Вы находитесь на странице: 1из 12

EPM 9000 Series

Performance Power Meter


& Data Acquisition Node
Available as a Stand-Alone Device
F or Industry & Utility or Integrated into GE Electrical
Distribution Equipment

n Power Quality Recorder


n Billing Grade Revenue Meter
n RTU with I/O & Control
n On-Board 10BASE-T Ethernet
n Internet or Intranet Data Retrieval

0.04% Billing Performance Power System Integrity Analysis


Grade Power Metering Quality Monitoring Sync. Check

Accu-Measure® Technology

MV90
COMPATIBLE
INDUSTRY
CANADA
MC#AE-1069

GE Industrial Systems
A Quantum Leap in Metering Accuracy
Obtain High -End Power Quality

GE
Presents the & Accurate Billing
most advanced Measurements
monitoring prod- High performance usage

uct ever designed. Envisioned to meet and power quality data is

the changing power metering needs of always available on-line in the

critical power applications, this unit pro- 9000 Series meters to provide

vides the total picture of power usage the needed power system

and power quality for any metered point assessment immediately. Use

within a power distribution network. The the precision accuracy of these

EPM 9000 Series signifies a profound meters for primary metering, sub-

advance in metering technology. metering or to check an installed utility Dual High Powered 16 Bit
meter. These meters are designed for A/D Converters
In the critical power environment,
both utility and industrial applications. Dual 16 Bit A/D converters provide
immediate access to power data is
supreme sampling accuracy and
paramount. Detailed load information
Expandable I/O & Trending— resolution.
and power quality are the prerequisite
Customize EPM 9000 Series for
for an effective energy management
Every Application Dual Internal References
program. These meters allow the user
These meters offer virtually unlimited Accurate to 1 PPM
to make power related decisions quickly
I/O capability in conjunction with all The unit auto-adjusts to dual internal
and effectively especially when used in
metering functions. Expandable I/Os references accurate to 1 part per mil-
conjunction with GE’s PQ Analyst and
enable these meters to be used for lion. These references ensure that the
Power Management Control System
every metering and data gathering monitoring equipment maintains its cali -
(PMCS) software .
application. bration.

The Most Advanced Revenue Auto-Calibration with


Metering Technology Temperature Compensation
The EPM 9000 Series offers the most The EPM 9000 Series uses an auto-

advanced power usage measurement calibration technique that recalibrates

technology. Utilizing patent pending the units on the fly when the tempera-

Accu-Measure® Technology, the accu- ture changes more than 5 degrees

racy of these meters has never been Centigrade. Temperature fluctuations

attained before at this pricing structure. have minimal effect on the precision

In your competitive environment, you and accuracy of the units.

need to know the precise amount of

consumed power. Accu-Measure ® i s


Precision Accuracy Specifications
With Accu-measure ®, these units far
a technique based on a multi-part
exceed all ANSI C-12 and IEC 687 accu-
approach allowing a field mounted
racy specifications. The units offer 0.04%
metering device to achieve laborato-
watt-hour accuracy.
ry accuracy. Using its auto -calibration

scheme, the units will remain within

calibration throughout their life.

Ethernet Connectivity - Perform Power System Assessments “On-line”


EPM 9000 Series
Designed for Primary Grade Utility Revenue Metering
Revenue Metering A time stamp is associated with each max are also recorded. Determine the

Features max and min. KW read number of capacitors needed, peak

TRANSFORMER LOSS AND LINE LOSS ings are integrated using: inefficiencies and many other issues.

COMPENSATION • Fixed Window


PASSWORD PROTECTION PREVENTS
The units compensate for transformer • Thermal Window
UNAUTHORIZED TAMPERING
and line losses. Power reading compen - • Rolling Window
Two, 10-character, alphanumeric pass-
sation is conducted for both iron and • Predictive Window
words protect the units from unautho-
copper losses. Any integration period is allowed. The
rized tampering. The first password is a
default is 15 minutes.
general password allowing a user to
TIME OF USE CAPABILITY
COINCIDENTAL READINGS view readings, but not change them.
The meters offer comprehensive time
When logging max Watt readings, the The second password allows the user to
of use capability.
coincidental VARs at the time of the change and re-program the units.
The TOU schedule has the following

capabilities: Historical Trends for Any Parameter


• Bi-Directional Consumption EPM 9000 Series Communicator Software
and Demand Quantities

• 20 Year Calendar
• 4 Seasons/Yr

• 12 Holidays/Yr Waveform Analyst Events

• 4 TOU
Schedules/Seasons

• Prior Month, Prior Season


Storage

• Present Month, Present Season


Storage

• Total Storage to Date


2
• Accumulated I t
2
• Accumulated V t

LOAD AGGREGATION /U NIVERSAL EPM 9450Q EPM 9650Q


METERING Log Storage 512K 512K 2 Meg 2 Meg 4 Meg 4 Meg
Using the status inputs, The EPM Options RAM Record Size RAM Record Size RAM Record Size
9450Q and 9650Q have the ability to

count pulses and aggregate different Historical Log 1 176K 58 Days 288K 96 Days 1808K 602 Days
loads providing a total picture of the
Historical Log 2 256K 42 Days 400K 66 Days 400K 66 Days
load and its component parts. The pulse
Out of Limit 48K 512 96K 1024 96K 1024
inputs can be used to accumulate and
CBEMA Log 16K 256 64K 1024 64K 1024
aggregate all other utility values such as

water and gas. Relay Output Log N/A N/A 48K 512 32K 512
Input Status Log N/A N/A 48K 512 32K 512
MAX/MIN INTEGRATION AND RECORDING
Waveform Recording N/A N/A 1040K 64 1568K 96
The units offer time stamped max and Number of Events
min values for every measured reading.
Note: Historical Log 1 is calculated recording 8 values every 15 minutes. Historical Log 2 is calculated
storing all integrated hour readings every 15 minutes. Every reading for every log is recorded with the
appropriate time stamps.

0.04% Watt-Hour Accuracy


Extensive On-Board Mass Memory Securely Records All Data
Multiple Programmable out of limit information to obtain a value returns to normal. All information

Memory Logs sequence of events for any occurrence. is time stamped to the nearest 1msec.

The EPM 9000 Series meters utilize Utilizing the 1msec clock resolution, the The 8 on-board high-speed inputs can

two separate logs of historical informa- logs can be combined with different be tied to the waveform recording.

tion. In addition to all power parameters, metered points through a distribution Record when the breaker tripped as

the historical logs allow users to trend system to provide an accurate system- compared to when the relay activated.

data from remote I/O devices. wide depiction of a power disturbance. This is very useful for fault and breaker

Furthermore circuit breaker pressure, integrity analysis.


Event-Triggered Waveform
transformer temperature or any other The unit can be programmed to take
Recording Log
analog or digital parameter can be more than one recording every time an
The EPM 9650Q records waveforms
monitored. Conduct preventative main - event occurs. Thousands of cycles can
with a resolution of up to 512 samples
tenance on critical equipment as well as be recorded per event.
per cycle. The amount of waveform
power analysis.
recording is based on the amount of

Primary Historical Trending Log memory installed.


File — Log 1 The unit records the waveform when a
— EPM 9450Q & EPM 9650Q
value goes out of limit and when the
Log any measured parameter from

either the main unit or any of the option


Log Storage 512K 512K 2 Meg 2 Meg 4 Meg 4 Meg
modules. Either 8, 16, 32 or 64 values
Options RAM Record Size RAM Record Size RAM Record Size
can be logged per programmable inter-

val.
Secondary Historical Trending Log Historical Log 1 176K 58 Days 288K 96 Days 1808K 602 Days
File — Log 2
Historical Log 2 256K 42 Days 400K 66 Days 400K 66 Days
— EPM 9450Q & EPM 9650Q
This log can be set up as an additional Out of Limit 48K 512 96K 1024 96K 1024
historical interval log or as an exclusive CBEMA Log 16K 256 64K 1024 64K 1024
energy log. Either 8, 16, 32 or 64 values
Relay Output Log N/A N/A 48K 512 32K 512
can be logged per interval.
Input Status Log N/A N/A 48K 512 32K 512
Out Of Limit Log Waveform Recording N/A N/A 1040K 64 1568K 96
— EPM 9450Q & EPM 9650Q Number of Events
The units offer an independent out of

limit log. This allows a user to download Note: Historical Log 1 is calculated recording 8 values every 15 minutes. Historical Log 2 is calculated storing all inte -
grated hour readings every 15 minutes. Every reading for every log is recorded with the appropriate time stamps.

Samples Number of Cycles Max. Number of Number of


Per Cycle Recorded Cycles Recorded Channels
Per Screen Per Event

16 8 Pre / 56 Post Event Screen 5760 7

32 4 Pre / 28 Post Event Screen 2880 7

64 4 Pre / 12 Post Event Screen 1536 7

128 1 Pre / 7 Post Event Screen 768 7

256 1 Pre / 3 Post Event Screen 384 3

512 1 Pre / 3 Post Event Screen 384 1

The Substation Automation Solution


EPM 9000 Series
0.04% Watt-hour Accuracy
CBEMA Log Input Status Log located in the unit. This ensures that the
— EPM 9450Q & EPM 9650Q — EPM 9650Q unit can be upgraded without removing
EPM 9000 Series meters store a sep- This log is similar to the Relay Output it from service.
arate CBEMA log that records magni- Log in that it allows the user to record
tude and duration of voltage and cur- when inputs change status
rent surges and sags for every power

quality event. This allows the user to Uploadable Flash Memory


— EPM 9650Q
conduct real-time CBEMA analysis
The EPM 9650Q utilizes uploadable
without downloading all stored wave -
flash memory technology on all proces-
forms. The separate CBEMA log also
sors and DSPs
allows the unit to provide a more com-

prehensive picture of quality over time.

Relay Output Log


— EPM 9650Q
The unit records when a relay output

from the external I/O is activated, time

stamps the event and provides a rea-

son why the relay changed status.

Expandable External I/O • RTU Capability • ElectroLogic® Control


programmable limit settings. Virtually graphical tree structure. The user can
Use EPM 9000 Series
any of the approximately 7000 values set logical descriptors such as:
Meters as RTUs
GE offers multiple Analog and Digital that the monitors measure can have
• AND/NAND/XAND Gates
I/O modules that mount externally to limits and logic set to trigger opera-
• OR/ NOR/XOR Gates
the EPM 9450Q and 9650Q. The units tions. This features allows a user to
• Hysteresis/ Hysteresis Control
support up to 4 I/O modules using inter- configure the EPM 9450Q and EPM
9650Q to be used as control devices for Using the graphical array, each tier
nal power. An additional power supply
many applications such as: configures to the desired logical
extends I/O capability.
scheme enabling the meters to address
The master port of the units eliminate
• Capacitor Control complex control requirements. The con -
the need for RTUs in many substation
• Load Shedding trol can be extended for a virtually
applications. The meters can poll • Automatic Transfer Schemes
unlimited number of relay outputs.
different I/O devices, log data, and • Transformer Monitoring & Control Simply extend additional I/O modules.
send data to a master station via
• Redundant Protection Response time is typically less than 200
Modbus protocol. This I/O functionality —Not designed for Primary Over-
Current Protection msec per I/O module extendible to multiple
is available in EPM 9450Q and 9650Q at seconds.
• Many other control functions
much lower costs than traditional substa-

tion RTUs. Graphical Programming Interface


Available for Relaying & Control
A unique structure allows users to
Programmable Logical
develop up to 3 tiers of logic control
Protection & Control
based on limits and status conditions.
The EPM 9000 Series power monitors
All data is displayed in a
provide advanced logic and control on

Graphical 3 Tier Programming

Precise Measurement • Analysis • Control


Precision Power Quality Monitoring
16 Bit Waveform and Fault Sub-Cycle Transient Recorders Robust Communication
Recorder The units record sub-cycle transients Options for Every
The EPM 9000 Series can record up on voltage and current readings. They Application
to 512 samples per cycle for an event. monitor switching noise from capacitors, 4 Isolated High-Speed
Record voltage and current with pre- static transfer switches, SCRs and many Communication Ports
and post-event analysis. Fault recording other “power quality harmful” devices. The units offer 4 built-in communica-

offers 8x full scale capture capability. Transients are often the cause of inter- tion ports. Each port can speak Modbus

All voltage and current readings are mittent and expensive downtime. RTU. All stored logs and Waveform

recorded using a 16 bit A/D converter. Without these meters, solving these events are available in Modbus format.

This provides precise waveform resolu- problems is often impossible. All four ports are identical. Port 4 can be

tion. Both hardware and software trig- used as a master for I/O modules.

gers are available to activate a wave- Phasor Analysis


form reading. This can be used for The monitors read a phase angle On-Board Ethernet TCP/IP
power quality surveys, fault analysis, analysis between the voltage and cur- Using the internal expansion port, the

breaker timing, etc. rent channels, allowing for efficiency and meters can be ordered with on-board

system integrity analysis. Ethernet TCP/IP functionality. The


Measure and Record Harmonics 10BASE-T design allows the unit to
to the 255th Order speak Open Modbus via TCP/IP. When
The units measure harmonics up to
one of these devices is configured with
the 255th order for each voltage and
the ethernet TCP/IP card, port 2
current channel. Real-Time harmonics
becomes a gateway enabling other
are resolved to the 128th order. Percent
Modbus based IED equipment to be
THD and K-Factor are also calculated.
interfaced to the network LAN.
This high performance harmonic analy -

sis allows users to conduct power quali-

ty analysis at the high end of the har-


Multiple-Socket Ethernet Interface
— EPM 9450Q & EPM 9650Q
monic spectrum. Independent CBEMA Log Plotting The unique Ethernet interface allows
The EPM 9000 Series meters store an
multiple requests to receive data simul-
Status Input Triggers independent CBEMA Log for magnitude
taneously. Twelve independent sockets
The units record the waveform at the and duration of voltage events. In this
can be opened at the same time. This is
time of the status change. The input manner, the user can quickly view total
like having 12 ports in one.
change and waveform recording are surges, total sags and average duration
time stamped to a 1msec resolution. without having to retrieve waveform

information.
On-Board Internal Modem
Additional Inputs If desired, the internal expansion port

EPM 9000 Series offers inputs for can be configured to provide an internal

Neutral to Ground Voltage measure- 56K baud modem. This gives the units

ments. This allows you to analyze rising dial-in and dial-out capability without
ground potential often damaging electri- additional hardware. This is ideal for
cal equipment. The unit also calculates small remote applications. When the
and measures the neutral current. device is configured with a modem

card, port 2 becomes a gateway allow-

ing other Modbus based serial devices

access to the phone line.

Cutting-Edge Technology Monitors Your Power Quality


EPM 9000 Series
On-Board Communication for Every Application
Additional Capabilities Sync. Check-Aux. Volt Input The Vaux channel can be used to get
the frequency, magnitude and phase
8 Built-In Digital High-Speed The units have high-speed Vaux
Status Inputs angle on both sides of a switch or
input. This input can be used for
between generator and bus voltage.
These inputs automatically sense multiple purposes:
whether the circuit is externally • Neutral to Ground
wetted. If externally wetted, the • Voltage Readings

input will accept up to 400VDC. If inter- • Synchronizing


Schemes
nally wetted, the unit supplies the need-

ed voltage for the desired control appli-

cation.

High-Speed Transducer Outputs


Each User is One
for Control Purposes
Socket Connection
The EPM 9450Q and 9650Q offer 50

msec updates for all instantaneous

readings. The units can be high-speed


TCP/IP Bus — Internet or Intranet
control transducers for power genera -

tion, transmission line synchronization

and any other synchronizing and control INTERNET PACKAGE LOCAL PC SCADA CONTROL SCHEME OTHER USERS

scheme.
Multiple Socket Internet or Intranet Meter Access
Up to 12 Sockets Simultaneously

4 Communication Ports 8 High-Speed IRIG-B


Status Inputs Input

Heartbeat
(Test Pulse)

On-Board
Modem or
RS-232 Ethernet TCP/IP

Rugged
Metal Case

Universal
Power Supply
4 Voltage 4 Current
Inputs Inputs

On-Board Ethernet Allows Access to Power Data “On-Line”


Superior Construction MOV protection and active line filtering to Communication Ports
& Isolation reduce any damaging occurrences to the All communication ports are isolated

These units are rugged and durable supply. from the main unit and additionally iso-

devices. They provide considerable pro - lated from each other. This avoids dan-

tection and isolation from damaging Voltage Inputs gerous ground loops.

outside forces. The voltage inputs are optically isolat-

ed. Issues such as noisy grounds, I/O Modules


Case Construction switching noise, SWC or any other such Each I/O module is isolated from the

The units are mounted in a shielded problems pose no threat to these units. main unit and from other I/O modules.

metal case. The case offers no visible No signal entering an I/O module can

openings and is resistant to contamina- Current Inputs damage any other part of the units.

tion from harmful dust, sand or other The current inputs are direct shorts.

matter. All screws and hardware are stain- They offer a stud input U-Bolt design

less steel. with an internal toroidal sensor. Since

this is a quarter-inch thick solid brass

Power Supply U-Bolt without solder or weld joints, the

The power supply offers both units’ current input and surge withstand

capability is significant.

Display & External I/O Options

EPM 9450Q & 9650Q Displays


Touch-Screen LCD Touch-Screen LCD for a graphical data
presentation. 320 x 240 pixels, CCFL
Backlight.
One screen can monitor up to 8 units

Multi-Function LED Multi-Function LED display. For multiple


display options, each display m o d u l e i s
an RS-485 master. One display
uses one communication port.

Analog Transducer Signal Outputs


n
4 Analog Outputs, 0–1mA, self-powered, scalable, bi-directional
Touch-Screen Display
n
8 Analog Outputs, 0–1mA, self-powered, scalable, bi-directional
n
4 Analog Outputs, 4–20mA, self-powered, scalable
n
8 Analog Outputs, 4–20mA, self-powered, scalable

Wiring: Common Mode


Accuracy: 0.1% of Full Scale
Calibration: Self-Calibrating
Scaling: Programmable
Ordering Specifics: Up to 4 Analog Output modules can be
used with each unit

Analog Transducer Signal Inputs


n
8 Analog Inputs, 0-1mA, bi-directional
n
8 Analog Inputs, 0-20mA, bi-directional
n
8 Analog Inputs, 0–5 VDC, bi-directional
LED Display
n
8 Analog Inputs, 0–10 VDC, bi-directional
EPM 9000 Series
Wiring: Common Mode
Additional I/O Accessories
Accuracy: 0.25% of Full Scale
Scaling: Programmable n
Additional power supply for up to 6 I/O modules. This accessory is
Ordering Specifics: Up to 4 modules can be used needed when using more than 4 modules.

n
Mounting bracket for I/O modules
Digital Dry Contact Relay Outputs
n
4 Relay Outputs, 5 amps, 125, AC/DC, Form C

Ordering Specifics: Multiple modules can be used

Digital Solid State Pulse Outputs


n
4 Solid State Pulse, Outputs, Form A or C KYZ Pulses

Maximum Pulse Speed: 20 pulses per second


Ordering Specifics: Up to 4 modules can be used

Digital Inputs
n
8 Digital Status Inputs Wet/Dry Auto-Detect Up to 300 Volts DC

Wiring Diagrams
EPM 9000 Series Meters support every wiring system and configuration. They configure easily for 2, 21/2 , or
3 element. All wiring and hookup configurations are software configured. Note: Download EPM 9000 Series
manual from www.gepowerleader.com to get additional wiring configurations

FUSES FUSES
0.25A 0.25A

SUPPLY POWER SUPPLY POWER


(DEPENDENTON (DEPENDENTON
EQUIPPED POWER EQUIPPED POWER
SUPPLY OPTION) CT SHORTING SWITCH SUPPLY OPTION) CT SHORTING SWITCH
CR TEST BLOCK CR TEST BLOCK

LOAD CTs LINE LOAD LINE


N CTs
C C
B B
A A
SWITCHGEAR CHASSIS GROUND SWITCHGEAR CHASSIS GROUND

4 WIRE WYE: 3 ELEMENT DIRECT VOLTAGE 3 WIRE: 3 ELEMENT DIRECT DEL TA


Mounting & Dimensions
Contact GE for additional mounting options.
10.5" (26.6cm) EPM 9450Q/
EPM 9650Q
2x3.25" (8.27cm) 2x4.0" (10.16cm) Monitors
Side View
2.35" 5.9cm

7.25"
(18.4cm)
EPM 9450Q/
EPM 9650Q
Monitors
Front View 6.74"
(17.1cm)

4x0.221" (0.56cm) Thru Slot


(For #10 Screw) 3.4" 8.6cm

3.375" Sq. (8.5cm) 0.71"


4 X 0.198" 4.375" Sq.(11.11cm) (1.8cm)
(0.5cm)

4.00"
(10.18cm)

1.687"
(4.3cm)

1.42"
Display Cutout Pattern Display
(3.6cm)
(ANSI C39.1) Front View
LED Display
Side View

Mounting
Aperture is 4.763" x 3.583" (12.1 x 9.1cm) Bracket
Pixel Matrix (320 x240) is 11.5 x 8.6cm Mounting
Bracket

4-40 screws, 8x

2.20" (5.5cm)
1.10"
3.43" (8.7cm)
(2.8cm)

7.36" (18.6cm) typ


3.76" (9.5cm) typ 2.1" (5.3cm) typ 0.250" (0.63cm)typ
1.125" 1.3"
8.00" (20.3cm) 0.625"
(2.8cm) (3.3cm)
(1.53cm)

I/O Modules
1.392"
(3.5cm)
1.55" Front View
0.156" (3.9cm)
(0.4cm)
Touch-Screen Display
Front and Side View
EPM 9000 Series
Input Voltage Range Isolation Control Power Requirements

150 Volt PH-N, 300V PH-PH All inputs and outputs are isolated to 2500 Volts. 90–276 Volts AC/DC

(Used with PTs for Extended Range) All Com Ports are additionally isolated from 18–60 Volts DC

300 Volt PH-N, 600 Volt PH-PH each other.


Frequency Range

Voltage Input Withstand Capability Temperature Rating 20–400Hz

Voltage Inputs optically isolated to 2500VDC. Operating Temperature: -40 to +70°C


Communication Format
Meets ANSI C37.90.1 (Surge Withstand Humidity: Up to 95% Non-Condensing
Programmable parity and stop bits
Capability)
Sensing Method Communication Protocols: Modbus, Modbus

Input Current Range Up to 512 Samples per Cycle ASCII/RTU and DNP 3.0

5 amp Inputs 2x Continuous programmable (Programmable) 4 Communication ports, 2 slave ports, 2

to any CT range 16 Bit A/D Resolution – Dual Converters selectable master/slave ports.

Fault Current recording to 60 amps peak Utilizes patent pending All ports use 2-wire RS-485 communication;

secondary based on 5 amp full scale Accu-measure® Technology Port 1 is RS-232 or RS-485 Selectable

Note: 1 amp and 0.25 amp current inputs True RMS Ethernet: 10baseT, RJ-485 running

available as special order Modbus/TCP Protocol


Accuracy Rating

Current Input Withstand Capability This unit complies with and exceeds ANCI Construction

100 amps for 10 Seconds C12.20 and IEC687 accuracy requirements. Constructed in a metal case. All hardware is

300 amps for 1 Second Industry Canada Revenue Metering stainless steel.

Approval:#AE-1069
Burden Shipping

Voltage Inputs: 0.05VA Max Update Time Total shipping weight:

Current Inputs: 0.005VA Max 50 msec. — High Speed Readings approx. 12 lbs (5.4 kgs)

1 Second — Revenue Accurate Readings Shipping container dimensions: 16" x13" x11"

(40.64cm x 33.02cm x 27.94cm)

Measurement Accuracy (% of Reading)


PARAMETER 50 MILLISECOND* 1 SECOND DISPLAY RESOLUTION

5 Digit
Voltage (L-N) 0.1% 0.01% 5 Digit
Voltage (L-L) 0.1% 0.01% 5 Digit
Current 0.1% 0.025% 00.001 Hz
Frequency 0.01 Hz 0.001 Hz 5 Digit
KW @ Unity PF 0.1% 0.04% 5 Digit
KW @ .5 PF 0.1% 0.08% 5 Digit
KVA 0.4% 0.06% 5 Digit
VAR 0.1% 0.06% 3 Digit
PF 0.1% 0.06% 3 Digit
Harmonics N/A 0.1% 16 Digit
KW/Hours N/A 0.04% 16 Digit
KVA/Hours N/A 0.06% 16 Digit
KVAR/Hours N/A 0.06%

* When high-speed readings are brought through the analog output modules,
update time is at approx. 180 msec. for each 2 channels of analog signals.

GE Industrial Systems
Ordering Information
EPM 9450Q Performance Power Monitor & Data Acquisition Node
P L 9 4 5 0 A 0 0 0 0
0 60 Hz Operation
FREQUENCY
1 50 Hz Operation
A 120/208 Volt Connection
VOLTAGE INPUT
B 277/480 Volt Connection
0 90-276 Volt AC/DC Power Supply
CONTROLPOWER
1 18-60 Volt DC Power Supply
A
0 No Modem or Ethernet Connection
1 COMMUNICATION Internal Ethernet Connection with Pass-Through Port
2 Internal 56k Modem Connection with Pass-Through Port
EPM 9650Q Performance Power Monitor & Data Acquisition Node with Memory
P L 9 6 5 0 A 0 0 0 0
0 FREQUENCY
60 Hz Operation
1 50 Hz Operation
A VOLTAGE INPUT
120/208 Volt Connection
B 277/480 Volt Connection
0 90-276 Volt AC/DC Power Supply
CONTROLPOWER
1 18-60 Volt DC Power Supply
A Standard 2MB Memory
MEMORY
B Advanced 4MB Memory
0 No Modem or Ethernet Connection
1 COMMUNICATION Internal Ethernet Connection with Pass-Through Port
2 Internal 56k Modem Connection with Pass-Through Port
Analog Output Modules
P L 9 0 0 0 0 0
1 M A O N 4 O 4 Channel 0-1 mAAnalog Outputs
1 M A O N 8 O 8 Channel 0-1 mAAnalog Outputs
2 O M A O N 4 4 Channel 4-20 mAAnalog Outputs
2 O M A O N 8 8 Channel 4-20 mAAnalog Outputs
Analog Input Modules
P L 9 0 0 0 0 0 0 0 0
8 A I 1 8 Channel 0-1 mAAnalog Inputs
8 A I 2 8 Channel 4-20 mAAnalog Inputs
8 A I 3 8 Channel 0-5 VDC Analog Inputs
8 A I 4 8 Channel 0-10 VDC Analog Inputs
Digital I/O Modules
P L 9 0 0 0 0 0 0 0 0
4 R O 1 4 Channel Control Relay Outputs
4 P O 1 4 Channel kyz Solid State Pulse Outputs
8 D I 1 8 Channel Auxiliary Digital Status Inputs
Auxiliary I/O Mounting
P L 9 0 0 0 M B I O 0 0 0 0 0 I/O Mounting Bracket (One set per module group)
Auxiliary I/O Power Supply
P L 9 0 0 0 P S I O 0 0 0 0 0 I/O Auxiliary Power Supply (For more than 4 modules)
9000 Series Meter Display Module
P L 9 0 0 0 0 0 0 0 0
P 4 0 N Three line LED Display
P 6 0 N Touch-Screen LCD Display
9000 Series Meter Software
P L 9 0 0 0 0 0 0 0 0
N C M 1 Communicator Software, Single User License
N C M 5 Communicator Software, Five User License
N C M S Communicator Software, Multiple User, Single Site License

Notes: Displays must be ordered separately from base meters

GE Industrial Systems
General Electric Company
41 Woodford Avenue, Plainville, CT 06062
www.GEindustrial.com
DET-301A 0602 ©2001 General Electric Company