Heat Recovery Ventilator

With today’s concern for a healthy indoor environment,


eco V is an integral component of HVAC system.
eco V Using in the HVAC system allows contaminants to be
removed quickly and effectively from the air-conditioned
space.

eco V

62 Features
63 Installation & Maintenance
64 Line-up
66 Specifications
Heat Recovery Ventilator

LG’s heat recovery ventilation system,


eco V, modulates the temperature and
humidity of incoming fresh air to match
indoor conditions. A balance is achieved
between indoor and outdoor ambient,

(Heat Recovery ventilator)


enabling the cooling or heating load
placed on the air conditioning system to
be reduced significantly.

LG Air Conditioners System


60_61
Features
• High efficiency heat exchanger
• Bypass ventilation
• Strong filter function

Supply Air High Efficiency Heat Exchanger


Efficiency and comfort is ensured by
the high-efficiency energy recovery
Exhaust Air central core which recovers energy
from the indoor air and transfers it to
Air Filter Air Filter
the fresh incoming air without mixing
airstream.
High performance Filter
Outdoor Air (Option)
{ Deodorization Filter
Indoor Air

• Enthalpy Heat • Bypass Mode Bypass Ventilation


Exchange Mode It switches automatically the ventilation mode
Damper
(Enthalpy Heat Exchange Mode / Bypass Mode)
Damper
according to the indoor/outdoor temperature.

[Summer / Winter] [A change of season]

• Air Filter Strong Filter Function


Air Filter
The air filter has collection efficiency above 80%, which
means it can filter particles up to 0.3 m including tobacco
of smoke and even floating particles from yellow sand.

• HEPA+Deodorization Filter (Accessory) HEPA + Deodorization Filter (Accessory)


The indoor air can be always kept fresh through these filters.

Yellow Sand Filter (Accessory)


This filter can make more comfortable and fresh
environment through removing harmful to health 5~20µm
sandy dust over 99%.

• Yellow Sand Filter (Accessory)


Dust Collection Efficiency (%) Pressure Loss (Pa)
Installation
& Maintenance
• Flexibility installation
• Easy cleaning and changeable filter

Flexibility of Installation
It’s possible to install the opposite direction
of upper and lower part. It needs the only one
inspection hole.

Normal installation Reverse installation


of 2 units of 1 unit (Left unit)

(Heat Recovery ventilator)


• Inspection hole

Top Low

Low Top

Easy Cleaning and Changing Filter


Door attached side panel and slide removable

LG Air Conditioners System


Enthalpy heat exchanger filter can be changed
without additional maintenance.

• Eco V unit • Remove side panel


62_63

• Remove free filter • Remove heat exchanger


The LG heat recovery ventilation system, eco V
is the solution for improving your indoor air quality.

LZ-H0106BA1 LZ-H0156BA1
Power Supply [Ø,V,Hz] _ Power Supply (Ø, V, Hz) _
1Ø, 220-240V, 50Hz 1Ø, 220~240V, 50Hz

Dimension [WxHxD]_ Dimension (WxHxD) _


204x509x509mm 590x204x590mm
[8.03x23.23x23.23inch] (23.23x8.03x23.23 inch)

Weight_ 24kg[52.91lb] Weight _ 24kg (52.91 lb)]

LZ-H0256BA1 LZ-H0356BA1
Power Supply (Ø, V, Hz) _ Power Supply (Ø, V, Hz) _
1Ø, 220~240V, 50Hz 1Ø, 220~240V, 50Hz

Dimension (WxHxD) _ Dimension (WxHxD) _


596x320x640mm 988x273x1014mm
(23.46x12.60x25.20 inch) (38.9x10.75x39.92 inch)

Weight _ 27kg (59.51 lb) Weight _ 45kg (99.2 lb)

LZ-H0506BA1
Power Supply (Ø, V, Hz) _ 1Ø, 220~240V, 50Hz
Dimension (WxHxD) _ 988x273x1014mm (38.9x10.75x39.92 inch)
Weight _ 52kg (114.7 lb)
• High Efficiency Heat Exchanger

• Bypass Ventilation

• Strong Filter Function

• Flexibility of Installation

• Easy Cleaning and changeable Filter

LZ-H0806BA1
Power Supply (Ø, V, Hz) _ 1Ø, 220~240V, 50Hz
Dimension (WxHxD) _ 1062x365x1140mm (41.9x14.4x44.9 inch)
Weight _ 67kg (147.7lb)

LZ-H1006BA1

(Heat Recovery ventilator)


Power Supply (Ø, V, Hz) _ 1Ø, 220~240V, 50Hz
Dimension (WxHxD) _ 1062x365x1140mm (41.9x14.4x44.9 inch)
Weight _ 67kg (147.7lb)

LG Air Conditioners System


LZ-H1506BA1
Power Supply (Ø, V, Hz) _ 1Ø, 220~240V, 50Hz
Dimension (WxHxD) _ 1313x737x1140mm (51.7x28.8x44.9 inch)
Weight _ 146kg (321.9 lb)

64_65

         

LZ-H2006BA1
Power Supply (Ø, V, Hz) _ 1Ø, 220~240V, 50Hz
Dimension (WxHxD) _ 1313x737x1140mm (51.7x28.8x44.9 inch)
Weight _ 146kg (321.9 lb)
Heat Recovery Ventilator

* Specifications

Item Unit LZ-H0106BA1 LZ-H0156BA1 LZ-H0256BA1 LZ-H0356BA1 LZ-H0506BA1


Nominal Capacity CMH(L/S) 100(28) 150(42) 250(69) 350(97) 500(139)
Power Supply Ø,V,Hz 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220~240, 50
Step - SUPER-HIGH/HIGH/LOW SUPER-HIGH/HIGH/LOW SUPER-HIGH/HIGH/LOW SUPER-HIGH/HIGH/LOW SUPER-HIGH/HIGH/LOW
Current SH/H/L Amps 0.32/0.3/0.28 0.36/0.36/0.35 0.55/0.5/0.34 1.40/1.33/0.9 1.51/1.39/1.06
Power Input SH/H/L W 68/60/50 83/80/78 130/115/80 205/195/170 260/225/200
eco V Mode

Air Flow SH/H/L CMH(L/S) 100/100/90(59/59/53) 150/150/100(42/42/28) 250/250/180(69/69/50) 350/350/210(97/97/58) 500/500/320(139/139/89)


External Static Pressure SH/H/L Pa(in.wg) 40/35/30(0.16/0.14/0.12) 70/55/45(0.28/0.22/0.18) 65/50/40(0.26/0.2/0.16) 170/88/40(0.68/0.35/0.16) 150/60/28(0.60/0.24/0.11)
Temperature Exchange Efficiency SH/H/L % 78/78/80 75/75/79 80/80/85 83/83/87 75/75/79
Enthalpy Exchange Efficiency Heating(SH/H/L) % 68/68/70 62/62/69 70/70/78 80/80/85 75/75/80
Cooling(SH/H/L) % 58/58/60 55/55/59 64/64/68 78/78/83 70/70/75
Noise Level(Sound Level, 1.5m) SH/H/L dBA 28/26/20 32/30/22 32/28/21 33/28/23 34/32/25
Step - -/-/- -/-/- -/-/- SUPER-HIGH/HIGH/LOW SUPER-HIGH/HIGH/LOW
Current SH/H/L Amps -/-/- -/-/- -/-/- 1.40/1.33/0.9 1.51/1.39/1.06
Power Input SH/H/L W -/-/- -/-/- -/-/- 205/195/170 260/225/200
Bypass Mode

Air Flow SH/H/L CMH(L/S) -/-/- -/-/- -/-/- 350/350/210(97/97/58) 500/500/320(139/139/89)


External Static Pressure SH/H/L Pa(in.wg) -/-/- -/-/- -/-/- 170/88/40(0.68/0.35/0.16) 150/60/28(0.60/0.24/0.11)
Temperature Exchange Efficiency SH/H/L % -/-/- -/-/- -/-/- -/-/- -/-/-
Enthalpy Exchange Efficiency Heating(SH/H/L) % -/-/- -/-/- -/-/- -/-/- -/-/-
Cooling(SH/H/L) % -/-/- -/-/- -/-/- -/-/- -/-/-
Noise Level(Sound Level, 1.5m) SH/H/L dBA -/-/- -/-/- -/-/- 33/28/23 34/32/25
Heat Exchanger Type - Crossflow Crossflow Crossflow Crossflow Crossflow
Weight kg(lb) 24(52.91) 24(52.91) 27(59.51) 45(99.20) 52(114.7)
Dimension WxHxD mm(inch) 590x204x590(23.23x8.03x23.23) 590x204x590(23.23x8.03x23.23) 596x320x640(23.46x12.60x25.20) 988x273x1014(38.9x10.75x39.92) 988x273x1014(38.9x10.75x39.92)

Duct work Qty EA 4 4 4 4 4


Size(Ø) mm(inch) Ø100(Ø3.94) Ø100(Ø3.94) Ø150(Ø5.91) Ø200(Ø7.87) Ø200(Ø7.87)
Supply Air Fan Qty EA 1 1 1 1 1
Type - Direct-Drive Direct-Drive Direct-Drive Direct-Drive Direct-Drive
Exhaust Air Fan Qty EA 1 1 1 1 1
Type - Direct-Drive Direct-Drive Direct-Drive Direct-Drive Direct-Drive
Filters Qty EA 2 2 2 2 2
Type - Cleanable Cleanable Cleanable Cleanable Cleanable
Size(WxHxD) mm(inch) 580x10x113(22.83x0.39x4.45) 580x10x113(22.83x0.39x4.45) 580x10x175(23.23x0.39x6.89) 855x10x166(33.66x0.39x6.54) 855x10x166(33.66x0.39x6.54)

Notes:
1. eco mode - Enthalpy Heat Recovery Ventilation mode
2. Noise level :
- The operating conditions are assumed to be standard.
- Sound measured at 1.5m below the center the body.
- Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed.
eco V ensures the fresh enviroment in your life!

* Specifications

Item Unit LZ-H0806BA1 LZ-H1006BA1 LZ-H1506BA1 LZ-H2006BA1


Nominal Capacity CMH(L/S) 800(222) 1000(278) 1500(417) 2000(556)
Power Supply Ø,V,Hz 1, 220~240, 50 1, 220~240, 50 1, 220~240, 50 1, 220~240, 50
Step - SUPER-HIGH/HIGH/LOW SUPER-HIGH/HIGH/LOW SUPER-HIGH/HIGH/LOW SUPER-HIGH/HIGH/LOW
Current SH/H/L Amps 2.8/2.7/2.6 3.0/2.9/2.6 5.6/5.4/5.2 6.0/5.8/5.2
Power Input SH/H/L W 405/360/320 560/540/470 950/925/795 1020/970/860
eco V Mode

Air Flow SH/H/L CMH(L/S) 800/800/660(222/222/183) 1000/1000/800(278/278/222) 1500/1500/1200(417/417/333) 2000/2000/1600(556/556/444)


External Static Pressure SH/H/L Pa(in.wg) 200/110/60(0.80/0.44/0.24) 160/90/50(0.80/0.44/0.24) 200/110/60(0.80/0.44/0.24) 160/90/50(0.80/0.44/0.24)

(Heat Recovery ventilator)


Temperature Exchange Efficiency SH/H/L % 79/79/82 75/75/78 79/79/82 75/75/78
Enthalpy Exchange Efficiency Heating(SH/H/L) % 70/70/75 66/66/71 70/70/75 66/66/71
Cooling(SH/H/L) % 65/65/70 61/61/66 65/65/70 61/61/66
Noise Level(Sound Level, 1.5m) SH/H/L dBA 36/34/30 37/35/31 39/37/33 39/37/33
Step - SUPER-HIGH/HIGH/LOW SUPER-HIGH/HIGH/LOW SUPER-HIGH/HIGH/LOW SUPER-HIGH/HIGH/LOW
Current SH/H/L Amps 2.8/2.7/2.6 2.8/2.7/2.4 5.6/5.4/5.2 5.6/5.4/4.8
Power Input SH/H/L W 405/360/320 560/540/470 950/925/795 1020/970/860
Bypass Mode

Air Flow SH/H/L CMH(L/S) 800/800/660(222/222/183) 1000/1000/800(278/278/222) 1500/1500/1200(417/417/333) 2000/2000/1600(556/556/444)


External Static Pressure SH/H/L Pa(in.wg) 200/110/60(0.80/0.44/0.24) 160/90/50(0.80/0.44/0.24) 200/110/60(0.80/0.44/0.24) 160/90/50(0.80/0.44/0.24)
Temperature Exchange Efficiency SH/H/L % -/-/- -/-/- -/-/- -/-/-

LG Air Conditioners System


Enthalpy Exchange Efficiency Heating(SH/H/L) % -/-/- -/-/- -/-/- -/-/-
Cooling(SH/H/L) % -/-/- -/-/- -/-/- -/-/-
Noise Level(Sound Level, 1.5m) SH/H/L dBA 36/34/30 37/35/31 37/35/31 37/35/31
Heat Exchanger Type - Crossflow Crossflow Crossflow Crossflow
Weight kg(lb) 67(147.7) 67(147.7) 146(321.9) 146(321.9)
Dimension WxHxD mm(inch) 1062x365x1140 (41.9x14.4x44.9) 1062x365x1140 (41.9x14.4x44.9) 1313x737x1140(51.7x28.8x44.9) 1313x737x1140(51.7x28.8x44.9)

Duct work Qty EA 4 4 4+2 4+2


66_67
Size(Ø) mm(inch) Ø250(Ø9.54) Ø250(Ø9.54) Ø250(Ø9.54)+Ø350(Ø13.77) Ø250(Ø9.54)+Ø350(Ø13.77)
Supply Air Fan Qty EA 1 1 2 2
Type - Direct-Drive Direct-Drive Direct-Drive Direct-Drive
Exhaust Air Fan Qty EA 1 1 2 2
Type - Direct-Drive Direct-Drive Direct-Drive Direct-Drive
Filters Qty EA 2 2 4 4
Type - Cleanable Cleanable Cleanable Cleanable
Size(WxHxD) mm(inch) 1056x10x212.5(41.57x0.39x8.37) 1056x10x212.5(41.57x0.39x8.37) 1056x10x212.5(41.57x0.39x8.37) 1056x10x212.5(41.57x0.39x8.37)

Notes:
1. eco mode - Enthalpy Heat Recovery Ventilation mode
2. Noise level :
- The operating conditions are assumed to be standard.
- Sound measured at 1.5m below the center the body.
- Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed.