Owner’s Manual
Automatic
Transfer Switch
Read the following information carefully before attempting to install, operate or service this
! equipment. Also read the instructions and information on tags, decals, and labels that may
be affixed to the transfer switch. Replace any decal or label that is no longer legible.
!
DANGER! Connection of a generator to an electrical system normally supplied by an electric
! utility shall be by means of suitable transfer equipment so as to isolate the electric system
from utility distribution system when the generator is operating (Article 701 Legally Required !
Standby Systems or Article 702 Optional Standby Systems, as applicable). Failure to isolate
electric system by these means may result in damage to generator and may result in injury
or death to utility workers due to backfeed of electrical energy.
Generac cannot possibly anticipate every possible This symbol points out important safety informa-
circumstance that might involve a hazard. The warn- ! tion that, if not followed, could endanger personal
ings in this manual, and on tags and decals safety and/or property.
affixed to the unit are, therefore, not all-inclusive. If a
procedure, work method or operating technique is This symbol points out potential explosion hazard.
used that Generac does not specifically recommend,
you must satisfy yourself that it is safe for you and This symbol points out potential fire hazard.
others. Also, make sure the procedure, work method
or operating technique choosen does not render the
transfer switch unsafe. This symbol points out potential electrical shock
hazard.
Throughout this publication, and on tags and
decals affixed to the generator, DANGER, WARNING, ! GENERAL HAZARDS !
CAUTION and NOTE blocks are used to alert the user
of special instruction about a particular operation
that may be hazardous if performed incorrectly or • Any AC generator that is used for backup power if
carelessly. Observe them carefully. Their definitions a NORMAL (utility) power source failure occurs,
are as follows: must be isolated from the NORMAL (utility) power
source by means of an approved transfer switch.
Failure to properly isolate the NORMAL and
DANGER STANDBY power sources from each other may
After this heading, are instructions that, if not result in injury or death to electric utility workers,
strictly complied with, will result in personal injury due to backfeed of electrical energy.
or property damage. • Improper or unauthorized installation, operation,
service or repair of the equipment is extremely
dangerous and may result in death, serious per-
sonal injury, or damage to equipment and/or per-
After this heading, are instructions that, if not sonal property.
strictly complied with, may result in personal injury
• Extremely high and dangerous power voltages are
or property damage.
present inside an installed transfer switch. Any
contact with high voltage terminals, contacts or
wires will result in extremely hazardous, and pos-
After this heading, are instructions that, if not strict- sibly LETHAL, electric shock. DO NOT WORK ON
ly complied with, could result in damage to equip- THE TRANSFER SWITCH UNTIL ALL POWER
ment and/or property. VOLTAGE SUPPLIES TO THE SWITCH HAVE
NOTE: BEEN POSITIVELY TURNED OFF.
• Competent, qualified personnel should install,
After this heading, are explanatory statements
operate and service this equipment. Adhere strict-
that require special emphasis.
ly to local, state and national electrical and build-
These safety warnings cannot eliminate the hazards ing codes. When using this equipment, comply
that they indicate. Common sense and strict compli- with regulations the National Electrical Code
ance with the special instructions while performing the (NEC), CSA Standard; C22.1 Canadian Electric
service are essential to preventing accidents. Code and Occupational Safety and Health
Four commonly used safety symbols accompany the Administration (OSHA) have established.
DANGER, WARNING and CAUTION blocks. The type • Never handle any kind of electrical device while
of information each indicates follows: standing in water, while barefoot, or while hands
or feet are wet. DANGEROUS ELECTRICAL
SHOCK MAY RESULT.
Generac® Power Systems, Inc.
Table of Contents
• Remove all jewelry (such as rings, watches, Safety Rules ..........................................Inside Front Cover
bracelets, etc.) before working on this equipment. Section 1 — General Information ....................................2
• If work must be done on this equipment while 1.1 Introduction............................................................2
standing on metal or concrete, place insulative 1.2 Equipment Description ..........................................2
mats over a dry wood platform. Work on this 1.3 Transfer Switch Data Plate ....................................2
equipment only while standing on such insulative 1.4 Transfer Switch Enclosure ....................................2
mats. 1.5 Safe Use Of Transfer Switch ..................................2
• Never work on this equipment while physically or Section 2 — Installation ....................................................3
mentally fatigued. 2.1 Introduction to Installation ....................................3
• Keep the transfer switch enclosure door closed and 2.2 Unpacking ..............................................................3
bolted at all times. Only qualified personnel 2.3 Mounting ................................................................3
should be permitted access to the switch interior. 2.4 Connecting Power Source and Load Lines ..............3
2.5 Connecting Start Circuit Wires ..............................4
• In case of an accident caused by electric shock,
2.6 Auxiliary Contacts ..................................................4
immediately shut down the source of electrical
2.7 Time Delay Neutral On-Off Switch ..........................5
power. If this is not possible, attempt to free the
2.8 Optional Accessories ..............................................5
victim from the live conductor but AVOID DIRECT
Section 3 — Operation ......................................................5
CONTACT WITH THE VICTIM. Use a nonconduct-
3.1 Functional Tests & Adjustments ............................5
ing implement, such as a rope or board, to free the
3.2 Manual Operation ..................................................6
victim from the live conductor. If the victim is
3.3 Voltage Checks........................................................7
unconscious, apply first aid and get immediate
3.4 Electrical Operation ................................................9
medical help.
3.5 Transfer Mechanism ..............................................9
• When an automatic transfer switch is installed for 3.6 Stationary and Moveable Main Contacts ................9
a standby generator set, the generator engine may 3.7 Main Contacts Operation ......................................10
crank and start at any time without warning. To 3.8 Switches and Advisory Lamps ..............................10
avoid possible injury that might be caused by such 3.9 System Test Switch ..............................................10
sudden start-ups, the system’s automatic start cir- 3.10 Standby-Operating Light ......................................11
cuit must be disabled before working on or around 3.11 Switch Position Lamps ........................................11
the generator or transfer switch. For that purpose, 3.12 Sequence of Operation..........................................11
a MAINTENANCE DISCONNECT is provided 3.13 Sequence of Operation Settings ............................12
inside the transfer switch. Always set the switch to 3.14 Transfer Switch Options ......................................14
its MANUAL position before working on the equip- 3.15 System Central Control (CPU) Circuit Board ........16
ment. Then place a “DO NOT OPERATE” tag on 3.16 Sensor and Timer Adjustments -
the transfer switch and on the generator. Sensing Circuit Board ..........................................16
3.17 Adjustments On Inphase Monitor
Control Circuit Board ..........................................17
3.18 Calibrating the Inphase Monitor
Control Circuit Board ..........................................19
3.19 Circuit Board Switch SW1 ....................................19
3.20 Adjustments On 7-Day Exerciser
Circuit Board ........................................................20
3.21 Optional Deluxe Exercise Circuit
Board Settings ......................................................21
3.22 Calibrate Utility Voltage Sensing
Circuit Board ........................................................21
Section 4 – Maintenance ................................................22
4.1 Operate Transfer Switch ......................................22
4.2 Clean and Inspect Transfer Switch ......................22
4.3 7-Day Exerciser ....................................................22
4.4 Lubrication ..........................................................22
4.5 Main Current Carrying Contacts ..........................22
4.6 Nine-Volt Battery ..................................................22
Section 5 – Mounting Dimensions ..............................23
Section 6 – Wiring Diagrams & Electrical
Schematics....................................................26
Section 7 – Exploded Views & Parts Lists ..................44
Section 8 – Warranty........................................Back Cover
Generac® Power Systems, Inc. 1
Section 1 — General Information
Generac GTS “Wn” Type Transfer Switch
2.1 INTRODUCTION TO INSTALLATION Wiring diagrams and electrical schematics are provided
This equipment has been wired and tested at the facto- in this manual. Power source and load connections are
ry. Installing the switch includes the following proce- made at a transfer mechanism, inside the switch enclo-
dures: sure.
• Mounting the enclosure.
2.4.1 TRANSFER MECHANISMS
• Connecting power source and load leads.
• Connecting the generator start circuit. The transfer mechanism may be either a 2-pole, 3-pole,
• Installing/connecting any options and accessories. or 4-pole type (Figure 2.1). The switch enclosure may
• Functional tests and adjustments. include a NEUTRAL BLOCK for connection of the NEU-
TRAL line. Connect power source and load leads to
2.2 UNPACKING transfer mechanism terminal lugs as follows:
Carefully unpack the transfer switch. Inspect closely for • LOAD Leads: Connect to terminals T1, T2, T3, etc.
any damage that might have occurred during shipment.
• NORMAL (utility) Source Leads: To terminals N1,
The purchaser must file with the carrier any claims for
N2, N3, etc.
loss or damage incurred while in transit.
• STANDBY (emergency) Source Leads: Connect to
Check that all packing material is completely removed transfer mechanism terminal lugs E1, E2, E3, etc.
from the switch prior to installation.
Figure 2.1 — Transfer Mechanism
Attach any lifting device to the transfer switch mounting
holes or brackets only. DO NOT LIFT THE SWITCH AT
ANY OTHER POINT.
062707-T
062707-T
062707-T
2.3 MOUNTING
Mounting dimensions for the transfer switch enclosure A
ON
B
OFF
STANDBY
062707-T
062707
062707-T
062707
-
062707-T
062707-T
2.4 CONNECTING POWER SOURCE AND Solderless, screw-type terminal lugs are standard.
Conductor sizes must be adequate to handle the maxi-
LOAD LINES mum current to which they will be subjected. The
installation must comply fully with all applicable codes,
DANGER standards and regulations.
Make sure to turn OFF both the normal (Utility) Before connecting wiring cables to terminals, remove
and standby (generator) power supplies before any surface oxides from the cable ends with wire brush.
trying to connect power source and load lines to If ALUMINUM conductors are used, apply joint com-
the transfer switch. Supply voltages are extremely pound. Tighten terminal lugs to the torque values on
high and dangerous. Contact with such high volt- page 4.
age power supply lines causes extremely haz- All power cables should enter the switch next to trans-
ardous, possibly lethal, electrical shock. fer mechanism terminals. Standard terminal lugs on
the transfer mechanism are solderless, screw-type.
Generac® Power Systems, Inc. 3
Section 2 — Installation
Generac GTS “Wn” Type Transfer Switch
The preceding applies to the standard 2-WIRE Auxiliary Contacts are rated 10 amps at 125 or 250
START SYSTEM. If a generator having a 3-WIRE volts AC. DO NOT EXCEED THE RATED VOLTAGE
START SYSTEM is to be installed, using the option- AND CURRENT OF THE CONTACTS.
al 3-wire start system. See TRANSFER SWITCH
OPTIONS, Section 3.15.
! nect transfer switch from all power sources by (N1, N2, N3).
approved means, such as a main circuit • Window “A” OFF, Window “B” ON - LOAD terminals
breaker(s). (T1, T2, T3) are connected to STANDBY terminals
A manual HANDLE is shipped with the transfer switch. (E1, E2, E3).
Manual operation must be checked BEFORE the trans-
fer switch is operated electrically. To check manual
operation, proceed as follows (Figure 3.1):
Do not use excessive force when operating the
!
1. In the transfer switch enclosure, set the transfer switch manually or you could damage
Maintenance Disconnect switch to MANUAL. This the manual handle.
prevents the generator from starting automatically
as soon as you turn OFF the UTILITY power source. ◆ 3.2.1 TRIP TO NEUTRAL POSITION
2. If so equipped, turn the generator’s Manual-Off-Auto
Remove handle from the square lug at the upper left
switch to OFF.
corner of the switch. Insert a screwdriver into the “T”
3. Turn OFF both NORMAL and STANDBY power sup- hole and push inward. The main contact should trip to
plies to the transfer switch, with whatever means the neutral position and the word OFF should appear in
provided (such as the main line circuit breakers). both windows “A” and “B”. See Figure 3.2.
3.4 ELECTRICAL OPERATION can check the automatic operating sequences and
Test transfer system electrical operation as follows: times. See SENSOR AND TIMER ADJUSTMENTS,
Section 3.16. For a detailed description of the auto-
1. On the Utility Voltage Sensor circuit board, check matic operating sequences, see SEQUENCE OF
that the UTILITY ON lamp (LED) is ON. OPERATION, Section 3.13.
2. On the enclosure door, check that the Switch 6. When the test is complete, return the System Test
Position-Utility lamp is ON. Switch to its AUTOMATIC MODE position. R etrans-
fer back to the UTILITY (NORMAL) power source.
The generator should shut down according to cir-
cuit board timers.
The UTILITY ON lamp (on circuit board) and the
! SWITCH POSITION-UTILITY lamp ( on enclosure
door) must both be ON before proceeding to
3.5 TRANSFER MECHANISM
The transfer mechanism main contacts are actuated by
Step 3.
an electro-magnetic coil. Power for that coil’s operation
3. Refer to the appropriate owner’s manual. Be sure is taken from the side to which the LOAD is being trans-
the standby generator is prepared for automatic ferred. Thus, transfer to any power source cannot occur
operation. unless that power source is available to the switch.
4. In the switch enclosure, set the Maintenance
Disconnect switch to AUTOMATIC.
5. Set the System Test switch to its NORMAL TEST
3.6 STATIONARY AND MOVEABLE MAIN
MODE position. Generator startup and transfer to CONTACTS
the STANDBY power source should occur. Refer to LOAD or “T” contacts, bolted to an insulated plastic
the SEQUENCE OF OPERATION, Section 3.13. pole piece are stationary. The NORMAL (UTILITY) and
NOTE: STANDBY (EMERGENCY) contacts are moveable
(Figure 3.5). The contacts are actuated by means of a
All systems are equipped with the Inphase Monitor closing coil and mechanical linkage. The pole assem-
Control board, and advisory lights on the circuit blies which retain the stationary and moveable main
board will light up to indicate operation of the vari- contacts are assembled together and retained by thru-
ous solid state timers that control automatic opera- bolts. Either 2, 3 or 4 pole assemblies may be used to
tion. By observing these lights (LED’s), the operator form a 2, 3 or 4-pole mechanism.
3.10 STANDBY-OPERATING LIGHT • If voltage dropout lasts longer than Line Interrupt
This light will go ON to tell the operator that the stand- Delay setting, circuit board action closes the auto-
by generator is running and that STANDBY (emergency) matic start circuit (Wires 178 and 183). When that
source power is available to the transfer switch. circuit closes, engine cranks and starts as controlled
by a circuit board in the generator’s control panel.
• Once the standby generator starts, circuit board is
3.11 SWITCH POSITION LAMPS turned ON (go to Sequence 3).
◆ 3.11.1 EMERGENCY ◆ 3.12.3 SEQUENCE 3 - ENGINE MINIMUM RUN
This light will go ON when main current-carrying con- AND WARMUP TIMERS
tacts have actuated to their STANDBY (EMERGENCY) • This timer establishes the minimum length of time
position and that power source is available to the trans- for the generator to run before it shuts down. Timer
fer switch. prevents shutdown of a cold engine.
◆ 3.11.2 UTILITY • Timer is adjustable from five to 30 minutes, (factory
setting is about 20 minutes).
This light will go ON when main contacts have actuated • An engine warmup timer is also turned ON. This
to NORMAL (utility) position and that power supply is timer permits engine to stabilize and warm up before
available to the transfer switch. loads are transferred to STANDBY. Timer is
The switch is equipped with the Inphase Monitor adjustable from five seconds to three minutes. (facto-
Control circuit board. The sensors and timers are ry setting is about one minute).
adjustable (see SENSOR AND TIMER ADJUSTMENTS,
Section 3.17). ◆ 3.12.4 SEQUENCE 4 - STANDBY VOLTAGE AND
FREQUENCY SENSORS
3.12 SEQUENCE OF OPERATION • If generator AC output voltage and frequency is above
When acceptable NORMAL source voltage is available, the setting of these sensors, loads transfer to the
observe the following: STANDBY power source.
• Utility voltage Sensor circuit board monitor’s NOR- • Adjust Standby Voltage Sensor between 75% and 95%
MAL source voltage and UTILITY ON lamp is ON. or nominal supply frequency, (factory setting is about
• Switch Position - UTILITY lamp is ON. 90%).
• Transformer reduced LOAD (T) terminal voltage is • Adjust Standby Frequency Sensor between 80% and
delivered to the 7-day exerciser board to operate the 90% or nominal supply frequency; factory setting is
7-day exercise timer. about 90%.
Automatic timers and sensors on the Inphase Monitor NOTE:
Control circuit board can be monitored by observing You can bypass the engine warmup timers by setting
light emitting diodes (LED’s) next to the sensor/timer the Engine Warmup Timer Bypass switch to ON.
adjustments. Loads are transferred to STANDBY as soon as gener-
ator AC voltage and frequency have reached the set-
◆ 3.12.1 SEQUENCE 1 - VOLTAGE DROPOUT tings of the Voltage and Frequency sensors without
having to wait for the engine to warm up.
• UTILITY source voltage drops below 75-95% of the
Voltage Pickup Setting (factory set to about 80%).
The UTILITY ON lamp goes OFF. ◆ 3.12.5 SEQUENCE 5 - VOLTAGE PICKUP
• Voltage Dropout sensor is factory set to about 80% of • If the UTILITY source voltage is restored above the
“pickup” voltage. setting of the Voltage Pickup sensor, Sequence 5
• Voltage dropout below this sensor’s setting triggers begins.
Sequence 2. • Adjust Voltage Pickup between 85% to 95% of the
normal supply voltage from the UTILITY source, (fac-
◆ 3.12.2 SEQUENCE 2 - LINE INTERRUPT DELAY tory setting is about 90%).
• UTILITY voltage dropout below setting of Voltage
Dropout sensor turns on a line Interrupt Delay ◆ 3.12.6 SEQUENCE 6 - RETURN TO UTILITY
Timer. TIMER
• Line Interrupt Delay may be set for 0.1 to 10 seconds, • This timer prevents retransfer that a Utility Source
(factory set to about 5 seconds). voltage surge or transient might cause.
• Adjust timer between one to 30 minutes, (factory set-
ting is about five minutes).
• If UTILITY voltage remains above the setting of the • Adjust timer between one to 30 minutes, factory set-
Voltage Pickup Sensor for the time interval of the ting is about 10 minutes).
Return to Utility Timer setting, loads are re-trans- NOTE:
ferred back to the UTILITY source.
Actual time between retransfer back to UTILITY and
◆ 3.12.7 SEQUENCE 7 - ENGINE COOL DOWN engine shutdown is whichever is longer of the Engine
Cool Down timer setting or any time remaining on
TIMER Engine Minimum run timer.
• After the switch retransfers loads back to UTILITY,
After the switch automatically retransferred loads back
this timer starts. When the interval has “timed out”,
to the UTILITY power source and generator has shut
the automatic start circuit (Wires 178/183) is opened,
down, the system is “armed” for Sequence 1 again.
and the engine shuts down.
• Timer permits engine to run at noload for a fixed
time, so the engine internal temperature can stabilize
before shutting down.
Figure 3.12 — Signal Before Transfer ◆ 3.14.5 MANUAL BYPASS FOR RETURN TO
NORMAL
The Manual Bypass for Return to Normal option
includes a door mounted toggle switch and associated
wiring (Figure 3.14).
This option will override the Return to Utility timer on
the GTS Controller PCB. When the toggle switch is acti-
vated (pushed down), and the Return to Utility timer is
active, the remaining time on the timer will be cleared.
Once the timer is cleared the GTS mechanism will
transfer and the LOAD will be connected to the UTILITY
source.
If the toggle switch is not activated, the Return to Utility
timer will function as normal. The retransfer of the GTS
NOTE: will be delayed until it times out.
This delay is not active on a Normal source failure.
Transfer during Normal source failure is immediate. Figure 3.14 — Manual Bypass for Return to
Normal
◆ 3.14.4 REMOTE AUTO CONTROL
The Remote Auto Control option includes a customer
connection terminal strip and the associated wiring
(Figure 3.13).
This option allows for remote starting of the generator
and transfer of the GTS to connect the LOAD to the
EMERGENCY source. This is done by paralleling the
Fast Test switch. A description of the Fast Test Mode
function can be found in Section 3.9.3 on page 10.
Reference wiring diagram for further details. The cus-
tomer connections are made on TS3. The associated
wire numbers are 0, 177, 178 and 201.
Figure 3.13 — Remote Auto Control ◆ 3.14.6 PREFERRED SOURCE SELECTOR SWITCH
The Preferred Source Selector Switch option includes a
door mounted rotary 2-position selector switch, cus-
tomer connection terminal strip and associated wiring
(Figure 3.9).
This option is normally used when there is not a
UTILITY supply present and both sources are a genera-
tor. It may be used when it is desirable for either source
of power to serve as the preferred source. The other
power source then becomes the backup source. The
switch is manually operated
When the rotary switch is in position Source #1 the
GTS will perform as a normal system. Generator #1
will be the primary source and generator #2 will be the
backup source.
When the rotary switch is in position #2, the GTS will
signal generator #2 to start and the GTS will transfer
the LOAD to generator #2. If Source #2 fails, Source #1
will be signaled to start. The GTS mechanism will trans-
fer the LOAD to Source #1. When Source #2 returns to
service, the GTS will transfer the LOAD to Source #2.
Reference wiring diagram No. 0D8035 for further ◆ 3.14.10 NEMA 3R ENCLOSURE
details. The customer connections are made on TS2.
The associated wire numbers are 178, 183, 253 and National Electrical manufacturer’s Association (NEMA)
254. 3R enclosure. This type of enclosure is intended for use
outdoors to protect enclosed parts from windblown
dust and water. The enclosure is sealed for dust, rain or
◆ 3.14.7 MANUAL 3-POSITION SELECTOR sleet and is ice resistant. Ask the local Dealer/Distributor
SWITCH (NORMAL-AUTO-STANDBY) or consult the factory for details.
The Manual 3-Position Selector Switch option includes
a door mounted rotary 3-position selector switch and ◆ 3.14.11 NEMA 4 ENCLOSURE
associated wiring (Figure 3.15). National Electrical Manufacturer’s Association (NEMA)
Under certain conditions it may be desirable to manu- 4 enclosure. This type of enclosure is intended for use
ally select the active power source. This can be done by indoors or outdoors to provide a degree of protection
means of the door mounted selector switch. The against windblown dust and rain, splashing water, and
Normal - Auto - Standby, 3-position selector switch pro- hose-directed water: undamaged by the formation of ice
vides the following: on the enclosure. Ask the local Dealer/Distributor or
1. When the switch is set to the Normal position, the consult the factory for details.
Load will be connected to the Normal source and
any other transfer will be inhibited. ◆ 3.14.12 NEMA 4X ENCLOSURE
2. When the switch is set to the Auto position, the ATS National Electrical Manufacturer’s Association (NEMA)
will function as normal. See the Sequence of 4X enclosure. This type of enclosure is intended for use
Operation section 3.13, page 12. indoors and outdoors to provide a degree of protection
3. When the switch is set to the Standby position, the against corrosion, windblown dust and rain, splashing
Load will be connected to the Emergency source water, and hose-directed water: undamaged by the
and any other transfer will be inhibited. formation of ice on the enclosure. Ask the local
Reference the wiring diagram No. 0D8035 for further Dealer/Distributor or consult the factory for details.
details.
◆ 3.14.13 ADDITIONAL OPTIONS
Figure 3.15 — Manual 3-Position Switch For information on additional options not covered in
this manual, ask the local Dealer/Distributor or consult
the factory.
Figure 3.19 — Circuit Board Switch SW1 3.20 ADJUSTMENTS ON 7-DAY EXERCISER
CIRCUIT BOARD
◆ 3.20.1 SET EXERCISE DAY AND TIME OF DAY
On the day, and at the time of day chosen for the system
to start and exercise, press the GENERATOR EXER-
CISE switch and hold it there for about 15 seconds
(Figure 3.20). The generator will start and exercise
seven days later at the selected time of day.
Figure 3.20 — 7-Day Exerciser
4.4 LUBRICATION
Operating parts inside the transfer mechanism have
been properly lubricated at the time of assembly. Under
normal conditions, no additional lubrication should be
required. The service technician should lubricate all
recommended points whenever major transfer mecha-
nism components are replaced.
TO
AX BX
ATS1 BTS1 CUSTOMER
LOAD
2 3
LS
SC TC
Generac GTS “Wn” Type Transfer Switch
Connection Diagram - Drawing No. 073658
1
5 6
C
AUX
4
LS
ATS2 BTS2 AUX
Section 6 — Electrical Schematics and Wiring Diagrams
A2 B2 AT2 BT2
NOTE:
ALL CONTACTS SHOWN WITH "B" POWER SOURCE (STANDBY)
MAIN POWER CONTACTS CLOSED
IN UTILITY POSITION
107
235
148 148
147
126 N2
N1 N1 N1
SW3 1 1 3 N1 N2 N3
TR
235
126 9
N1
126
107
194
194 NC NC
TD ATS
193 107
107 COM
0 126
N2
233
192 177
191
191 NC
N2
23
126
126
126
107
107
125
107
194
194
NO
234
E2 E1 E2 E3
0
191
191
177
148
147
192
177 COM
B1
A1
B2
A2
BT1
BT2
AT2
SW2
CL RL YL 107
0 107
191
191
177
193
192
N1
N2
N1 107 T1 T2 T3
0 126
201
178
E1 E1
202
202
203 126 234 E2
126 E1
N2
192
177
194 H1 H4 T1 T1
177 T2 T2
194
194
TR2 185 185 185
CPU N3
TS X2 X1
23 NOTE:
178
WIRE NO. N3 & 226
USED ON 3 Ø
185 E2 SYSTEM ONLY
193 0
199
178
N1 N1 N1
202
23 E1
191 0 N2 N2
N3 N3
185
15 0 224 224
H1 H4 225 225
178
183
183
4 177 177 TS LEGEND
ATS TRANSFER SWITCH CONTACTOR
178 CL
178 CPU CONNECTOR, CENTRAL PROCESSING UNIT
CUSTOMER CONNECTION
P CONNECTOR, UTILITY VOL. SENSING PCB
178 178
S CONNECTOR, UTILITY VOL. SENSING PCB
224 SW1 SWITCH, MAINTENANCE DISCONNECT
Generac GTS “Wn” Type Transfer Switch
Wiring Diagram - 240V with CPU - Drawing No. 74324
Section 6 — Electrical Schematics and Wiring Diagrams
TS TERMINAL STRIP
YL YELLOW LIGHT, STANDBY OPERATING
T1
N1
T3
T2
107
T1
T3
T2
E2 185 185
N2
107
233
14
65
PSW AT2 AT1 A2 A1 TR2
H1
FM
ATS N1 N2 N3
VM
X2
185
16 240V
0
E2
64
N2
126
107
X1
199
202
19 COM COM
E2
N2
H4
T1
NO E1 E2 E3
18 NC
T1
T2
T2
1 2
204 BT2 BT1 B2 B1
Generac GTS “Wn” Type Transfer Switch
T1 T2 T3
0
185
E1
126
E2
E2
PSW
148
147
234
AM
0
E2
178
177
67
191
204
4 L12
1 191 HI
X2
191
59
57
58
TD
240V YL LO
192 L13 L2
CT3 TR X1 192
6 9 H4
107 108 E1 D
CT1 L11
SW1 23 LO CPU
A
Electrical Schematic - 240V with CPU - Drawing No. 74325
TR PCB
CL OPTIONAL B L1
Section 6 — Electrical Schematics and Wiring Diagrams
194 +12V
AM METER, AMP RL B
7
CL CLEAR LIGHT, SWITCH POSITION UTILITY 1
A L10
CR RELAY, 3 WIRE START CONTROL 0 0 235 193 LO
7 4 SW3
FM METER, FREQUENCY 178
HM METER, HOUR L3 L4 L6 L7
PSW SWITCH, PHASE SELECTOR SW2
18
RL RED LIGHT, SWITCH POSITION EMERGENCY
136
213
178 201
SW2 SWITCH, SYSTEM TEST A B
SW3 SWITCH, TDN ON/OFF 10 CR 183 177 202
COM.
TR1 TRANSFORMER, STANDBY SENSING CUSTOMER CONNECTION
177
TR2 TRANSFORMER, LOAD POWER SUPPLY
VM METER, VOLT
N.C. STOP
178 178 178
N.O. START
YL YELLOW LIGHT, STANDBY OPERATING
T1
13 N2 177 HI
S2
T2
65
TR SW1
N1
1 MAN
FM
T3
T1
T3
N2
N3
T2
VM
20 19 PSW 107 3 185 185
N2
E2 N1
233
18 17 N2
64
1 2 AT2 2 A1 TR2
204 LS AX ATS
N1 N2 N3 T1
4 H1 X1 E2
COM COM 185 185 7 DAY
LS H2
X2 18/20V E6 EXERCISE
0 0
199
NC NO
202
T1
E2
AM
N2
126
107
7 8 PSW H3 X3 TIMER
208/240V
AUX H4 PCB
E1
N1
N2
T2 TEST 195
204
178
177
12 T1 T2 T3 POINT LO HI
67
COM COM T2 E5 E4
59
57
58
TR3 E7
CT3 178
BTS1 NC NO N1 2 WIRE START
BX E9
Generac GTS “Wn” Type Transfer Switch
H1 X1 177
CT2 E1 E2 E3 264
198
202
E2
X3
148
147
H3
234
208/240V
E2 E2
YL
N2 L13
1
E1
E2
LEGEND 126
L4
A1 A2 A POWER SOURCE SIDE(ON) 264 L12
AM METER, AMP (OPT) 7 E1
SW1 H1 L2
AT1 AT2 A POWER SOURCE SIDE(TRIP) MAN 191 191
6 9 L5
SWITCH, TRIP CONTROL 107 108 L1
BTS1 BTS2 202 266 N.C.
AUT
ATS TRANSFER SWITCH CONTACTOR 18/20V
AUX SWITCH, AUXILIARY TR
208/240V
266 194 265
Ax Bx SWITCH, CONTROL H4
E2 B A * SW4 L11
B1 B2 267
0
Electrical Schematic - 240V Inphase - Drawing No. 91287
178
177
202
236
240
237
238
HM METER, HOUR (OPT) CR A 235 193
7 SW2
PSW SWITCH, PHASE SELECTOR (OPT) A B
1 10 CR 183 177
RL RED LIGHT, SWITCH POSITION EMERGENCY
SC COIL, SELECTIVE
SR 7 4 SW1 FAST TEST L14
RELAY, SIGNAL BEFORE TRANSFER (OPT) MAN 201
SW1
183 NORMAL TEST
SW2 SWITCH, SYSTEM TEST CR 203
OPTIONS 2 WIRE START AUT
SW3 SWITCH, TDN ON/OFF
18
136
213
L3
CUSTOMER CONNECTION 202 202
TC COIL, TRIP L7
TD RELAY, TIME DELAY 178 178 178
2 WIRE START L8
TR1 178 177
COM.
TRANSFORMER, STANDBY SENSING
TR2 TRANSFORMER, LOAD POWER SUPPLY 202
TRANSFORMER, UTILITY SENSING
177
N.C. STOP
VM METER, VOLT (OPT)
N.O. START
YL YELLOW LIGHT, STANDBY OPERATING 201
107
235
148 148
147 147
126 N2
N1 N1 N1
SW3 1 1 3 N1 N2 N3
TR 6
235
126 7 9 7 9
A A
N1
B B
126
107
194
194 NC
108 TD NO
193 ATS
107 COM
0 126 NB
N2
233
192 177
191 SW1
191 NC
23
126
126
126
107
107
125
107
194
194
234
00 00 00 E1 E2 E3 NO
0 177
191
191
148
147
192
177 COM
A1
B2
A2
SW2
BT1
AT1
BT2
AT2
CL 107
0 107 107
191
192
N1
107 T1 T2 T3
E1
0 126
178
E1 E1
126 234
191
201
177
193
202
203 126 126 E1
00 00 00
192
177
1 194 H1 H4 T1 T1
2 177 T2 T2
194
194 194 E2 E2
4 TR2 185 185 185
5 CPU N3
6 TS X2 X1
23 NOTE:
7
WIRE NO. N3 & 226
USED ON 3 Ø
9 185 SYSTEM ONLY
193 0
199
178
178
N1 N1 N1
23 E1
191 0 N2 N2
N3 N3
185
0 224
H1 H4 225 225
178
178
183
183
4 177 177 TS CL CLEAR LIGHT, SWITCH POSITION UTILITY
CPU CONNECTOR, CENTRAL PROCESSING UNIT
2-WIRE START NB BLOCK, NEUTRAL
178 CUSTOMER CONNECTION
178 178 RL RED LIGHT, SWITCH POSITION EMERGENCY
178 178 S CONNECTOR, UTILITY VOL. SENSING PCB
T1
SENSING
S3 PCB
T2 178 LO
S4
177 HI
S2
1
126 126 126 125
15 7
T1
T3
T2
9
SW1
T1
N1
T3
T2
107
N2
N3
65
00
107
PSW
233
FM
64
X2
185
19
240V
0
126
107
X1
199
202
18 COM COM
00
00
00
H4
T1
00 NO E1 E2 E3
NC
T1
1 2
T2
204
T2
BT2 BT1 B2 B1
5
Generac GTS “Wn” Type Transfer Switch
PSW
AM T1 T2 T3
0
185
E1
126
E2
148
147
234
9
67
204
0
178
177
4
H1 TR1 L15 L14
E2
59
57
58
191
L12 L5
1 191 HI
CT3 X2
TD 191
240V YL LO
192 L13 L2
TR X1 192
CT1
6 9 H4
107 108 E1 D
L11
SW1 23 LO
A CPU
LEGEND
AM METER, AMP TR PCB
CL OPTIONAL B L1
ATS TRANSFER SWITCH CONTACTOR
Section 6 — Electrical Schematics and Wiring Diagrams
194 +12V
Electrical Schematic - 416V 3P with CPU - Drawing No. 74329
18
SW1 SWITCH, MAINTENANCE DISCONNECT
136
213
SW2 178 201
SW3 SWITCH, TDN ON/OFF A B
TD RELAY, TIME DELAY 10 CR 183 177 202
OPTIONAL
SW1 203
TR1 TRANSFORMER, STANDBY SENSING 2-WIRE START
COM.
TR2 TRANSFORMER, LOAD POWER SUPPLY CUSTOMER CONNECTION
177
VM METER, VOLT
YL YELLOW LIGHT, STANDBY OPERATING
N.C. STOP
178 178 178
N.O. START
OPTION - 3 WIRE START
Section 6 — Electrical Schematics and Wiring Diagrams
Generac GTS “Wn” Type Transfer Switch
Wiring Diagram - 416V 3P Inphase - Drawing No. 91399
1-2
N1 P1
3-4 224 18-25V
5-6
N2
7-8 X
225
00
9 - 10 XX X N3 UTILITY
11 - 12 X
226
X INDICATES CLOSED VOLTAGE
P4
T3 227 LO
SENSING
00
PCB
T2 S3
T1 178 LO
2 WIRE START S4
177 HI
T1
13 S2
T2
00
65 TR SW1
N1
1 MAN
FM
T1
T3
T3
N2
N3
T2
VM
PSW TD
20 19 107 3 185 185
00 00 N1
233
N2
64
1 2 AT2 AT1 A2 A1 TR2
204 ATS
ATS2 LS T1
3 4 N1 N2 N3 H1 X1 E2
M COM 185 185 7 DAY
6 E6
X2 18V EXERCISE
416V 0 0
199
C NO
202
AM T1
7 8 PSW H3 X3 TIMER
00
126
107
9 10 AUX H4 PCB
E1
N1
N2
T2 TEST
204
195
178
177
12 T2 T3 POINT LO HI
67
TC SC COM COM T2 E5 E4
59
57
58
CT3 E7
178
NC NO N1
BTS1 BX 2 WIRE START E9
Generac GTS “Wn” Type Transfer Switch
X1
CT2 E1 E2 E3 264 177
198
202
BT2 BT1 B2 B1
CT1 X2 18V
416V 202 202
00 X3
148
147
234
E1
126 H4
E2
LEGEND YL
N2 L13
A1 A2 A POWER SOURCE SIDE(ON) 1
L4
AM METER, AMP (OPT) TD 264 L12
AT1 AT2 A POWER SOURCE SIDE(TRIP) 7 E1
SW1 H1 L2
SWITCH, TRIP CONTROL MAN 191 191
BTS1 BTS2 6 9 H2 18V L5
107 108 L1
ATS TRANSFER SWITCH CONTACTOR 416V 202 266 N.C.
AUT
AUX SWITCH, AUXILIARY 18V
TR H3 X3 L16
Ax Bx SWITCH, CONTROL 266 194 265
B1 B2 B POWER SOURCE SIDE(ON) H4
E2 A * SW4
BT1 BT2 B POWER SOURCE SIDE(TRIP) 267
0
D
178
177
CR RELAY, 3 WIRE START CONTROL (OPT) ALL RELAY CONTACTS SHOWN WITH
CT1,CT2,CT3 TRANSFORMER, CURRENT (OPT) ATS IN UTILITY POSITION TR
Electrical Schematic - 416V 3P Inphase - Drawing No. 91288
L6 INPHASE
D
Section 6 — Electrical Schematics and Wiring Diagrams
0 194
FM METER, FREQUENCY (OPT) MONITOR
HM METER, HOUR (OPT) TD SW3
178 ON L10 PCB
CR SR A 235 193
NB BLOCK, NEUTRAL SW2
7 4 9 6
PSW SWITCH, PHASE SELECTOR (OPT) 1 A B
10 CR 183 177
SC COIL, SELECTIVE
7 4 SW1 FAST TEST L14
SR RELAY, SIGNAL BEFORE TRANSFER (OPT) MAN
236
240
237
238 201
183 NORMAL TEST L15
SW2 SWITCH, SYSTEM TEST OPTIONS CR 203
AUT
SW3
18
SWITCH, TDN ON/OFF 2 WIRE START
136
213
L3
CUSTOMER CONNECTION 202 202
TC COIL, TRIP L7
TD RELAY, TIME DELAY 178 178 178
2 WIRE START L8
178 177
COM.
TR1 TRANSFORMER, STANDBY SENSING
TR2 TRANSFORMER, LOAD POWER SUPPLY 202
TR3 TRANSFORMER, UTILITY SENSING
N.C. STOP
177
VM METER, VOLT (OPT)
N.O. START
YL YELLOW LIGHT, STANDBY OPERATING 201
107
235
148 148
147 147
126 N2
N1 N1 N1
SW3 1 1 3 N1 N2 N3 N4
TR 6
235
126 7 9 7 9
A A
N1
B B
126
107
194
194 NC
108 TD NO
193 107 ATS
107
0
N2
233
192 177
191
191 N4
23
N3
N4
126
126
126
107
107
125
107
185
194
194
E4
234
0 177 E1 E2 E3 E4
191
191
148
147
192
177
B1
A1
B2
A2
SW2
BT1
AT1
BT2
AT2
CL 107
0 107 107
191
192
N1
N1 N1 107
E1 T1 T2 T3 T4
0 126
178
E1 E1
126 234 E4
191
201
177
193
202
202
203 126 126 N4 N4
192
177 E1 E1
1 194 H1 H4 T1 T1
2 177
194 T2 T2
3 194 194 E2 E2
4 TR2
185 185 185
5 TS N3 N3
6 X2 X1
23
8
9 185
10 193 0
199
178
178
11 23 E1
12 191 0
13
185 N1 N1 N1
15 0
N2 N2
H1 H4
N3 N3 LEGEND
1 224 ATS TRANSFER SWITCH CONTACTOR
TR1 224 224
2 225 CL CLEAR LIGHT, SWITCH POSITION UTILITY
P 3 226 225 225 CPU CONNECTOR, CENTRAL PROCESSING UNIT
P CONNECTOR, UTILITY VOL. SENSING PCB
4 227 X2 X1
226 226 RL RED LIGHT, SWITCH POSITION EMERGENCY
S CONNECTOR, UTILITY VOL. SENSING PCB
227 227
191 SW2 SWITCH, SYSTEM TEST
192 SW3 SWITCH, TDN ON/OFF
199 1 UTILITY
183
2 202 SENSING TR2 TRANSFORMER, LOAD POWER SUPPLY
S 3 178 TD RELAY, TIME DELAY
INTERFACE
178
183
4 177 177 TR RELAY,, TRANSFER
TS TERMINAL STRIP
YL YELLOW LIGHT, STANDBY OPERATING
178 CUSTOMER CONNECTION
178 178
178 178
224
Wiring Diagram - 416V 4P with CPU - Drawing No. 88790
Generac GTS “Wn” Type Transfer Switch
Section 6 — Electrical Schematics and Wiring Diagrams
226
227
T2
14 13 1
T1
T4
65 126 126 126 125
7
9
FM SW1
T1
N1
T3
T2
107
T4
N2
N3
N4
TD TR
16 15
T3
185 185
N4
107
E4
233
PSW
20 19 VM
AT2 AT1 TR2
H1
ATS2
ATS
N1 N2 N3 N4
18 17 ATS1
64 COM COM COM
X2
185
NO NO 416V 21V
NC NC
0
E4
T1
N4
126
107
1 2
204
199
202
AUX H4
3 4
5 6 T1 T2 T3 T4
AM COM COM T2
7 PSW
NC NO
9 10 BTS1 BX
204
BT2 BT1 B2 B1 E1 E2 E4
11 12 AUX
67
Generac GTS “Wn” Type Transfer Switch
N4
59
E4
57
58
148
147
234
185
CT3 E4 E4
E1
126
E2
178
177
CT2
H1 TR1 L15 L14
191
CT1
L12 L5
POSITION
1 191 191 HI
X2
CONTACTS 123 OFF TD 191
7 416V 21V YL LO
192 L13 L2
TR X1 192 192
1-2
3-4 X OPTIONAL 6 9 H4 SYSTEM
192
5-6 107 108 E1 D
7-8 CENTRAL
INSTRUMENT L11
SW1 HM 23 23 LO
PACKAGE A CONTROL
(CPU)
CL OPTIONAL B L1
LEGEND 194 194 +12V PCB
RL B
A1 A2 A POWER SOURCE SIDE(ON) 7
Section 6 — Electrical Schematics and Wiring Diagrams
TD
Electrical Schematic - 416V 4P with CPU - Drawing No. 88791
AM METER, AMP 1
AT1 AT2 A POWER SOURCE SIDE(TRIP) L10
A
0 0 235 193 193 LO
BTS1 BTS2
ATS TRANSFER SWITCH CONTACTOR 7 4 SW3
178
AUX SWITCH, AUXILIARY L3 L4 L6 L7
Ax Bx SWITCH, CONTROL
B1 B2 B POWER SOURCE SIDE(ON) CR SW2
18
BT1 BT2 B POWER SOURCE SIDE(TRIP)
136
213
178 201
CL CLEAR LIGHT, SWITCH POSITION UTILITY FAST TEST
CR RELAY, 3 WIRE START CONTROL 2-WIRE START 183 177 202
CT1,CT2,CT3 TRANSFORMER, CURRENT
CUSTOMER CONNECTION NORMAL TEST
D DIODE
FM METER, FREQUENCY
A B SW1 203
10 CR 183
HM METER, HOUR
COM.
177
PSW SWITCH, PHASE SELECTOR OPTIONAL 2-WIRE START
RL RED LIGHT, SWITCH POSITION EMERGENCY
N.C. STOP
178 178 178
N.O. START
SWITCH, MAINTENANCE DISCONNECT
SWITCH, SYSTEM TEST
SWITCH, TDN ON/OFF
COIL, TRIP OPTION - 3 WIRE START
TD RELAY, TIME DELAY
TR RELAY, TRANSFER
1-2
ALL RELAY CONTACTS SHOWN WITH
ATS IN UTILITY POSITION N1 P1
3-4 224 18-25V
5-6
N2
7-8 X
225
9 - 10 XX X N3 UTILITY
11 - 12 X
226
X INDICATES CLOSED VOLTAGE
P4
T3 227 LO
SENSING
T4 PCB
T2 S3
178 LO
T1 2 WIRE START S4
N4 N4 177 HI
S2
T1
13
T2
T4
65 TR SW1
N1
1 MAN
T1
T3
T4
N2
N3
T2
N4
T3
VM TD
20 19 PSW 107 3 185 185
N4
E4 N1
233
N2
64
AT2 AT1 A2 A1 TR2
1 2 ATS
204 ATS2 LS
N1 N2 N3 N4 T1
H1 X1 E2
3 4 M COM 185 185 7 DAY
5 6 X2 E6 EXERCISE
416V 0 0
199
C NO
202
T1
E4
N4
126
107
AM H3 X3 TIMER
8 PSW AUX H4 PCB
E1
N1
N2
T2 TEST 195
178
177
204
T2 T3 POINT LO HI
11 12
67
TC SC COM COM T2 E5 E4
TR3
59
57
58
E7
CT3 178
NC NO N1
BTS1 BX H1 X1 2 WIRE START E9
Generac GTS “Wn” Type Transfer Switch
E1 E2 E3 E4 264 177
198
CT2
202
BT2 BT1 B2 B1
X2 18V
CT1 416V 202 202
N4
E4
X3
148
147
234
E4 E4 H4 YL
N2 L13
1
E1
LEGEND
E2
126
L4
A1 A2 A POWER SOURCE SIDE(ON) TD 264 L12
AM METER, AMP (OPT) 7 E1
SW1 H1 L2
AT1 AT2 A POWER SOURCE SIDE(TRIP) MAN 191 191
ATS1 ATS2 6 9 H2 18V L5
SWITCH, TRIP CONTROL 107 108 L1
BTS1 BTS2 416V 202 266 N.C.
AUT
ATS TRANSFER SWITCH CONTACTOR 18V
TR H3 X3 L16
AUX SWITCH, AUXILIARY 266 194 265
Ax Bx SWITCH, CONTROL H4
E2 A * SW4
B1 B2 B POWER SOURCE SIDE(ON) 267
0
D
178
177
0 194
D DIODE (OPT) MONITOR
FM METER, FREQUENCY (OPT) TD SW3
178 ON L10 PCB
236
240
237
238
CR A 235 193
LS SWITCH, SELECTIVE SW2
7
PSW SWITCH, PHASE SELECTOR (OPT) 1 A B
10 CR 183 177
SC COIL, SELECTIVE
7 4 SW1 FAST TEST L14
SR RELAY, SIGNAL BEFORE TRANSFER (OPT) MAN 201
183 NORMAL TEST L15
SW2 SWITCH, SYSTEM TEST OPTIONS CR 203
AUT
SW3 2 WIRE START
18
SWITCH, TDN ON/OFF
136
213
L3
CUSTOMER CONNECTION 202 202
TC COIL, TRIP L7
TD RELAY, TIME DELAY 178 178 178
2 WIRE START L8
178 177
COM.
TR1 TRANSFORMER, STANDBY SENSING
TR2 TRANSFORMER, LOAD POWER SUPPLY 202
TR3 TRANSFORMER, UTILITY SENSING
N.C. STOP
177
VM METER, VOLT (OPT)
N.O. START
YL YELLOW LIGHT, STANDBY OPERATING 201
107
107
110
110
110
107
107
107
1 1 3
235
N1 N2 N3
6
7 9
N1
N2
N3
A A
23 B B
194 NC
208
235 235 NO
194 ATS LEGEND
COM ATS TRANSFER SWITCH CONTACTOR
110
110
110
107
194
TS CL CLEAR LIGHT, SWITCH POSITION UTILITY
0 CPU CONNECTOR, CENTRAL PROCESSING UNIT
N1
N2
192 P CONNECTOR, UTILITY VOL. SENSING PCB
208
191 RL RED LIGHT, SWITCH POSITION EMERGENCY
191 NC S CONNECTOR, UTILITY VOL. SENSING PCB
107
108
194
110 126
SW1 205 NO SW2 SWITCH, SYSTEM TEST
0 201 107 E1 E2 E3 SW3 SWITCH, TDN ON/OFF
191
191
185
148
147
192
177 COM
110
107
194
233
234
B1
A1
194 TR2
B2
A2
TRANSFORMER, LOAD POWER SUPPLY
BT1
AT1
BT2
AT2
CL RL SW2 TR3,TR4 TRANSFORMER, STEP DOWN
YL
125 233 TR RELAY,, TRANSFER
177 177 TS TERMINAL STRIP
177 234 T1 T2 T3 YL YELLOW LIGHT, STANDBY OPERATING
0 206 107 107
0
203 T1 110 110
23
191
193
177
192
194
202
202
191
185
177
192
194 H1 H4
178
H1 H4
T1
T1
E1
T2
T2
E2
126
125
183
185
206
205
TR2
CPU
X2 X1 TR4
178
N1
N2
N3
199
178
193 N1 N1
23 0 0 126
191 0 0 125 N2 N2
E1
E2 N3
185
E1 E2 224 224
0
H1 H4 225 225
H1 H2 226 226
H4
T1
T2
1
205
T1
TR1
T2
2
191
178
192
177
183
206
227 227
P 3
4 X2 X1
191 TR3 UTILITY
SENSING
192 INTERFACE
X4 X1
1
226
225
227
224
2
S 206 205
178
178
178
183
4 177 177 TS
T1 T1
T2 T2
178 CUSTOMER CONNECTION
178
178 178
224 224 224
Wiring Diagram - 480V with CPU - Drawing No. 74332-B
Generac GTS “Wn” Type Transfer Switch
Section 6 — Electrical Schematics and Wiring Diagrams
108
X4
126 N1 224 224 18-25V
ATS IN UTILITY POSITION 1 H1
N2 225 225 18-25V
TR TR4 P3 UTILITY
7 N3 226 226
P4
VOLTAGE
T3 227 227 LO
SENSING
T2 PCB
S3
T1 178 178 LO
2-WIRE START
S4
110
177 177 HI
T1
14 13 S2
T2
65 110 110
9
T1
N1
N1
T3
T2
N2
N2
N3
16 15
TD
3
T3
107 185 185
126
233
PSW 205
20 19 VM
AT2 AT1 A2 A1 TR2
LS AX ATS H1
N1 N2 N3
18 17
64 COM COM COM COM
X2
480V 185
NO NO OR 24V
NC NC
T1 600V 0
126
1 2 X1
204
199
202
C AUX
110
107
205
3 4 H4
5 6 T1 T2 T3
AM TC SC COM COM T2
7 8 PSW
NC NO
9 10 BTS1 BX
204
BT2 BT1 B2 B1 E1 E2 E3
11 12 AUX
67
205
0
59
57
58
126
185
234
Generac GTS “Wn” Type Transfer Switch
E1
110
E2
148
147
CT3
7 1
205
178
CT2 177
H1 H4 TR1 L15 L14
FM E1
191
CT1
X1 L12 L5
205 191 191 HI
X2
OFF 480V 480V 191
14 - 13 240V OR OR 24V YL LO
206
20 - 19
600V 600V 192 L13 L2
107
107
TR X4
18 - 17 192 192
1-2
OPTIONAL 6 9 H1
192
5-6 107 208 206 E2 D SYSTEM
7-8
9 - 10
INSTRUMENT TR3 L11
SW1 HM 23 23 LO CONTROL
A
X INDICATES CLOSED PACKAGE
TR (CPU)
CL
OPTIONAL
B L1
LEGEND 194 194 +12V PCB
RL B
A1 A2 A POWER SOURCE SIDE(ON) 7
AM
Electrical Schematic - 480V with CPU - Drawing No. 74333-B
1
AT1 AT2 A POWER SOURCE SIDE(TRIP)
Section 6 — Electrical Schematics and Wiring Diagrams
A L10
ATS1 ATS2 0 0 235 193 193 LO
SWITCH, TRIP CONTROL CR
BTS1 BTS2
ATS TRANSFER SWITCH CONTACTOR 7 4 SW3
178
AUX SWITCH, AUXILIARY L3 L4 L6 L7
Ax Bx SWITCH, CONTROL
CR SW2
18
BT1 BT2 B POWER SOURCE SIDE(TRIP)
136
213
C COIL, CLOSING 178 201
FAST TEST
CR RELAY, 3 WIRE START CONTROL 2-WIRE START 183 177 202
TRANSFORMER, CURRENT
CUSTOMER CONNECTION NORMAL TEST
D DIODE
FM METER, FREQUENCY
B SW1 203
10 183
HM METER, HOUR
COM.
LS SWITCH, SELECTIVE 177
2-WIRE START
PSW SWITCH, PHASE SELECTOR
N.C. STOP
178 178 178
N.O. START
RL RED LIGHT, SWITCH POSITION EMERGENCY
SC
SW1 SWITCH, MAINTENANCE DISCONNECT
SW2 SWITCH, SYSTEM TEST
SW3 SWITCH, TDN ON/OFF OPTION - 3 WIRE START
TD RELAY, TIME DELAY
TR RELAY, TRANSFER
108
X4 N1 224 18-25V
126
7-8 X H4 P2
1 N2 225 18-25V
9 - 10 XX X UTILITY
P3
TR TR4 N3 226 18-25V
X INDICATES CLOSED 7 VOLTAGE
P4
T3 227 LO
SENSING
T2
PCB
T1 S3
178 LO
2 WIRE START S4
110
T1
14 13 177 HI
S1 S2
T2
65
110 110
16 15
N1
T3
T1
N2
N3
T2
9
126
20 19
T3
107 3 185 185
126 N1
18 17
233
64 205 N2
1 2 AT2 AT1 A2 A1
204
ATS
4 N1 N2 N3 TR2
5 6 M COM T1
H1 X1 E2
AM 185 185 7 DAY
C NO H2
7 8 PSW T1 480V X2 20V E6 EXERCISE
0 0
199
202
10 AUX
110
107
TIMER
205
126
H3 X3
204
N1
N2
11 12 T1 T2 T3 H4 E1 PCB
67 TEST 195
178
177
59
POINT
57
58
TC SC COM COM T2 LO HI
CT3
E5 E4
BTS2 BTS1 NC NO TR3
CT2 BX E7
178
BT2 BT1 B2 B1 E1 E2 E3 N1
AUX 2 WIRE START E9
Generac GTS “Wn” Type Transfer Switch
X1
264 177
198
202
H2
126 480V X2 20V
202 202
148
147
205
234
110
600V H3 X3
E1
E2
TD
LEGEND YL
7 1 FM N2 L13
107
205
A1 A2 A POWER SOURCE SIDE(ON) E1
AM METER, AMP (OPT) H1 H1 L4
AT1 AT2 A POWER SOURCE SIDE(TRIP) 205 191 264 L12
ATS1 ATS2 TR SW1 480V 480V X2 L2
SWITCH, TRIP CONTROL
107
BTS1 BTS2 MAN 240V OR OR 202 191
206
ATS TRANSFER SWITCH CONTACTOR 6 9 600V 600V L5
107 208 X4 X3 20V L1
AUX SWITCH, AUXILIARY 266 266 N.C.
Wiring Diagram - 480V Inphase - Drawing No. 91290
AUT
H4 L16
E2 194
B1 B2 B POWER SOURCE SIDE(ON) 265
BT1 BT2 B POWER SOURCE SIDE(TRIP) D B A * SW4 L11
SR 267
0
178
177
202
236
240
237
SW3
238 201
183 NORMAL TEST L15
SW4 SWITCH, RETURN TO NORMAL BYPASS (OPT) OPTIONS CR 203
AUT
2 WIRE START
18
TC COIL, TRIP
136
213
L3
CUSTOMER CONNECTION 202 202
TR RELAY, TRANSFER L7
TR1 TRANSFORMER, STANDBY SENSING 178 178 178
2 WIRE START L8
178 177
COM.
TR3 TRANSFORMER, UTILITY SENSING
TR4 TRANSFORMER, SWITCH OPERATION 202
TR5 TRANSFORMER, SWITCH OPERATION
177
N.C. STOP
VM METER, VOLT (OPT)
N.O. START
YL YELLOW LIGHT, STANDBY OPERATING 201
A B C
FOR FOR FOR
400/416/480/600 VOLT 208/240 VOLT 240 VOLT
THREE PHASE THREE PHASE SINGLE PHASE
OPERATION OPERATION OPERATION
1 1
N1 N1
2 6 2 6 2 6
A 3 7 C 3 N1 A 3 7 A
E E
4 8 4 8 N1 4
B
1 5 1 5 1
N2 227 224 N2 227 224 225
N2
B 2 6 2 6 N2 2 6
D D
A 3 7 N1 A 3 7 A
N1 E E 227
4 8 4 8 4 8
N2
B
1 5 1 5
N2 224
C 2 6 N3 2 6
A 3 7 3 7
C
N3
227 225 227 225
N1
4 8 4 8
N2
N3
224
225
226
227
226 226
N3 N3
224 224
Generac GTS “Wn” Type Transfer Switch
Electrical Schematic - Interface - Drawing No. 70067617-B
Section 6 — Electrical Schematics and Wiring Diagrams
N1
N1
N2
N3
N2
N3
224
225
226
227
224
225
226
227
88 90
60
85 SENSING PCB-
COVER ONLY
61 60
89
COVER * NOTES:
NOT USED ON 1-PHASE, 3 POLE
24 SYSTEMS OR ANY 4 POLE SYSTEM.
MANUFACTURING NOTE
1
P.C.BOARD WIPE OFF AICHI INSIGNIA USING SOLVENT,
FROM TRANSFER SWITCH CONTACTOR (ITEM #1)
P.C. INSTALLATION (TYPICAL)
2
REMOVE AICHI MODEL AND RATING DECAL.
28 2 38 39 34 2 54 54 41 42 43
DECAL
82
DECAL
66 66 66
52
37 37 37
OUTSIDE
29 30 31 32
27
5
9 **
45 49
22 26
74 73 87
54
* ONLY ON
7 1 80
16 400/416V SYSTEM
36
47 48 3
35
75
57 DECAL
58 15 10 11
54
4 25 79
51
33
DECAL 86 DECAL
59 54 84
54 17 40 34
17
26 18
71 50
69 24
12
17
54
17
54 71
DECAL
84
17
18 53
78 ** 21
62
33
19
20
25 79 55 70 85
22 26
65
ITEM PART NO. QTY. DESCRIPTION ITEM PART NO. QTY. DESCRIPTION
1 064787 1 SWITCH ASSEM, TRANSFER, 100A, 3 - POLE 073619-D DECAL TESTING SEQUENCE 300 AMP
064788 SWITCH ASSEM, TRANSFER, 100A, 4 - POLE 073619-E DECAL TESTING SEQUENCE 400 AMP
064790 SWITCH ASSEM, TRANSFER, 200A, 3 - POLE 36 0A2111 2 10-32 - 5/16 FASTENER
064791 SWITCH ASSEM, TRANSFER, 200A, 4 - POLE 37 057514 3 HOLDER LAM
064793 SWITCH ASSEM, TRANSFER, 300A, 3 - POLE 38 038150 4 WASHER FLAT -NO.8
064794 SWITCH ASSEM, TRANSFER, 300A, 4 - POLE 39 0A2284 4 8-32 X 1/2 FASTENER
064796 SWITCH ASSEM, TRANSFER, 400A, 3 - POLE 40 036917 8 PPHMS 8-32 X 3/8"
064797 SWITCH ASSEM, TRANSFER, 400A, 4 - POLE 41 090388 3 M6-1 .0 X 12 TAPTITE
2 063617 2 RELAY, TRANSFER 42 049811 3 WASHER FLAT - M6
3 063384 LUG ASSEMBLY NEUTRAL - 100 AMP 43 022097 3 WASHER LOCK-M6
063657 1* LUG ASSEMBLY NEUTRAL - 200 & 300 AMP 44 058000-L 1 TRIC-NUT - M6 100-200 AMP
062633 LUG ASSEMBLY NEUTRAL - 400 AMP 45 0A2312 2 10-32 - 1" FASTENER 100 AMP
4 057329 1 LUG GROUNDING 200-300-400 AMP 0A2311 2 1/4-20-1 SCREW 150-400 AMP
062684 LUG GROUNDING 100 AMP 46
5 074509 1 BRACKET SAFE DISCONNECT SWITCH 47 024526 1 SCREW TAPTITE - 5/16"-18 X 3/4"
6 074511 1 DECAL MAINTENANCE DISCONNECT SWITCH 48 022129 1 WASHER LOCK-5/16"
7 055868 1 SWITCH SAFETY DISCONNECT -4PDT 49 022678 1 CC LOC-TITE TYPE A
8 099084 9 LUG SOLDERLESS - 100 AM 50 064113 1 STUD MANUAL HANDLE INCLUDES WIN NUT
062706 LUG SOLDERLESS - 200&300 AM 51 072252 1 GROMMET
062707 LUG SOLDERLESS - 400 AM 52 074398 1 NEMA 12 ENCLOSURE 100 AMP
9 074513-B 1 DECAL, 100 AMP, 3 POLE SWITCH 074399 NEMA 12 ENCLOSURE 150-200-300-400 AMP
074513-F DECAL, 100 AMP, 4 POLE SWITCH 53 063378 8 TIE-DOWN CABLE
074513-C DECAL, 200 AMP, 3 POLE SWITCH 54 057593 11 TIE-DOWN CABLE
074513-G DECAL, 200 AMP, 4 POLE SWITCH 55 067629 1 BOARD UTILITY VOLTAGE SENSING
074513-D DECAL, 300 AMP, 3 POLE SWITCH 56 ---- - NOT USED
074513-H DECAL, 300 AMP, 4 POLE SWITCH 57 067626 1 BOARD SYSTEM CONTROL CPU
074513-E DECAL, 400 AMP, 3 POLE SWITCH 58 071775 1 COVER CPU
074513-J DECAL, 400 AMP, 4 POLE SWITCH 59 063582 1 DOOR CIRCUIT BOARD COMPARTMENT
10 073662-B 2 COVER 100 AMP, SWITCH 60 064525 20 SUPPORT CIRCUIT BOARD
073662-C COVER, 100 AMP, 4-POLE SWITCH 61 063526 24 SCREW IN - NO. 6-32 X 3/8"
073662-D COVER, 200 AMP, 3-POLE SWITCH 62 046669 2 JUMPER TERMINAL BLOCK
073662-E COVER, 200 AMP, 4-POLE SWITCH 63 ---- - NOT USED
073662-F COVER, 300 & 400 AMP 3-POLE SWITCH 64 ---- - NOT USED
073662-G COVER, 300 & 400 AMP 4-POLE SWITCH 65 064152 1 SUB-PLATE - 100 AMP
11 067210-A 1 DECAL GROUND 064151 SUB-PLATE - 150-400 AMP
12 074525 1 DECAL MANUAL OPERATION 66 040587 3 LAMP
13 073617-B 1 DECAL 100 AMP 3-POLE SWITCH 67 ---- - NOT USED
073617-F DECAL 100 AMP 4-POLE SWITCH 68 ---- - NOT USED
073617-C DECAL 200 AMP 3-POLE SWITCH 69 063981 2 GUIDE SIDE
073617-G DECAL 200 AMP 4-POLE SWITCH 70 020A67616 1 COVER, UTILITY VOLTAGE SENSING BOARD
073617-D DECAL 300 AMP 3-POLE SWITCH 71 064126 2 TRANSFORMER 480 VOLTS ONLY
073617-H DECAL 300 AMP 4-POLE SWITCH 72 073964 1 HARNESS WIRING - 100 AMP
073617-E DECAL 400 AMP 3-POLE SWITCH 073965 HARNESS WIRING - 150-200-300-400 AMP
073617-J DECAL 400 AMP 4-POLE SWITCH 73 0BH-45761 4 SUPPORT SWITCH COVER - 200 AMP
14 063357 1 DECAL MAC - DT - GTS 0BJ-45761 SUPPORT SW. COVER - 100-300-400 AMP
15 046357 1 BLOCK TERMINAL 480V SYSTEM 74 063986 4 KNOB HOLD-DOWN
057701 BLOCK TERMINAL - 208, 240, 416 VOLT 75 026902 3 EA TAPTITE #8-32 X 1/4" 3 PER POLE
SYSTEM 76
16 028199 1 SWITCH TIME DELAY NEUTRAL BYPASS 77 ---- - NOT USED
17 056893 20 SCREW CRIMPTITE - NO. 10-24 X 1/2" 78 062209 1 DECAL UL
18 047616 2 TRANSFORMER 79 022131 10 WASHER FLAT-3/8"
19 046689 1 BLOCK, TERMINAL 80 026902 1 TAPTITE #8-32 X 1/4" 416 VOLT ONLY)
20 063580 1 DECAL, TERMINAL BLOCK 81 ---- - NOT USED
21 063321 1 HANDLE, MANUAL 82 064510 1 DECAL TERMINAL NOTE
22 063578 1 PLATE, DATA 83 ---- - NOT USED
23 NOT USED 84 030A67617 1 INTERFACE - "GTS" UTIL. (416/480 VOLTS 3Ø)
24 068212 1 COMPARTMENT, CIRCUIT BOARD 030B67617 INTERFACE - "GTS" UTIL. (208/240 VOLTS, 3Ø)
25 064101 10 NUT FLANGED LOCK - 3/8"-16 030C67617 INTERFACE - "GTS" UTIL. (240 VOLTS 1Ø)
26 036261 10 RIVET POP - 1/8" X 0.23" 072160 INTERFACE - "GTS" UTILITY (400V, 3Ø)
27 073681 1 GTS - DECAL 85 068337 4 STANDOFF HEX 1"LG. STD. SENSING ONLY)
28 063385 1 DECAL - AUTOMATIC SEQUENCE 86 054199 1 DECAL HIGH VOLTAGE
29 057328 1 LENS LAM -CLEAR 87 064210 4 COVER SUPPORT - 100-300-400 AMP
30 057327 1 LENS LAM -RED 064210 8 COVER SUPPORT - 150-200 AMP
31 057325 1 LENS LAM -YELLOW 88 072829 3 GSKT LM HOLDER LENS (NEMA 3R ENCL.
32 055142 1 SWITCH MODE -DPDT ONLY)
33 0A1661 4 RIVET, POP.156 D X.5 LG. 89 074548 3 GASKET, LAMPHOLDER (NEMA 3R ENCL.
34 022264 12 WASHER, LOCK -NO.8 ONLY)
35 073619-B 1 DECAL, TESTING SEQUENCE 100 AMP 90 072828 1 SW. BOOT, WTRPROOF (NEMA 3R ENCL.
073619-C DECAL TESTING SEQUENCE 200 AMP ONLY)
NOTES:
98
* NOT USED WITH 1Ø, 3 POLE OR 4 POLE SYSTEMS.
55 54 96
** USED WITH 200, 300 AND 400 AMP SWITCH.
55
97
COVER MANUFACTURING NOTES:
LAMP HOLDER TOGGLE SWITCH
21 1. WIPE OFF AICHI INSIGNIA USING SOLVENT, FROM
32 25 2 71 35 36 38 39 85 73 86 20 83 22
99 23
24 OUTSIDE DOOR
8 72
42 46
31 46 **
13
77 62 ONLY ON
400/416V
26 34 57 27 34 57 28 34 57
82 SYSTEM
5
33 1
73
6
69 70 90 3
29
48
76 10
75 68
65
15
44 45
7
80
30
58
63 4 63
11
79 78
12
47 40
9 72
74 51 81
14 15
59
95 94 49 19
16
67 21 ***
15
73
53
49
52 50
41 43
30
23
84
22 83
91
17 59 18 56 61 23 20
ITEM PART NO. QTY. DESCRIPTION ITEM PART NO. QTY. DESCRIPTION
1 064787 1 SWITCH, TRANSFER - 100 AMP, 3-POLE 5 074509 1 BRACKET, SAFETY DISCONNECT
064788 1 SWITCH, TRANSFER - 100 AMP, 4-POLE SWITCH
064790 1 SWITCH, TRANSFER - 200 AMP, 3-POLE 6 074511 1 DECAL, SAFETY DISCONNECT SWITCH
064791 1 SWITCH, TRANSFER - 200 AMP, 4-POLE 7 055868 1 SWITCH, SAFETY DISCONNECT - 4PDT
064796 1 SWITCH, TRANSFER - 300/400 AMP, 8 099084 - LUG, 100-150 AMP SWITCH (3/POLE)
3-POLE 062706 - LUG, 200, 300 AMP SWITCH (3/POLE)
064797 1 SWITCH, TRANSFER - 300/400 AMP, 062707 - LUG, 400 AMP SWITCH (3/POLE)
4-POLE 9 36917 8 PPHMS 8-32 X 3/8
2 063617 2 RELAY, TRANSFER 10 073662-B 2 COVER, 100 AMP, 3-POLE SWITCH
3* 063384 1 LUG, NEUTRAL - 100 & 150 AMP SWITCH 073662-C 2 COVER, 100 AMP, 4-POLE SWITCH
063657 1 LUG, NEUTRAL - 200 & 300 AMP SWITCH 073662-D 2 COVER, 200 AMP, 3-POLE SWITCH
062633 1 LUG, NEUTRAL - 400 AMP SWITCH 073662-E 2 COVER, 200 AMP, 4-POLE SWITCH
4 062684 1 LUG, GROUNDING - 100 & 150 AMP 073662-F 2 COVER, 300/400 AMP, 3-POLE SWITCH
SWITCH 073662-G 2 COVER, 300/400 AMP, 4-POLE SWITCH
057329 1 LUG, GROUNDING - 200 - 400 AMP 11 067210-A 1 DECAL, GROUND
SWITCH 12 074525 1 DECAL, MANUAL OPERATION
46 Generac® Power Systems, Inc.
Section 7 — Exploded Views & Parts Lists
Generac GTS “Wn” Type Transfer Switch
100-400A Inphase Assembly - Drawing No. 091186-B
ITEM PART NO. QTY. DESCRIPTION ITEM PART NO. QTY. DESCRIPTION
13 073617-B 1 DECAL, 100 AMP, 3 & 4-POLE SWITCH 58 063998 1 BATTERY, 9 VOLT
073617-C 1 DECAL, 200 AMP, 3 & 4-POLE SWITCH 59 046669 - JUMPER, TERMINAL BLOCK
073617-D 1 DECAL, 300 AMP, 3 & 4-POLE SWITCH 60 073964 - HARNESS-WRG 100 AMP SW (NOT
073617-E 1 DECAL, 400 AMP, 3 & 4-POLE SWITCH SHOWN)
14 057701 - BLOCK, TERMINAL - 8 POS. 073965 - HARNESS-WRG 150-400A SW (NOT
15 056893 14 SCR. CRIMPTITE #10-24 X 1/2” SHOWN)
16 090975 3 TRANSFORMER - 25VA 61 062209 1 DECAL, UL
17 046689 - BLOCK, TERMINAL - 4 POS. 62 026902 1 SCR. TAPTITE #8-32 X 1/4” 100/150A SW
18 091466 1 DECAL, TERMINAL BLOCK 63 030A67617 1 INTERFACE, UTILITY 416/480V 3-PHASE
19 063321 1 HANDLE, MANUAL TRANSFER 030B67617 1 INTERFACE, UTILITY 208/240V 3-PHASE
20 63578 1 PLATE, DECAL 086961 1 INTERFACE, UTILITY 240V 1-PHASE
21 068212 1 COMPARTMENT, PRINTED CIRCUIT 072160 1 INTERFACE, UTILITY 400V 3-PHASE
BOARD 072158 1 INTERFACE, UTILITY 600V 3-PHASE
22 064101 10 NUT, FLANGED LOCK 3/8” - 16 64 068337 4 STANDOFF, HX SPCR 1.0”L (STD SENS.)
23 036261 14 RIVET, POP 1/8” X .23” SS 65 054199 1 DECAL, HIGH VOLTAGE
24 073681 1 DECAL, GTS 66 064761 - TIE-WRAP, 5 5/8” LG. (NOT SHOWN)
056298 1 DECAL, GTS NEMA 3R ENCLOSURE 67 063981 2 GUIDE, SIDE
090257 1 DECAL, CTS NEMA 3R ENCLOSURE 68 063357 1 DECAL, MAC DT GTS
087227 1 DECAL, CTS 69 0BH-45761 4 SUPPORT, SWITCH COVER 200 AMP
25 091478 1 DECAL, AUTOMATIC SEQUENCE 0BJ-45761 4 SUPT., SWITCH COVER 100, 300-400A
26 057328 1 LENS, LAMP CLEAR 70 063986 4 KNOB, HOLD-DOWN
27 057327 1 LENS, LAMP RED 71 022264 12 WASHER, LOCK #8
28 057325 1 LENS, LAMP YELLOW 72 026902 - SCR., TAPTITE #8-32 X 1/4”
29 055142 1 SWITCH, MODE DPDT 73 063378 31 TIE-DOWN, CABLE
30 0A1661 4 RIVET, POP .156 D X .5 LG. 74 063996 1 CVR., EXERCISER CIRCUIT BRD. (STD.)
31 0A2311 2 1/4-20-1” SCREW 064298 1 CVR., EXERCISER CIRCUIT BRD. (DLX.)
32 073619-B 1 DECAL, TESTING SEQUENCE 100 AMP 75 0722525 1 GROMMET
073619-N 1 DECAL, TESTING SEQUENCE 150 AMP 76 028199 1 SWITCH, TIME DELAY NEUTRAL BYPASS
073619-C 1 DECAL, TESTING SEQUENCE 200 AMP 77 074513-B 1 SWITCH PART #64787
073619-D 1 DECAL, TESTING SEQUENCE 300 AMP 074513-C 1 SWITCH PART #64790
073619-E 1 DECAL, TESTING SEQUENCE 400 AMP 074513-D 1 SWITCH PART #64793
33 0A2111 2 10-32 X 5/16” FASTENER 074513-E 1 SWITCH PART #64796
34 057514 3 HOLDER, LAMP 074513-F 1 SWITCH PART #64788
35 038150 4 WASHER, FLAT #8 074513-G 1 SWITCH PART #64791
36 0A2284 4 8-32 X 1/2 FASTENER 074513-H 1 SWITCH PART #64794
37 091477 5 RIVET, NYLON “PUSH” 074513-J 1 SWITCH PART #64797
38 090388 3 M6-1.0 X 12 TAPTITE 78 092734 1 PCB, INPHASE MONITOR
39 049811 3 WASHER, FLAT M6 79 094446 1 COVER, INPHASE CONTROL
40 058000-L 1 TRIC-NUT - M6 X 1.0 THD. 80 029357 2 RIVET
41 091472 1 DUCT, WIRE 24 1/4” LG. 81 063982 1 CLIP, BATTERY
1 DUCT, WIRE 33 1/2” LG. 82 067989 9 NUT, FLANGED LOCK M8-1.25
42 0A2312 2 10-32 - 1” FASTENER 83 022131 10 WASHER, FLAT 3/8”
43 91472-A 1 COVER, WIRE DUCT 24 1/4” LG. 84 083736 1 DECAL, CSA
1 COVER, WIRE DUCT 33 1/2” LG. 85 022097 3 WASHER, LOCK M6
44 024526 1 SCR., TAPTITE 5/16”-18 X 3/4” 86 064510 1 DECAL, TERMINAL NOTE
45 022129 1 WASHER, LOCK 5/16” 87*** 033139 4 SCR.C HEX HS. MACH. #6-32 X 3/4”
46 022678 1 CC LOC-TITE (TYPE A) 88*** 022188 4 NUT, HEX #6-32
47 064113 1 STUD (INCLUDES WING NUT) 89*** 022155 4 LOCKWASHER, #6
48 063558 1 ENCLOSURE, 100-150 AMP INST. PKG. 90*** 064210 12 TUBE, NYLONE Ø .17 X .43
073959 1 ENCLOSURE, 100-150 AMP NEMA 12 91 077228 1 DECAL, ENCLOSURE TYPE
073961 1 ENCLOSURE, 100-150 AMP NEMA 1 92 064153-A 4 WIRE, XFORMER JUMPER (NOT
073961-C 1 ENCLOSURE, 100-150 AMP NEMA 3R SHOWN)
063559 1 ENCLOSURE, 200-400 AMP INST. PKG. 93 056326 - TRIM, VINYL 1/8” GAP (NOT SHOWN)
073960 1 ENCLOSURE, 200-400 AMP NEMA 12 94*** 064861-A 1 RED PLEXI 1.5 X 3
073962 1 ENCLOSURE, 200-400 AMP NEMA 1 95*** 064861-B 1 RED PLEXI 1.5 X 1
073962-C 1 ENCLOSURE, 200-400 AMP NEMA 3R 96 072829 3 GASKET-LAMPHOLDER LENS (NEMA 3R)
49 064126 2 TRANSFORMER, 480V ONLY 97 074548 3 GASKET, LAMPHOLDER (NEMA 3R
072162 2 TRANSFORMER, 600V ONLY ENCL.)
50 067629 1 BRD., UTIL. VOLT. SENS. MULTI-VOLT 98 072828 1 SWITCH BOOT-WATERPROOF (NEMA 3R)
51 064217 1 BOARD, CIRCUIT EXERCISER (STD.) 99∇∇ 095080-A 1 DECAL 600 VOLT RATINGS 100 AMP
063919 1 BOARD, CIRCUIT EXERCISER (DELUXE) 095080-B 1 DECAL 600 VOLT RATINGS 150/200 AMP
52 020A67616 1 CVR., UTIL. VOLT. SENS. BOARD 095089-A 1 DECAL 600 VOLT RATINGS 300-400 AMP
53 63582 1 DOOR, PRINTED CIRCUIT BRD. COMPT.
54 064525 20 SUPPORT, PRINTED CIRCUIT BOARD * NOT USED WITH 1Ø, 3-POLE OR 4-POLE SYSTEMS.
55 064526 48 SCR., TAPTITE #6-32 X 3/8” ** USED WITH 200,300 AND 400 AMP SWITCH.
56 064152 1 SUBPLATE, 100 AMP SWITCH *** USED ONLY WITH #63919 BOARD.
064151 1 SUBPLATE, 150-400 AMP SWITCH ∇ LOCATION FOR 100 AMP SWITCH ONLY.
57 040587 3 LAMP, 28 VOLT ∇∇ USED ONLY WITH 600 VOLT SWITCHES.
60
91 SENSING PCB-COVER
ONLY
94 96
61 60
95
MANUFACTURING NOTE
NOTES:
COVER
1. * NOT USED ON 1-PHASE, 3-POLE SYSTEMS
1 24
WIPE OFF AICHI INSIGNIA USING SOLVENT, FROM TRANSFER OR ANY 4-POLE SYSTEM
SWITCH CONTACTOR (ITEM #1).
2 REMOVE AICHI MODEL AND RATING DECAL.
B 2. ** INSULATING BARRIER (ITEM #97)
MAY BE USED.
P.C. BOARD
76
54 97 8
86 84 83 82
86
66 85
66 66 85
81 42 13 81
37 37 37 28 9 1 42 52
OUTSIDE 77 77
29 30 31 32 DECAL 41 41
27
14
35
DECAL
33 71 72
70
54 87
NOTE:
79 TRANSFER SWITCH,
DECAL ITEM #1, 62 97
40 TO BE CENTERED 10
IN ENCLOSURE
74 24 64 39
38 17 46 40
2 53 18 92
88 DECAL
DECAL
57 58
25 80
54 11
7 47
16 69 4 45 49
*
50 43 12
59
76
H2
21 3
36
X2 X3
26 17
DECAL 26 22
25 55
34
80 63 20 19 54 90
65
91 DECAL
ITEM PART NO. QTY. DESCRIPTION ITEM PART NO. QTY. DESCRIPTION
55
97
55
NEMA 3R ENCLOSURE (TYPICAL) * NOT USED ON 1Ø, 3 POLE OR 1. WIPE OFF AICHI INSIGNIA USING SOLVENT, FROM
TRANSFER SWITCH CONTACTOR (ITEM #1).
4 POLE SYSTEMS.
** USED ONLY WITH 600 VOLT SWITCHES. 2. REMOVE AICHI MODEL AND RATING DECAL.
TYPICAL
25 8 36
104 71 43
104
57 57 57
103 71 103
34 34 34
29 83 44 83
OUTSIDE 24 26 27 28 1
102 9 38 44 104 38 9 102
48
13
85
** 68 77
32
61 86
70 42 101
100
65
10
75
79 78 73
84
16
67 21
81
15
31 39 35 22 83
58
106 31
15
2
74 51 69 45
11
94 95
49 46
40 4
80
7
72
*
3
53
76
6
15
5
23 12 19
33 47 82
NOTE:
1 99
HANDLE
MOUNTED
ON SIDE
83 22 50 52 64 14 30 59 17 30 59 56 63 23 20
18
91
ITEM PART NO. QTY. DESCRIPTION ITEM PART NO. QTY. DESCRIPTION
ITEM PART NO. QTY. DESCRIPTION ITEM PART NO. QTY. DESCRIPTION
60
95
61
NEMA 3R ENCLOSURE (TYPICAL)
COVER
MANUFACTURING NOTE:
24
1. WIPE OFF AICHI INSIGNIA USING SOLVENT,
FROM TRANSFER SWITCH CONTACTOR
(ITEM #1)
2. REMOVE AICHI MODEL AND RATING DECAL.
3. CONNECT SOLENOID COIL FOR CORRECT
P.C. BOARD OPERATING VOLTAGE, FOLLOWING INSTRUCTIONS
ON TRANSFER SWITCH CONTACTOR.
81 83
54 88
8 36 DECAL
13
14
Generac GTS “Wn” Type Transfer Switch
27
OUTSIDE 35
DECAL
87 0 36 98
70
Section 7 — Exploded Views & Parts Lists
54
34 10
1200-1600A CPU Assembly - Drawing No. 074544-D
74 24 39 92
34 46 DECAL
38 17 79
2 18
DECAL
57 58
11 48 80 25
54
7 47
69 4 45 49
64 16 *
12
59 DECAL
76
50
36
21 3
26
DECAL 26 22
25 55
33
80 63 20 19 54 90
65
91 DECAL
NOTES: UNLESS OTHERWISE SPECIFIED
1. * NOT USED ON 1-PHASE, 3-POLE SYSTEMS
OR ANY 4-POLE SYSTEM
Section 7 — Exploded Views & Parts Lists
Generac GTS “Wn” Type Transfer Switch
1200-1600A CPU Assembly - Drawing No. 074544-D
ITEM PART NO. QTY. DESCRIPTION ITEM PART NO. QTY. DESCRIPTION
NOTES:
98 * NOT USED ON 4 POLE SYSTEMS.
55 54
96
** USE ONLY WITH 600 VOLT SWITCHES.
*** USE ONLY WITH #63919 BOARD.
55
MANUFACTURING NOTES:
55
8 36
85 **
32
13
68 77 61
Generac GTS “Wn” Type Transfer Switch
OUTSIDE 24 84
70 31 101
Section 7 — Exploded Views & Parts Lists
86
75 100
10
79 78
73 65
16
81
67 21
1200-1600A Inphase Assembly - Drawing No. 091395-D
107 39 35 15
58
22 83
105 106 92
69 45
11
74 51
40 4 49 46
80
*** * 72
7
53 3
76 6
5
12 19
33
47 92
23
MOUNTED ON SIDE
99
107 108
83 22 50 52 64 14 30 59 17 30 59 56 63 23 20
18
91
Section 7 — Exploded Views & Parts Lists
Generac GTS “Wn” Type Transfer Switch
1200-1600A Inphase Assembly - Drawing No. 091395-D
ITEM PART NO. QTY. DESCRIPTION ITEM PART NO. QTY. DESCRIPTION
1 072124 1 XFRSW1200A 3P WN600V 53 063582 1 DOOR-PCB ENCL
072125 1 XFRSW1200A 4P WN600V 54 064525 20 STANDOFF HEX 3/4
072114 1 XFRSW1600A 3P WN600V 55 064526 48 SCREW S-THR PH #6-25 X 3/8 ZNC
072120 1 XFR SW 1600A 4P WN600V 56 064935 1 SUBPLT GTS 600-2600
2 063617 2 RELAY PNL 12VDC DPDT 10A@240VA 57 040587 3 LIGHT 28V .17A LAMP #757
3 062641 1 NEUTRAL BL 800-2600A 58 063998 1 BATTERY 9V
4 057329 1 LUG SLDLSS 350-#6X13/32 AL/CU 59 046669 - BLOCK TERM JUMPER
5 074509 1 BRACKET SWITCH 60 074540 - HARNESS 1600A,240V
6 074511 1 DECAL TDN MAINTENANCE SW 61 062209 1 DECAL UL LABEL E84929-GTS
7 055868 1 SWITCH TOGGLE 4PDT 15A SPADE 62 022196 4 NUT HEX 1/2-13 STEEL
8 063963 - LUG SLDLSS 750-1/2X13/32 AL/CU 63 067617030A 1 INTRFC,3PHS 416/480V
9 075099 2 MOUNTING BRACKET-WN 067617030B 1 INTRFC,3PHS 208/240V
10 074349E 2 SW CVR 1200/1600A 3P 072160 1 INTRFC,3P 400V 50/60
074349F 2 SW CVR 1200/1600A 4P 072158 1 INTRFC,3PHS 600V
11 067210A 1 DECAL GROUND LUG 64 068337 4 STANDOFF-HEX 1.00 LG
12 074525 1 DECAL MANUAL OPERATION 65 054199 1 DECAL HIGH VOLTAGE
13 073617N 1 DECAL-TRAN SW 1200WN 66 064761 - TIE WRAP UL 5.6 X .10 NATL
073617P 1 DECAL-TRAN SW 1600WN 67 063981 2 SIDE GUIDE PCB ENCL
14 057701 - BLOCK TERM 20A 8 X 6 X 1100V 68 063357 1 DECAL MAC-DT GTS
15 056893 10 SCREW CRIMPTITE 10-24 X 1/2 69 024526 1 SCREW HHTT 5/16-18 X 3/4 CZ
16 090975 3 XFMR 240/40V 25VA 70 063986 4 KNOB,COVER HOLD-DOWN
17 046689 - BLOCK TERM 20A 4 X 6 X 1100V 71 022195 4 WASHER LOCK 1/2
18 091466 1 DECAL 2 WR TERM STRP 72 026902 - SCREW HHTT #8-32 X 1/4 CZ
19 072164 1 MNL HNDL 6-1600A WN 73 063378 31 HOLDER CABLE TIE
20 063578 1 PLATE DATA - GTS 74 063996 1 ASSY, COVER STANDARD EXERCISER
21 068212 1 ENCLOSURE PCB GTS 064298 1 ASSY, COVER DELUXE EXERCISER
22 064101 10 NUT LOCK FL 3/8-16 75 072252 1 GROMMET 1.37 X .06 X 1.00
23 036261 10 RIVET POP .125 X .275 AL 76 028199 1 SWITCH TOGGLE SPST 6A TAB C-H
24 073681 1 DECAL, DOOR GTS 77 074513N 1 DECAL-SW.P/N 3P1200A
056298 1 DECAL GENERAC 2IN HIGH 074513W 1 DECAL-SW.P/N 4P1200A
090257 1 DECAL OLYMPN 2IN HI 074513P 1 DECAL-SW.P/N 3P1600A
087227 1 DECAL, DOOR CTS-OLY 074513X 1 DECAL-SW.P/N 4P1600A
25 091478 1 DECAL, SWITCH OPER 78 092734 1 ASSY INPHASE MONITOR
26 057328 1 LIGHT T-3-1/4 LENS (CLEAR) 79 094446 1 COVER PLT INPH CONTL
27 057327 1 LIGHT T-3-1/4 LENS (RED) 80 029357 2 RIVET AVDEL3/32X1/8L
28 057325 1 LIGHT T-3-1/4 LENS (AMBER) 81 063982 1 CLIP BATT-9V TRANSIS
29 055142 1 SWITCH TOG DPDT 15A MOM W/SEAL 83 022131 18 WASHER FLAT 3/8-M10 ZINC
30 0A1661 4 RIVET POP .156 X .675 AL 84 083736 1 DECAL-CSA GTS
31 024469 8 SCREW HHTT #10-32 X 3/8 CZ **85 095089D 1 DEC 600V10-1200ARTGS
32 073619I 1 DECAL-TEST SEQ1200WN 86 064510 1 DECAL-TERMINAL NOTE
073619K 1 DECAL-TEST SEQ1600WN ***87 033139 4 SCREW HHM #6-32 X 3/4
33 0A2111 2 SCREW SWAGE 10-32 X 5/16 Z/YC ***88 022188 4 NUT HEX #6-32 STEEL
34 057514 3 LIGHT 120V T-3-1/4 LAMP/HOLDER ***89 022155 4 WASHER LOCK #6
35 038150 4 WASHER FLAT #8 ZINC ***90 064210 4 NYLON-TUBE .17 X .43
36 026902 9 SCREW HHTT #8-32 X 1/4 CZ 91 077228 1 DECAL-ENCLOSURE NOTE
37 091477 5 RIVET, WIRE DUCT MNT 92 022473 9 WASHER FLAT 1/4-M6 ZINC
38 061342 4 SCREW HHC 1/2-13 X 1-1/4 G5 93 056326 - TRIM VINYL BLACK 1/8GP 74"
39 0A2284 4 SCREW SWAGE 8-32 X 1/2 Z/YC ***94 064861A 1 RED PLEXI 1.5 X 3 IN
40 064932 2 TRANSFRM 480/240V 250VA ***95 064861B 1 RED PLEXI 1.5 X 1 IN
074652 2 TRANSFRM 600V TO 240V 250VA 96 072849 3 GASKET WATERPROOF
41 091472 1 DUCT WIRING 1X1.5 6 FT 97 074548 3 O-RING.625IDX.75X.06
43 022258 - SCREW HHC 3/8-16 X 2 G5 98 072828 1 SWITCH WATERPROOF RUBBER BOOT
44 022304 4 WASHER FLAT 1/2 ZINC 99 091472A 1 COVER WIRE DUCT 1 IN
45 022129 1 WASHER LOCK M8-5/16 100 074351 2 CVR BRCKT 600-1600A
46 022678 1CC LOCTITE THRDLOKR 242 074351A 2 CVR BRCKT600-1600 LH
47 025870 1 NUT WING 1/4-20 101 022152 8 WASHER LOCK #10
48 074542 1 NEMA12 ENC 1200-1600 102 031863 8 SCREW HHC 3/8-16 X 1-1/4 G5
074542C 1 ENCL 3R BLDR 12-1600 103 022237 32 WASHER LOCK 3/8
49 024979 2 SCREW HHTT 5/16-18 X 5/8 CZ 104 022241 - NUT HEX 3/8-16 STEEL
50 067629 1 ASSY STANDARD SENSNG 105 090388 8 SCREW HHTT M6-1.0 X 12 ZINC
51 064217 1 ASSY 7-DAY EXERCISER 106 022097 8 WASHER LOCK M6-1/4
063919 1 ASSY DELUXE EXERCISR 107 022264 12 WASHER LOCK #8-M4
52 067616020A 1 ASS'Y-STNDSNS CVRPLT 108 036917 8 SCREW PPHM #8-32 X 3/8
61 60
95
COVER
MANUFACTURING NOTE: 24
37 37 37 52
29 30 31 32
28
DECAL
13
14
Generac GTS “Wn” Type Transfer Switch
27
Section 7 — Exploded Views & Parts Lists
OUTSIDE 35
DECAL
87
2000-2600A CPU Assembly - Drawing No. 075331-C
54
70
34
10
74 24 81
39 92 81
97 DECAL
77 38 17 23 34 97 79
53 18 77
2 DECAL
57 58
11 48 80 81 82 83
54
7 47
69 4 45 49
64 16 *
12
59 DECAL
76
50
36
21 3
X3
17
26
DECAL 26 22
25 55
33
80 63 20 19 54 90
65
91 DECAL
Section 7 — Exploded Views & Parts Lists
Generac GTS “Wn” Type Transfer Switch
2000-2600A CPU Assembly - Drawing No. 075331-C
ITEM PART NO. QTY. DESCRIPTION ITEM PART NO. QTY. DESCRIPTION
1 072115 1 SWITCH ASSY, TRANSFER, 2000A, 3-POLE 57 067626 1 BOARD, SYSTEM CONTROL (CPU)
072121 SWITCH ASSY, TRANSFER, 2000A, 4-POLE 58 071775 1 COVER, CPU
072116 SWITCH ASSY, TRANSFER, 2600A, 3-POLE 59 063582 1 DOOR, CIRCUIT BOARD COMPARTMENT
072122 SWITCH ASSY, TRANSFER, 2600A, 4-POLE 60 064525 20 SUPPORT, CIRCUIT BOARD
2 063617 2 RELAY, TRANSFER/TIME DELAY 61 064526 24 SCREW, SELF-TAPPING - NO. 6-32 X 3/8”
3 062641 1 LUG ASSEMBLY, NEUTRAL 62 - - NOT USED
4 057329 1 LUG, GROUNDING 63 020A67616 1 COVER, UTILITY VOLTAGE SENSING
5 074509 1 BRACKET, SAFETY DISCONNECT SWITCH BOARD
6 074511 1 DECAL, MAINT. DISCONNECT SWITCH 64 072252 1 GROMMET
7 055868 1 SWITCH, SAFETY DISCONNECT - 4PDT 65 064935 1 SUBPLATE 600-2600 AMP
8 - - NOT USED 66 040587 3 LAMP - 28 VOLTS
9 074375-A 2 BRACKET, SWITCH MOUNTING 67 - - NOT USED
10 072126 1 COVER, SWITCH 68 - - NOT USED
11 067210-A 1 DECAL, GROUND 69 064933 2 TRANSFORMER, 400 & 480V SYSTEMS
12 074525 1 DECAL, MANUAL OPERATION ONLY, 500VA
13 073617-R 1 DECAL, 2000 AMP 70 025870 4 WING NUT, 1/4”-20
073617-S DECAL, 2600 AMP 72 - - NOT USED
14 063357 1 DECAL, MAC - DT - GTS 73 074570 1 HARNESS, WIRE
15 057701 1 BLOCK, TERMINAL 74 063981 2 GUIDE, SIDE
16 028199 1 SWITCH, TIME DELAY NEUTRAL BYPASS 75 - - NOT USED
17 056893 20 SCREW, (CRIMPTITE) - NO. 10-24 X 1/2” 76 026902 2 SCREW, TAPTITE - NO. 8-32 X 1/4” (416
18 047616 2 TRANSFORMER VOLT ONLY)
19 046689 1 BLOCK, TERMINAL 77 022238 18 HHCPSC - 3/8”-16 X 1”
20 063580 1 DECAL, TERMINAL BLOCK 78 022097 8 WASHER, LOCK - M6 (480 VOLT ONLY)
21 072164 1 HANDLE, MANUAL 79 062209 1 DECAL - UL
22 063578 1 PLATE, DATA 80 022131 12 WASHER, FLAT - 3/8”
23 036917 8 PPHMS 8-32 X 3/8” 81 022237 22 WASHER, LOCK - 3/8”
24 068212 1 COMPARTMENT, CIRCUIT BOARD 82 022258 - CAPSCREW, HEX HEAD 3/8-16 X 1.5”
25 064101 6 NUT, FLANGED LOCK - 3/8”-16 83 022241 4 NUT, HEX, 3/8”-16
26 036261 10 RIVET, POP - 1/8” X 0.23” 84 - - NOT USED
27 073681 1 GTS - DECAL 85 022195 4 WASHER, LOCK - 1/2”
28 063385 1 DECAL - AUTOMATIC SEQUENCE 86 022196 4 HEX NUT - 1/2”-13
29 057328 1 LENS, LAMP - CLEAR 87 074513-R 1 DECAL, 2000A, 3-POLE SWITCH
30 057327 1 LENS, LAMP - RED 074513-Y DECAL, 2000A, 4-POLE SWITCH
31 057325 1 LENS, LAMP - YELLOW 074513-S DECAL, 2600A, 3-POLE SWITCH
32 055142 1 SWITCH, MODE - DPDT 074513-Z DECAL, 2600A, 4-POLE SWITCH
33 0A1661 4 RIVET, POP .156 D X .5 LG. 88 064510 1 DECAL - TERMINAL NOTE
34 022264 12 WASHER, LOCK #8 89 090388 8 M6-1.0 X 12 TAPTITE
35 073619-L 1 DECAL, TESTING SEQUENCE 2000 AMP 90 030A67617 1 INTERFACE - GTS UTILITY 416/480V
073619-M DECAL, TESTING SEQUENCE 2600 AMP 3-PHASE
36 0A2111 2 10-32 - 5/16 FASTENER 030B67617 INTERFACE - GTS UTILITY 208/240V
37 057514 3 HOLDER, LAMP 3-PHASE
38 038150 4 WASHER, FLAT - NO.8 030C67617 1 INTERFACE - GTS UTILITY 240V 1-PHASE
39 0A2284 4 8-32 X 1/2 FASTENER 072160 INTERFACE - GTS UTILITY 400V, 3-PHASE,
40 022473 8 FLAT, WASHER 1/4-M6 50 HZ.
41 060277 4 CAPSCREW, HEX HEAD - 1/2”-13 X 2.0 91 068337 4 STANDOFF - HEX SPACER 1.00 LONG
42 022304 4 WASHER, FLAT - 1/2” 92 054199 1 DECAL - HIGH VOLTAGE
45 024979 2 5/16”-18 X 5/8” TAPTITE 93 028739 - TIE WRAP 4” LONG (NOT SHOWN)
46 - - NOT USED 94 072849 3 GASKET, LAMPHOLDER LENS (NEMA 3R
47 024526 1 SCREW (TAPTITE) - 5/16”-18 X 3/4” ENCLOSURE ONLY)
48 022129 1 WASHER, LOCK - 5/16” 95 074548 3 GASKET, LAMPHOLDER (NEMA 3R
49 022678 1 CC LOC-TITE, TYPE A ENCLOSURE ONLY)
50 025870 1 WING NUT 1/4-20 96 072821 1 SWITCH BOOT, WATERPROOF (NEMA 3R
52 073669 1 ENCLOSURE, NEMA 12 ENCLOSURE ONLY)
074577 ENCLOSURE, NEMA 3R 97 074376 2 BRACKET, SUBPLATE MOUNTING
53 063378 - TIE-DOWN, CABLE
54 057593 - TIE-DOWN, CABLE NOTE: UNLESS OTHERWISE SPECIFIED -
55 067629 1 BOARD, UTILITY VOLTAGE SENSING * NOT USED ON 1-PHASE, 3-POLE SYSTEMS OR ANY 4-POLE SYSTEM.
56 - - NOT USED
55 54
NOTES:
38
42 **
103
83 32
13
102
68 86
77
Generac GTS “Wn” Type Transfer Switch
61
OUTSIDE 24
84
Section 7 — Exploded Views & Parts Lists
75
79 78
47 70 10
2000-2600A Inphase Assembly - Drawing No. 091396-B
103
65
81 16 73
67 21 83 39 35 106
102
58
15
92 70 105 69 45
11
74 51
2
80
94 95 40 4
53 7 72
106 107 15
76 3
33
23
19 12 NOTE: HANDLE
47 70 MOUNTED ON SIDE
83 22
14 30 59 18
63 23 20 85
17 30 59 56
91 50 52 64
48
Section 7 — Exploded Views & Parts Lists
Generac GTS “Wn” Type Transfer Switch
2000-2600A Inphase Assembly - Drawing No. 091396-B
ITEM PART NO. QTY. DESCRIPTION 54 064525 20 SUPPORT, PRINTED CIRCUIT BOARD
ITEM PART NO. QTY. DESCRIPTION
1 072115 1 SWITCH, TRANSFER - 2000 AMP, 3-POLE
072121 1 SWITCH, TRANSFER - 2000 AMP, 4-POLE 55 064526 48 SCR., TAPTITE #6-32 X 3/8”
072116 1 SWITCH, TRANSFER - 2600 AMP, 3-POLE 56 064935 1 SUBPLATE, 600-2600 AMP SWITCH
072122 1 SWITCH, TRANSFER - 2600 AMP, 4-POLE 57 040587 3 LAMP, 28 VOLT
2 063617 2 RELAY, TRANSFER 58 063998 1 BATTERY, 9 VOLT
3 062641 1 LUG, NEUTRAL 59 046669 - JUMPER, TERMINAL BLOCK
4 057329 1 LUG, GROUNDING 60 074570 - HARNESS - WIRING (NOT SHOWN)
5 074509 1 BRACKET, SAFETY DISCONNECT SWITCH 61 062209 1 DECAL, UL
6 074511 1 DECAL, SAFETY DISCONNECT SWITCH 62 022196 4 NUT, HEX 1/2”-13
7 055868 1 SWITCH, SAFETY DISCONNECT - 4PDT 63 030A67617 1 INTERFACE, UTILITY 416/480V 3-PHASE
9 074375-A 2 SUPPORT, 2000 AMP 3-POLE SWITCH 030B67617 1 INTERFACE, UTILITY 208/240V 3-PHASE
074375-B 2 SUPPORT, 2000 AMP 4-POLE SWITCH 072160 1 INTERFACE, UTILITY 400V 3-PHASE
074375-C 2 SUPPORT, 2600 AMP 3-POLE SWITCH 072158 1 INTERFACE, UTILITY 600V 3-PHASE
074375-D 2 SUPPORT, 2600 AMP 4-POLE SWITCH 64 068337 4 STANDOFF, HX SPCR 1.0” L (STD SNES.)
10 072126 1 COVER, SWITCH 65 054199 1 DECAL, HIGH VOLTAGE
11 067210-A 1 DECAL, GROUND 66 064761 - TIE-WRAP, 5 5/8” LG (NOT SHOWN)
12 074525 1 DECAL, MANUAL OPERATION 67 063981 2 GUIDE, SIDE
13 073617-R 1 DECAL, 2000 AMP 68 063357 1 DECAL, MAC DT GTS
073617-S 1 DECAL, 2600 AMP 69 024526 1 SCR., TAPTITE 5/16”-18 X 3/4”
14 057701 - BLOCK, TERM - 8 POS. 70 022473 13 WASHER, FLAT 1/4”
15 056893 10 SCR., CRIMPTITE #10-24 X 1/2” 71 022195 4 WASHER, LOCK 1/2”
16 09075 3 TRANSFORMER - 25VA 72 026902 - TAPTITE #8-32 X 1/4”
17 046689 - BLOCK, TERMINAL - 4 POS. 73 036678 31 TIE-DOWN, CABLE
18 091466 1 DECAL, TERMINAL BLOCK 74 036996 1 CVR, EXERCISER CIRCUIT BRD. (STD.)
19 074327 1 HANDLE, MANUAL TRANSFER 064298 1 CVR, EXERCISER CIRCUIT BRD. (DLX.)
20 063578 1 PLATE, DATA 75 072252 1 GROMMET
21 068212 1 COMPARTMENT, PRINTED CIRCUIT BOARD 76 028199 1 SWITCH, TIME DELAY NEUTRAL BYPASS
22 064101 4 NUT, FLANGED LOCK 3/8”-16 77 074513-R 1 SWITCH PART #72115
23 036261 10 RIVET, POP 1/8” X .23” SS 074513-S 1 SWITCH PART #72116
24 073681 1 DECAL, GTS 074513-Y 1 SWITCH PART #72121
056298 1 DECAL, GTS NEMA 3R ENCLOSURE 074513-Z 1 SWITCH PART #72122
090257 1 DECAL, CTS NEMA 3R ENCLOSURE 78 092734 1 PCB, INPHASE MONITOR
087227 1 DECAL, CTS 79 094446 1 COVER, INPHASE CONTROL
25 091478 1 DECAL, AUTOMATIC SEQUENCE 80 029357 2 RIVET
26 057328 1 LENS, LAMP CLEAR 81 063982 1 CLIP, BATTERY
27 057327 1 LENS, LAMP RED 82
28 057325 1 LENS, LAMP YELLOW 83 022131 30 WASHER, FLAT 3/8”
29 055142 1 SWITCH, MODE DPDT 84 083736 1 DECAL, CSA
30 0A1661 4 RIVET, POP .156 D X .5 LG. 85 074376 2 BRACKET, SUBPLATE MOUNTING
31 86 064510 1 DECAL, TERMINAL NOTE
32 073619-L 1 DECAL, TESTING SEQUENCE 2000 AMP 87*** 0333139 4 SCR., HEX HD. MACH. #6-32 X 3/4”
33 0A2111 2 10-32 - 5/16 FASTENER 88*** 022188 4 NUT, HEX #6-32
34 057514 3 HOLDER, LAMP 89*** 022155 4 LOCKWASHER, M6
35 038150 4 WASHER, FLAT #8 90*** 064210 4 TUBE, NYLON Ø .17 X .43
37 091477 5 RIVET, NYLON “PUSH” 91 077228 1 DECAL, ENCLOSURE TYPE
38 061342 4 CAPSCR., HEX HD. 1/2”-13 X 1 1/4” 92 022097 8 WASHER, LOCK M6
39 0A2284 4 8-32 X 1/2 FASTENER 93 056326 - TRIM, VINYL 1/8” GAP (NOT SHOWN)
40 064932 2 TRANSFORMER, 480/240 250VA 94*** 064861-A 1 RED PLEXI 1.5 X 3
074652 2 TRANSFORMER, 600/240 250VA 95*** 064861-B 1 RED PLEXI 1.5 X 1
41 091472 1 DUCT, WIRE 33 1/2” LG. 96 072849 3 GASKET-LAMPHOLDER LENS (NEMA 3R)
42** 095089-A 1 DECAL, 600 VOLT RATINGS 2000 AMP 97 074548 3 GASKET-LAMPHOLDER (NEMA 3R ENCL.)
095089-B 1 DECAL, 600 VOLT RATINGS 2600 AMP 98 072828 1 SWITCH BOOT - WATERPROOF (NEMA 3R)
43 022258 4 CSCR, HEX HD 3/8”-13 X 2” 99 091472-A 1 COVER, WIRE DUCT 33 1/2” LG.
44 022304 8 WASHER, FLAT 1/2” 102 031863 18 CSCR., 3/8”-16 X 1 1/4”
45 022129 1 WASHER, LOCK 5/16” 103 022237 22 WASHER, LOCK 3/8”
46 022678 1 CC LOCK-TITE (TYPE A) 104 022241 4 NUT, HEX 3/8”-16
47 025870 5 WING NUT, 1/4”-20 105 090388 8 M6-1.0 X 12 TAPTITE
48 073669 1 ENCLOSURE, NEMA 12 106 022264 12 WASHER, LOCK #8
073669-C 1 ENCLOSURE, NEMA 3R 107 036917 8 PPHMS 8-32 X 3/8”
49 024979 2 5/16”-18 X 5/8” TAPTITE
50 067629 1 BRD., UTIL. VOLT. SENS. MULTI-VOLT NOTE:
51 064217 1 BOARD, CIRCUIT EXERCISER (STD.) * NOT USED ON 4-POLE SYSTEMS.
063919 1 BOARD, CIRCUIT EXERCISER (DELUXE) ** USE ONLY WITH 600 VOLT SYSTEMS.
52 020A67616 1 CVR., UTIL. VOLT. SENS. BOARD *** USE ONLY WITH #63919 BOARD.
53 063582 1 DOOR, PRINTED CIRCUIT BRD. COMPT.
PROGRAMABLE
EXERCISER
PM
TO PROGRAM TIMER
TO SET
TO SET TIME OF DAY PRESS "FAST" OR "SLOW EXERCISE DAY
SET" BUTTONS UNTIL PROPER TIME IS DISPLAYED.
PRESS AT TOP OF
TO SET DAY OF WEEK PRESS "ADVANCE DAY" BUTTON DAY OF WEEK ROCKER SWITH TO
UNTIL PROPER DAY IS DISPLAYED IN DAY OF WEEK ROW.
SELECT DESIRED
TO SET EXERCISE TIME EXERCISE DAY
OR DAYS. THE
PRESS AND HOLD "DISPLAY EXERCISE TIME" BUTTON AND
GENERATOR WILL
PRESS "FAST SET" OR "SLOW SET" BUTTONS UNTIL DESIRED SM T W T F S EXERCISE THESE
EXERCISE TIME IS DISPLAYED.
DAYS AT THE
TIME PROGRAMMED.
DISPLAY
FAST SLOW ADVANCE
EXERCISER
SET SET DAY
TIME
64298
1 2
(NOT TO SCALE)