TCD - 023 TCD 23 : Run CPU SPEC data sum error Point of Application ● DI120~150
TCD - 024 TCD 24 : Run CPU communication data sum error detection ● Speed CPU ● DI180~420

[Meaning] TCD23 : In case that sum value of SPEC data which is communicated to [Action to take]

DPRAM is different 5 times continuously.


TCD24 : In case that sum value of normal data which is communicated to 1. Check if the adjustment of VR1 for power check on the
DPRAM is different 5 times continuously DPC-1XX,300 PCB is correct .
2. Check the connection condition of DOR-230 PCB connector.
[Explanation]
Start
3. Try to replace ROM of DPC-1XX,300 PCB.
(Inverter ROM damage or bad quality)
It reads the SYNC data of
4. Replace DPC-1XX, 300 PCB
RUN CPU in DPRAM
(PCB communication buffer fault)
No
Does the SYNC data
increased as 1?
Yes
DPRAM Read
Sum Value Read

Count Read data Sum Value

Does the Sum Value No


match?
Yes

Counter Reset Increase Counter

Count >= 5 times?


No
Yes

TCD 23 or 24 set
Yes

End