Академический Документы
Профессиональный Документы
Культура Документы
Abstract- The paper presents a comparison of four Flexible of the many problems that could be caused due to the random
AC Transmission Systems (FACTS) controllers, the Static Var nature of the wind [2]. Many potential problems like low
Compensator (SVC), the STATic synchronous COMpensator voltage ride through, unbalanced faults impact etc [3] need to
(STATCOM), the Thyristor Controlled Series Compensator be analyzed.
(TCSC) and the Static Synchronous Series Compensator (SSSC)
on power system steady state voltage stability. The choice of the The recent development and use of Flexible Alternating
location and sizing of these devices is also presented and an Current Transmission Systems (FACTS) in the bulk power
analysis is made on the IEEE 14 bus system using Power System transmission system has led to many applications where these
Analysis Toolkit (PSAT) software. A cost comparison of these devices are not only able to improve the voltage and angle
FACTS devices with traditional reactive power/voltage stability stability but are also able to provide flexible operation
devices is also presented. capabilities. Several distinct models have been proposed to
represent FACTS in static and dynamic analysis of the system
[4]. This paper mentions the application of four such FACTS
I. INTRODUCTION
devices that are more used for voltage stability problem. Static
The present day power system is a large complex Synchronous Compensator (STATCOM), Static VAR
interconnected network that consists of thousands of buses and Compensator (SVC), Thyristor Controlled Series
hundreds of generators. The network is increasing everyday Compensator (TCSC), Static Synchronous Series
with the increase in demand and to meet this, either new Compensator (SSSC) are the FACTS devices that are used for
installation of power generating stations and transmission this purpose. The operational characteristics and capabilities
lines is required or the existing infrastructure operation has to of each of these devices in improving the steady state voltage
be extended to limits. The laying of new lines or installation of stability of a selected test system are dealt in this paper along
new generating stations imposes many environmental and with the simulation results.
economical constraints. As a result, the existing transmission
lines are more heavily loaded than ever before and one The paper is organized as follows: Section II introduces
consequence of this is the threat of losing stability following a steady state voltage stability in general. A brief introduction of
disturbance. It was found that the voltage instability was one the stability of FACTS devices is presented in Section III.
of the main reasons for the recent North American blackout in The selected test case system and software tool is then briefly
August 2003 [1]. Voltage instability causes system voltage stated in Section IV. In Section V, the location and ratings of
collapse, which makes the system voltage to decrease to a FACTS device and the results obtained are presented along
level that is unacceptable and is unable to recover leading to with a discussion.
interruption of the power supply in the system. The only way
to counteract this problem is by reducing the reactive power II. STEADY STATE VOLTAGE STABILITY
load in the system or by adding new reactive generation Steady state voltage stability and Dynamic voltage
systems in the weakest points in the system, thereby, stability are two types of voltage stability defmed based on the
increasing the voltage at those points. The stability could get time frame of simulation [5]. Since the steady state analysis
much worsened as the percentage of power generated from the only involves the solution of algebraic equations it is
renewable energy systems like wind power increase [2]. The computationally less extensive than dynamic analysis. Also,
recent potential grid instability caused by too much wind this analysis is ideal for the bulk of studies in which voltage
power generated from the wind systems in Oregon area is one stability limit for many pre-contingency and post-contingency
v.
cases must be determined [5]. Slow variations in the power
system that eventually lead to voltage collapse is analyzed in
the steady state voltage study. This can be seen from the plot
, -'-��-'-�
-LL Filter-
a'1
of the power with the voltage at the bus also known as the "P
u
V" curve or "nose" curve. Figure 12 is a typical P-V curve
�
plot. It can be seen from the figure that as the power
transferred increases, the voltage at the receiving end
decreases, eventually reaching a nose point where any further Vref
2
v
voo... r 1
\,.
-'--�----��---�'
Va.p
- � +.,.-
I,
Figure 8.
6 (rad)
3
V. RESULTS AND DISCUSSION C. Simulation Results
/) Base case
A. Location a/Compensation Devices
As described in the earlier section, the continuation power
The best location for shunt reactive power compensation
flow analysis using PSAT is run for the test system and the
for steady state voltage stability margin is the weakest bus of
voltage profile without any FACTS devices is obtained. It was
the system [5]. Using continuation power flow (CPF) feature
found from the results that bus 14 was the weakest bus and the
of PSAT, the voltage profile of the test system is determined
following Fig. 11 gives the voltage profile and Fig.12 gives
and the weakest bus i.e., the bus where the voltage collapse
the PV curve for the weakest bus which is bus 14. It can be
first occurs is identified. Shunt compensation is provided in
seen from the figure that the maximum loading parameter A =
that bus to improve the system performance. The ideal
2.7699 pu for the base case.
location for Series compensation is still under investigation
[5]. However, a widely used and accepted method is by using Voltage Magnitude Profile
B. Device Ratings
The required shunt compensation capacity is determined
by knowing the amount of reactive power support needed at
the weakest bus. This could be determined by placing a
synchronous condenser without any limit on the reactive
power at the weakest bus and observing the amount of reactive
power generated at the maximum loading point. Another Bus #14
./
0.6
Select the Standard Network
051:---
0. 40!:-----=0'=-
.5 -
- !:-
, --""'.,5
'='--'!:-----=
.2'=-
5-!
Loadirg Parameter I. (p.u.)
for BLS 14 (v.eakest bus)
2) With STATCOM
from PV curves
It is seen from Fig. 12 that the voltage collapse occurs at
the maximum loading of A = 2.7699 and bus 14 is the best
Determine the FACTS rating location for shunt compensation. Using the procedure
according to reactive power
requirements obtained from power
described in the earlier section, a STATCOM of 0.7717 pu
flow was placed at bus 14 and CPF analysis was performed. Fig. 13
gives the voltage profile at bus 14 with STATCOM. It can be
seen from the figure that the maximum loading factor A =
4
1.01
5 .--�--�--�-�--, 1.1____
1.01
1.00
5
0.9
0.99
5 0.8
0.99
07
.
0.98
5
0.6
0.98
0.
5
0.97
5
0.97 �
0.
4
0. 5
96 0!:-=="':'=05. 1.
5 2.
5
Loading Parameter A. (p.u.) 0.
5 1.
5 2.
5
for Sus 14 Loading Parameter /,. (p.u.)
1
Bus 4
1.1
1.1,--�--�--,--,
0.9 0.9
\
0.8
0.8
/
0.7
0.7
0.6
0.
5
0.
5
e--
0 ...,0
:'-: -
5. -----,15 '-:- --
. �- -='
2 5...,. --.I
Loading Parameter I. (p.u.) 0.4
Bus 14
0.
5 1.
5 2.
5
Loading Parameter I. (p.u.)
Figure 14. "Nose" curve with sve Bus 14
4) With SSSC Figure 16. "Nose" curve for Bus 14 with TeSe at bus line 13-14
For the series compensation, as was described in the earlier
section, the SSSC was placed in the weakest bus lines one at D. Analysis ofResults
a time and it was found that for this system bus line 13 -14
Based on the results above, it can be seen that the
series compensation has better results. Hence, a 0.2 pu SSSC
maximum loading factor with STATCOM is highest while
was placed in that bus line. Fig. 15 gives the voltage profile
that with SSSC is lowest when compared to the base case. It
for the system with SSSC. It is seen that the maximum can also be seen that the voltage reduction is lowest in case of
loading factor A = 2.8047 has increases when compared to STATCOM. Shunt compensation device injects the reactive
the base case but is less than the shunt compensation devices. power at the connected bus but series compensation device
inserts the reactive power at the connected line. The test
system needs reactive power at the load bus more than the
line; hence shunt compensation gives better results. It can also
5
be seen that the SVC has a flat voltage profile until the [4] C. A. Canlzares, Z. T. Faur, "Analysis SVC and TCSC Controllers in
collapse point and then rapidly decreases as it approaches the Voltage Collapse," IEEE Trans. Power Systems, Vol. 14, No. I,
February 1999, pp. 158-165.
operational limits. From fig. 18 in appendix, it can also be
[5] Arthit Sode-Yome, Nadarajah Mithulananthan and Kwang Y. Lee, "A
seen that with the addition of FACTS devices with appropriate
Comprehensive comparison of FACTS Devices for Enhancing Static
ratings the overall system performance can be improved. Voltage Stability," IEEE Power Engineering Society General Meeting,
June 2007.
Table I gives the average costs of various FACTS devices
[6] Mehrdad Ahmad, Mostafa Alinezhad, "Comparison of SVC and
[10, 11] used for steady state voltage stability. The cost of
STATCOM in Static Voltage Stability Margin Enhancement",
capacitor-based compensation is also provided for reference. Proceedings of World Academy of Science, Engineering and
Technology, Vol. 38, Feb. 2009
[7] Lennart Angquist*, Gunnar Ingestrom, Hans-Ake Jonsson, "Dynamic
TABLE I. COST COMPARISON OF FACTS DEVICES
performance of TCSC schemes", ABB Power Systems, 1996.
Compensation Device Cost (US $) [8] Understanding FACTS by N.Hingorani, L.Gyugyi: IEEE Press
[9] F. Milano, "Power System Analysis Toolbox," Version 1.3.4, Software
SYC 40-60/kYar
and Documentation, July 14, 2005.
TCSC 25-40/kYar [10] John Kueck, Brendan Kirby, Tom Rizy, Fangxing Li and Ndeye Fall,
"Reactive power from Distributed energy", Electricity Journal, Dec.
STATCOM 55 - 70/kYar 2006
[II] N.Acharya, "Facts and Figures abour FACTS", Training workshop of
Shunt Capacitor 8-12/kYar
FACTS application, EPSM, Energy, Dec. 2004
Series Capacitor 12-15/kYar
It can be seen from the table that even though the cost for
FACTS is more than the capacitor-based compensation, the
benefits of flexible operation, and safety extend their
advantages. It is interesting to note that the average cost for
synchronous condensers used for dynamic reactive power
compensation varies $10-40 per kVAR and maintenance cost
is about $OA-0.8/kVAR per year [10].
VI. CONCLUSION
ACKNOWLEDGMENTS 0.7
0.
4
0;-----='
5-=- ----'-,----'":
0. 15=---
. 25
----0-.- --::
-'::-
. ----'
REFERENCES
Loading Parameter ,. (p.u.)
[I] C. A. Ca\iiizares, "Power flow and transient stability models of FACTS
controllers for voltage and angle stability studies," Proc. 2000
IEEEIPower Eng. Soc. Winter Meeting, pp. 8, Jan. 2000. Figure 17. Bus voltages result for NO FACTS case
[2] Shravana Musunuri, Herb Ginn, "Comprehensive Review of Wind
Maximum Power Extraction Algorithms", to be submitted at PES In the above figure the light blue color curve corresponds
General Meeting, July 2011 to the bus 14, which is the weakest bus. It is clear from fig. 17
[3] Baggu, M.M.; Watson, L.D.; Kimball, J.W.; Chowdhury, B.H, "Direct and fig. 18 that by placing STATCOM at bus 14, not only the
Power Control of double fed generator based wind turbine converters to voltage profile at that bus has improved significantly, but also
improve Low voltage ride through during system imbalance",Applied the voltage profile of other buses has also improved.
Power Electronics Conference, March 2010.
6
-
0.9
O.B
0.7
'\
0.6
0.4