Trip Circuit Supervision Relay Explained


Posted by Pranali N | Aug 16, 2018 | Circuit Breaker, Protection Relay | 1  |     

1.principle of operation:

https://electricalfundaz.com/trip-circuit-supervision-relay-explained/ 1/6
5/21/2020 Trip Circuit Supervision Relay Explained in detail !!!!!!!

Principle: A Continous Negative Voltage is given to one end of the Tripping Coil . If the Trip Circuit is
Continous (Healthy)
this Negative Voltage gets extended futher down the Trip Circuit, which can be used by the TCS Relay to
check the continuity in the Tripping Circuit.
Importance:

A Breaker has a Closing Coil & A Tripping Coil. Now if a Closing Coil is Faulty, we can Close it
Mechanically also. But Tripping is Automatic in the case of Fault and so when the Trip Circuit is
Faulty, the Breaker won’t Trip which can have very bad consequences.

If its a 22kv or 33 kv bkr, Tfr LV bkr will operate, which will result in unnecessary power
interruption for other Feeders.

If its 100 kv or 220 kv level, and if the breaker does not trip, LBB wil operate, tripping all the feeder
in that section which will result in Huge Power Loss.

We will be using Areva make VAX31 Type Trip Circuit Supervision Relay.

2. construction:

1. Post Close Element (95A)- It is Energised when the Breaker is in ON Condition (Post Close Condition) &
hence monitors the Healthiness of the TC in the Bkr is in ON cond. Permanant Positive is given to one
end of Coil of 95A and the other end of Coil of 95A is connected to the Tripping Coil through NC
Auxillary contact of the breaker.

2. Pre Close Element (95B)- It is Energised when the Breaker is in OFF Condition (PreClose
Condition). Permanant Positive is given to one end of Coil of 95B and the other end of Coil of 95B is
connected to the Tripping Coil through NO Auxillary contact of the breaker.

Wire Wound Resistor


Under UL Certi cating. High Quality, Value, Precision

setfuse.com OPEN

3. Main Element (95C)- Positive is given to the 95C through the parallely connected contacts of 95A &
95B. Permanant Negative is given to the other end of 95C. It is Energised when either 95A or 95B is

Energised & used for Annunciation purpose. It is a reverse Flag Relays (Normally when the Relay is
operated, we get an indication, but in the case of 95C Relay, when the Relay is not operated, we get the
Indiction).

https://electricalfundaz.com/trip-circuit-supervision-relay-explained/ 2/6
5/21/2020 Trip Circuit Supervision Relay Explained in detail !!!!!!!

4. Resistances- Current flowing in the TCH ckt is restricted with the help resistances placed in series
with the TCH relays, so that the Tripping coil does not operate. Also, in case the TCS Element gets
shorted, the current through TC is limited and breaker does not Trips.

3. WORKINNG OF TCS RELAY WHEN THE BREAKER IS IN OFF


POSITION:

1. Permanant Positive is given to one end of Coil of 95A and now, the other end of Coil of 95A gets the
Negative Voltage coming through the Tripping Coil & NC Auxillary contact of the breaker. Hence, 95A
Relay gets operated and so its Contact is Closed and so Positive is extended to the 95C Relay. As the 95C
Relay is already given Negative and now it is gettig Positive and so it gets OPerated & so there are Faulty
Indications & Breaker Closing Interlock is also Inactive.

2. Permanant positive is given to the 95 B Relay but it is not getting the Negative Voltage coming through
the Coil, and it remains in Reset Condition.

Wire Wound Resistor


Under UL Certi cating. High Quality, Value, Precision

setfuse.com OPEN

3. Positive is given to the 95C through the parallely connected contacts of 95A & 95B. Permanant Negative
is given to the other end of 95C.

4.

https://electricalfundaz.com/trip-circuit-supervision-relay-explained/ 3/6
5/21/2020 Trip Circuit Supervision Relay Explained in detail !!!!!!!

Subscribe to get more post like these !!


Just enter your Email Adress and hit the Subscribe Button !!!!!!

EMAIL SUBSCRIBE!

SHARE:           RATE:

 PREVIOUS NEXT 

Tan Delta Testing of CT/Bushing What is the difference between Main Contacts and
Auxiliary Contacts of circuit breaker

RELATED POSTS

https://electricalfundaz.com/trip-circuit-supervision-relay-explained/ 4/6
5/21/2020 Trip Circuit Supervision Relay Explained in detail !!!!!!!

What is the Duty Closing Circuit of What is the What is Local


Cycle/Operating 33 kv Outdoor difference Breaker Backup
Sequence of Gang Operated between Main or Breaker Failure
Circuit Breaker Vaccume Circuit Contacts and Relay for
specified on the Breaker Auxiliary Protection of
Name Plate 07.01.19 Contacts of Local end
02.03.19 circuit breaker Breaker
24.09.18 26.12.18

1 Comment

Dattatreya.G on 21.02.19 at 7:12 pm

Hi Team,

Gretings of the Day…!

I was studying VAX 31 AREVA make TCS relay. It was explained very good manner.. But detailed circuit diagram
not mentioned. Kindly provide the Circuit diagram followed by explanation.

The circuit what i’m having seems to be quite different.. where i’m mis leading with explanation.. If required i
will share the same for clarification..

REPLY


Leave a reply
Your email address will not be published. Required fields are marked *

COMMENT