Вы находитесь на странице: 1из 1

J-H(St)H…Lg FE180 E30/E90

HALOGEN-FREE FIRE ALARM INSTALLATION CABLE

APPLICATION: These cables fields of use are fire proof and halogen free cables which, on the basis of a fixed operating mode, can continue with
O
the supply of a power for a period of 180 minutes under the existing fire conditions (at a temperature of 750 C and under the flames ). Also these
o
cables shall satify EN50200 test which is a fire resistant with mechancal shock test (under the conditions at 842 C and mechenical shock) by the
classes PH15-PH30-PH60-PH90. And also the test of DIN 4102-12, E30 and E90 which is a sysyem test with all components and cables to satisfy
the system circuit integrity. hese halogen-free cables are used for fire alarm systems, signal and data communications as an fixed indoor
installations. And also screen provides protection against external pulses . These cables are used at schools, airpots, hospitals, etc. and in the
environments which have no corrosive gases are emitted in the event of fire. In case of fire, these cables inhibit the propagation of the flames
whereby the development of smoke is extremely low.

CABLE DESIGN TECHNICAL DATA


Conductor : Plain copper conductor, solid Standard : VDE 0815
Insulation : Halogen-free elastomer comp., EN 50290-2-26 (Designed according to)
Core identification : VDE 0815 Conductor resistance (loop) :
Pair : Two conductors twisted to a pair Insulation resistance : Min. 100 MΩ.km
1)
Lay-up : Pairs laid up in layers of optimum pitch Mutual Capacitance (800 Hz) : Max. 100 nF/km
2)
Separator : Polyester tape Capacity Unbalanced (k) : Max. 300 pF / 100 mt
Wrapping : Fiber glass textile tape Operating voltage, peak : Max. 300 V
Screen : Tinned Cu drain wire under the AL-PES tape Test voltage (AC 50 Hz) : Core / core : 800 V
Drain wire; : 1000 V
o o
Ø : 0,40 mm ≤ 10 çift / pairs Temperature range : Fixed : - 30 C ~ + 70 C
o o
Ø : 0,60 mm > 10 çift / pairs Mobile : - 5 C ~ + 50 C
Outer sheath : HFFR compound, HM2, VDE 0207-24 Min. bending radius : 7,5xD
Sheath colour : RAL 3000, Red Smoke density test
: IEC 61034-2 & TS/DIN EN 61034-2

Halogen-free properties test : IEC 60754-1/2 & TS/DIN EN 50267-2


Flame test : IEC 60332-3 & TS/DIN EN 50266-2-4
Insulation integrity : IEC 60331 , VDE 0472-814
Fire resis. with mech. shock DIN EN 50200; PH30-PH60-PH 90
System circuit integrity : DIN 4102-12; E30 & E90
1)
This value may be exceeded by 20% by cables with up to 4 pairs
2)
20% of the values, at least one value up to 400 pF permitted

Cross Sections

No. of pairs Approx. Approx.


Copper
Part- x Conductor Outer Cable
Weight
number Diameter Diameter Weight
(Kg/km )
(mm ) ( mm ) ( Kg/km )
1920 03 002 2x2x0,60 6,4 13 38
1920 03 004 4x2x0,60 7,1 24 50
1920 03 006 6x2x0,60 7,9 35 70
1920 03 008 8x2x0,60 8,5 45 100
1920 03 010 10x2x0,60 9,5 58 120
1920 03 020 20x2x0,60 11,4 115 210
1920 03 040 40x2x0,60 15,0 230 380
1920 03 050 50x2x0,60 16,5 285 470

1920 04 002 2x2x0,80 8,5 21 65


1920 04 004 4x2x0,80 9,6 41 105
1920 04 006 6x2x0,80 10,9 62 150
1920 04 008 8x2x0,80 11,9 82 180
1920 04 010 10x2x0,80 13,7 102 235
1920 04 020 20x2x0,80 16,8 205 380
1920 04 040 40x2x0,80 21,7 405 735
1920 04 050 50x2x0,80 25,6 505 940