ANNEXURE-A (25kV Current Transformers)

INDEX
SN Description Page No

1 Statement for Altitude Corrections Factors as per relevant IS/IEC 2


Extract of IS2075 (Part-I) regarding Temperature Rise Calculation
2 for Current Transformers 3-6
Extract of IEC 61869-1 regarding Altitude Corrections for Current
3 Transformers 6-12
List of changes required for High Altitude Installations w.r.t. RDSO
4 approved GTP/Drawings (for installations upto 1000 Meters) for 13
132kV Isolator’s OEM, i.e. M/S MEHRU, Certifications in this regard.
List of modified design/drawings/documents duly incorporated with
Altitude Corrections & List of already approved
5 design/drawings/documents those are also applicable for the present
14
case
RDSO/CORE Approved Drawings for 132kV Isolator, Make- MEHRU
6 for installation upto altitude 1000 Meter
15-25
2

25kV Current Transformer


Calculations for operation at 1600meter Altitude above MSL (Mean Sea Level)
With reference to above, please be informed below the changes to be made if Current Transformer
is operating at 1600 meter altitude above MSL (mean sea level):
1) Temperature rise at high altitude as per IS2705‐Part 1:
As per clause 7.2.1.2 of this standard “If a transformer is specified for service at an altitude in
excess of 1000 m and tested at an altitude below 1 000 m, the limits of temperature rise given
in Table 2 shall be reduced by the following amounts for each 100 m, the altitude at the
operating site exceeds 1000 m.”.
a) Oil-immersed transformers — 0.4 percent,
b) Dry-type transformers — 0.5 percent.
In this case temperature rise reduction would be: (1600 – 1000)*0.4 = 2.4 Deg. C.
Hence allowable top oil temperature rise and winding temp rise values will be reduced from
40 and 50 Deg. C to 37.6 and 47.6 Deg. C.
2) Requirement of External Insulation
25KV system is 1- phase which is not standard system voltage level as per IS &IEC.
The 25KV 1-phase traction system shall be converted to three phase system as per railways
norm which is as follows:
Conversion of 25kV single phase system voltage to three phase system voltage
Description Value
Traction Nominal Voltage (1-phase) 25kV
1-phase to 3-phase factor 1.732
Highest system Voltage (1-phase) 27.5kV
3-phase Nominal system Voltage =25*1.732=43.3kV
3-Phase highest system Voltage =27.5*1.732= 47.63kV

Calculation of Altitude correction factor (Ref: Clause No. 2.2.1 of IEC61869-1)


Altitude correction factor k = e m(H‐1000)/8150
Where
m = 1 for power frequency and lightening impulse voltage
H = altitude = 1600
k = e 1(1600‐1000)/8150 = 1.076
s
Insulation Level for altitude
Requirement for Insulation
<=1000m
Parameters Level considering correction
for Selected equipment
factor (Altitude 1600m) for Altitude
Um=47.63kV
1600mm
Power Frequency Withstand
87kV* =87X1.076=93.6 95kVrms
voltage
Lightening Withstand voltage 228kV* =228X1.076=246 250kVp
*The Um value 47.63KV is not standard under IS/IEC. These values are arrived by interpolating the curve
drawn with available voltages (36kV & 52kV) for finding BIL for 47.63KV
3

IS 2705 (Part 1) : 1992

transformers having highest system voltages and lightning impulse withstand voltages, shall
up to and including 72.5 kV, defined by the be one of the sets of value given in Table 1C.
power frequency and the lightning impulse Table 1C Rated Insulation Level for Highest
withstand voltage, shall be one of the sets of System Voltage of 420 kV and Above
values given in Table 1A.
( Clauses 6.7.3, 9.3.1, 9.8.1, 9.9 and 9.11.1 )
Table 1A Rated Insulation Levels for Highest Nom inal Highest Lightning Switching
System Voltages Up to and Including 72.5 kV System System Im pulse Im pulse
( Clauses 6.7.1, 9.3.1, 9.8.1 and 9.9 ) Voltage Voltage W ithstand W ithstand
Voltage Voltage
N om inal Highest Power Lightning (1) (2) (3) (4)
System System Frequency Im pulse kV (rms) kV (rms) kV (peak) kV (peak)
Voltage Voltage W ithstand W ithstand 400 420 1 175 950
Voltage Voltage 1 300 1 050
(1) (2) (3) (4) 1 425 1 050
kV (rms) kV (rms) kV (rms) kV (peak) 525 525 1 425 1 050
 1 550 1 175






List 1 List 2 765 765 1 800 1 300
Up to 2 100 1 425
0.60 0.66 3 — — 2 400 1 550
3.3 3.6 10 20 40 6.7.4 The choice of rated insulation level of a
6.6 7.2 20 40 60 current transformer shall be made in accordance
11 12.0 28 60 75 with IS 2165 (Part 1):1977 and IS 3716:1978. If
15 17.5 38 75 95 thereby, the rated insulation level is less than any
22 24.0 50 95 125 of the sets of values in this standard, the lowest
33 36.0 70 145 170 values therein specified shall apply.
45 52.0 95 250 250 7 REQUIREMENTS
66 72.5 140 325 325
7.1 All current transformers shall comply with
NOTES the relevant requirements of Parts 2, 3 and 4 of
1 Underlined values are preferred. this standard. Current transformers for dual
2 The choice between Lists 1 and 2 should be made by purpose applications shall comply with the
considering the degree of exposure to lightning and requirements of current transformers for both
switching overvoltages, the type of system neutral applications.
earthing and the kind of the overvoltage protection.
Some guidance is given in IS 2165 (Part 1) : 1977. 7.2 Limits of Temperature-Rise
6.7.2 The rated insulation levels of current 7.2.1 The temperature-rise of a current
transformers having highest system voltages of transformer winding when carrying a primary
current equal to the rated continuous thermal
123 kV and above, up to and including 245 kV,
current, at a rated frequency and with a unity
defined by the power frequency and lightning pow er factor burden corresponding to rated output
impulse withstand voltages, shall be one of the connected to the secondary windings, shall not
values given in Table 1B. exceed the appropriate values given in Table 2.
Table 1B Rated Insulation Levels for The temperature-rise of the windings is limited by
Highest System Voltages of 123 kV and the lowest class of insulation either of the winding
itself or of the surrounding medium in which it is
Above, Up to and Including 245 kV embedded.
( Clauses 6.7.2, 9.3.1, 9.8.1 and 9.9 ) Table 2 Limits of Temperature-Rise of
Nom inal Highest Power Lightning Windings
System System Frequency Im pulse ( Clauses 7.2.1, 7.2.1.1, 7.2.1.2 and 7.2.4 )
Voltage Voltage W ithstand W ithstand
Voltage Voltage Class of Insulation M axim um Tem perature-Rise
(1) (2)
(1) (2) (3) (4) (k)
kV (rms) kV (rms) kV (rms) kV (peak) All classes immersed in oil 55
110 123 185 450 All classes immersed in oil 60
and hermetically sealed
230 550
All classes immersed in 45
132 145 230 550 bituminous compound
275 650 C lasses n ot im m ersed in oil
or bitu m in ou s com pou n d
220 245 360 850
Y 40
395 950 A 55
460 1 050 E 70
B 80
NOTE — Underlined values are preferred. F 105
6.7.3 The rated insulation levels of current H 130
transformers having highest system voltage of NOTE — For some materials (such as epoxy resin) the
420 kV and above, defined by the rated switching manufacturer should specify the relevant insulation
class.

5
4

IS 2705 (Part 1) : 1992

7.2.1.1 The values given in Table 2 are based on NOTE — The items (g) and (h) may be combined into
the standard reference ambient temperature one marking (for example, 72.5/140/325 kV).
conditions given in 4.2.1. For higher reference j) Rated short-time thermal current or short-
ambient temperature in accordance with 4.2.2, time factor with rated time (if different from
the permissible temperature rise in Table 2 shall 1 second) (for example 13.1kA/0.5 or
be reduced by an amount equal to the difference STF 100/0.5);
between such reference ambient temperature
and 40°C. k) Rated dynamic current if different than 2.5
times the rated short-time thermal current;
7.2.1.2 If a transformer is specified for service at and
an altitude in excess of 1 000 m and tested at an
altitude below 1 000 m, the limits of temperature- m) Reference to this standard.
rise given in Table 2 shall be reduced by the 8.1.1 All information shall be marked in an
following amounts for each 100 m, the altitude at indelible manner on the current transformer itself
the operating site exceeds 1 000 m. or on a rating plate securely attached to the
a) Oil-immersed transformers — 0.4 percent, transformer.
and 8.1.2 The following shall be marked if required by
b) Dry-type transformers — 0.5 percent. agreement between the purchaser and the
manufacturer:
7.2.2 When the transformer is fitted with
conservator tank or has any gas above the oil, or a) Class of insulation, and
is hermetically sealed, temperature-rise of the oil b) The use of secondary winding(s) and the
at the top of the tank or housing shall not corresponding terminals.
exceed 50 K. NOTE — If several classes of insulating material are
7.2.3 When the transformer is not fitted or used, the one which limits the temperature-rise of
arranged as in 7.2.2, the temperature-rise of the the windings shall be indicated.
oil at the top of the tank or housing shall not
8.2 Terminal Markings
exceed 45 K.
7.2.4 The temperature-rise measured on the The terminal markings shall be in accordance
external surface of the core and other metallic with Annex C.
parts in contact with, or adjacent to, insulation (if 8.3 The current transformers may also be marked
accessible) shall not exceed the appropriate value with BIS Standard Mark.
in Table 2.
9 TESTS
7.3 Dielectric Tests
9.1 Classification of Tests
7.3.1 The current transformer shall withstand the
specified dielectric tests corresponding to the 9.1.1 Type Tests
rated insulation level specified. The following shall constitute the type tests:
8 MARKING a) Short-time current tests ( see 9.6 ).
b) Temperature-rise test ( see 9.7 ).
8.1 Rating Plate
c) Lightning impulse test for current
All current transformers shall carry at least the transformers for service in electrically
following markings: exposed installation ( see 9.8 ).
a) The manufacturer’s name and country of d) Switching impulse voltage tests for current
origin; transformers of 420 kV and above
b) Year of manufacture; ( see 9.11 ).
c) A serial number and a type designation; e) High voltage power-frequency wet withstand
d) The rated primary and secondary currents voltage tests on outdoor current
(for example, 200-100/1-1A); transformers up to and including 245 kV
( see 9.9 ).
e) Rated frequency; and
NOTE — If the porcelain weather casing/bushing
f) R ated output and the corresponding accuracy has been subjected to this test separately, the
class (for example, 10 VA, class 1 or requirements of this test shall be deemed to have
10 VA/1); been complied with.

NOTE — When more than one separate secondary


f) Determination of errors or other characteris-
windings are provided, the marking should indicate tics according to the requirements of the
the output of each secondary winding in VA, the appropriate designation or accuracy class
corresponding accuracy class and the rated current ( see individual parts of this standard ).
of each winding.
g) Highest system voltage (for example, NOTES
72.5 kV); 1 The dielectric type tests in (c), (d) and (e) shall all be
carried out on the same transformer unless otherwise
h) Rated insulation level (for example, agreed.
140/325 kV);

6
5

!"#$%&# '(%)

Disclosure to Promote the Right To Information


Whereas the Parliament of India has set out to provide a practical regime of right to
information for citizens to secure access to information under the control of public authorities,
in order to promote transparency and accountability in the working of every public authority,
and whereas the attached publication of the Bureau of Indian Standards is of particular interest
to the public, particularly disadvantaged communities and those engaged in the pursuit of
education and knowledge, the attached public safety standard is made available to promote the
timely dissemination of this information in an accurate manner to the public.

Ò7"#1 &" 8+9&"), 7:1 &" 8+9&")Ó Ò/0)"1 &2 324 #' 5 *)6Ó
Mazdoor Kisan Shakti Sangathan Jawaharlal Nehru
ÒThe Right to Information, The Right to LiveÓ ÒStep Out From the Old to the NewÓ

IS/IEC 62271-102 (2003): High-Voltage Switchgear and


Controlgear, Part 102: Alternating Current Disconnectors
and Earthing Switches [ETD 8: High Voltage Switchgear and
Controlgear]

Ò!"# $ %& #' (")* &" +#,-.Ó


Satyanarayan Gangaram Pitroda
ÒInvent a New India Using KnowledgeÓ

Ò!"# %& ;<" =7"#" > 72 &(: ?0)"@" #AB 7" <&*" A*Ó
Bhart+hariÑN,ti-atakam
ÒKnowledge is such a treasure which cannot be stolenÓ

3DJHRI
6

3DJHRI
7

3DJHRI
8

3DJHRI
9

NORTHEN RAILWAY
EPC CONTACTOR IRCON INTERNATIONAL LTD.
CONTACTOR KEI Industries Limited
Design, Supply, Installation, Testing&Commissioning of 132/25 kV, 21.6/30.24 MVA,
ONAN/ONAF (Double Transformer) TractionSub-Station complete in all respect in
PROJECT
Banihal- Qazigund-Baramulla Section of USBRL Project ofNorthern Railway (TSS
Package)
LOA No-I (Supply) IRCON/ELECT/5021/USBRL/TSS/4/ Date: 4-2-2019
EQUIPMENT 25kV Current Transformer (1500-750/5A) Mehru make)

Details of deviation required for installation at site altitude of 1600 Mtr above MSL w.r.t. latest RDSO/CORE
approved GTP/Drawing:

Parameter as per latest RDSO /IS


Parameter offered for
,IEC approved GTP/Drg (For
Sr.no. `Description installation at altitude of
altitude upto 1000 Mtr above
1600 Mtr above MSL
MSL)
Temperature Rise over a max.
1 ambient temperature of 50oC after
continuous full load operation
(i) of Oil (By Thermometer) 40°C 37.6°C (Max)*
(ii) of Winding (By Resistance) 50°C 47.6°C (Max)*
Certificate:
It is to confirm that
a) All other major parameters except stated above shall be as per latest RDSO/CORE approved
GTP/Drawing (copy attached).
b) The tested Power frequency and Lightning impulse voltage of offered Current transformers meet the
BIL requirement for installation at 1600m altitude
c) Temperature Rise test shall be conducted after manufacturing of equipment and may be witnessed
by RDSO/CORE/IRCON if required.
d) The equipment offered are suitable for installation in environmental condition as below:
i) Max Ambient Air Temperature (0C): 35
ii) Avg. Day Temperature (0C): 22
iii) Min Ambient Air Temperature (0C): -15
iv) Wind pressure up to 30m height (kg/m2): 195
v) Altitude above MSL (mtr): 1600
vi) Relative Humidity: 100%
vii) Annual rain fall (max.) (mm): 705
viii) Average thunderstorm days/annum: 47
ix) Terrain: Hilly
x) Climate: Snow Bound

Signature and Seal


10

CONTRACTOR: EPC CONTRACTOR: CLIENT


KEI INDUSTRIES LIMITED.
REVISIONS
IRCON INTERNATIONAL LTD.
NORTHERN RAILWAY
QUALITY ASSURANCE APPROVED IN PRINCIPLE APPROVED IN PRINCIPLE

DATE NAME / SIGNATURE


DR 10-06-2020 ARJUN
CH 10-06-2020 MANISH/RKS
LIST OF DRAWINGS FOR
PROJECT 10-06-2020
REV. DATE DESCRIPTION
MANAGER A. KUMAR 25kV CURRENT TRANSFORMER RATIO: 1500-750/5A