4 5.9 5.7
(150) (114) (345) (381) (417) (566) (86) (569) (150) (145)
8 5.3 16.3 17.2 19.5 27.5 2.9 27.5 5.2 6.7
(200) (135) (414) (437) (495) (699) (74) (699) (132) (170)
Notes:
1. Dimensions based on drain valves being open.
2. Dimensions do not provide installation clearance.

J B C D
A

E
G

H F

FIGURE 15
DV-5 a VALVE
DELUGE ELECTRIC ACTUATION TRIM ASSEMBLY
NOMINAL DIMENSIONS
TFP1306
Page 23 of 34

Valve Setting NOTICE


In order to prevent the possibility of a
• If the Diaphragm Gauge (K) indicates
no drop in pressure, re-open the Dia-
Procedure subsequent operation of an overheated
solder type pilot sprinkler, any solder
phragm Supply Valve (P) and pro-
ceed to the next step.
Perform Steps 1 through 13 when ini- type pilot sprinklers that were possibly Step 10. Partially open the System
tially setting the TYCO DV-5a Valve, exposed to a temperature greater than Main Control Valve (B). Slowly close the
after an operational test of the fire pro- their maximum rated ambient must be Main Drain Valve (D) as soon as water
tection system, or after system opera- replaced. discharges from the Main Drain Valve
tion due to a fire. Refer to Figures 16, (D). Observe the Automatic Drain Valve
17, or 18, as applicable. Step 7. Operate (open) the Manual
(F) for leaks. If there are leaks, deter-
Control Station (M) and then open
Step 1. Close the System Main Control mine/correct the cause of the leakage
the Diaphragm Supply Valve (P). After
Valve (B). problem before proceeding.
unaerated water ceases to discharge
Step 2. Close the Diaphragm Supply from the Manual Control Station (M)
drain tube, slowly close the operating NOTICE
Valve (P). For Dry Pilot Actuation, close
the Dry Pilot Air Supply Valve (U). lever by pushing it up. Do not close the When the System Main Control Valve
hinged cover at this time. (B) is partially opened, the pressure on
Step 3. Open the Main Drain Valve (D), the DV-5a Diaphragm Chamber may
System Drain Valve (E), and all auxil- Step 8. After allowing water to flow out
of the Manual Reset Actuator (N) drain increase. This increase in pressure is
iary drains in the system. Close the normal, and if the pressure is greater
auxiliary drain valves and the System tube until aerated water ceases to dis-
charge, reset the Manual Reset Actua- than the valve trim maximum pressure
Drain Valve (E) after water ceases to rating provided in the Technical Data
discharge. Leave the Main Drain Valve tor (N) by pressing the Reset Knob and
hold until water stops flowing from its section, the pressure is to be relieved
(D) open. to at least the valve trim pressure rating
drain tube and the pressure builds and
At this time make certain that the reaches approximately 15 psi (1,0 bar) by partially and temporarily opening the
Pressure Gauge Valves and the Alarm on the Diaphragm Gauge (K). Pressure Manual Control Station (M); however,
Control Valve (H), as applicable, are will then build up in the DV-5a Dia- do not allow the pressure as indicated
open. phragm Chamber. on the Diaphragm Gauge (K) to drop
below the supply pressure shown on
Step 4. Depress the plunger of the For Wet Pilot Actuation, crack open the Water Supply Gauge (J), since this
Automatic Drain Valve (F) to verify that the Inspector’s Test Connection and action may result in tripping of the
it is open. any other vent valves on the wet pilot DV-5a Valve.
Step 5. Clean the Diaphragm Supply line to relieve trapped air. After the dis-
charge of air has stopped, close the Step 11. Close the hinged cover of the
Strainer (Q) by removing the clean- Manual Control Station (M), and insert a
out plug and strainer basket. The Dia- vent valves and the Inspector’s Test
Connection. new break rod in the small hole through
phragm Supply Strainer (Q) may be the top of the enclosing box.
flushed out by momentarily opening Note: After relieving trapped air, check
the Diaphragm Supply Valve (P). the Manual Reset Actuator (N) to make Step 12. Fully open the System Main
sure there is no water draining from its Control Valve (B).
Step 6. Reset the automatic actuation
system. drain tube. If water is draining, reset Step 13. After setting a fire protec-
the Manual Reset Actuator (N) as pre- tion system, notify the proper authori-
• Wet Pilot Actuation — Replace oper- viously instructed. ties and advise those responsible for
ated pilot sprinklers and/or reset the monitoring proprietary and/or central
remote manual control stations. Step 9. Verify the ability for the DV-5a
Diaphragm to hold pressure as follows: station alarms.
• Dry Pilot Actuation — Replace oper-
ated pilot sprinklers and/or reset • With the diaphragm chamber pres-
the remote manual control stations. surized per Step 8, temporarily close
Re-establish dry pilot pneumatic the Diaphragm Supply Valve (P), and
pressure. then observe the Diaphragm Gauge
(K) for a drop in pressure.
• Electric Actuation — Reset the elec-
tric detection system in accordance • If a drop in pressure is noted, the
with the manufacturer’s instructions DV-5a Diaphragm is to be replaced
to de-energize the solenoid valve. and/or any leaks must be corrected
before proceeding to the next step.
TFP1306
Page 24 of 34

Item Description Item Description External Trim Connections


A DV-5a Valve J Water Supply Gauge C1 Diaphragm Supply Connection
B System Main Control Valve K Diaphragm Gauge C2 Water Motor Alarm Connection
C Waterflow Pressure Switch L System Gauge (Optional) C3 Wet Pilot Line Connection
D Main Drain Valve M Manual Control Station C4 Waterflow Pressure Alarm
E System Drain Valve N Manual Reset Actuator Switch Connection
F Automatic Drain Valve P Diaphragm Supply Valve C5 Main Drain Connection
G Alarm Test Valve Q Diaphragm Supply Strainer C6 Drip Funnel Drain Connection
H Alarm Control Valve (Optional) R Inverted Flare Shut-Off Valve

LOCATION
L
FOR OPTIONAL
ELECTRICALLY
SUPERVISED
C N.O. ALARM
CONTROL P4
P7
VALVE
F
P5
C2
C4
C3
D
P6

H A
P3

P1 C6 M
P2 C5
E

J K
B

Q
G
P
C1
R

Note:
Port Connections P1 through P7 are described in Figure 2.

FIGURE 16
DV-5 a VALVE
DELUGE WET PILOT ACTUATION TRIM
(Refer To Figure 10 For Specific Bills Of Materials)
TFP1306
Page 25 of 34

Item Description Item Description External Trim Connections


A DV-5a Valve M Manual Control Station C1 Diaphragm Supply Connection
B System Main Control Valve N Manual Reset Actuator C2 Water Motor Alarm Connection
C Waterflow Pressure Switch P Diaphragm Supply Valve C3 Dry Pilot Line Connection
D Main Drain Valve Q Diaphragm Supply Strainer C4 Dry Pilot Air Supply Connection
E System Drain Valve R Inverted Flare Shut-Off Valve C5 Waterflow Pressure Alarm
F Automatic Drain Valve S Dry Pilot Actuator Switch Connection
G Alarm Test Valve T Low Air Pressure Alarm Switch C6 Low Air Pressure Switch
H Alarm Control Valve (Optional) U Dry Pilot Air Supply Valve Connection
J Water Supply Gauge V Dry Pilot Line Gauge C7 Main Drain Connection
K Diaphragm Gauge W Pressure Relief Valve C8 Drip Funnel Drain Connection
L System Gauge (Optional)

T
C3 W

C6
LOCATION
L V
FOR OPTIONAL
ELECTRICALLY
SUPERVISED
C N.O. ALARM U
CONTROL P4 C4
P7
VALVE
F
P5
C2
C5
S
D
P6

H A
P3

P1 C8 M
P2 C7
E

J K
B

Q
G
P
C1
R

Note:
Port Connections P1 through P7 are described in Figure 2.

FIGURE 17
DV-5 a VALVE
DELUGE DRY PILOT ACTUATION TRIM
(Refer To Figure 11 For Specific Bills Of Materials)
TFP1306
Page 26 of 34

Item Description Item Description External Trim Connections


A DV-5a Valve K Diaphragm Gauge C1 Diaphragm Supply Connection
B System Main Control Valve L System Gauge (Optional) C2 Water Motor Alarm Connection
C Waterflow Pressure Switch M Manual Control Station C3 Waterflow Pressure Alarm
D Main Drain Valve N Manual Reset Actuator Switch Connection
E System Drain Valve P Diaphragm Supply Valve C4 Main Drain Connection
F Automatic Drain Valve Q Diaphragm Supply Strainer C5 Drip Funnel Drain Connection
G Alarm Test Valve R Inverted Flare Shut-Off Valve
H Alarm Control Valve (Optional) S Solenoid Valve
J Water Supply Gauge

LOCATION
L
FOR OPTIONAL
ELECTRICALLY
SUPERVISED
C N.O. ALARM
CONTROL P4
P7 S
VALVE
F
P5
C2
C3

D
P6

H A
P3

P1 C5 M
P2 C4
E

J K
B

Q
G
P
C1
R

Note:
Port Connections P1 through P7 are described in Figure 2.

FIGURE 18
DV-5 a VALVE
DELUGE ELECTRIC ACTUATION TRIM
(Refer To Figure 12 For Specific Bills Of Materials)
TFP1306
Page 27 of 34

Care and break or repair), and there is a subse-


quent drop in the diaphragm chamber
• Close System Main Control Valve (B).
Open Main Drain Valve (D).
Maintenance water pressure below its normal range
(for example, due to a leak in a piping
• Open System Main Control Valve (B)
one turn beyond position at which
The following procedures and inspec- connection to or from the diaphragm water just begins to flow from Main
tions must be performed as indicated, chamber or, a leak in the diaphragm Drain Valve (D).
in addition to any specific require- chamber check valve caused by dirt or
debris in the check valve seal area), a • Slowly close the Main Drain Valve (D).
ments of the NFPA and any applicable
standards recognized by the Approval deluge valve such as the DV-5a could Step 2. Open the Inspector’s Test
agency. Any impairment must be imme- inadvertently trip, if its water supply Connection.
diately corrected. Refer to Figure 16, 17, pressure is quickly restored.
Note: Be prepared to quickly perform
or 18, as applicable. A drop in the water supply pressure Steps 3, 4, and 5 if water must be pre-
to below its normal range (as in the vented from flowing beyond the riser.
NOTICE case of an interrupted water supply
condition) constitutes an emergency Step 3. Verify that the DV-5a Valve has
If the water supply needs to be shut off impairment. tripped, as indicated by the flow of
to the DV-5a valve and trim and cannot water into the system.
be shut off upstream of the system, Should this condition occur, immedi-
close the System Main Control Valve ately close the System Main Control Step 4. Close the System Main Control
(B), the Diaphragm Supply Valve (P), Valve (B) and use the following proce- Valve (B).
and the Inverted Flare Shut-Off Valve dure to reset the system: Step 5. Close the Diaphragm Supply
(R). This will allow any trim above the Step 1. Prior to the water supply pres- Valve (P).
System Main Control Valve (B) to be sure being restored to the closed
taken apart for service if necessary. Step 6. Reset the DV-5a Valve in accor-
System Main Control Valve (B), note the dance with the Valve Setting Procedure.
The frequency at which the following pressure indicated by the Diaphragm
procedures and inspections are to be Gauge (K) and determine if the pres- Dry Pilot Actuation
performed are to be in accordance with sure is within the normally expected Operation Test Procedure
the NFPA and any applicable specific range. Proper operation of the DV-5a Valve
requirements of the standards recog- (i.e., opening of the DV-5a Valve as
Step 2. If the diaphragm chamber pres-
nized by the Approval agency. during a fire condition) must be veri-
sure is below the normal range, check fied as follows:
Before closing a fire protection system for and correct any source of leakage
main control valve for maintenance from the diaphragm chamber prior to Step 1. If water must be prevented
work on the fire protection system that resetting the system. from flowing beyond the riser, perform
it controls, permission to shut down the following steps:
Step 3. After the water supply pres-
the affected fire protection systems sure is restored to the System Main • Close System Main Control Valve (B).
must first be obtained from the proper Control Valve (B), reset the DV-5a Valve Open Main Drain Valve (D).
authorities and all personnel who may in accordance with the Valve Setting
be affected by this action must be • Open System Main Control Valve (B)
Procedure section. one turn beyond position at which
notified.
water just begins to flow from Main
The owner is responsible for the NOTICE Drain Valve (D).
inspection, testing, and maintenance For fire protection systems subject to
of their fire protection system and • Slowly close the Main Drain Valve (D).
an emergency impairment caused by
devices in compliance with this docu- an interrupted water supply condition, Step 2. Open the Inspector’s Test
ment, as well as with the NFPA and any it is recommended that consideration Connection.
applicable standards recognized by the be given to installing a low water supply
Approval agency. Contact the install- Note: Be prepared to quickly perform
pressure switch with the appropriate Steps 3, 4, and 5 if water must be pre-
ing contractor or product manufacturer alarm/indications to monitor the water
with any questions. vented from flowing beyond the riser.
supply pressure.
Some procedures in this section result Step 3. Verify that the DV-5a Valve has
Waterflow Alarm Test Procedure tripped, as indicated by the flow of
in the operation of the associated To test the waterflow alarm, open the
alarms. Notify the owner and the fire water into the system.
Alarm Test Valve (G), which will allow a
department, central station, or other flow of water to the Waterflow Pressure Step 4. Close the System Main Control
signal station to which the alarms are Switch (C) and/or Water Motor Alarm. Valve (B).
connected before performing the tests. Upon satisfactory completion of the Step 5. Close the Diaphragm Supply
It is recommended that automatic test, close the Alarm Test Valve (G). Valve (P).
sprinkler systems be inspected, tested, To ensure drainage of the alarm line, Step 6. Reset the DV-5a Valve in accor-
and maintained by a qualified Inspec- depress the plunger on the Automatic dance with the Valve Setting Procedure.
tion Service in accordance with the Drain Valve (F).
NFPA and any applicable standards Electric Actuation
recognized by the Approval agency. Wet Pilot Actuation Operation Test Procedure
Operation Test Procedure Proper operation of the DV-5a Valve
Drop in Water Supply Pressure Proper operation of the DV-5a Valve (i.e., opening of the DV-5a Valve as
Below Normal Range (i.e., opening of the DV-5a Valve as during a fire condition) must be veri-
during a fire condition) must be veri- fied as follows:
NOTICE
fied as follows:
If the water supply pressure is signif- Step 1. If water must be prevented
icantly reduced below the normally Step 1. If water must be prevented from flowing beyond the riser, perform
expected static pressure range (as from flowing beyond the riser, perform the following steps.
could occur in the case of a water main the following steps:
TFP1306
Page 28 of 34

• Close System Main Control Valve (B). Step 7. Partially open the System Main Step 8. Open the Diaphragm Supply
Open Main Drain Valve (D). Control Valve (B). Slowly close the Main Valve (P).
Drain Valve (D) as soon as water dis-
• Open System Main Control Valve (B) Step 9. Partially open the System Main
charges from the Main Drain Valve (D)
one turn beyond position at which Control Valve (B). slowly close the Main
and then close the Main Drain Valve
water just begins to flow from Main Drain Valve (D) as soon as water dis-
(D). Observe the Automatic Drain Valve
Drain Valve (D). charges from the Main Drain Valve (D).
(F) for leaks. If there are leaks, deter- Observe the Automatic Drain Valve
• Slowly close the Main Drain Valve (D). mine/correct the cause of the leakage (F) for leaks. If there are leaks, deter-
Step 2. Test the deluge releasing panel problem. If there are no leaks, the mine/correct the cause of the leakage
in accordance with the manufacturer’s DV-5a Valve is ready to be placed in problem. If there are no leaks, the
instructions to energize the solenoid service and the System Main Control DV-5a Valve is ready to be placed in
valve. Valve (B) must then be fully opened. service and the System Main Control
Note: Be prepared to quickly perform Low Pressure Alarm and Valve (B) must then be fully opened.
Steps 3, 4, and 5 if water must be pre- Condensate Drain for Dry Pilot Electric Actuation Solenoid Valve
vented from flowing beyond the riser. Actuation Test Procedures Test Procedure
For Dry Pilot Actuation, testing of the Proper operation of the Solenoid Valve
Step 3. Verify that the DV-5a Valve has Dry Pilot Low Pressure Switch (T) and
tripped, as indicated by the flow of for electric actuation must be verified
drainage of the pilot line condensate at as follows:
water into the system. must be performed as follows:
Step 4. Close the System Main Control Step 1. Close the System Main Control
Step 1. Close the System Main Control Valve (B).
Valve (B). Valve (B).
Step 5. Close the Diaphragm Supply Step 2. Open the Main Drain Valve (D).
Step 2. Close the Diaphragm Supply
Valve (P). Valve (P). Step 3. Test the deluge releasing panel
Step 6. Reset the DV-5a Valve in accor- in accordance with the manufacturer’s
Step 3. Open the Main Drain Valve (D). instructions to energize the solenoid
dance with the Valve Setting Procedure.
Step 4. Open the Inspector’s Test Con- valve.
Dry Pilot Actuator Test Procedure nection, and slowly relieve pneumatic
Proper operation of the Dry Pilot Actua- Step 4. Verify that there is a flow of
pressure. Verify that the Dry Pilot Low water from the Solenoid Valve drain
tor for dry pilot actuation must be veri- Pressure Switch (T) is operational and
fied as follows: connection.
that the low pressure set points are as
Step 1. Close the System Main Control follows: Step 5. Verify that the Diaphragm
Valve (B). Chamber pressure has decreased
• Low pressure alarm setting at to below 25% of the water supply
Step 2. Open the Main Drain Valve (D). approximately 6 psi (0,4 bar) below pressure.
the minimum pilot line service pres-
Step 3. Open the Inspector’s Test Con- sure requirement shown in Graph B Step 6. Reset the electric detection
nection on the Dry Pilot Line. system in accordance with the manu-
• Fire alarm setting at approximately facturer’s instructions to de-energize
Step 4. Verify that there is a flow of 14.5 psi (1,0 bar) below the minimum
water from the Dry Pilot Actuator (S) the Solenoid Valve (S), and proceed as
pilot line service pressure require- follows:
drain connection. ment shown in Graph B.
Step 5. Verify that the Diaphragm • Water should cease draining from the
Step 5. Close the Inspector’s Test Con- Solenoid Valve (S) but remain drain-
Chamber pressure has decreased nection and allow the Dry Pilot Line to
to below 25% of the water supply ing from the Manual Reset Actuator
automatically repressurize. (N).
pressure.
Step 6. Individually open each low • Press the Reset Knob on the Man-
Step 6. Close the Inspector’s Test point drain and then close after dis-
Connection and allow the dry pilot line ual Reset Actuator (N) and hold it a
charge of any trapped condensate. few seconds until water stops flow-
pressure to re-establish, and proceed
as follows: The gauge test valve to which the Dry ing from its drain tube.
Pilot Line Gauge (V) is connected must • Pressure will then build up in the
• Water should cease draining from be used as a low point drain. Close the
the Dry Pilot Actuator (S) but remain DV-5a Diaphragm Chamber.
gauge test valve, remove the plug, and
draining from the Manual Reset Actu- partially open the gauge test valve (as • After system pressure is restored
ator (N). necessary, collect water in a cup). After in the DV-5a Diaphragm Chamber,
• Press the Reset Knob on the Man- condensate water ceases to drain, inspect the Solenoid Valve (S) and
ual Reset Actuator (N) and hold it a close the gauge test valve, replace the Manual Reset Actuator (N) for leaks
few seconds until water stops flow- plug, and then completely open the at the drain tube. Any leaks must be
ing from its drain valve. gauge test valve. corrected before proceeding to the
next step.
• Pressure will then build up in the Step 7. Allow the Dry Pilot Line to auto-
DV-5a Diaphragm Chamber. matically repressurize.
• After system pressure is restored
in the DV-5a Diaphragm Chamber,
inspect the Dry Pilot Actuator (S) and
Manual Reset Actuator (N) for leaks
at the drain tubes. Any leaks must be
corrected before proceeding to the
next step.
TFP1306
Page 29 of 34

Step 7. Partially open the System Main by completing the following steps to
Control Valve (B). Slowly close the Main assure the Diaphragm Cover Fasteners Torque
Drain Valve (D) as soon as water dis- are uniformly and securely tightened. Nominal lb-ft
charges from the Main Drain Valve (D). Valve Sizes (N∙m)
Step 1. With reference to Figure 1, ANSI
Observe the Automatic Drain Valve Inches Short
ensure that the Diaphragm is properly
(F) for leaks. If there are leaks, deter- (DN) Nuts Hex
oriented and that the proper hardware
mine/correct the cause of the leakage Bolts
arrangement is utilized when assem-
problem. If there are no leaks, the bling the Diaphragm Covers. The hard- 1-1/2 44 35
DV-5a Valve is ready to be placed in ware arrangements differ depending on (40) (59,7) (47,5)
service and the System Main Control the size of the DV-5a Valve.
Valve (B) must then be fully opened. 2 44 35
Step 2. By first using the Long Hex (50) (59,7) (47,5)
Internal Valve Inspection Bolts, support of the Diaphragm Cover
Once every five years during the 3 188 150
will be provided before installing the (80) (254,9) (203,4)
annual operational test procedure, Short Hex Bolts. Align Diaphragm in
and prior to the DV-5a Valve being proper orientation with Valve Body, and 4 396 316
reset and the DV-5a Valve de-pres- then align Diaphragm Cover in proper (100) (536,9) (428,4)
surized, the interior of the DV-5a Valve orientation with Valve Body. Hand- 6 265 212
must be cleaned and inspected for tighten all fasteners. (150) (359,3) (287,4)
wear and damage. Damaged or worn
parts must be replaced. Replacement Step 3. Using crossdraw sequence 8 545 436
of the Diaphragm every ten years is to assure uniformity, wrench-tighten (200) (738,9) (591,1)
recommended, or more frequently if Long Hex Bolts and Short Hex Bolts
to appropriate torque values. Repeat TABLE C
inspections and/or wear and tear of DIAPHRAGM COVER BOLTS
the Diaphragm warrants more frequent crossdraw sequence two to three
times at incremental torque valves MINIMUM TORQUE
replacement.
until reaching the torque valves found
in Table C. With reference to Figure 1, make
NOTICE certain that the Diaphragm is correctly
The Diaphragm Cover may be removed Step 4. Inspect to assure all Hex Bolts oriented; otherwise, the DV-5a Deluge
between Steps 4 and 5 of the Valve are securely tightened. Valve cannot be properly set.
Setting Procedure instructions, since Step 5. Using the union, secure the Under-tightening the Diaphragm Cover
at that point the DV-5a Valve should MRA-1 Manual Reset Actuator to the Bolts can result in internal and external
be de-pressurized as evident by a Diaphragm Cover. leakage.
zero gauge reading on the Diaphragm
Gauge (K) and Water Supply Gauge (J), Step 6. Using the union, secure the Use only TYCO replacement fasteners
as well as no water discharging from Actuation Trim (Wet, Dry, or Electric). as specified in Figure 1.
the Automatic Drain Valve (F). Step 7. Replace the Copper Tube Do not apply adhesives, lubricants, or
To perform internal valve inspection Fitting between the Diaphragm Supply other substances to the Diaphragm or
between Steps 4 and 5 of the Valve Valve (P) and the Inverted Flare Shut- Valve Body.
Setting Procedure, remove the Dia- Off Valve (R).
phragm cover as follows: Step 8. Ensure that the unions and flare
Step 1. Close the Inverted Flare Shut- fittings are securely tightened.
Off Valve (R). Step 9. With the Diaphragm Supply
Step 2. Remove the Copper Tube Valve (P) closed, fully open the Inverted
Fitting between the Diaphragm Supply Flare Shut-Off Valve (R) stainless steel
Valve (P) and the Inverted Flare Shut- screw (approximately ½ in.) until resis-
Off Valve (R). tance is met so as not to break the
internal roll-pin. The internal roll-pin
Step 3. Loosen the union securing the stops the removal of the Inverted Flare
Actuation Trim (Wet, Dry, or Electric) Shut-Off Valve (R) stainless steel screw.
and remove the Actuation Trim.
Step 10. Proceed with Step 5 of the
Step 4. Loosen and remove the union Valve Setting Procedures section in this
between the Diaphragm Cover and the data sheet.
MRA-1 Manual Reset Actuator (N) and
remove the MRA-1 Manual Reset Actu-
ator (N) subassembly. NOTICE
If the water supply contains chemicals
Step 5. Remove the Diaphragm Valve which tend to attack a polyester fabric-
Cover hardware, then slowly remove reinforced, EPDM rubber or the five
the Diaphragm Cover and perform year inspection indicates a build-up of
internal valve inspection. Clean the
debris within the DV-5a Valve that could
valve interior and replace parts as
affect its proper operation, then the
necessary.
frequency of the internal valve inspec-
After cleaning and inspecting valve tion procedure must be appropriately
interior, and replacing parts as nec- increased.
essary, reinstall the Diaphragm Cover
TFP1306
Page 30 of 34

Limited GxG
Valve Size
AMERICAS1

Warranty 1-1/2 in. (DN40)


Wet
551010115
Dry
551010215
Electric
551010315
For warranty terms and conditions, visit
www.tyco-fire.com. 2 in. (DN50) 551010120 551010220 551010320
3 in. (DN80) 551010130 551010230 551010330
Ordering 4 in. (DN100) 551010140 551010240 551010340

Procedure 6 in. (DN150)


8 in. (DN200)
551010160
551010180
551010260
551010280
551010360
551010380
The TYCO DV-5a Automatic Water
Control Valves may be ordered as Notes;
1. AMERICAS DV-5A Valve with Trim and Butterfly Valve: Americas pressure switches,
follows: P/N 52-287-1-124 Solenoid Valve, and psi/kPa water pressure gauges are provided.
Pre-Assembled Ordering TABLE D
DV-5A Valves with Galvanized Valve DV-5 a VALVES WITH GALVANIZED VALVE TRIM AND BUTTERFLY VALVE
Trim and Butterfly Valve PART NUMBER SELECTION
Specify: Size (specify), DV-5 a Auto- — DELUGE SYSTEM —
matic Water Control Valve, G x G con-
nections with assembled galvanized (Wet Dry, or Electric) Actuation Valve
Americas (Wet Dry, or Electric) Actua- Trim for DV-5a Automatic Water Control
tion Valve Trim, complete with assem- Valves used in Deluge Fire Protection
bled Model BFV-300 Butterfly Valve, System, P/N (Ref. Table G)
P/N (Ref. Table D) DV-5A Valve Trim Accessories
Note: This arrangement is available (for separately ordered valve trim)
for EMEA and APAC upon request. Refer to Table H for separately ordered
Contact your local distributor. accessories not included with the Valve
Trim.
DV-5A Valves with Galvanized Valve
Trim DV-5A Valve Replacement Parts
Specify: Size (specify), DV-5 a Auto- Specify: (Description) for use with
matic Water Control Valve, (specify) (specify size) DV-5a Automatic Water
end connection with assembled gal- Control Valve, P/N (Ref. Figure 1)
vanized (Americas, EMEA, or APAC),
DV-5A Valve Trim Replacement
(Wet, Dry, or Electric) Actuation Valve
Trim, P/N (Ref. Table E) Parts
Specify: (Description) for use with
VdS Approved DV-5A Valves with DV-5a Valve Trim, P/N (Refer to Figures
Galvanized Valve Trim 10, 11, and 12 as applicable)
Specify: VdS Approved, Size (specify),
DV-5a Automatic Water Control Valve,
(specify) end connection with assem-
bled galvanized (Wet, Dry, or Electric)
Actuation Trim, P/N (Ref. Table J)
Separate Parts Ordering
DV-5A Valves
Refer to Table A for flange drilling
specifications.
Specify: Size (specify), DV-5 a Auto-
matic Water Control Valve, (specify)
end connection, P/N (Ref. Table F)
DV-5A Valve Trim
Specify: Size (specify), finish (specify),
TFP1306
Page 31 of 34

GxG AMERICAS1 EMEA2 APAC3


Valve Size Wet Dry Electric Wet Dry Electric Wet Dry Electric
1-1/2 (DN40) 550010115 550010215 550010315 550110115 550110215 550110315 550010115 550010215 550010315
2 in. (DN50) 550010120 550010220 550010320 550110120 550110220 550110320 550010120 550010220 550010320
3 in. (DN80) 550010130 550010230 550010330 550110130 550110230 550110330 550010130 550010230 550010330
4 in. (DN100) 550010140 550010240 550010340 550110140 550110240 550110340 550010140 550010240 550010340
6 in. (DN150) 550010160 550010260 550010360 550110160 550110260 550110360 550010160 550010260 550010360
8 in. (DN200) 550010180 550010280 550010380 550110180 550110280 550110380 550010180 550010280 550010380
F x F ANSI Wet Dry Electric Wet Dry Electric Wet Dry Electric
Valve Size
3 in. (DN80) 550020130 550020230 550020330 550120130 550120230 550120330 550020130 550020230 550020330
4 in. (DN100) 550020140 550020240 550020340 550120140 550120240 550120340 550020140 550020240 550020340
6 in. (DN150) 550020160 550020260 550020360 550120160 550120260 550120360 550020160 550020260 550020360
8 in. (DN200) 550020180 550020280 550020380 550120180 550120280 550120380 550020180 550020280 550020380
F x G ANSI Wet Dry Electric Wet Dry Electric Wet Dry Electric
Valve Size
3 in. (DN80) 550030130 550030230 550030330 550130130 550130230 550130330 550030130 550030230 550030330
4 in. (DN100) 550030140 550030240 550030340 550130140 550130240 550130340 550030140 550030240 550030340
6 in. (DN150) 550030160 550030260 550030360 550130160 550130260 550130360 550030160 550030260 550030360
8 in. (DN200) 550030180 550030280 550030380 550130180 550130280 550130380 550030180 550030280 550030380
T x T NPT Wet Dry Electric Wet Dry Electric Wet Dry Electric
Valve Size
1-1/2 in. (DN40) 550060115 550060215 550060315 — — — 550060115 550060215 550060315
2 in. (DN50) 550060120 550060220 550060320 — — — 550060120 550060220 550060320
F x F ISO Wet Dry Electric Wet Dry Electric Wet Dry Electric
Valve Size
3 in. (DN80) — — — 550140130 550140230 550140330 550040130 550040230 550040330
4 in. (DN100) — — — 550140140 550140240 550140340 550040140 550040240 550040340
6 in. (DN150) — — — 550140160 550140260 550140360 550040160 550040260 550040360
8 in. (DN200) — — — 550140180 550140280 550140380 550040180 550040280 550040380
F x G ISO Wet Dry Electric Wet Dry Electric Wet Dry Electric
Valve Size
3 in. (DN80) — — — 550150130 550150230 550150330 550050130 550050230 550050330
4 in. (DN100) — — — 550150140 550150240 550150340 550050140 550050240 550050340
6 in. (DN150) — — — 550150160 550150260 550150360 550050160 550050260 550050360
8 in. (DN200) — — — 550150180 550150280 550150380 550050180 550050280 550050380
T x T ISO Wet Dry Electric Wet Dry Electric Wet Dry Electric
Valve Size
1-1/2 in. (DN40) — — — 550170115 550170215 550170315 — — —
2 in. (DN50) — — — 550170120 550170220 550170320 — — —
Notes:
1. AMERICAS DV-5A Valve with Trim: Americas pressure switches, P/N 52-287-1-124 solenoid valve, and psi/kPa water pressure gauges are provided.
2. EMEA DV-5A Valve with Trim: EMEA pressure switches, P/N 52-287-1-124 solenoid valve, bar/psi water pressure gauges, and NPT to ISO threaded trim
adaptors for external connections are provided.
3. APAC DV-5A Valve with Trim: APAC pressure switches, P/N 52-287-1-124 solenoid valve, and psi/kPa water pressure gauges are provided.

TABLE E
DV-5 a VALVES WITH GALVANIZED VALVE TRIM
PART NUMBER SELECTION
— DELUGE SYSTEM —
TFP1306
Page 32 of 34

REGIONS OF TYPICAL AVAILABILITY (indicated by “✔”)


AMERICAS ✔ ✔ ✔ ✔ — — —
EMEA ✔ ✔ ✔ ✔ ✔ ✔ ✔
APAC ✔ ✔ ✔ ✔ ✔ ✔ ✔
Nominal Groove
Valve Size GxG F X F ANSI F x G ANSI T x T NPT F x F ISO F x G ISO T x T ISO
O.D.
1-1/2 in. (DN40) 1.990 in. (50,5 mm) 530010015 — — 530060015 — — 530070015
2 in. (DN50) 2.375 in. (60,3 mm) 530010020 — — 530060020 — — 530070020
3 in. (DN80) 3.500 in. (88,9 mm) 530010030 530020030 530030030 — 530040030 530050030 —
4 in. (DN100) 4.500 in. (114,3 mm) 530010040 530020040 530030040 — 530040040 530050040 —
6 in. (DN150) 6.625 in. (168,3mm) 530010060 530020060 530030060 — 530040060 530050060 —
8 in. (DN200) 8.625 in. (219,1 mm) 530010080 530020080 530030080 — 530040080 530050080 —
Notes:
1. Valves are typically provided with flange drilling per ANSI B16.1 (Class 125) or ISO (7005-2 PN16).
2. Upon request, valves can be provided with flange drilling per JIS B 2210 or AS 2129. In which case part numbers are not assigned.
TABLE F
DV-5 a VALVES PART NUMBER SELECTION

AMERICAS Galvanized1 AMERICAS Black1


Valve Size Wet Dry Electric Wet Dry Electric
1½ in. (DN40) 540000120 540000220 540000320 542000120 542000220 542000320
2 in. (DN50) 540000120 540000220 540000320 542000120 542000220 542000320
3 in. (DN80) 540000130 540000230 540000330 542000130 542000230 542000330
4 in. (DN100) 540000140 540000240 540000340 542000140 542000240 542000340
6 in. (DN150) 540000160 540000260 540000360 542000160 542000260 542000360
8 in. (DN200) 540000180 540000280 540000380 542000180 542000280 542000380
EMEA Galvanized 2
EMEA Black 2

Valve Size Wet Dry Electric Wet Dry Electric


1½ in. (DN40) 540100120 540100220 540100320 542100120 542100220 542100320
2 in. (DN50) 540100120 540100220 540100320 542100120 542100220 542100320
3 in. (DN80) 540100130 540100230 540100330 542100130 542100230 542100330
4 in. (DN100) 540100140 540100240 540100340 542100140 542100240 542100340
6 in. (DN150) 540100160 540100260 540100360 542100160 542100260 542100360
8 in. (DN200) 540100180 540100280 540100380 542100180 542100280 542100380
APAC Galvanized 3 APAC Black3
Valve Size Wet Dry Electric Wet Dry Electric
1½ in. (DN40) 540000120 540000220 540000320 542000120 542000220 542000320
2 in. (DN50) 540000120 540000220 540000320 542000120 542000220 542000320
3 in. (DN80) 540000130 540000230 540000330 542000130 542000230 542000330
4 in. (DN100) 540000140 540000240 540000340 542000140 542000240 542000340
6 in. (DN150) 540000160 540000260 540000360 542000160 542000260 542000360
8 in. (DN200) 540000180 540000280 540000380 542000180 542000280 542000380
Notes:
1. Americas Valve Trim: Pressure switches and/or solenoid valves for electric actuation are separately ordered.
2. EMEA Valve Trim: Pressure switches, solenoid valves for electric actuation, water pressure gauges, and BFV-300 Butterfly Valve are separately ordered.
NPT to ISO threaded adaptors are provided for External Trim Connections (drains, pressure switches, water motor alarms, etc.).
3. APAC Valve Trim: Pressure switches and/or solenoid valves for electric actuation are separately ordered.

TABLE G
DV-5 a VALVE TRIM
PART NUMBER SELECTION
— DELUGE SYSTEM —
TFP1306
Page 33 of 34

CONSIDERED FOR USE WITH


Data ACTUATION TYPE:
ACCESSORIES, DELUGE FIRE PROTECTION SYSTEMS P/N Sheet
Wet Pilot Dry Pilot Electric

Waterflow Pressure Alarm Switch, Potter PS10-2 (America/APAC) 25720 — ✔ ✔ ✔


Waterflow Pressure Alarm Switch PS10-1 (EMEA) 0260 — ✔ ✔ ✔
Air Pressure Alarm Switch, Potter PS40-2 (America/APAC) 25710 — — ✔ —
Air Pressure Alarm Switch PS40-1 (EMEA) 0262 — — ✔ —
Model WMA-1 Water Motor Alarm (America/APAC) 526301001P TFP921 ✔ ✔ ✔
Model WMA-1 Water Motor Alarm (EMEA) 526301021R TFP922 ✔ ✔ ✔
Model AMD-1 Air Maintenance Device 523242002 TFP1221 — ✔ —
Model AMD-2 Air Maintenance Device 523262001 TFP1231 — ✔ —
Model AMD-3 Nitrogen Maintenance Device 523282001 TFP1241 — ✔ —
Model MC-1 Manual Control Stations 522892001 TFP1382 ✔ ✔ —
Water Gauges with bar/psi 025500013 — ✔ ✔ ✔
Refer to Technical
Solenoid Valve for Releasing Service TFP2180 — — ✔
Data Sheet
600 psi Water Gauge psi/kPa (service pressure over 300 psi) 923431004 — ✔ ✔ ✔

TABLE H
DV-5 a VALVES ACCESSORIES
PART NUMBER SELECTION
— DELUGE SYSTEM —
TFP1306
Page 34 of 34

VdS Approved1
GxG
Valve Size Wet Dry Electric

1-1/2 (DN40) 550110115VDS 550110215VDS 550110315VDS


2 in. (DN50) 550110120VDS 550110220VDS 550110320VDS
3 in. (DN80) 550110130VDS 550110230VDS 550110330VDS
4 in. (DN100) 550110140VDS 550110240VDS 550110340VDS
6 in. (DN150) 550110160VDS 550110260VDS 550110360VDS
8 in. (DN200) 550110180VDS 550110280VDS 550110380VDS
F x F ANSI Wet Dry Electric
Valve Size
3 in. (DN80) 550120130VDS 550120230VDS 550120330VDS
4 in. (DN100) 550120140VDS 550120240VDS 550120340VDS
6 in. (DN150) 550120160VDS 550120260VDS 550120360VDS
8 in. (DN200) 550120180VDS 550120280VDS 550120380VDS
F x G ANSI Wet Dry Electric
Valve Size
3 in. (DN80) 550130130VDS 550130230VDS 550130330VDS
4 in. (DN100) 550130140VDS 550130240VDS 550130340VDS
6 in. (DN150) 550130160VDS 550130260VDS 550130360VDS
8 in. (DN200) 550130180VDS 550130280VDS 550130380VDS
F x F ISO Wet Dry Electric
Valve Size
3 in. (DN80) 550140130VDS 550140230VDS 550140330VDS
4 in. (DN100) 550140140VDS 550140240VDS 550140340VDS
6 in. (DN150) 550140160VDS 550140260VDS 550140360VDS
8 in. (DN200) 550140180VDS 550140280VDS 550140380VDS
F x G ISO Wet Dry Electric
Valve Size
3 in. (DN80) 550150130VDS 550150230VDS 550150330VDS
4 in. (DN100) 550150140VDS 550150240VDS 550150340VDS
6 in. (DN150) 550150160VDS 550150260VDS 550150360VDS
8 in. (DN200) 550150180VDS 550150280VDS 550150380VDS
T x T ISO Wet Dry Electric
Valve Size
1-1/2 in. (DN40) 550170115VDS 550170215VDS 550170315VDS
2 in. (DN50) 550170120VDS 550170220VDS 550170320VDS
Notes:
1. VdS Approved DV-5A Valve with Trim: EMEA pressure switches, P/N 52-287-1-124 solenoid valve, bar/psi water pressure gauges, NPT to ISO threaded
trim adaptors for external connections, and VdS required water column prevention drain components are provided.

TABLE J
VDS APPROVED DV-5 a VALVES WITH GALVANIZED VALVE TRIM
PART NUMBER SELECTION
— DELUGE SYSTEM —

1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700


© 2020 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.

NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;
TEFLON is a registered trademark of DuPont