Vendor

No Item Dimension
Carrier Jonson-york Daikin Naga kirloskar Trane-CRTHE Trane-CRTHD Trane-CRTHG Design
1 kW 909,8 773,7 818,37 967,13
Cooling Capacity 773,7 219 773,7 885,5 773,7

2 m3/h 156,2 132,80 140,8 166,5 133 132 132,8 152,11 140
Flow Rate Chilled Water Pump
3 Condenser Cooling type - Water Cooling Water Cooling Water Cooling Water Cooling Water Cooling Water Cooling Water Cooling Water Cooling Water Cooling
4 Evap, Temperature
T in oC 7 7 7 7 7 7 7 7 7
Tout oC 12 12,0 12 12 12 12 12 12 12
5 Type Starter - Not Available Start Delta Not Available VSD Start Delta wye-Delta stater AdaptiR wye-Delta stater/Adaptir Variable Flow
6 Refrigerane type - R-134 R-134 R-134a R-134a R-134a R-134a R-134a R-134a R-134a
7 Refrigerane Weight kg Not Available 250 Not Available 200 Not Available 87 Not Available 222 -
8 Full Load-COP* kW/kW 5,50 6,59 5,07 5,48 5,8 4,75 5,93 5,32 > 5,172
9 Partload Performance (IPLV)* kW/kW 6,47 5,81 5,16 6,37 Not Available Not Available Not Available Not Available > 6,064
8. COP Complies with USGBC 8. COP Complies with USGBC 8. COP not Complies with 8. COP Complies with USGBC 8. COP Complies with USGBC 8. COP not Complies with 8. COP Complies with USGBC 8. COP Complies with USGBC
LEED requirements LEED requirements USGBC LEED requirements LEED requirements LEED requirements USGBC LEED requirements LEED requirements LEED requirements
Comment
9. IPLV Complies with USGBC 9. IPLV not Complies with 9. IPLV not Complies with 9. IPLV Complies with USGBC
LEED requirements USGBC LEED requirements USGBC LEED requirements LEED requirements 9.HOLD, NA 9.HOLD, NA 9.HOLD, NA 9.HOLD, NA

* Requirement of LEED about Chiller efficiency, refer to ASHRAE 90.1 .