Page 1 of 10 PT Citra Rekontama

CTDC Design Guidelines


Version :

Item Rated 2
Improved availability due to addition of redundant
Expected Outcome
components to critical parts of the infrastructure
Single path for power, telcom, cooling with
Redundancy design (high level)
component redundancy i.e. N+1
Component redundancy is not required on systems
like fire suppression, security etc
Allows for some level maintenance on equipment and
failures
Path maintenance often lead to downtime

Site Selection Considerations Zoning, environmental law, flooding risk, cooling


No Asbestos (with declaration letter), no lead based
Building Selection
paint, no PCB, seismic standards
Parking Area not required
Multi-tenant building Allowed only if occupancies are non-hazardous
Building Construction (IBC-2006) no restriction
Fire Rating of walls, glass Code allowable
NFPA-75 Requirements yes

Confidential
Page 2 of 10 PT Citra Rekontama

CTDC Design Guidelines


Version :

Item Rated 2
Vapor barrier yes
Roofing Class-A
Roofing type fully adhered / non mechanically attached system
Roof wind uplift resistance FM I-90
Roof slope Minimum code requirements
Floor Loading 8.4 kPa/840 kg/m2
Screed Layer Screed layer should be able to carry same weight
Bolted stringers, non combustible panel, class-A fire
Raised Floor
rating, bonded to ground
Ceiling height requirements 2.6 mtr from floor to any obstruction
Fixed at an appropriate height, non-porous material,
Suspended ceiling mold and mildew resistant, free of off-gassing,
shedding of fibers into the air, use clean room tiles
Height ratio (Raised floor : Suspended Ceiling) 1 : 1.5
No exterior windows in the computer room, entrance
Physical Separation requirements
room separate from computer room
Continuous (no PTZ camera), done for all restricted
CCTV critical areas (UPS, generator, etc.), building
perimeter, parking

Confidential
Page 3 of 10 PT Citra Rekontama

CTDC Design Guidelines


Version :

Item Rated 2
CCTV Recording Digital recording with 20 fps minimum (not required)
Security access control for rooms intrusion detection (door open alarm)
Main door onto computer room floor card access
Bullet proofing for security counter no requirement
Security staffing During scheduled operational hours
Measured at 1 meter from finished floor, 500 lux in
Lighting
horizontal plane, 200 lux in vertical plane
Emergency light Code requirements
Security checkpoints (primary building entrance) not required
Entry lobby (space which individuals come from
Physically separated from data center
outside to enter the building)
Doors without doorsills, open outward, no center post
Shipping and receiving area required which can be
Shipping and receiving areas
part of the data center
Physical protection of walls for shipping and receiving
no measures
area
Loading docks 1 per 2500 m2
physically separated from areas of the data center, no
Administrative office sharing of computer room cooling, PDU's etc, fire
rated, no windows recommended

Confidential
Page 4 of 10 PT Citra Rekontama

CTDC Design Guidelines


Version :

Item Rated 2
Same as administrative office, doors and walls should
Security office
be hardened, 180 degree peepholes/CCTV at door
Operations center Same as administrative office
Restrooms and break room areas Leak prevention barrier
UPS and battery room aisle width no specification
UPS room Fire separated as code requirements
Battery room Properly vented, hydrogen detection
Generator Area no requirements
Location of bulk fuel tank depends on local code,
Fuel Storage Area when above ground ensure bund walls are erected
and can contain the entire fuel storage volume
Generator and Fuel Storage Area no requirement
Computer Room Location No external windows
Computer Room environment MICE-1 per ANSI/TIA-568-C.0 and ASHRAE
Minimum height from finished floor to first
Computer Room ceiling height
obstruction > 2.6m
Sprinkler and fire suppression nozzles 46 cm clearance
Electrical Substation Single substation with single feeder to site
Utility feeders no specification
High Voltage / High Tension Switchgear no specification
Main Utility Board Stationary circuit breakers
Surge protection no specification

Confidential
Page 5 of 10 PT Citra Rekontama

CTDC Design Guidelines


Version :

Item Rated 2
Short circuit analysis, Load flow analysis, Arc flash
Power system analysis
analysis
Single generator supporting UPS systems and
Generator supply
mechanical system (Best practice is N+1 generators)
If redundant generator, allow a 'single bus'
Busbar
configuration
Bus 'Tie' connection / busbar coupling no specification
Fuel Supply Redundancy on the pumps
UPS Technology VFI class, VI are acceptable with power quality analysis
UPS should have a maintenance bypass feature to
UPS Bypass allow continuous operation during maintenance of the
UPS system
Automatic bypass required. The feed does not have to
UPS Maintenance Bypass arrangement
be separate from rectifier input
UPS Topology N+1, Parallel modules
Batteries are allowed to be in the same room as the
Battery Room separation UPS and other switchgear equipment rooms except
flooded cells
Battery bank/string separation no specification
Battery room aisle width no specification
Battery room fire separation Local Codes
Battery backup time 7 minutes

Confidential
Page 6 of 10 PT Citra Rekontama

CTDC Design Guidelines


Version :

Item Rated 2
Battery backup time configuration Provide backup time required on a N configuration

Battery bank configuration Dedicated battery string(=bank) for each UPS system
Battery Type and Life 10 year, VRLA or flooded
Battery monitoring not required
PDU High efficiency Isolation Transformer
required where single corded equipment is used to
(A)STS enable it to be connected to dual supply, with
maintenance bypass circuit
(A)STS Location Before/after PDU
Signal Reference Grid, every metal component
Grounding (TIA-607-B & IEEE-1100)
grounded
Surge protection devices must be monitored by the
Surge protection monitoring
Central Power Monitoring (CPM) system
Emergency Power Off (EPO) Only if required by local code
Monitoring of utility, UPS, and generator, notification
Central Power Monitoring
to control room console
Requires provision for a connection for a
Load banks (capacitive type preferred) portable/rental load bank, testing capability for
generators only
Factory Acceptance Testing (FAT) not required
Site circuit breaker testing (thermograph) no requirements
Testing and commissioning Component level testing (equipment)

Confidential
Page 7 of 10 PT Citra Rekontama

CTDC Design Guidelines


Version :

Item Rated 2
IPVT/IST not required
Operations and maintenance staff to be onsite during
Day Shift, on-call outside day shift hours, only
Equipment maintenance
generator requires maintenance, limited training by
the vendor (or reseller/supplier)
Every 100 sqm or use of water vacuum
Water drains
cleaners/pumps
ASHRAE Standards 18-27 C, 5.5 to 15 C DP up to 60% RH
Temperature change should not exceed 5 C per hr,
Environment Rate of Change
humidity change should not exceed 5% RH per hr
1.5 m above floor, 0.4 m in front of equipment, every
Temperature / Humidity Measurements 5th cabinet, equipment level at 3 height, 50 mm from
front
N+1 Capacity to be supplied (additional chiller and
additional CRAC units), 1 additional CRAC for every 3-4
Water Cooled system units serving the N capacity, supply can be single path,
connected to generator, with (de)humidification
required
Condenser water/Cooling towers Single piping going in (CDWR) and out (CDWS)
Two utility supplies or one utility supply and one on-
Make-up water
site storage to each condenser water circuit

Confidential
Page 8 of 10 PT Citra Rekontama

CTDC Design Guidelines


Version :

Item Rated 2
Redundancy on HVAC units (1:4 ratio), power supply is
Air cooled system
allowed to be single supply
Controllers with "No State Change" function upon loss
HVAC Control System of power to the controller and loss of control signal to
the controller
Plumbing Doesn't go above equipment
Refers to NFPA-75, openings fire-stopped, pre-action
sprinkler, no abandoned cables, remote disconnect to
Fire suppression HVAC and automatic closing of dampers, all metal
objects grounded, emergency lights, plans, handheld
fire extinguishers
Sprinkler System Pre-action sprinkler systems
Required, at perimeter of computer room, along any
Water Leak Detection water carrying pipe within computer room, along air
conditioners located within computer room
Telecommunications topology Star topology
Entrance Room Single
Multiple access provider yes
Access provider entrance and maintenance holes 20 m separation
Backbone cabling Redundant
Customer owned maintenance hole Two

Confidential
Page 9 of 10 PT Citra Rekontama

CTDC Design Guidelines


Version :

Item Rated 2
Critical equipment redundant power yes
4-pair 100-ohm balanced twisted-pair cable, Cat 6
Balanced twisted pair
minimum and recommended 6A
850nm Laser-optimized 50/125 um multimode fiber
Multimode fiber
cable OM3 or OM4 (ANSI/TIA-568-C.3)
Single Mode Fiber Single-mode optical fiber cable (ANSI/TIA-568-C.3)
75-ohm (734 and 735 type) coaxial cable used for T-1,
Coaxial cable
T-3, E-1, and E-3 circuits only
Type 735 26 AWG is used for interconnects up to 68
Coaxial cable range m, and type 734 20 AWG is used for interconnects up
to 137 m
Characteristic Impedance of 75-ohm, max. insertion
loss at 1 MHz to 22.5 MHz of 0.02 dB, min. return loss
Coaxial connectors
at 1 MHz to 22.5 MHz of 35 dB, recommended BNC
connectors
Two fibers - LC connector, more than two fibers -
Optical fiber connector
MPO connector
Fiber limit OM3 limit : 100 m, OM4 limit : 150 m
Should not run through public spaces, if so, either use
Data Cabling
enclosed conduit or concealed pathways
Should be in separate cable trays, if not possible, fiber
Fiber and copper separation
cables on top

Confidential
Page 10 of 10 PT Citra Rekontama

CTDC Design Guidelines


Version :

Item Rated 2
Minimal 2.7 m for the overhead trays above the
Overhead cable trays
access floor, max 150 mm depth of cable tray
All cables labeled at the connector level, both from
Cable Labeling and to should be indicated with proper labeling
material (UL969)
Center conductor continuity, shield continuity,
Coaxial cable testing
impedance (75-ohms), insertion loss
Fiber cable testing TIA-568-C.0 (optical testing and limits only)
TIA-568-C.2 (Channels, permanent links, cord, and
Balance Twisted Pair Cable Testing connectors, pair assembly, color code, performance
marking, reliability)
Return loss, insertion loss, NEXT loss, PSNEXT loss,
FEXT loss, ACRF, PSACRF, TCL, TCTL, ELTCTL, coupling
Balance Twisted Pair Cable Testing attenuation, propagation delay, propagation delay
skew, PSANEXT loss, average PSANEXT loss, PSAACRF,
and average PSAACRF

Confidential