1. INTRODUCTION 5

2. DEMARRAGE ET FONCTIONNEMENT 6
2.1 Vérification et préréglage 6
2.2 Carte mère 6
2.2.1 Cavaliers d’alimentation 6
2.2.2 Configuration 6
2.3 BLOC D’ALIMENTATION (ALIM) 5 8
2.3.1 Réglage en usine 8
2.3.2 Commutateur 1 9
2.3.3 Fusible 9
2.4 Carte de traitement BF (LFS) 10
2.4.1 Pré-réglage 10
2.4.2 Description des cavaliers à "goutte de soudure" du module LFS 12
2.4.3 Carte fille LFS3 13
2.5 Convertisseur d’Appel Universel 14
2.6 Interface de transit (INTE) 17
2.7 Interface de supervision (INSU) 19
2.8 Modem haute fréquence (MODAF) 21
2.9 Amplificateur 20 W (AMPL) 23
2.10 Interface de la ligne de transmission (INTX) 24
2.10.1 Pré-réglage 24
2.10.2 Programmation de la largeur de bande de transmission 25
2.11 INTERFACE DE LIGNE DE Reception (INRX) 37
2.11.1 Pré-réglage 37
2.11.2 Programmation de l’impédance de ligne HF 38
2.11.3 Tableaux de programmation pour les fréquences comprises entre 40 et 500 kHz 40

3. TEST ET MISE EN SERVICE 49


3.1 Configuration logicielle 49
3.2 Instruments nécessaires 49
3.3 Opération préliminaire 49
3.4 Test local de l'équipement PLC 50
3.4.1 Alimentation 50
3.4.2 Niveau de transmission 51
3.5 Test de ligne point à point 57
3.5.1 Présentation 57
3.5.2 Signal reçu HF 57
3.6 Égalisation de la bande BF 59
1790B/FR CM/F11 Mise en service

Page 2/70 PLC 1790/B

3.7 Signal BF reçu 60


3.8 Indications des DEL 60
3.9 Vérification BF point à point 60
3.9.1 Réponse de la ligne 60
3.9.2 Vérification de la signalisation 62
3.9.3 Critères de commutation automatique 2/4 fils 62
3.9.4 Vérification des alarmes et des DEL 62

4. ANNEXE 65
4.1 Voie phonie 65
4.2 Voies télégraphiques 68
Mise en service 1790B/FR CM/F11

PLC 1790/B Page 3/70

HISTORIQUE DES ÉVOLUTIONS

Version DATE COMMENTAIRES

A Juin 1998 Création du document

Déc. 1998 Modification des pages 9, 10, 11, 14, 15, 16, 33, 35, 36, 37,
B
38, 39, 41, 46, 47, 49, 52, 53,54, 57, 64.
Sept. 1999 Nouvelle Présentation + Modification des pages 10, 11,
C
14, 15, 51, 57, 64 (Nouvelle pagination)
D Mai 2000 Modification des pages 10 et 11.
Nouvelle présentation + Description de la PLC1790B
E Mars 2004
Révision 2
F Sept. 2004 Modification mineure, édition pour impression recto-verso
1790B/FR CM/F11 Mise en service

Page 4/70 PLC 1790/B

PAGE BLANCHE
Mise en service 1790B/FR CM/F11

PLC 1790/B Page 5/70

1. INTRODUCTION
Une fois l’installation du matériel achevée, l’opérateur doit procéder au démarrage, aux
réglages et à la mise en service.
Le présent chapitre décrit la marche à suivre correspondant à ces opérations.
L'organigramme suivant décrit les procédures étape par étape de la mise en service de
l’équipement à courants porteurs PLC 1790/B rév2.

EQUIPEMENT
HORS TENSION

VERIFIER
CONFIGURATION PROBLEME CONTROLER COMMANDE
EQUIPEMENT EQUIPEMENT
.

OK

INSTALLATION
MATERIELLE

CONTROLER
CONTROLER SOURCE ET
ALIMENTATION PROBLEME
CABLE D’ALIMENTATION
PRINCIPALE

OK

METTRE L’EQUIPEMENT
PROBLEME
SOUS TENSION

OK

CONTROLER INSTALLATION
LOGICIELLE- OPERATIONS DE OPERATIONS DE
DEMARRAGE REGLAGE
(SECTION INTERFACE
HOMME MACHINE)

D0237FRa

FIGURE 1 – ORGANIGRAMME DE MISE EN SERVICE


1790B/FR CM/F11 Mise en service

Page 6/70 PLC 1790/B

2. DEMARRAGE ET FONCTIONNEMENT
Pour éviter tout dysfonctionnement, débrancher tous les câbles extérieurs avant de procéder
aux opérations de mise en route.
2.1 Vérification et préréglage
Selon les besoin du site, l’utilisateur peut être amené à modifier le réglage usine standard.
Les tableaux suivants décrivent les paramètres matériels (HW) par défaut correspondant à
chaque unité.
Les cavaliers portant l’intitulé "FACTORY SET-UP" (REGLAGE USINE) ne doivent pas être
modifiés.
La configuration des différentes cartes ne requiert aucun outil particulier.
Les schémas des connexions des groupes indiquent l’emplacement des cavaliers à "goutte
de soudure".
2.2 Carte mère
La carte mère de l'équipement PLC 1790/B rév2 est pourvue de plusieurs cavaliers à "goutte
de soudure" situés sur les faces avant et arrière de l’unité. Pour accéder à l’arrière de l’unité,
l’opérateur doit retirer le panneau de protection.
2.2.1 Cavaliers d’alimentation
Ces cavaliers sont accessibles depuis la face avant de l'équipement.
La source d’alimentation peut être raccordée à la terre sur le pôle négatif ou positif, par
l’intermédiaire de deux cavaliers situés sur la carte mère, "A" et "B".
Si les cavaliers "A" et "B" sont tous deux ouverts, la source d’alimentation sera isolée de la
terre.

PROCEDURE REFERENCE CONNEXIONS


SCHÉMA FERME OUVERT
Alimentation flottante A(°)-B(°)
Alimentation avec pôle positif relié à la B(°) A(°)
terre
Alimentation avec pôle négatif relié à la A(°) B(°)
terre

TABLEAU 1 – (°) LES CAVALIERS A ET B SONT SITUES SUR LA CARTE MERE DE L'ÉQUIPEMENT PLC
2.2.2 Configuration
Le préréglage usine est donné pour information. Étant donné qu'ils sont situés à l'arrière de
l'équipement, le contrôle visuel ne peut se faire qu'à l'occasion d'une opération de
maintenance.

REFERENCE CONNEXIONS
PROCEDURE
SCHÉMA FERMÉ OUVERT
TC-1 1-2
TC-2 1-2
TC-3 1-2
TC-4 1-2
Préréglage usine
TC-8 1-2
TC-9 1-2
TC-8 1-2
TC-9 1-2
Mise en service 1790B/FR CM/F11

PLC 1790/B Page 7/70

REFERENCE CONNEXIONS
PROCEDURE
SCHÉMA FERMÉ OUVERT
TC-5 1-2
Alarme commune PLC1&2 disponible
TC-6 1-2
sur M13-M15-M17 et M14-M16-M18
TC-7 1-2
Alarme PLC 1&2 isolée. PLC1 sur M13- TC-5 1-2
M15-M17 et TC-6 1-2
PLC2 sur M14-M16-M18 TC-7 1-2

TABLEAU 2 – CONFIGURATION TC

J2 J3
PLC PLC
M2 LF0 M4 LF0 M8 M7 M6 LIGNE CHARGE
Ph/Sig/L2 MTU ALARMES INSU R.C. P.C. HF FICTIVE

M3 LF1 M5 LF1
Alimentation Ph/Sig/L2 MTU
ALARMES RACK

M13-M14

M15-M16

M17-M18

(–) A (+) B
Masse
Alimentation

Non M32 LF1 M37 Non J4 J1 M38 J5


utilisé TÉLÉGRAPHE ALARMES utilisé POINT LIGNE HF CÂBLE COAX.
COLL. OUVERT TEST
3 x E/S

Non M10 LF0


utilisé TÉLÉGRAPHE
3 x E/S
D0206FRa

FIGURE 2 – CAVALIERS EN FACE AVANT DE LA PLC

FIGURE 3 – CAVALIERS EN FACE ARRIÈRE DE LA PLC


1790B/FR CM/F11 Mise en service

Page 8/70 PLC 1790/B

2.3 BLOC D’ALIMENTATION (ALIM) 5


Les réglages en usine sont indiqués pour information uniquement, la carte étant protégée
par un couvercle qui ne doit pas être retiré.
2.3.1 Réglage en usine
L'unité est programmée pour une tension d'entrée de 48 Vcc.

JP1

JP3
JP2

JP4

FIGURE 4 – ENTRÉE ALIM 48 VCC


Mise en service 1790B/FR CM/F11

PLC 1790/B Page 9/70

2.3.2 Commutateur 1
L'unité offre la possibilité de modifier la fréquence de commutation (selon le tableau 2.3) de
façon à éviter toute interférence avec un harmonique éventuel. Cette opération peut être
effectuée automatiquement par logiciel, ou manuellement sur le matériel.
Le module est équipé d'un commutateur DIP accessible depuis l'extérieur et utilisé pour
modifier la fréquence d'échantillonnage du circuit de commutation interne.
Automatiquement par logiciel :
Le logiciel MODAF permet la sélection automatique. Dans ce cas, le réglage de
l'alimentation est montré à la figure 2.4 ci-après.

123
ON
J1 OFF
SW1

FIGURE 5 – COMMUTATEUR ALIM


Manuellement sur matériel :
Principe de la commutation de fréquence :
Selon la bande Rx, il est possible de modifier la fréquence de commutation de façon à éviter
qu'un harmonique éventuel quelconque, de rang 1 ou 2, ne tombe dans la bande Rx
± 8 kHz : c'est-à-dire :
Bande PLC Rx 200-204 kHz
Largeur de bande Rx= de (200-8) à (204+8)= 192 – 212 kHz
FÉCHANTILLONNAGE

F kHz 1er harmonique 2nd harmonique Sélection


100 200 400 KO
134 268 536 OK

FRÉQUENCE SW1
D’ÉCHANTILLONNAGE
kHz I1 I2 I3
100 OFF OFF OFF
114 OFF OFF ON
134 OFF ON OFF
160 OFF ON ON

TABLEAU 3 – TABLE DE FRÉQUENCES D’ÉCHANTILLONNAGE


2.3.3 Fusible
Un fusible est accessible sans qu'il soit nécessaire d'ouvrir le couvercle.
1790B/FR CM/F11 Mise en service

Page 10/70 PLC 1790/B

2.4 Carte de traitement BF (LFS)


2.4.1 Pré-réglage
Vérifiez et préréglez l’unité en fonction des caractéristiques du site, seuls les réglages usine
sont indiqués ci-après. Les cartes LFS ont les deux références :
411.410.034 en cas d'utilisation sans carte fille (LFS)
411.410.035 en cas d'utilisation avec carte fille (LFS3)

SZ10
8 7
6 5
4 3

2 1
2 1

SZ11
2 SZ24
1
1 2
SZ12 SZ9
1
1 2 3
2
TC1

SZ28
2 4

1 3 1 2 3
TC2

SZ13
SZ27 1
SZ30
2 42 4
2 2 4 2
1 31 3
1 1 3
SZ26
SZ29

SZ16
2 42 4

1 31 3

SZ15

I1

2 1
4 3

2 1

SZ25
SZ22
2 6

1 2 1 5
SZ1 2 6

1 5
2 4
SZ21
1 3

SZ20
2 4

SZ4 1 3
1 SZ7
2

SZ23
2

1
2 4

1 3

SZ14

SZ8
2

1
1
2 4
2
SZ3 1 3

SZ6

FIGURE 6 – DISPOSITION USINE DES CAVALIERS DU MODULE LFS 411.410.034


Mise en service 1790B/FR CM/F11

PLC 1790/B Page 11/70

SZ10
8 7
6 5
4 3

2 1
2 1

SZ11
2 SZ24
1
1 2
SZ12 SZ9
1
1 2 3
2
TC1

SZ28
2 4

1 3 1 2 3
TC2

SZ13
SZ27 1
SZ30
2 42 4
2 2 4 2
1 31 3
1 1 3
SZ26
SZ29

SZ16
2 42 4

1 31 3

SZ15

I1

2 1
4 3

2 1

SZ25
SZ22
2 6

1 2 1 5
SZ1 2 6

1 5
2 4
SZ21
1 3

SZ20
2 4

SZ4 1 3
1 SZ7
2

SZ23
2

1
2 4

1 3

SZ14

SZ8
2

1
1
2 4
2
SZ3 1 3

SZ6

FIGURE 7 – DISPOSITION USINE DES CAVALIERS DU MODULE LFS 411.410.035


1790B/FR CM/F11 Mise en service

Page 12/70 PLC 1790/B

2.4.2 Description des cavaliers à "goutte de soudure" du module LFS

RÉFÉRENCE CAVALIERS
PROCEDURE
SCHÉMA FERME OUVERT
SZ1 1-2
SZ3 1-2
SZ4 1-2
SZ6 1-2 3-4
SZ7 1-2 3-4
SZ8 1-2
SZ11 1-2
SZ12 1-2
Préréglage usine SZ23 1-2
SZ25 3-4 1-2
SZ26 1-2 3-4
SZ27 1-2 3-4
SZ28 1-2 3-4
SZ29 1-2 3-4
SZ30 1-2
TC1 2-3
TC2 2-3
SZ14 1-2; 3-4
Réglage LFS
SZ15 1-2; 3-4
(sans carte fille)
SZ16 1-2; 3-4
SZ14 3-4 1-2
Réglage LFS3
SZ15 1-2; 3-4
(avec carte fille)
SZ16 1-2; 3-4
*Suppression Service BF Rx SZ9 1-2
fil "-" sur référence interne - 15 VCC SZ13 1-2
Suppression service BF Rx SZ9 1-2
fil "-" sur référence externe
(max. 210 Vcc) SZ13 1-2
SZ10 1-2 3-4 5-6 7-8
Configuration avec CCUN
SZ24 1-2
SZ10 5-6 7-8 1-2 3-4
Configuration sans CCUN
SZ24 1-2
Fil "M" vers l’autocommutateur SZ21 5-6 1-2, 3-4
Fil "E" partant de l’autocommutateur SZ22 5-6 1-2, 3-4
Fil "M" vers le CCUN SZ21 3-4, 5-6 1-2
Fil "E" partant du CCUN SZ22 3-4 1-2, 5-6
1-2
Signalisation Tx SZ20 1-2 (Activé)
(Désactivé)
3-4
Compresseur SZ20 3-4 (Activé)
(Désactivé)
Permanent
1 - RTS CTS on RTS
Modem interne I1 CTS
(commutateur DIP) Permanent
2 - DTR DSR on DTR
DSR
TABLEAU 4 – CAVALIERS LFS

* Remarque importante : L'équipement sera endommagé si ce


réglage est utilisé par erreur avec une référence de source externe.
Mise en service 1790B/FR CM/F11

PLC 1790/B Page 13/70

2.4.3 Carte fille LFS3

TC6 TC7 TC10

1 1 1 1 1
2 2 2 2 2
TC5 TC9

1 2 3 1 2 3 1 2 3 1 2 3
TC2 TC1 TC4 TC3

1 2 1 2
TC8 TC11

FIGURE 8 – DISPOSITION DES CAVALIERS DE LA CARTE FILLE LFS-3

REFERENCE CONNEXIONS
PROCEDURE
SCHÉMA FERMÉ OUVERT
Préréglage usine TC-1 1-2
TC-2 2-3
TC-3 1-2
TC-4 2-3
TC-7 1-2
TC-8 1-2
TC-9 1-2
TC-10 1-2
TC-11 1-2
FORMAT DE 8 BITS / ASYNC TC-5 1-2
TC-6 1-2
FORMAT DE 9 BITS / ASYNC TC-5 1-2
TC-6 1-2
FORMAT DE 10 BITS / ASYNC TC-5 1-2
TC-6 1-2
FORMAT DE 11 BITS / ASYNC TC-5 1-2
TC-6 1-2
TABLEAU 5 – STRAPS DE LA CARTE FILLE DU MODULE LFS-3
NOTA : Le nombre de bits du format inclut aussi les bits de START et de
STOP
1790B/FR CM/F11 Mise en service

Page 14/70 PLC 1790/B

2.5 Convertisseur d’Appel Universel


Vérifiez et préréglez la carte en fonction de la demande du site :

gd_eccu.vsd

SZ4
2 4

1 3

SZ8
2 4

1 3

1 2
SZ5
SZ6
1 2

SZ11
1

SZ7
SZ9
1
1
2
2

SZ1
1 2

1 2

SZ2

SZ10
SZ3
1
1
2
2

FIGURE.9 DISPOSITION DES 8 CAVALIERS DU MODULE CCUN


Mise en service 1790B/FR CM/F11

PLC 1790/B Page 15/70

Description des cavaliers à "goutte de soudure" du module CCUN

REFERENCE CONNEXIONS
PROCEDURE
SCHÉMA FERMÉ OUVERT
CCUN-1 (LFS-0)
CONFIGURATION PLA-T SZ1 1-2
(FXS) SZ2 1-2
SZ3 1-2
SZ4 1-2 3-4
SZ10 1-2
CONFIGURATION BC SZ1 1-2
(LIGNE DIRECTE) SZ2 1-2
SZ3 1-2
SZ4 3-4 1-2
SZ10 1-2
CONFIGURATION PLA-C SZ1 1-2
(FXO) SZ2 1-2
SZ3 1-2
SZ4 1-2 3-4
SZ10 1-2
CONFIGURATION BL SZ1 1-2
(Inutilisée) SZ2 1-2
SZ3 1-2
SZ4 1-2 3-4
SZ10 1-2
CCUN-2 (LFS-1)
CONFIGURATION PLA-T SZ5 1-2
(FXS) SZ6 1-2
SZ7 1-2
SZ8 1-2 3-4
SZ11 1-2
CONFIGURATION BC SZ5 1-2
(LIGNE DIRECTE) SZ6 1-2
SZ7 1-2
SZ8 3-4 1-2
SZ11 1-2
CONFIGURATION PLA-C SZ5 1-2
(FXO) SZ6 1-2
SZ7 1-2
SZ8 1-2 3-4
SZ11 1-2
1790B/FR CM/F11 Mise en service

Page 16/70 PLC 1790/B

REFERENCE CONNEXIONS
PROCEDURE
SCHÉMA FERMÉ OUVERT
CONFIGURATION BL SZ5 1-2
(Inutilisée) SZ6 1-2
SZ7 1-2
SZ8 1-2 3-4
SZ11 1-2
Liaison de masse analogique / SZ9 1-2
numérique

TABLEAU 6 – CAVALIERS DU MODULE CCUN


BL = "Hot Line" - ligne directe avec batterie locale BC = "Hot Line" - ligne directe avec
batterie centralisée
FXO = Côté PAX abonné éloigné FXS = Côté téléphone abonné éloigné
Mise en service 1790B/FR CM/F11

PLC 1790/B Page 17/70

2.6 Interface de transit (INTE)


Vérifier et prérégler la carte en fonction de la demande du site :

SZ7 SZ12
SZ3
2 4 6 8 10 12 14 16 18 20
2 4 2 1 2

1 3 1 2 1
SZ5 1 3 5 7 9 11 13 15 17 19 SZ6

SZ9
2 4 6 8 10 12 14 16 18 20

1 3 5 7 9 11 13 15 17 19

SZ10
2 4 6 8 10 12 14 16 18 20

1 3 5 7 9 11 13 15 17 19

SZ13
SZ14
1
1 1 2
2
2
SZ4

SZ11
SZ15
2 4 6 8 10 12 14 16 18 20
2 4

1 3
1 3 5 7 9 11 13 15 17 19

SZ8
2 4 6 8 10 12 14 16 18 20

1 3 5 7 9 11 13 15 17 19

SZ1
2 4

1 3

2 4

1 3
SZ2

FIGURE 10 – DISPOSITION DES CAVALIERS DU MODULE INTE


1790B/FR CM/F11 Mise en service

Page 18/70 PLC 1790/B

Description des cavaliers à "goutte de soudure" du module INTE :

REFERENCE CONNEXIONS
PROCEDURE
SCHÉMA FERME OUVERT
CAVALIERS COMMUNS
Validation voie 0 SZ1 1-2 3-4
SZ2 3-4 1-2
Validation voie 1 SZ1 3-4 1-2
SZ2 1-2 3-4
Validation des deux canaux SZ1 1-2 3-4
Voie 0 & Voie 1 SZ2 1-2 3-4
Désactivation test de bouclage SZ15 1-3
numérique 2-4
(sur les deux canaux)
Désactivation test de bouclage SZ15 3-4 1-2
numérique
(sur les deux canaux)
Préréglage usine SZ3 1-2
SZ4 1-2
SZ5 1-2
SZ6 1-2
SZ7 1-2 3-4
SZ12 3-4 7-8
11-12 15-16
SZ13 1-2
SZ14 1-2
VOIE 0
Atténuateur Rx (pour –18 dBm en SZ10 Régler à 8 dB
sortie )
Atténuateur Tx (pour –18 dBm en SZ9 Régler à 4 dB
entrée)
VOIE 1
Atténuateur Rx (pour –18 dBm en SZ8 Régler à 8 dB
sortie )
Atténuateur Tx (pour –18 dBm en SZ11 Régler à 4 dB
entrée)
TABLEAU 7 – CAVALIERS DU MODULE INTE

2
8 dB
4
6
4 dB
8
10
2 dB
12
14
1 dB
16
x dB x dB
18
N.U.
20
CELLULE INCLUSE CELLULE EXCLUSE
D0238FRa

FIGURE 11 – CELLULE D’AFFAIBLISSEMENT ENTREE / SORTIE


Mise en service 1790B/FR CM/F11

PLC 1790/B Page 19/70

2.7 Interface de supervision (INSU)

2 4

1 3

SZ18

2 1
SZ9
I1

1 2
O
N

1 2 1 2
SZ12 SZ13

1 2 1 2
SZ11 SZ10

3 1 3 1

SZ6 SZ7
4 2 4 2

SZ8
2

1
1
2

SZ4

SZ16
2
SZ15 SZ17
1

1
SZ19
2

3 1

SZ5
4 2
3 1 3 1

SZ1 SZ2
4 2 4 2

3 1

SZ3
4 2

2 1

SZ14

FIGURE 12 – DISPOSITION DES CAVALIERS DU MODULE INSU


1790B/FR CM/F11 Mise en service

Page 20/70 PLC 1790/B

Description des straps "goutte de soudure" du module INSU

REFERENCE CONNEXIONS
PROCEDURE
SCHÉMA FERME OUVERT
SZ1 1-2 3-4
SZ2 1-2 3-4
SZ3 1-2 3-4
SZ4 1-2
Préréglage usine
SZ5 1-2 3-4
SZ6 3-4 1-2
SZ7 1-2 3-4
SZ8 1-2
Commun des boucles d'alarmes
SZ9 1-2
référencé à la masse
Commun des boucles d'alarmes
SZ9 1-2
à contact sec
Commun distant 1, fil commun 1-2
SZ10
référencé à la masse
Commun distant 1, fil commun 1-2
SZ10
à contact sec
Commun distant 2, fil commun 1-2
SZ11
référencé à la masse
Commun distant 2, fil commun 1-2
SZ11
à contact sec
SZ12 1-2 1-2
SZ13 1-2 1-2
SZ14 1-2
SZ15 1-2 1-2
Préréglage usine SZ16 1-2
SZ17 1-2
SZ18 1-2 ; 3-4
SZ19 1-2
I1 NOT USED

TABLEAU 8 – CAVALIERS DU MODULE INSU


Mise en service 1790B/FR CM/F11

PLC 1790/B Page 21/70

2.8 Modem haute fréquence (MODAF)


Vérifier les cavaliers suivants :

SZ3

TC8 TC7
AN39
AN41
AN40
AN42
SZ2
TC14
SZ1 TC15 TC16

AN44
AN43

TC1
TC3
TC2

AN12 GND
TC4

TC12 TC10
1 2 3
TC18 TC17

TC9

TC13
3
2 TC19
1

TC5
TC6

FIGURE 13 – DISPOSITION DES CAVALIERS DU MODULE MODAF


1790B/FR CM/F11 Mise en service

Page 22/70 PLC 1790/B

Description des cavaliers à "goutte de soudure" du module MODAF

REFERENCE CONNEXIONS
PROCEDURE
SCHÉMA FERMÉ OUVERT
Préréglage usine TC2 1-2
TC4 1-2
TC7 1-2
TC8 1-2
TC9 1-2
TC12 1-2
TC13 1-2
TC14 1-2
TC15 1-2
TC16 1-2
TC17 1-2
TC18 1-2
TC19 2-3 1-2
TC10 2-3 1-2
SZ1 1-2
Atténuateur d'entrée 7 dB exclu TC1 1-2
(configuration standard)
TC3 1-2
Atténuateur d'entrée 7 dB inclus TC1 1-2
(atténuation de ligne HF faible)
TC3 1-2
Fréquence de commutation ALIM TC5 1-2
commandée par DSP
TC6 1-2
Fréquence de commutation ALIM à TC5 1-2
commander manuellement
TC6 1-2
Puissance HF 10 W SZ2 1-2
Puissance HF 20/40 W SZ2 1-2
Amplificateur de puissance 1 HF SZ3 1-2
(AMPL1 -> 10/20W)
Amplificateur de puissance 2 HF SZ3 1-2
(AMPL1 + AMPL2 -> 40W)
TABLEAU 9 – CAVALIERS DU MODULE MODAF
Point de soudage MODAF

REFERENCE
PROCEDURE
SCHÉMA
MASSE AN 12; AN 39
AN 42; AN 44
AN 42
Tx HF 1 AN 40
Tx HF 2 AN 41
Rx HF AN 43
TABLEAU 10 – CAVALIERS DU MODULE MODAF
Mise en service 1790B/FR CM/F11

PLC 1790/B Page 23/70

2.9 Amplificateur 20 W (AMPL)


Vérifier le préréglage de la carte :

SZ1
1 2

FIGURE 14 – DISPOSITION DES CAVALIERS DU MODULE AMPL


Description des cavaliers à "goutte de soudure" du module AMPL :

RÉFÉRENCE CONNEXIONS
PROCÉDURE
SCHÉMA FERMÉ OUVERT
Préréglage usine SZ1 1-2

TABLEAU 11 – CAVALIERS AMPL


1790B/FR CM/F11 Mise en service

Page 24/70 PLC 1790/B

2.10 Interface de la ligne de transmission (INTX)


2.10.1 Pré-réglage
Vérifier et prérégler la carte en fonction de la demande du site :

1 2 2 4 6 8 10 12 14 16 18 20 2 4

SZ-26
3 4 1 3 5 7 9 11 13 15 17 19 1 3
SZ-29 SZ-18

1 2 1 2
SZ-25 SZ-27
2
SZ-22 3 4
1 3 4

2
SZ-21
1

M-1
1
SZ-20
2

1
2 4 6 8 10 12 14 16 18 20 2 SZ-19

SZ-23
1 3 5 7 9 11 13 15 17 19
2 4 6 8 10 12 14 16 18 20

SZ-17
1 3 5 7 9 11 13 15 17 19 SZ-24
1 2
2 4
SZ-1 1 3

3 4 4 3 3 1

SZ-16
2 1 4 2
SZ-15

2 4 6 8 10 12 14 16 18 20 1 2

SZ-9 SZ-2
1 3 5 7 9 11 13 15 17 19 3 4

2
SZ-5
1

2
SZ-6
1

2
SZ-7
1

2
SZ-8
1

SZ-28 SZ-4
4 3
3 1 2 4 6 8 10 12 14 16 18 20
SZ-3
2 1
4 2 1 3 5 7 9 11 13 15 17 19

FIGURE 15 – DISPOSITION DES CAVALIERS DU MODULE INTX


Cavaliers supplémentaires de choix de la puissance d'émission INTX :

RÉFÉRENCE CONNEXIONS
PROCÉDURE
SCHÉMA FERMÉ OUVERT
Amplificateur de puissance unique SZ15 1-2 3-4
Amplificateur de puissance double SZ15 1-3 2-4

TABLEAU 12 – CAVALIERS DU MODULE INTX


Mise en service 1790B/FR CM/F11

PLC 1790/B Page 25/70

2.10.2 Programmation de la largeur de bande de transmission


Les tableaux suivants décrivent la programmation du filtre de transmission mono- ou double-
voie pour les fréquences comprises entre 40 et 500 kHz.
Le filtre de transmission PLC peut être réglé par paliers de 1 kHz, entre 40 et 500 kHz, avec
les cavaliers des canaux de transmission standard les plus proches signalés dans les
tableaux.
2.10.2.1 Filtre double-voie

Bande de fréquences 40 ÷ 248 kHz

SZ5 SZ6 SZ7 SZ8


kHz SZ4-SZ23 SZ9-SZ18 SZ17
SZ19 SZ20 SZ21 SZ22
40-48 1-2 5-6 9-10 1-2 5-6 9-10 13-14 1-2 3-4 7-8 11-12
13-14 17-18 17-18
48-56 1-2 9-10 13-14 1-2 1-2 7-8 9-10 13-14 1-2 3-4 9-10
17-18 19-20
56-64 1-2 5-6 13-14 1-2 1-2 7-8 13-14 19-20 1-2 5-6 7-8 13-14
64-72 5-6 13-14 5-6 13-14 1-2 9-10
72-80 1-2 13-14 17- 1-2 5-6 13-14 17-18 1-2
18
80-88 1-2 9-10 1-2 3-4 9-10 13-14 19-20 3-4 5-6 7-8 11-12 13-
14
88-96 1-2 17-18 1-2 5-6 17-18 3-4 5-6 9-10
96-104 1-2 7-8 19-20 1-2 5-6 17-18 3-4 5-6 13-14
104-112 1-2 5-6 17-18 1-2 3-4 7-8 9-10 19-20 3-4 9-10 11-12 13-14
112-120 1-2 7-8 15-16 1-2 1-2 9-10 13-14 3-4 9-10 13-14
120-128 5-6 17-18 1-2 7-8 9-10 15-16 17-18 3-4 9-10
128-136 3-4 9-10 15-16 1-2 1-2 1-2 3-4 5-6 15-16 17-18 3-4 11-12 13-14
136-144 1-2 7-8 15-16 1-2 3-4 7-8 13-14 19-20 3-4 11-12
144-152 3-4 9-10 15-16 1-2 1-2 3-4 13-14 19-20 3-4 13-14
152-160 1-2 7-8 11-12 1-2 1-2 1-2 11-12 13-14 19-20 3-4
160-168 1-2 7-8 11-12 3-4 7-8 11-12 13-14 5-6 7-8 9-10
15-16 19-20
168-176 1-2 7-8 15-16 3-4 7-8 13-14 5-6 7-8 11-12 13-14
176-184 1-2 7-8 11-12 1-2 1-2 13-14 5-6 7-8 11-12
184-192 1-2 7-8 19-20 1-2 17-18 5-6 7-8 13-14
192-200 1-2 7-8 11-12 1-2 1-2 7-8 11-12 15-16 17- 5-6 7-8
18
200-208 3-4 7-8 9-10 3-4 7-8 11-12 15-16 5-6 9-10 13-14
15-16 19-20 17-18
208-216 13-14 1-2 17-18 7-8 9-10 11-12
216-224 13-14 1-2 17-18 7-8 9-10 13-14
224-232 1-2 7-8 11-12 1-2 3-4 7-8 11-12 17-18 5-6 11-12 13-14
15-16
232-240 1-2 7-8 15-16 1-2 3-4 7-8 17-18 5-6 11-12
240-248 1-2 1-2 1-2 1-2 1-2 17-18 7-8 11-12

Les connexions suivantes sont communes à toutes les fréquences ci-dessus.

SZ2-SZ3-SZ24- SZ1-SZ26 SZ16 SZ27 SZ28-SZ29


SZ25
1-2 1-3 3-4 3-4 3-4
1790B/FR CM/F11 Mise en service

Page 26/70 PLC 1790/B

Bande de fréquences 248 ÷ 456 kHz

SZ5 SZ6 SZ7


kHz SZ4-SZ23 SZ8 SZ22 SZ9-SZ18 SZ17
SZ19 SZ20 SZ21
248-256 1-2 7-8 15-16 1-2 1-2 7-8 13-14 19-20 1-2 13-14
256-264 1-2 7-8 15-16 1-2 3-4 7-8 13-14 3-4 5-6 7-8 9-10 13-14
19-20
264-272 3-4 5-6 15-16 1-2 1-2 7-8 15-16 3-4 5-6 7-8 9-10
17-18
272-280 3-4 5-6 11-12 3-4 7-8 11-12 3-4 5-6 7-8 11-12 13-
15-16 19-20 13-14 17-18 14
280-288 1-2 5-6 9-10 1-2 3-4 7-8 11-12 3-4 5-6 7-8 11-12
13-14
288-296 1-2 7-8 11-12 1-2 1-2 1-2 11-12 13-14 19- 3-4 5-6 7-8 13-14
20
296-304 1-2 7-8 11-12 1-2 1-2 1-2 11-12 13-14 19- 3-4 5-6 7-8
20
304-312 1-2 7-8 11-12 1-2 1-2 1-2 11-12 13-14 19- 3-4 5-6 9-10 13-14
20
312-320 1-2 7-8 11-12 3-4 7-8 11-12 3-4 5-6 11-12 13-14
15-16 19-20 13-14 19-20
320-328 1-2 7-8 15-16 3-4 7-8 13-14 5-6 11-12 13-14
328-336 1-2 7-8 15-16 3-4 7-8 13-14 3-4 5-6 13-14
336-344 1-2 7-8 11-12 1-2 1-2 13-14 3-4 7-8 11-12
344-352 5-6 1-2 1-2 13-14 3-4 7-8 13-14
352-360 5-6 1-2 1-2 13-14 3-4 7-8 13-14
360-368 9-10 13-14 1-2 11-12 15-16 17- 3-4 9-10 11-12
18
368-376 1-2 7-8 15-16 1-2 3-4 7-8 15-16 3-4 9-10 13-14
19-20 17-18
376-384 1-2 7-8 15-16 3-4 7-8 15-16 3-4 9-10
19-20 17-18
384-392 1-2 11-12 19- 3-4 11-12 17-18 3-4 11-12 13-14
20
392-400 1-2 11-12 19- 3-4 11-12 17-18 5-6 7-8 9-10 11-12 13-
20 14
400-408 1-2 11-12 19- 3-4 11-12 17-18 5-6 7-8 9-10 11-12
20
408-416 1-2 11-12 19- 3-4 11-12 17-18 5-6 7-8 9-10 13-14
20
416-424 1-2 11-12 19- 3-4 11-12 17-18 5-6 7-8 9-10
20
424-432 13-14 1-2 17-18 5-6 7-8 11-12 13-14
432-440 13-14 1-2 17-18 5-6 7-8 11-12
440-448 13-14 1-2 17-18 5-6 7-8 13-14
448-456 1-2 7-8 15-16 1-2 3-4 7-8 17-18 5-6 7-8 13-14

Les connexions suivantes sont communes à toutes les fréquences ci-dessus.

SZ2-SZ3-SZ24-SZ25 SZ1-SZ26 SZ16 SZ27 SZ28-SZ29


3-4 1-2 3-4 3-4 3-4 3-4
Mise en service 1790B/FR CM/F11

PLC 1790/B Page 27/70

Bande de fréquences 456 ÷ 472 kHz

SZ5- SZ6- SZ7- SZ8-


kHz SZ4-SZ23 SZ9-SZ18 SZ17
SZ19 SZ20 SZ21 SZ22
456- 1-2 7-8 15-16 1-2 3-4 7-8 17-18 5-6 7-8
464
464- 1-2 7-8 15-16 1-2 3-4 7-8 17-18 5-6 7-8
472

Les connexions suivantes sont communes à toutes les fréquences ci-dessus.

SZ2-SZ3-SZ24-SZ25 SZ1-SZ26 SZ16 SZ27 SZ28-SZ29


3-4 1-2 3-4 3-4 3-4 3-4

Bande de fréquences 472 ÷ 496 kHz

SZ5- SZ6- SZ7- SZ8-


kHz SZ4-SZ23 SZ9-SZ18 SZ17
SZ19 SZ20 SZ21 SZ22
472- 1-2 1-2 1-2 1-2 1-2 17-18 5-6 9-10 13-14
480
480- 1-2 1-2 1-2 1-2 1-2 17-18 5-6 9-10 13-14
488
488- 1-2 1-2 1-2 1-2 1-2 17-18 5-6 9-10 13-14
496

Les connexions suivantes sont communes à toutes les fréquences ci-dessus.

SZ2-SZ3-SZ24-SZ25 SZ1-SZ26 SZ16 SZ27 SZ28-SZ29


3-4 1-2 3-4 1-2 3-4 3-4

TABLEAU 13 – CAVALIERS DU MODULE INTX POUR CONFIGURATION DOUBLE-VOIE


1790B/FR CM/F11 Mise en service

Page 28/70 PLC 1790/B

2.10.2.2 Filtre mono-voie

Bande de fréquences 44 ÷ 144 kHz

SZ5 SZ6 SZ7- SZ8-


kHz SZ4-SZ23 SZ9-SZ18 SZ17
SZ19 SZ20 SZ21 SZ22
40-44 1-2 5-6 9-10 13-14 1-2 5-6 9-10 13-14 1-2 3-4 5-6 7-8
17-18 17-18 9-10
44-48 1-2 5-6 9-10 1-2 5-6 9-10 1-2 3-4 5-6 9-10
11-12 13-14
48-52 1-2 9-10 13-14 17-18 1-2 1-2 7-8 9-10 13-14 1-2 3-4 5-6 9-10
19-20 13-14
52-56 1-2 5-6 9-10 17-18 1-2 3-4 5-6 9-10 15-16 1-2 3-4 5-6
17-18
56-60 1-2 5-6 13-14 1-2 1-2 7-8 13-14 19- 1-2 3-4 9-10
20
60-64 1-2 9-10 1-2 1-2 13-14 1-2 5-6 7-8
64-68 5-6 13-14 5-6 13-14 1-2 5-6 9-10
68-72 1-2 5-6 1-2 3-4 5-6 13-14 19- 1-2 5-6
20
72-76 1-2 13-14 17-18 1-2 5-6 13-14 17-18 1-2 7-8
76-80 9-10 13-14 9-10 13-14 1-2 11-12 13-14
80-84 1-2 9-10 1-2 3-4 9-10 13-14 19- 1-2 11-12 13-14
20
84-88 1-2 17-18 1-2 5-6 17-18 1-2
88-92 1-2 17-18 1-2 5-6 17-18 3-4 5-6 7-8 9-10
92-96 1-2 7-8 19-20 1-2 5-6 17-18 3-4 5-6 7-8
96-100 1-2 7-8 19-20 1-2 5-6 17-18 3-4 5-6 7-8
100-104 1-2 5-6 17-18 1-2 3-4 7-8 9-10 19-20 3-4 5-6 9-10
104-108 1-2 5-6 17-18 1-2 3-4 7-8 9-10 19-20 3-4 5-6 9-10
108-112 1-2 7-8 15-16 1-2 1-2 9-10 13-14 3-4 5-6 11-12
112-116 1-2 7-8 15-16 1-2 1-2 9-10 13-14 3-4 5-6 11-12
116-120 5-6 17-18 1-2 7-8 9-10 15-16 17- 3-4 5-6 11-12
18
120-124 5-6 17-18 1-2 7-8 9-10 15-16 17- 3-4 5-6 13-14
18
124-128 3-4 9-10 15-16 1-2 1-2 1-2 3-4 5-6 15-16 17- 3-4 5-6 13-14
18
128-132 3-4 9-10 15-16 1-2 1-2 1-2 3-4 5-6 15-16 17- 3-4 7-8
18
132-136 1-2 7-8 15-16 1-2 3-4 7-8 13-14 19- 3-4 9-10
20
136-140 1-2 7-8 15-16 1-2 3-4 7-8 13-14 19- 3-4 9-10
20
140-144 3-4 9-10 15-16 1-2 1-2 3-4 13-14 19-20 3-4 11-12

Les connexions suivantes sont communes à toutes les fréquences ci-dessus.

SZ2-SZ3-SZ24-SZ25 SZ1-SZ26 SZ16 SZ27 SZ28-SZ29


1-2 1-3 3-4 3-4 3-4
Mise en service 1790B/FR CM/F11

PLC 1790/B Page 29/70

Bande de fréquences 144 ÷ 248 kHz

SZ5 SZ6 SZ7 SZ8


kHz SZ4-SZ23 SZ9-SZ18 SZ17
SZ19 SZ20 SZ21 SZ22
144-148 3-4 9-10 15-16 1-2 1-2 3-4 13-14 19- 3-4 11-12
20
148-152 5-6 9-10 1-2 7-8 11-12 13- 3-4
14
152-156 1-2 7-8 11-12 1-2 1-2 1-2 11-12 13-14 3-4
19-20
156-160 1-2 7-8 11-12 15-16 3-4 7-8 11-12 3-4
13-14 19-20
160-164 1-2 7-8 11-12 15-16 3-4 7-8 11-12 3-4
13-14 19-20
164-168 1-2 7-8 15-16 3-4 7-8 13-14 5-6 7-8 11-12
13-14
168-172 1-2 7-8 15-16 3-4 7-8 13-14 5-6 7-8 11-12
13-14
172-176 1-2 7-8 11-12 1-2 1-2 13-14 5-6 7-8 11-12
176-180 1-2 7-8 11-12 1-2 1-2 13-14 5-6 7-8 11-12
180-184 1-2 7-8 19-20 1-2 17-18 5-6 7-8 13-14
184-188 1-2 7-8 19-20 1-2 17-18 5-6 7-8 11-12
188-192 1-2 7-8 11-12 1-2 1-2 7-8 11-12 15- 5-6 7-8 13-14
16 17-18
192-196 1-2 7-8 11-12 1-2 1-2 7-8 11-12 15- 5-6 7-8 13-14
16 17-18
196-200 3-4 7-8 9-10 15-16 19- 3-4 7-8 11-12 5-6 7-8 13-14
20 15-16 17-18
200-204 3-4 7-8 9-10 15-16 19- 3-4 7-8 11-12 5-6 7-8
20 15-16 17-18
204-208 5-6 11-12 19-20 7-8 11-12 17- 5-6 9-10 11-12
18
208-212 13-14 1-2 17-18 5-6 9-10 13-14
212-216 13-14 1-2 17-18 5-6 9-10 13-14
216-220 13-14 1-2 17-18 5-6 9-10 13-14
220-224 1-2 7-8 11-12 15-16 1-2 3-4 7-8 11-12 5-6 9-10
17-18
224-228 1-2 7-8 11-12 15-16 1-2 3-4 7-8 11-12 5-6 9-10
17-18
228-232 1-2 7-8 15-16 1-2 3-4 7-8 17-18 5-6 11-12 13-
14
232-236 1-2 7-8 15-16 1-2 3-4 7-8 17-18 7-8 9-10 13-14
236-240 1-2 1-2 1-2 1-2 1-2 17-18 7-8 9-10
240-244 1-2 1-2 1-2 1-2 1-2 17-18 5-6 11-12
244-248 1-2 1-2 1-2 1-2 1-2 17-18 5-6 11-12 13-
14

Les connexions suivantes sont communes à toutes les fréquences ci-dessus.

SZ2-SZ3-SZ24-SZ25 SZ1-SZ26 SZ16 SZ27 SZ28-SZ29


1-2 1-3 3-4 3-4 3-4
1790B/FR CM/F11 Mise en service

Page 30/70 PLC 1790/B

Bande de fréquences 248 ÷ 352 kHz

SZ5 SZ6 SZ7 SZ8


kHz SZ4-SZ23 SZ9-SZ18 SZ17
SZ19 SZ20 SZ21 SZ22
248-252 1-2 7-8 15-16 1-2 1-2 7-8 13-14 19-20 1-2 5-6 11-12
13-14
252-256 1-2 7-8 15-16 1-2 1-2 7-8 13-14 19-20 1-2 5-6 11-12
13-14
256-260 1-2 7-8 15-16 1-2 3-4 7-8 13-14 19- 1-2 9-10 11-12
20 13-14
260-264 1-2 7-8 15-16 1-2 3-4 7-8 13-14 19- 1-2 9-10 11-12
20 13-14
264-268 3-4 5-6 15-16 1-2 1-2 7-8 15-16 17- 1-2 9-10 11-12
18 13-14
268-272 3-4 5-6 15-16 1-2 1-2 7-8 15-16 17- 1-2 9-10 11-12
18 13-14
272-276 3-4 5-6 11-12 15-16 3-4 7-8 11-12 13- 1-2 9-10 11-12
19-20 14
17-18
276-280 3-4 5-6 11-12 3-4 7-8 11-12 13- 1-2 9-10 11-12
15-16 19-20 14
17-18
280-284 1-2 5-6 9-10 1-2 3-4 7-8 11-12 13- 1-2 9-10
14
284-288 1-2 5-6 9-10 1-2 3-4 7-8 11-12 13- 1-2 9-10
14
288-292 5-6 9-10 1-2 7-8 11-12 13-14 1-2 9-10
292-296 5-6 9-10 1-2 7-8 11-12 13-14 1-2 9-10
296-300 7-8 13-14 19-20 1-2 5-6 17-18 1-2 11-12
300-304 7-8 13-14 19-20 1-2 5-6 17-18 1-2 11-12
304-308 1-2 7-8 11-12 3-4 7-8 11-12 13- 1-2 11-12
15-16 19-20 14
19-20
308-312 1-2 7-8 11-12 3-4 7-8 11-12 13- 1-2 11-12
15-16 19-20 14
19-20
312-316 1-2 7-8 11-12 3-4 7-8 11-12 13- 1-2 11-12
15-16 19-20 14
19-20
316-320 1-2 7-8 11-12 3-4 7-8 11-12 13- 1-2 11-12
15-16 19-20 14
19-20
320-324 1-2 7-8 15-16 3-4 7-8 13-14 3-4 5-6 7-8 9-10
324-328 1-2 7-8 15-16 3-4 7-8 13-14 3-4 5-6 7-8 9-10
328-332 1-2 7-8 15-16 3-4 7-8 13-14 3-4 5-6 7-8 9-10
332-336 1-2 7-8 11-12 1-2 1-2 13-14 3-4 5-6 7-8 11-12
336-340 1-2 7-8 11-12 1-2 1-2 13-14 3-4 5-6 7-8 11-12
340-344 1-2 7-8 11-12 1-2 1-2 13-14 3-4 5-6 7-8 11-12
344-348 5-6 1-2 1-2 14-14 3-4 5-6 7-8 11-12
348-352 5-6 1-2 1-2 13-14 3-4 5-6 7-8 11-12

Les connexions suivantes sont communes à toutes les fréquences ci-dessus.

SZ2-SZ3-SZ24-SZ25 SZ1-SZ26 SZ16 SZ27 SZ28-SZ29


3-4 1-2 3-4 3-4 3-4 3-4
Mise en service 1790B/FR CM/F11

PLC 1790/B Page 31/70

Bande de fréquences 352 ÷ 456 kHz

SZ5 SZ6 SZ7 SZ8


kHz SZ4-SZ23 SZ9-SZ18 SZ17
SZ19 SZ20 SZ21 SZ22
352-356 5-6 1-2 1-2 13-14 3-4 5-6 7-8 11-
12
356-360 9-10 13-14 1-2 11-12 15-16 17-18 3-4 5-6 9-10
360-364 9-10 13-14 1-2 11-12 15-16 17-18 3-4 5-6 9-10
364-368 9-10 13-14 1-2 11-12 15-16 17-18 3-4 5-6 9-10
368-372 1-2 7-8 15-16 19-20 1-2 3-4 7-8 15-16 17-18 3-4 5-6 9-10
372-376 1-2 7-8 15-16 19-20 3-4 7-8 15-16 17-18 3-4 5-6 9-10
376-380 1-2 7-8 15-16 19-20 3-4 7-8 15-16 17-18 3-4 5-6 11-12
380-384 1-2 7-8 15-16 19-20 3-4 7-8 15-16 17-18 3-4 5-6 11-12
384-388 1-2 11-12 19-20 3-4 11-12 17-18 3-4 5-6 11-12
388-392 1-2 11-12 19-20 3-4 11-12 17-18 3-4 5-6 11-12
392-396 1-2 11-12 19-20 3-4 11-12 17-18 3-4 9-10
396-400 1-2 11-12 19-20 3-4 11-12 17-18 3-4 9-10
400-404 1-2 11-12 19-20 3-4 11-12 17-18 3-4 9-10
404-408 1-2 11-12 19-20 3-4 11-12 17-18 3-4 9-10
408-412 1-2 11-12 19-20 3-4 11-12 17-18 3-4 9-10
412-416 1-2 11-12 19-20 3-4 11-12 17-18 3-4 9-10
416-420 1-2 11-12 19-20 3-4 11-12 17-18 3-4 9-10
420-424 13-14 1-2 17-18 3-4 9-10
424-428 13-14 1-2 17-18 3-4 9-10
428-432 13-14 1-2 17-18 3-4 9-10
432-436 13-14 1-2 17-18 3-4 9-10
436-440 13-14 1-2 17-18 3-4 9-10
440-444 13-14 1-2 17-18 3-4 9-10
444-448 13-14 1-2 17-18 5-6 7-8 9-10
11-12
448-452 1-2 7-8 15-16 1-2 3-4 7-8 17-18 5-6 7-8 9-10
452-456 1-2 7-8 15-16 1-2 3-4 7-8 17-18 5-6 7-8 9-10

Les connexions suivantes sont communes à toutes les fréquences ci-dessus.

SZ2-SZ3-SZ24-SZ25 SZ1-SZ26 SZ16 SZ27 SZ28-SZ29


3-4 1-2 3-4 3-4 3-4 3-4
1790B/FR CM/F11 Mise en service

Page 32/70 PLC 1790/B

Bande de fréquences 456 ÷ 472 kHz

SZ5 SZ6 SZ7 SZ8


kHz SZ4-SZ23 SZ9-SZ18 SZ17
SZ19 SZ20 SZ21 SZ22
456-460 1-2 7-8 15-16 1-2 3-4 7-8 17-18 5-6 7-8 9-10
460-464 1-2 7-8 15-16 1-2 3-4 7-8 17-18 5-6 7-8 9-10
464-468 1-2 7-8 15-16 1-2 3-4 7-8 17-18 5-6 7-8 9-10
468-472 1-2 7-8 15-16 1-2 3-4 7-8 17-18 5-6 7-8 9-10

Les connexions suivantes sont communes à toutes les fréquences ci-dessus.

SZ2-SZ3-SZ24-SZ25 SZ1-SZ26 SZ16 SZ27 SZ28-SZ29


3-4 1-2 3-4 3-4 3-4 3-4

Bande de fréquences 472 ÷ 500 kHz

SZ5 SZ6 SZ7 SZ8


kHz SZ4-SZ23 SZ9-SZ18 SZ17
SZ19 SZ20 SZ21 SZ22
472-476 1-2 1-2 1-2 1-2 1-2 17-18 5-6 7-8 13-14
476-480 1-2 1-2 1-2 1-2 1-2 17-18 5-6 7-8 13-14
480-484 1-2 1-2 1-2 1-2 1-2 17-18 5-6 7-8 13-14
484-488 1-2 1-2 1-2 1-2 1-2 17-18 5-6 7-8 13-14
488-492 1-2 1-2 1-2 1-2 1-2 17-18 5-6 7-8 13-14
492-496 1-2 1-2 1-2 1-2 1-2 17-18 5-6 7-8 13-14
496-500 1-2 1-2 1-2 1-2 1-2 17-18 5-6 7-8 13-14

Les connexions suivantes sont communes à toutes les fréquences ci-dessus.

SZ2-SZ3-SZ24-SZ25 SZ1-SZ26 SZ16 SZ27 SZ28-SZ29


3-4 1-2 3-4 1-2 3-4 3-4

TABLEAU 14 – CAVALIERS DU MODULE INTX POUR CONFIGURATION MONOVOIE


2.10.2.3 Mise au point du filtre émission
Instruments nécessaires

• Générateur de signaux W&G PS 30 ou équivalent

• Voltmètre sélectif W&G SPM 30 ou équivalent

• Charge fictive 75 ohms


Préréglage de la fréquence
Programmez le filtre Tx pour la largeur de bande de l'équipement PLC selon les tableaux de
programmation.

Régler l’unité pour un seul amplificateur de puissance


(cavaliers SZ-15 1-2 fermé, 3-4 ouvert)
Mise en service 1790B/FR CM/F11

PLC 1790/B Page 33/70

BANC D’ESSAI
Organisez le banc d’essai comme indiqué dans la figure ci-après.

75 Ω
10 ac 6 ac

G V

75 Ω
18 ac 18 ac

D0239XXa

FIGURE 16 – MONTAGE D’ESSAI POUR LA MISE AU POINT DU FILTRE TX


Test du filtre pour application mono-voie
Réponse en fréquence et perte dans la bande passante
Injecter une tonalité test à la fréquence Fx = Fc +2 kHz, un niveau égal à 0 dBV (Fc =
fréquence porteuse).
Régler les deux bobines pour obtenir une perte de signal minimale. Vérifier que la perte
d’insertion du filtre correspond à la valeur indiquée dans le tableau 15 - Perte maximale pour
filtre mono-voie.

FRÉQUENCE Fx =
kHz Fc + 2 kHz
MIN. MAX. Perte (dB)
40 104 ≤ 0.5
104 304 ≤ 1.5
304 396 ≤ 2.0
396 496 ≤ 2.2

TABLEAU 15 – PERTE MAXIMALE POUR FILTRE MONO-VOIE


Régler les deux bobines et vérifier que la réponse en fréquence du filtre correspond au
gabarit de la figure 17 - Gabarit de réponse en fréquence pour Fc ≤ 392 kHz ou à la figure
18 - Gabarit de réponse en fréquence pour Fc ≥ 396 kHz.

PERTE
dB

15

0.3 dB

-18 -10 -2 Fx +2 +10 +18 F (kHz)


D0240FRa

FIGURE 17 – GABARIT DE RÉPONSE EN FRÉQUENCE POUR FC ≤ 392 KHZ


1790B/FR CM/F11 Mise en service

Page 34/70 PLC 1790/B

PERTE
dB

0.3 dB

-18 -14 -2 Fx +2 +14 +18 F (kHz)


D0241FRa

FIGURE 18 – GABARIT DE RÉPONSE EN FRÉQUENCE POUR FC ≥ 396 KHZ


Test de l'impédance hors bande
Organiser le banc d’essai comme indiqué dans la figure 19 – Montage du test de
l'impédance hors bande.

75 Ω
6 ac 10 ac
I

G V

75 Ω 75 Ω
18 ac 18 ac

D0195XXa

FIGURE 19 – MONTAGE DU TEST DE L'IMPÉDANCE HORS BANDE


Procéder de la manière suivante :

• Ouvrir le commutateur I.

• Envoyer une tonalité test avec une fréquence Fx et un niveau de 0 dBv. Vérifier que le
voltmètre indique un niveau de 0 dBv ;

• Fermer le commutateur I;

• Vérifier qu’à la fréquence indiquée au tableau 16 - Limites d'atténuation hors bande -


le filtre n'est pas chargé en impédance.

FRÉQUENCE
Fx -10 kHz Fx +10 kHz
kHz
MIN. MAX.
40 392 ≤ 0.8 ≤ 0.8
396 500 ≤ 1.4 ≤ 1.4

TABLEAU 16 – LIMITES D'ATTÉNUATION HORS BANDE


NOTA : Une fois les procédures de mise au point du filtre achevées,
repositionner le strap SZ15 en fonction de la puissance HF de votre
équipement CPL.
Mise en service 1790B/FR CM/F11

PLC 1790/B Page 35/70

Test du filtre pour application double-voie


Réponse en fréquence et perte dans la bande passante
Injecter une tonalité test à la fréquence Fx = Fc, un niveau égal à 0 dBv (Fc = fréquence
porteuse).
Régler les deux bobines pour obtenir une perte de signal minimale. Vérifier que la perte
d’insertion du filtre correspond à la valeur indiquée dans le tableau 17 - Perte maximum
dans le filtre double-voie.

FRÉQUENCE
Fx
kHz
MIN. MAX. Perte (dB)
40 96 ≤ 0.5
104 296 ≤ 1.5
304 392 ≤ 2.0
400 500 ≤ 2.2
TABLEAU 17 – PERTE MAXIMUM DANS LE FILTRE DOUBLE-VOIE
Régler les deux bobines et vérifier que la réponse en fréquence du filtre correspond au
gabarit de la figure 20 - Gabarit de réponse en fréquence pour Fc ≤ 392 kHz ou à la figure
21 - Gabarit de réponse en fréquence pour Fc ≥ 400 kHz.

PERTE
dB

14

0.3 dB

-20 -12 -4 Fx +4 +12 +20 F (kHz)


D0242FRa

FIGURE 20 – GABARIT DE RÉPONSE EN FRÉQUENCE POUR FC ≤ 392 KHZ

PERTE
dB

14

0.3 dB

-20 -12 -4 Fx +4 +12 +20 F (kHz)


D0242FRa

FIGURE 21 – GABARIT DE RÉPONSE EN FRÉQUENCE POUR FC ≥ 400 KHZ


1790B/FR CM/F11 Mise en service

Page 36/70 PLC 1790/B

Test de l'impédance hors bande


Organisez le banc d’essai comme indiqué dans la figure 19 – Montage du test de
l'impédance hors bande.
Procéder de la manière suivante :

• Ouvrir le commutateur I.

• Envoyer une tonalité test avec une fréquence Fx et un niveau de 0 dBv. Vérifier que le
voltmètre indique un niveau de 0 dBv ;

• Fermer le commutateur I;

• Vérifier qu’à la fréquence indiquée au tableau 16 - Limites d'atténuation hors bande -


le filtre n'est pas chargé en impédance.

FRÉQUENCE
Fx -12 kHz Fx +12 kHz
kHz
MIN. MAX.
40 392 ≤ 0.8 ≤ 0.8
396 500 ≤ 1.4 ≤ 1.4

TABLEAU 18 – LIMITES D'ATTÉNUATION HORS BANDE POUR LE FILTRE DOUBLE-VOIE


NOTA : Une fois les procédures de mise au point du filtre achevées,
repositionner le strap SZ15 en fonction de la puissance HF de votre
équipement PLC.
Mise en service 1790B/FR CM/F11

PLC 1790/B Page 37/70

2.11 INTERFACE DE LIGNE DE Reception (INRX)


2.11.1 Pré-réglage
Vérifier et prérégler la carte en fonction de la demande du site :

AN-11
AN-3 AN-2
AN-4 AN-7 AN-9
AN-1 AN-10
AN-5
AN-8

1 2
SZ-1
AN-12
3 4
AN-6

1 2
M-1
2 4
SZ-2
1 2
SZ-6
3 4
SZ-3 1 3
3 4

TC10 TC16 TC9 TC7


TC8
TC15

FIGURE 22 – CAVALIERS DU MODULE INRX POUR CONNEXION DE LA LIAISON HF


1790B/FR CM/F11 Mise en service

Page 38/70 PLC 1790/B

2.11.2 Programmation de l’impédance de ligne HF

RÉFÉRENCE CONNEXIONS
PROCÉDURE
SCHÉMA FERMÉ OUVERT
Sortie HF symétrique AN8-AN9 X
Sortie HF asymétrique AN8-AN9 X
Impédance HF 75 ohms AN2-AN10 X
(asymétrique seulement)
(standard) AN1-AN3 X
AN4-AN11 X
AN5-AN7 X
AN6-AN12 X
Impédance HF 150 ohms AN1-AN3 X
(symétrique ou asymétrique) AN4-AN11 X
AN2-AN1 X
AN5-AN7 X
AN6-AN12 X
Impédance HF 125 ohms AN1-AN3 X
(symétrique ou asymétrique) AN5-AN7 X
AN2-AN10 X
AN4-AN11 X
AN6-AN12 X
Impédance HF 50 ohms AN1-AN3 X
(asymétrique seulement) AN6-AN12 X
AN2-AN10 X
AN5-AN7 X
AN4-AN11 X
Ligne HF 2 fils SZ1 1-2 3-4
SZ2 1-2 3-4
SZ3 1-2 3-4
SZ6 1-2 3-4
Ligne HF 4 fils SZ1 1-3 2-4
SZ2 2-4 1-3
SZ3 TOUT
OUVERT
SZ6 TOUT
OUVERT
Atténuateur Rx 3 dB TC8 X
inclus TC10 X
Atténuateur Rx 3 dB TC8 X
exclu TC10 X
Mise en service 1790B/FR CM/F11

PLC 1790/B Page 39/70

RÉFÉRENCE CONNEXIONS
PROCÉDURE
SCHÉMA FERMÉ OUVERT
Atténuateur Rx 6 dB TC15 X
inclus TC16 X
Atténuateur Rx 6 dB TC15 X
exclu TC16 X
Atténuateur Rx 9 dB TC7 X
inclus TC9 X
Atténuateur Rx 9 dB TC7 X
exclu TC9 X

TABLEAU 19 – RÉGLAGE DE LA SORTIE HF DU MODULE INRX


Configuration recommandée pour atténuateur Rx

RÉFÉRENCE CONNEXIONS
PROCÉDURE
SCHÉMA FERMÉ OUVERT
TC8 x
Atténuateur 6 dB TC10 x
PLC mono-voie 10 W TC15 x
ou TC16 x
PLC double-voie 10/20/40 W TC7 x
TC9 x
TC8 x
TC10 x
Atténuateur 9 dB TC15 x
PLC mono-voie 20 W TC16 x
TC7 x
TC9 x
TC8 x
TC10 x
Atténuateur 12 dB TC15 x
PLC mono-voie 40 W TC16 x
TC7 x
TC9 x

TABLEAU 20 – ATTÉNUATEUR D’ENTRÉE DU MODULE INRX


1790B/FR CM/F11 Mise en service

Page 40/70 PLC 1790/B

2.11.3 Tableaux de programmation pour les fréquences comprises entre 40 et 500 kHz
NOTA :
Le tableau suivant décrit la programmation complète du filtre pour une largeur de bande
mono- ou double-voie.
Attention ! Seuls les straps TC fermés sont indiqués. Tous les autres doivent rester ouverts,
à l’exception de celui indiqué au tableau 19 – Réglage de la sortie HF du module INRX.
Le filtre de réception de l'équipement CPL peut être réglé par paliers de 1 kHz, entre 40 et
496 kHz, à l’aide des cavaliers du canal de réception standard le plus proche.
Les chiffres correspondant aux straps TC sont inscrits de manière lisible sur la carte de
circuit imprimé.

UNE VOIE DEUX VOIES RÉFÉRENCE SCHÉMA


kHz kHz (TC FERMÉ)
40 – 44 40 - 48 24,25,26,27,20,21,22,23,46,47,48,49,147,148,174,175,143,144,
145,146,170,171,172,173,55,56,52,54,79,81,116,117,113,115,140,
142,86,87,88,82,83,84,107,108,109,13,160,18,73,134
44 – 48 24,25,27,21,22,47,48,20,45,37147,148,175,144,145,171,172,143,
148,169,55,56,51,76,66116,117,112,137,127,86,87,83,84,108,109,
82,106,89,13,160,18, 73,134
48 – 52 48 - 56 24,26,27,20,46147,174,175,143,170,55,51,52,78,79,116,112,113,
139,140,86,88,82,107,83,101,97,13,160,18,73, 134
52 – 56 24,27,21,22,47,48,147,175,144,145,171,172,55,51,54,78,81,116,
112,115,139,142,86,82,84,107,109,7,8,15,13, 160,18,73,134
56 – 60 56 64 24,20,42,40,39,35,34,37147,143,166,162,161,156,155,158,55,52,
54,79,81,51,75,65116,113,115,140,142,112,136,126,86,82,103,95,
109,13,160,18,73, 134
60 64 25,26,27,21,40,35,49148,174,175,144,162,156,173,55,72,79,116,
113,140,87,88,82,107,13,160,18,73, 134
64 – 68 64 - 72 13,18,22,25,26,33,37,40,41,53,55,73,80,82,84,85,87,107,109,110,
114,116,134,141,145,148,154,158,160,162,165,174
68 – 72 25,27,23,49,20,44,36,148,175,146,173,143,168,157,56,51,52,53,
54,78,79,80,81,117,112,113,114,115,139,140,141,142,87,83,84,
108,109,13,160,18,73,134
72 – 76 72 - 80 25,21,23,47,49,20,44,36,148,144,146,171,173,143,168,157,56,51,
52,54,78,79,81,117,112,113,115,139,140,142,87,83,108,13,160,18,
73,134
76 – 80 25,20,45,37,21,40,36148,143,169,158,144,162,157,56,51,52,78,79,
117,112,113,139,140,87,82,105,95,94,102,110,13,160,18,73,134
80 - 84 80 - 88 26,27,21,23,47,49,20,44,36,174,175,144,146,171,143,168,157,56,
51,53,78,80,52,71,66,117,112,114,139,141,113,132,127,88,82,83,
107,108,13,160,18,73,134
84 - 88 26,27,23,49,20,42,38,174,175,146,173,143,166,159,56,51,78,52,
70,65,117,112,139,113,131,126,88,83,84,108,109,13,160,18,73,
134
88 - 92 88 - 96 26,27,20,42,34,35,39,49,174,175,143,166,155,156,161,173,56,51,
78,52,70,64,81,112,139,113,131,125,142,117,88,83,108,82,106,98,
13,160,18,73, 134
92 - 96 26,21,22,47,48,20,45,37,174,144,145,171,172,143,169,158,56,52,
53,54,79,80,81,117,113,114,115,140,141,142,88,85,110,83,101,97,
13,160,18,73,134
Mise en service 1790B/FR CM/F11

PLC 1790/B Page 41/70

UNE VOIE DEUX VOIES RÉFÉRENCE SCHÉMA


kHz kHz (TC FERMÉ)
96 - 100 96 - 104 26,20,46,22,39,37,143,170,145,161,158,174,56,52,54,79,81,51,75,
65,117,113,115,140,142,112,136,126,88,82,103,101,95,97,13,160,
18,73,134
100 - 104 26,23,49,21,40,36,174,146,173,144,162,157,56,53,54,80,81,51,72,
67,117,114,115,141,142,112,133,128,88,85,106,103,93,90,13,160,
18,73,134
104 - 108 104 - 112 26,22,44,42,32,29,174,145,168,166,153,150,56,52,54,79,81,117,11
3,115,140,142,88,82,105,96,11013,160,18,73,134
108 - 112 27,20,21,46,47,22,39,37,175,143,144,171,145,161,158,170,56,52,
79,117,113,140, 88,13,160,18,73,134
112 - 116 112 - 120 27,20,21,46,47,175,143,144,170,171,56,51,54,76,72,70,63,65,117,
112,115,137,133,131,124,126,82,85,107,110,83,101,97,13,160,18,
73,134
116 - 120 27,20,46,23,49,175,143,146,170,173,56,52,72,75,76,60,57,58,117,
113,133,136,137,121,118,119,83,84,108,109,82,106,98,13,160,18,
73,134
120 - 124 120 - 128 27,21,23,47,49,175,144,146,171,173,56,54,81,52,70,65,117,115,14
2,113,131,126,82,84,107,109,13,160,18,73,134
124 - 128 27,22,48,20,42,38,175,145,172,143,166,159,56,53,75,72,76,61,57,
66,117,114,133,136,137,118,122,127,82,85,107,11013,160,18,73,
134
128 - 132 128 - 136 27,23,49,20,44,36,175,146,173,143,168,157,56,52,70,65,117,113,
131,126,83,84,108,109,13,160,18,73,134
132 - 136 27,20,22,44,42,41,33,37,175,143,145,168,166,165,154,158,56,52,
71,66,117,113,132,127,82,107,83,102,98,13,160,18,73,134
136 - 140 136 - 144 27,20,44,39,35,37175,143,168,161,156,158,56,51,72,63,68,66,117,
112,133,124,129,127,82,107,83,101,96,110,13,160,18,73,134
140 - 144 27,23,45,42,32,29,175,146,169,166,153,150,56,117,83,108,82,105,
97,13,160,18,73,134
144 - 148 144 - 152 27,20,45,34,40,48,33,175,143,169,155,162,172,154,51,52,53,78,
79,80,112,113,114,139,140,141,83,108,82,106,98,13,160,18,73,
134
148 - 152 20,22,23,46,48,49,143,145,146,170,172,173,51,52,53,78,79,80,
112,113,114,139,140,141,83,108,84,100,98,13, 160,18,73,134
152 - 156 152 - 160 27,175,51,52,53,78,79,80,112,113,114,139,140,141,82,107,13,160,
18,73,134
156 - 160 21,22,23,47,48,49,144,145,146,171,172,173,51,52,54,78,79,81,
112,113,115,139,140,142,85,110,82,103,99,13,160,18,73,134
160 - 164 160 - 168 20,21,46,47,143,144,170,171,51,52,54,78,79,81,112,113,115,139,
140,142,85,110,82,105,97,13,160,18,73,134
164 - 168 26,27,20,46,174,175,143,170,55,56,52,53,79,80,116,117,113,114,
141,88,83,84,108,109,11,12,164,163,17,19,77,138,69,130
168 - 172 168 - 176 26,27,20,44,36,21,41,37,174,175,143,168,157,144,165,158,55,56,
52,79,51,76,66,116,117,113,140,112,137,127,88,82,107,83,102,98,
11,12,164,163,17,19,77,138,69,130
172 - 176 26,27,23,45,42,32,29,174,175,146,169,166,153,150,55,56,54,81,
51,72,67,116,117,115,142,112,133,128,88,83,108,82,105,97,11,12,
164,163,17,19,77,138,69,130
176 - 180 176 - 184 26,20,21,46,47,22,39,37,174,143,144,170,171,145,161,158,55,56,
4 81 1 6 116 11 11 142 112 136 126 88 82 10 11 12 164
1790B/FR CM/F11 Mise en service

Page 42/70 PLC 1790/B

UNE VOIE DEUX VOIES RÉFÉRENCE SCHÉMA


kHz kHz (TC FERMÉ)
54,81,51,75,65,116,117,115,142,112,136,126,88,82,107,11,12,164,
163,17,19,77,138,69,130
180 - 184 26,20,21,46,47,174,143,144,170,171,55,56,51,75,65,116,117,112,
136,126,88,84,109,82,103,94,110,11,12,164,163,17,19,77,138,69,
130
184 - 188 184 - 192 26,20,23,46,49,174,143,146,170,173,55,56,52,70,64,81,116,117,
113,131,125,142,88,82,85,106,103,101,95,97,11,12,164,163,17,19,
77,138,69,130
188 - 192 26,20,46,21,41,37,174,143,170,144,165,158,55,56,116,117,88,84,
109,11,12,164,163,17,19,77,138,69,130
192 - 196 192 - 200 26,22,48,20,42,38,174,145,172,143,166,159,55,51,52,53,78,79,80,
116,112,113,114,139,140,141,88,82,105,96,100,97,11,12,164,163,
17,19,77,138,69,130
196 - 200 26,23,49,20,44,36,174,146,173,143,168,157,55,51,52,78,79,53,68,
66,116,112,113,139,140,114,129,127,82,83,84,107,108,109,11,12,
164,163,17,19,77,138,69,130
200 - 204 200 - 208 26,20,32,42,44,35,39,37,174,143,153,166,169,156,161,158,55,51,
52,78,79116,112,113,139,140,88,82,103,94,96,100,110,11,12,164,
163,17,19,77,138,69,130
204 - 208 26,21,42,31,44,48,174,144,166,152,168,172,55,51,53,54,78,80,81,
116,112,114,115,139,141,142,88,82,103,94,110,11,12,164,163,17,
19,77,138,69,130
208 - 212 208 - 216 26,21,40,36,174,144,162,157,55,51,54,78,81,52,70,65,116,112,
115,139,142,113,131,126,82,84,85,107,109,110,11,12,164,163,17,
19,77,138,69,130
212 - 216 27,20,22,23,46,48,49,175,143,145,170,172,173,146,55,51,78,52,
70,65,116,112,139,113,131,126,88,11,12,164,163,17,19,77,138,69,
130
216 - 220 216 - 224 26,174,55,51,78,52,71,66,116,112,139,113,132,127,82,84,107,109,
83,102,98,11,12,164,163,17,19,77,138,69,130
220 - 224 27,20,21,46,47,175,143,144,170,171,55,51,78,116,112,139,82,85,
107,110,83,101,97,11,12,164,163,17,19,77, 138,69,130
224 - 228 224 - 232 27,21,23,47,49,20,44,36,175,144,146,171,173,143,168,157,55,52,
53,54,79,80,81,116,113,114,115,140,141,142,82,83,107,108,11,12,
164,163,17,19,77,138,69,130
228 - 232 27,20,23,46,49,175,143,146,170,173,55,52,53,79,80,51,76,66,116,
113,114,140,141,112,137,127,83,84,108,109,82,106,98,11,12,164,
163,17,19,77,138,69,130
232 - 236 232 - 240 27,21,22,47,48,175,144,145,171,172,55,52,53,79,80,116,113,114,
140,141,83,85,108,110,82,105,97,11,12,164,163,17,19,77,138,69,
130
236 - 240 27,37,41,21,46,175,143,144,170,165,158,65,55,52,79,51,75,116,
113,140,112,136,126,82,107,84,109,11,12,164,163,17,19,77,138,
69,130
240 - 244 240 - 248 27,20,46,21,40,35,49,175,143,170,144,162,156,173,55,52,54,79,
81,116,113,115,140,142,84,85,109,110,82,103,99,11,12,164,163,
17,19,77,138,69,130
Mise en service 1790B/FR CM/F11

PLC 1790/B Page 43/70

UNE VOIE DEUX VOIES RÉFÉRENCE SCHÉMA


kHz kHz (TC FERMÉ)
244 - 248 27,22,48,20,42,38,175,145,172,143,166,159,55,52,79,51,75,64,81,
116,113,140,112,136,125,142,55,52,79,51,75,64,81,116,113,140,
112,136,125,142,11,12,164,163,17, 19,77,138,69,130
248 - 252 248 - 256 27,20,46,175,143,170,55,52,79,116,113,140,83,84,108,109,11,12,
164,163,17,19 ,77,138,69,130
252 - 256 27,23,49,20,44,36,175,146,173,143,168,157,55,51,72,67,53,68,66,
116,112,133,128,114,129,127,83,84,108,109,11,12,164,163,17,19,
77,138,69,130
256 - 260 256 - 264 27,21,47,175,144,171,55,52,72,75,60,58,116,113,133,136,121,119,
82,107,83,101,97,11,12,164,163,17,19,77,138,69,130
260 - 264 27,20,23,45,42,40,34,36,175,143,146,169,166,162,155,157,55,54,
81,52,70,65,116,115,142,113,131,126,82,107,83,101,97,11,12,164,
163,17,19,77,138,69,130
264 - 268 264 - 272 27,22,48,175,145,172,55,53,80116,114,141,82,107,83,102,98,11,
12,164,163,17,19,77,138,69,130
268 - 272 27,21,42,44,45,31,28,37,175,144,166,168,169,149,152,158,55,51,
72,63,64,68,81,116,112,133,124,125,129,142,82,107,83,101,96,
110,11,12,164,163,17,19,77,138, 69,130
272 - 276 272 - 280 27,22,42,44,45,32,28,29,175,145,166,168,169,149,153,150,55,54,
76,75,72,60,61,58,116,115,137,136,133,121,122,119,82,107,83,
101,96,110,11,12,164,163,17,19,77, 138,69,130
276 - 280 20,21,22,46,47,48,143,144,145,170,171,172,55,51,72,63,68,66,
116,112,133,124,129,127,83,108,82,105,97,11,12,164,163,17,19,
77,38,69,130
280 - 284 280 - 288 27,21,40,36,175,144,162,157,56,51,52,53,54,78,79,80,81,117,112,
113,114,115,139,140,141,142,83,108,82,105,97,11,12,164,163,17,
19,77,138,69,130
284 - 288 27,21,40,31,28,45,49,175,144,162,152,149,169,173,55,116,84,85,
109,110,11,12,164,163,17,19,77,138,69,130
288 - 292 288 - 296 27,20,44,35,49,175,143,168,156,173,56,51,52,53,78,79,80,117,
112,113,114,139,140,141,84,109,82,103,9911,12,164,163,17,19,
77,138,69,130
292 - 296 20,22,23,46,48,49,143,145,146,170,172,173,56,51,52,53,78,79,80,
117,112,113,114,139,140,141,84,109,82,103,99,11,12,164,163,17,
19,77,138,69,130
296 - 300 296 - 304 20,21,46,47,22,39,37,143,144,170,171,145,161,158,56,51,52,54,
78,79,81,117,112,113,115,139,140,142,82,10711,12,164,163,17,
19,77,138,69,130
300 - 304 27175,56,51,52,54,78,79,81,117,112,113,115,139,140,142,82,107,
11,12,164,163,17,19,77,138,69,130
304 - 308 304 - 312 20,22,46,48,21,41,37,143,145,170,172,144,165,158,56,51,52,78,
79,53,68,66117,112,113,139,140,114,129,127,84,109,82,106,98,
11,12,164,163,17,19,77,138,69, 130
308 - 312 21,22,23,47,48,49144,145,146,171,172,173,56,51,52,78,79,117,
112,113,139,140,85,110,82,103,99,11,12,164,163,17,19,77,138,69,
130
312 - 316 312 - 320 20,23,46,49,21,40,36,143,146,170,173,144,162,157,56,51,52,78,
79,117,112,113,139,140,84,109,83,102,9811,12,164,163,17,19,77,
138,69,130
316 - 320 20,21,46,47,143,144,170,171,56,51,52,78,79,117,112,113,139,140,
8 110 82 10 9 11 12 164 163 1 19 138 69 130
1790B/FR CM/F11 Mise en service

Page 44/70 PLC 1790/B

UNE VOIE DEUX VOIES RÉFÉRENCE SCHÉMA


kHz kHz (TC FERMÉ)
85,110,82,105,97,11,12,164,163,17,19,77, 138,69,130
320 - 324 320 - 328 20,21,46,47,143,144,170,171,56,51,53,54,78,80,81,117,112,114,
115,139,141,142,84,109,82,103,94,110,11,12,164,163,17,19,77,
138,69,130
324 - 328 21,22,47,48,20,45,37,144,145,171,172,143,169,158,56,51,53,54,
78,80,81,117,112,114,115,139,141,142,84,109,82,103,94,110,11,
12,164,163,17,19,77,138,69,130
328 - 332 328 - 336 21,23,47,49,20,44,36,144,146,171,173,143,168,157,56,51,53,78,
80,52,71,66,117,112,114,139,141,113,132,127,83,108,11,12,164,
163, 17,19,77,138,69,130
332 - 336 20,22,46,48,143,145,170,172,56,51,54,78,81,52,70,65,117,112,
115,139,142,113,131,126,83,10,811,12,164,163,17,19,77,138,69,
130
336 - 340 336 - 344 22,23,48,49,20,42,38,145,146,172,173,143,166,159,56,51,53,78,
80,117,112,114,139,141,83,108,11,12,164,163,17,19,77,138,69,
130
340 - 344 22,23,48,49,20,42,38,145,146,172,173,143,166,159,56,51,53,78,
80,117,112,114,139,141,83,108,11,12,164,163,17,19,77,138,69,
130
344 - 348 344 - 352 20,23,46,49,143,146,170,173,56,51,78,52,70,65,117,112,139,113,
131,126,85,110,82,103,95,109,11,12,164,163,17,19,77,138,69,130
348 - 352 21,22,47,48,144,145,171,172,56,51,78,52,70,65,117,112,139,113,
131,126,82,85,106,103,101,95,97,11,12,164,163,17,19,77,138,69,
130
352 - 356 352 - 360 21,22,47,48,144,145,171,172,51,54,56,78,81,112,115,117,139,142,
82,89,95,99,100,101,106,11,12,164,163,17,19,77,138,69,130
356 - 360 21,22,47,48,144,145,171,172,56,51,60,66,68,78,117,112,121,127,
129,139,83,93,103,105,96,100,98,11,12,164,163,17,19,77,138,69,
130
360 - 364 360 - 368 21,22,47,48,144,145,171,172,56,51,78,52,70,64,81,117,112,139,
113,131,125,142,82,93,103,105,100,96,98,11,12,164,163,17,19,77,
138,69,130
364 - 368 20,46,21,40,36,143,170,144,162,157,56,51,78,117,112,139,82,106,
98,83,101,97,11,12,164,163,17,19,77,138,69,130
368 - 372 368 - 376 20,46,21,41,37,143,170,144,165,158,56,51,78,117,112,39,82,103,
101,100,96,95,99,11,12,164,163,17,19,77,138,69,130
372 - 376 20,46,21,41,37,143,170,144,165,158,56,51,78,117,112,139,84,109,
11,12,164,163,17,19,77,138,69,130
376 - 380 376 - 384 21,23,47,49,144,146,171,173,56,52,53,54,79,80,81,117,113,114,
115,140,141,142,84,109,11,12,164,163,17,19, 77,138,69,130
380 - 384 20,46,21,40,35,49,143,170,144,162,156,173,56,52,53,54,79,80,81,
117,113,114,115,140,141,142,82,103,101,95,97,11,12,164,163,17,
19,77,138,69,130
384 - 388 384 - 392 20,46,21,40,35,49,143,170,144,162,156,173,56,52,53,54,79,80,81,
117,113,114,115,140,141,142,82,103,101,95,97,11,12,164,163,17,
19,77,138,69,130
Mise en service 1790B/FR CM/F11

PLC 1790/B Page 45/70

UNE VOIE DEUX VOIES RÉFÉRENCE SCHÉMA


kHz kHz (TC FERMÉ)
388 - 392 21,47,20,44,36,144,171,143,168,157,56,52,54,79,81,51,75,65,117,
113,115,140,142,112,136,126,82,103,101,95,97,11,12,164,163,17,
19,77,138,69,130
392 - 396 392 - 400 21,47,20,44,36,144,171,143,168,157,56,52,54,79,81,51,75,65,117,
113,115,140,142,112,136,126,82,103,101,95,97,11,12,164,163,17,
19,77,138,69,130
396 - 400 22,23,48,49,145,146,172,173,56,52,53,79,80,117,113,114,140,141,
83,103,105,106,92,89,90,11,12,164,163,17,19,77,138,69,130
400 - 404 400 - 408 22,23,48,49,145,146,172,173,56,52,53,79,80,117,113,114,140,141,
82,105,100,96,98,11,12,164,163,17,19,77,138,69,130
404 - 408 22,48,20,42,38,145,172,143,166,159,56,52,53,79,80,117,113,114,
140,141,82,105,100,96,98,11,12,164,163,17, 19,77,138,69, 130
408 - 412 408 - 416 22,48,20,42,38,145,172,143,166,159,56,53,54,80,81,51,72,67,117,
114,115,141,142,112,133,128,82,105,100,96,98,11,12,164,163,17,
19,77,138,69,130
412 - 416 22,48,20,42,38,145,172,143,166,159,56,52,79,51,75,65,117,113,
140,112,136,126,83,103,105,92,90,11,12,164,163,17,19,77,138,69,
130
416 - 420 416 - 424 20,46,143,170,56,52,54,79,81,117,113,115,140,142,83,103,106,89,
90,11,12,164,163,17,19,77,138,69,130
420 - 424 20,46,143,170,56,52,54,79,81,117,113,115,140,142,85,110,11,12,
164,163,17,19,77,138,69,130
424 - 428 424 - 432 20,46,143,170,56,52,79,51,76,66,117,113,140,112,137,127,84,103,
105,106,93,89,90,11,12,164,163,17,19,77,138,69,130
428 - 432 22,48,20,45,37,145,172,143,169,158,56,52,79,53,68,66,117,113,
140,114,129,127,84,105,103,93,90,11,12,164,163,17,19,77,138,69,
130
432 - 436 432 - 440 22,48,20,45,37,145,172,143,169,158,56,53,54,80,81,117,114,141,
115,142,84,105,103,93,90,11,12,164,163,17,19,77,138,69,130
436 - 440 23,49,20,42,38,146,173,143,166,159,56,52,79,51,75,64,81,117,
113,140,112,136,125,142,84,105,103,93,90,11,12,164,163,17,19,
77,138,69,130
440 - 444 440 - 448 22,48,21,41,37,145,172,144,165,158,56,52,79,117,113,140,83,101,
100,96,98,11,12,164,163,17,19,77,138,69,130
444 - 448 23,49,20,44,36,146,173,143,168,157,56,52,79,117,113,140,84,105,
106,89,90,11,12,164,163,17,19,77,138,69, 130
448 - 452 448 - 456 23,49,20,44,36,146,173,143,168,157,56,51,72,70,68,63,64,66,117,
112,133,131,129,124,125,127,84,105,106,89,90,11,12,164,163,17,
19,77,138,69,130
452 - 456 22,48,20,42,33,49,145,172,143,166,154,173,56,54,81,51,72,67,
117,115,142,112,133,128,84,101,102,94,9811,12,164,163,17,19,
77,138,69,130
456 - 460 456 - 464 22,48,20,42,33,49,145,172,143,166,154,173,51,72,63,80,56,117,
112,133,124,141,84,101,102,94,98,11,12,164,163,17,19,77,138,69,
130
460 - 464 23,49,21,40,36,146,173,144,162,157,56,51,72,67,53,68,66,117,
112,133,128,114,129,127,84,101,102,94,98,11,12,164,163,17,19,
77,138,69,130
464 - 468 464 - 472 21,47,144,171,56,51,72,62,81,117,112,133,123,142,85,106,103,93,
90 11 12 164 163 1 19 138 69 130
1790B/FR CM/F11 Mise en service

Page 46/70 PLC 1790/B

UNE VOIE DEUX VOIES RÉFÉRENCE SCHÉMA


kHz kHz (TC FERMÉ)
90,11,12,164,163,17,19,77,138,69,130
468 - 472 21,47,144,171,56,51,72,62,81,117,112,133,123,142,85,106,103,93,
90,11,12,164,163,17,19,77,138,69,130
472 - 476 472 - 480 21,47,144,171,56,53,80,51,76,66,117,112,133,123,142,85,106,103,
93,90,11,12,164,163,17,19,77,138,69,130
476 - 480 21,47,144,171,56,53,80,51,72,62,81,117,114,141,112,133,123,142,
85,106,105,92,90,11,12,164,163,17,19,77,138,69,130
480 - 484 480 - 488 21,47,144,171,56,81,51,75,65,54,117,115,142,112,136,126,85,106,
105,92,90,11,12,164,163,17,19,77,138,69,130
484 - 488 23,49,20,42,34,48,146,173,143,166,155,172,56,51,72,67,53,68,66,
117,112,133,128,114,129,127,85,102,101,95,97,11,12,164,163,17,
19,77,138,69,130
488 - 492 488 - 496 20,28,45,44,40,34,36,143,149,169,168,162,155,157,56,54,81,52,
70,65,117,115,142,113,131,126,85,102,101,95,97,11,12,164,163,
17,19,77,138,69,130
492 - 496 20,23,45,42,40,34,36,143,146,169,166,162,155,157,56,51,75,68,
64,66,117,112,136,129,125,127,83,101,97,11,12,164,163,17,19,77,
38, 69,130
496 - 500 20,23,45,42,40,34,36,143,146,169,166,162,155,157,56,51,75,68,
64,66,117,112,136,129,125,127,83,101,97,11,12,164,163,17,19,77,
38, 69,130

TABLEAU 21 – TABLEAU DE PROGRAMMATION DU FILTRE DU MODULE INRX


2.11.3.1 Mise au point du filtre réception
Instruments nécessaires
Générateur de signaux W&G PS 30 ou équivalent
Voltmètre sélectif W&G SPM 30 ou équivalent
Programmation de la largeur de bande
Programmer le filtre mono-voie ou double-voie en vous reportant au tableau 21 – Tableau de
programmation du filtre du module INRX.
Test du filtre
Les procédures suivantes concernent à la fois le filtre mono-voie et double-voie.
Avant d’organiser le banc d’essai, réglez le module INRX de la manière suivante :

• Ouvrir SZ-6 1-2 et 3-4.

• Fermer SZ2 2-4 et ouvrir 1-3.

• Exclure l’atténuateur d’entrée, ouvrir TC9, TC10, TC16 et fermer TC7, TC8, TC15.
Mise en service 1790B/FR CM/F11

PLC 1790/B Page 47/70

75 Ω
20 ac 30 ac

G V

75 Ω
18 ac 18 ac

D0243XXa

FIGURE 23 – MONTAGE D’ESSAI POUR LA MISE AU POINT DU FILTRE RX


Organiser le banc de test comme indiqué à la figure 2.21.
Envoyer une tonalité test avec une fréquence Fx = Fc+2 KHz et un niveau 0 dBv (mono-
voie).
Envoyer une tonalité test avec une fréquence Fx = Fc et un niveau 0 dBv (double-voie).
Régler les trois bobines de manière à obtenir une perte minimale.
Vérifier que la valeur de la perte d’insertion du filtre est conforme aux indications du tableau 22 –
Perte maximale du filtre Rx.

FRÉQUENCE
Fx
kHz
MIN. MAX. PERTE
(dB)
40 168 ≤ 1.0
168 320 ≤ 2.0
320 496 ≤ 3.2

TABLEAU 22 – PERTE MAXIMALE DU FILTRE RX


Vérifier que la réponse en fréquence du filtre correspond au gabarit de la figure 24 – Gabarit
de réponse en fréquence mono-voie ou de la figure 25 – Gabarit de réponse en fréquence
double-voie.
Régler les trois bobines de manière à obtenir la meilleure réponse en fréquence.

PERTE dB

19

10

0.8 dB

-14 -10 -2 Fx +2 +10 +14 F (kHz)


(Fc+2kHz)
D0244FRa

FIGURE 24 – GABARIT DE RÉPONSE EN FRÉQUENCE MONO-VOIE


1790B/FR CM/F11 Mise en service

Page 48/70 PLC 1790/B

PERTE dB

19

10

1 dB

-14 -10 -4 Fx=Fc +4 +10 +14 F (kHz)

D0245FRa

FIGURE 25 – GABARIT DE RÉPONSE EN FRÉQUENCE DOUBLE-VOIE


NOTA : Une fois les procédures de réglage du filtre achevées, configurer le
filtre en fonction des caractéristiques HF de votre équipement CPL.
Mise en service 1790B/FR CM/F11

PLC 1790/B Page 49/70

3. TEST ET MISE EN SERVICE


3.1 Configuration logicielle
Veuillez vous reporter à la section Interface homme machine (IHM).
3.2 Instruments nécessaires
Le tableau suivant répertorie les instruments de mesure et les accessoires nécessaires au
démarrage de l’équipement (quantité nécessaire pour une équipe) :

INSTRUMENTS ET ACCESSOIRES QTE. TYPE


Multimètre numérique 1 Type FLUKE 77 ou
équivalent
Générateur de signaux 1 PS 30 W&G ou équivalent
Voltmètre sélectif 1 SPM 30 W&G ou équivalent
(mesure du niveau)

PC 1 Compatible IBM
Système d’exploitation Windows 3.x ou version
ultérieure
Câble de connexion HF 1
Câble de connexion BF 2

TABLEAU 23 – ACCESSOIRES ET INSTRUMENTS DE MESURE


3.3 Opération préliminaire
Lorsque l'équipement PLC est installé et connecté à l’autre équipement à travers la ligne HF,
avant la mise sous tension, observer les recommandations suivantes :
1. Placer la sortie HF de l'équipement PLC sur la charge fictive.
2. Débrancher le connecteur de l’alimentation M1 et vérifier que la connexion est
correcte (au moyen d’un multimètre numérique).
3. Vérifier la connexion à la terre.
4. Vérifier la connexion du câble HF.
5. Vérifier la connexion du service BF.
6. Vérifier que toutes les cartes sont bien en place et insérées correctement dans les
glissières.
7. Vérifier que la partie supérieure et inférieure de l'équipement PLC ne sont pas
obstruées.
Ces recommandations sont nécessaires, car nous supposons que le technicien chargé de la
mise en service ne prend pas en charge les activités relatives à l’installation.
Les opérations préliminaires concernent également l’ensemble des unités
correspondantes, le préréglage du groupe de couplage, le circuit bouchon et
l’installation correcte des condensateurs de couplage. Nous vous conseillons
vivement de contrôler la réponse de la ligne HT sans l’équipement PLC, entre deux
groupes de couplage, et de vérifier la réponse de la ligne, l’impédance caractéristique
et l’affaiblissement d’adaptation sur la largeur de bande opérationnelle.
Une fois les opérations préliminaires achevées, le test de l'équipement PLC peut démarrer.
1790B/FR CM/F11 Mise en service

Page 50/70 PLC 1790/B

3.4 Test local de l'équipement PLC


3.4.1 Alimentation
Mettre l’alimentation (ALIM) sous tension et vérifier, en examinant les DEL allumées, que
l'équipement PLC est alimenté.
2 DEL et 5 points test sont présents sur la partie frontale de l’ALIM.
Procéder aux vérifications suivantes :
1. DEL ROUGE éteinte
2. DEL VERTE allumée
3. Vérifier les tensions de sortie : de haut en bas, les 5 points test sont respectivement
+5V ; -5V ; +15V ; -15V ; -36V (voir figure 26 – Points test de l'alimentation).

DEL_1 VERTE

DEL_2 ROUGE

+5 V
-5 V
+15 V
-15 V
-36 V

D0246FRa

FIGURE 26 – POINTS TEST DE L’ALIMENTATION

Tension Nominale (CC) Tolérance


+ 5 V, - 5 V,
+5%
+ 15 V, - 15 V
- 36 V + 10, -5 %

TABLEAU 24 – TOLÉRANCES
Mise en service 1790B/FR CM/F11

PLC 1790/B Page 51/70

3.4.2 Niveau de transmission


3.4.2.1 DEL et points test de l'équipement PLC
La figure suivante indique l’emplacement des DEL et des points test sur l'équipement PLC.

5 dB

PLC-1

RX

M8 J4 TX

PLC-2

OVF LF0

OVF LF1
PLC 1790/C

RX

DEL 1 VERTE
DEL 2 ROUGE

ALIM

TX

2 14 20 26 32 36 40 45 55 65 76 OVF A/D
RX
RX -5dB

INRX RX +5dB
LF
SQUELCH
DSP OK
DEL 1 VERTE DEL 2 VERTE
LOOP

RX DSP KO
DEL 3 VERTE DEL 4 ROUGE

DEL 5 VERTE DEL 6 JAUNE


MODAF

LFS
D0247FRa

FIGURE 27 – DEL ET POINTS TEST SUR L'ÉQUIPEMENT CPL


1790B/FR CM/F11 Mise en service

Page 52/70 PLC 1790/B

3.4.2.2 Contrôle préliminaire


Après la mise sous tension de l'équipement PLC, commencez par vérifier l’état des DEL sur
la carte MODAF :
Lorsque l'équipement PLC est hors ligne, les conditions doivent être les suivantes :

DEL ETAT DESCRIPTION REMARQUE


5dB ALLUME 5 dB Pas de PORTEUSE Rx
Rx ALLUME Rx RAPPORT SIGNAL /
BRUIT
Tx ETEINT PORTEUSE Tx NIVEAU PORTEUSE Tx
HF DANS LES LIMITES
TOLEREES
Rx –5dB ALLUME Porteuse Rx Niveau de la porteuse
Rx 5 dB sous le niveau
nominal
Squelch BF ALLUME ALARME Alarme Rx active et
COMMUNE démodulateur HF
bloqué
PLC1
PLC2
0VF LF0
0VF LF1
0VF A/D Rx
Rx -5dB
Rx +5dB
Squelch BF
DSP
BOUCLE

TABLEAU 25 – DEL DU MODULE MODAF HORS LIGNE


Si la DEL Tx est allumée, avant de passer au test local, vérifiez que la programmation et la
mise au point du filtre de transmission sont correctes, que l’amplificateur de puissance est
inséré correctement. Dans tous les cas, passez à la section § 3.4.2.4 et exécutez le test HF.
Mise en service 1790B/FR CM/F11

PLC 1790/B Page 53/70

3.4.2.3 Service BF
La première étape consiste à contrôler le niveau de la section BF.
Procéder de la manière suivante :
Indications des DEL
Pour chaque DEL, différentes conditions seront analysées. Voir figure 29 – Niveaux
d'entrées BF.
Lorsque la PLC n'est pas en ligne, seules les indications valides sont rapportées :

DEL 1 VERTE DEL 2 VERTE

DEL 3 VERTE DEL 4 ROUGE

DEL 5 VERTE DEL 6 JAUNE

D0248FRa

FIGURE 28 – DEL DE LA CARTE BFS

DEL_4 : Défaut Rx signalisation FSK (couleur rouge)


ÉTAT EFFET explication
ETEINT Signal Rx OK 1) CPL en ligne
ALLUME Défaut signal Rx 2) CPL hors ligne
3) Signal Rx faible
4) Fréquence Rx incorrecte
DEL_5 : état du DSP (couleur verte )
ÉTAT EFFET explication
clignotement rapide Équipement 1) L’unité fonctionne normalement
opérationnel
clignotement lent Équipement hors 1) DSP en programmation
ligne
2) DSP en test
3) DSP en déclenchement chien de
garde (Watch Dog)
4) EEPROM vide
ETEINT Hors service 1) Carte défectueuse

TABLEAU 26 –DEL DU MODULE LFS ÉTAT HORS LIGNE


1790B/FR CM/F11 Mise en service

Page 54/70 PLC 1790/B

3.4.2.3.1 Configuration du niveau nominal du signal d’entrée/sortie


Une fois le contrôle visuel achevé, vous pouvez commencer le test du matériel.
1. Charger le logiciel INTERFACE HOMME-MACHINE (IHM) sur le PC.
2. Activer la connexion du module LFS à tester (voir le manuel de l'Interface homme-
machine (IHM))
3. Sélectionner l’option "TEST". A partir de ce moment, le DSP génère deux tonalités
test sur les sorties PHONIE et TELEGRAPHE, respectivement à 800 Hz et 3180 Hz.
Le niveau de sortie est réglé par l’atténuateur de sortie. Tout niveau avant
l’atténuateur peut être considéré comme un niveau nominal.
4. Dans le menu TEST, sélectionner l’option "GENERATION DES TONALITES DE
TEST", puis choisir la fréquence de référence. Le DSP génère sur les sorties Ligne
HF et LIGNE-2 une tonalité de test avec la fréquence et le niveau nominal
sélectionnés. Les niveaux de sortie sont fixes.
5. Revenir au menu TEST, puis sélectionner l’option "MESURE DES NIVEAUX
D’ENTREE". La fenêtre suivante s’affiche.

MESURES UBBP/LFS - NIVEAUX D'ENTRÉE

LIGNE 1 TÉLÉGRAPHE

xxx.x xxx.x

NIVEAU NOMINAL:-20 dBm NIVEAU NOMINAL:-17 dBm

LIGNE 2 PHONIE

xxx.x xxx.x

NIVEAU NOMINAL:-20 dBm NIVEAU NOMINAL:-13 dBm


D0249FRa

FIGURE 29 – MESURES DES NIVEAUX D’ENTRÉES BF


Le tableau suivant décrit le niveau d’entrée et de sortie nominal pour les services BF. A
l’aide d’un voltmètre sélectif, contrôler le signal de sortie ; si les niveaux sont différents du
niveau nominal, régler l’atténuateur correspondant. Pour le signal d’entrée, au moyen du
générateur de signal, envoyer la tonalité test et vérifier sur le PC que le niveau affiché à
l’écran correspond à celui indiqué ; si les deux valeurs ne correspondent pas, régler
l’atténuateur correspondant. Voir le manuel de l'Interface homme-machine (IHM).

Signal Niveau nominal Fréquence de Point test en Point test en


BF dBm réf. en Hz entrée sortie
Phonie 4 fils Tx -3.5 800 4 fils_tx
Phonie 2 fils Tx 0 800 2 fils
Phonie 4 fils Rx -3.5 800 4 fils_rx
Phonie 2 fils Rx -7 800 2 fils
Télégraphe Tx -14 3180 Tg_tx
Télégraphe Rx -14 3180 Tg_rx
LIGNE 2 Tx -10 800 L2_tx
LIGNE 2 Rx -10 800 L2_rx

TABLEAU 27 – NIVEAUX DE RÉFÉRENCE DU MODULE LFS


Mise en service 1790B/FR CM/F11

PLC 1790/B Page 55/70

Points test entrée/sortie du module LFS, vue de face

Non
L2_RX 4W_TX TG1_TX TG2_TX TG3_TX E/M
utilisé

L2_TX 4W_RX ou TG1_RX TG2_RX TG3_RX


CÔTÉ UTIL.
CÔTÉ ÉQUIPEMENT 2W D0250FRa

FIGURE 30 – POINTS TEST DU MODULE LFS


PROCEDURE
Procéder de la manière suivante :
Signaux de sortie

Tonalités de sortie
Procédure
BF à contrôler
Phonie Rx 1) Régler le voltmètre sur une impédance d’entrée de 600 Ω et une
(4 fils et 2 fils) fréquence de 800 Hz.
2) Contrôler le niveau de sortie sur 4 fils_Rx.
Télégraphe Rx 1) Régler le voltmètre sur une impédance d’entrée de 600 Ω et une
fréquence de 3180 Hz.
2) Contrôler le niveau de sortie sur TG_Rx.
Sortie ligne 2 1) Régler le voltmètre sur une impédance d’entrée de 600 Ω et sur la
fréquence choisie avec le PC.
2) Contrôler le niveau de sortie sur L2_Tx.

Signaux d’entrée

Entrée BF
Procédure
mesures à contrôler
Phonie 4 fils Tx 1) Régler le générateur de signaux sur une impédance de sortie de 600 Ω,
800 Hz et le niveau nominal.
2) Transmettre le signal au point test 4 fils_Tx.
3) Lire le niveau mesuré sur le PC et le comparer au niveau de référence.
Phonie 2 fils Tx 1) Régler le générateur de signaux sur une impédance de sortie de 600 Ω,
800 Hz et le niveau nominal.
2) Transmettre le signal au point test 2 fils_Tx.
3) Lire le niveau mesuré sur le PC et comparer-le au niveau de référence.
Télégraphe Tx 1) Régler le générateur de signaux sur une impédance de sortie de 600 Ω,
3180 Hz et le niveau nominal.
2) Transmettre le signal au point de mesure TG_Tx.
3) Lire le niveau mesuré sur le PC et le comparer au niveau de référence.
Entrée ligne 2 1) Régler le générateur de signaux sur une impédance de sortie de 600 Ω,
800 Hz et le niveau nominal.
2) Transmettre le signal au point de mesure L2_Tx.
3) Lire le niveau mesuré sur le PC et le comparer au niveau de référence.

TABLEAU 28 – TEST MATÉRIEL ENTRÉE / SORTIE DU MODULE LFS


Une fois le test du service BF achevé, mettre le module LFS en ligne.
1790B/FR CM/F11 Mise en service

Page 56/70 PLC 1790/B

3.4.2.4 Niveau HF
Il n’existe que deux points test pour la section HF :
6. Point test Tx sur la carte MODAF :
Ce point test est situé avant l’amplificateur de puissance. Le voltmètre sélectif doit être
sur une impédance élevée.
7. Point test HF J4 sur la carte mère :
Ce point test est situé à la sortie HF, après l’amplificateur de puissance, le filtre de
transmission et le transformateur hybride (Line Hybrid). Le niveau mesuré à ce point
est atténué de 35 dB, le voltmètre sélectif doit être positionné sur 75 ohms.
8. Il n’existe pas de réglage matériel pour les niveaux HF. Leur réglage n’est possible
que par les outils logiciels inclus dans l'IHM. Savoir que l’opération influe sur tous les
signaux. Veuillez vous reporter à la section Interface Homme Machine (IHM),
paragraphe 6.
9. Répéter la procédure du tableau 28 et lire le point indiqué à l'aide du voltmètre
sélectif.
Le tableau suivant indique les niveaux de référence, à l'exception de l'atténuateur 7 dB
INAF/MODAF :

Interface HF -dBv- Sortie HF 75 Ω -dBm-


Niveau d'entrée (Point test Tx) (Point test J4)
nominal
Mono-voie Double-voie Mono-voie Double-voie
Signal dBm 10W 20W 40W 10W 20W 40W 10W 20W 40W 10W 20W 40W
Porteuse -14 -11 -11 -20 -17 -17 +22 +25 +28 +16 +19 +22
Phonie 4 fils -3.5 -6 -3 -3 -12 -9 -9 +30 +33 +36 +24 +27 +30
Phonie 2 fils 0 -6 -3 -3 -12 -9 -9 +30 +33 +36 +24 +27 +30
Ligne-2 -18 -6 -3 -3 -12 -9 -9 +30 +33 +36 +24 +27 +30
Télégraphe 1 -14 -12 -9 -9 -22 -15 -15 +20 +23 +26 +14 +17 +20
Télégraphe 2 -14 -12 -9 -9 -22 -15 -15 +20 +23 +26 +14 +17 +20
Signalisation FSK -12 -9 -9 -22 -15 -15 +20 +23 +26 +14 +17 +20
MTU 200 -10 -7 -7 -16 -13 -13 +26 +29 +32 +20 +23 +26
Bd
TABLEAU 29 – NIVEAUX DE RÉFÉRENCE HF
Les niveaux précédents sont corrects pour la sortie HF de l'équipement PLC avec la charge
fictive.
3.4.2.4.1 Niveau LIGNE 2
Selon la programmation LFS, la LIGNE-2 peut être considérée comme une sortie de la PLC,
fonctionnant sur la bande 0 ÷ 4 kHz.

Niveau d'entrée LIGNE-2 Tx -


nominal dBm-
Signal dBm
Phonie 4 fils -3.5 -18
Phonie 2 fils 0 -18
Télégraphe 1 -14 -28
Télégraphe 2 -14 -28
Signalisation FSK -28
TABLEAU 30 – NIVEAU D'ENTRÉE NOMINAL LIGNE-2
Mise en service 1790B/FR CM/F11

PLC 1790/B Page 57/70

3.4.2.5 Test en ligne


Une fois le test avec la charge fictive achevé, basculer la sortie de l'équipement PLC sur la
ligne HF.
10. Répéter l’opération de mesure du niveau HF (voir § 3.4.2.4/2).
11. Régler l’équilibrage de l'hybride HF en prenant comme référence la fréquence
porteuse.
3.5 Test de ligne point à point
3.5.1 Présentation
Le test à exécuter côté réception suppose la présence, à l’autre extrémité de la liaison, d’un
opérateur capable de transmettre la tonalité de test et d’activer la procédure d’égalisation
(pour cette opération, voir la section Interface Homme-Machine, §11 et §9).
Normalement, le test principal est exécuté sur deux signaux :

• Porteuse Rx

• Tonalité test équivalente d’un signal phonie nominal

• Égalisation de la bande BF
3.5.2 Signal reçu HF
Une fois l'équipement PLC en ligne, vérifier l’état des DEL.
Les DEL du module MODAF fournissent deux types d’indications :

• Alarme équipement

• Alarme ligne
1790B/FR CM/F11 Mise en service

Page 58/70 PLC 1790/B

Indications sur la porteuse Rx

DEL ETAT DESCRIPTION REMARQUE


5 dB 5 dB 5 dB PORTEUSE Rx
PLC-1 ALLUME NIVEAU 5 dB inférieur au niveau
PORTEUSE Rx nominal ou pas de
RX
FAIBLE réception
TX
ETEINT NIVEAU Rx OK Porteuse reçue
PLC-2
Rx Rx RAPPORT SIGNAL /
OVF LF0 BRUIT
OVF LF1 ALLUME ALARME Signal trop faible ou
SIGNAL/BRUIT bruit trop important à
ACTIVE l’entrée HF de
l'équipement CPL.
RX
ETEINT PARAMETRES Rx Niveaux OK
OK
Rx –5dB
ALLUME NIVEAU 5 dB inférieur au niveau
PORTEUSE Rx nominal ou pas de
FAIBLE réception
ETEINT NIVEAU Rx OK Porteuse reçue

Rx +5dB
ALLUME NIVEAU 5 dB au dessus du
PORTEUSE Rx niveau nominal
FAIBLE
TX ETEINT NIVEAU Rx OK Porteuse reçue

OVF A/D
OVF A/D Rx
RX
ALLUME NIVEAU D'ENTRÉE (PLC en PARALLELE
RX +5dB EN SURCHARGE ou MAUVAISE
RX -5dB ADAPTATION LIGNE
LF
HF)
SQUELCH
ETEINT NIVEAU D'ENTRÉE
DSP OK OK
LOOP SQUELCH
DSP KO BF
ALLUME SERVICE BF N'importe quelle alarme
D0251ENa BLOQUÉ programmée par IHM
Figure 31 – DEL
MODAF

TABLEAU 31 –DEL DU MODULE MODAF EN LIGNE


Si les deux DEL sont éteintes, la porteuse de réception est reçue et le CAG fonctionne
correctement.
Après avoir vérifié que ces conditions sont remplies, procéder au contrôle du niveau de
réception.
Mise en service 1790B/FR CM/F11

PLC 1790/B Page 59/70

Contrôle du niveau Rx
Sur l'équipement PLC 1790, seuls deux points de test sont disponibles pour tester le niveau
reçu. Sur le circuit de réception, avant le filtre Rx, un atténuateur variable peut être configuré
de la manière suivante :

Puissance HF de Atténuateur Remarque


l'équipement PLC
mono-voie 10 W 6 dB Si l’affaiblissement de la ligne HF
double-voie 10/20/40 W est très faible, l’opérateur peut
décider d’inclure d’autres
mono-voie 20 W 9
atténuateurs ; mais il ne doit jamais
mono-voie 40 W 12 descendre en deçà du niveau
indiqué.

TABLEAU 32 – ATTÉNUATEUR D’ENTRÉE RX


L’affaiblissement maximal est de 18 dB.
Point test Rx
Le premier point test est situé sur l'interface de ligne Rx et entre le transformateur hybride
HF et l’atténuateur de ligne réception (Rx). Le voltmètre sélectif doit être sur une impédance
élevée.
Le niveau indiqué à ce point est inférieur de 12 dB au niveau reçu à l’entrée HF.
Le second point test se trouve sur la carte MODAF et est appelé "Rx".
Ce point est placé après l'étage CAG (Contrôle Automatique de Gain). Le niveau indiqué en
ce point doit correspondre au niveau nominal.
Aucun réglage n’est possible.
Pour vérifier le point de fonctionnement du CAG, veuillez vous reporter à la section Interface
homme-machine (IHM), paragraphe 10 "MESURE EN LIGNE".
Après avoir vérifié que le niveau du signal est correct après le CAG, procéder à l’égalisation
de la bande BF.
3.6 Égalisation de la bande BF
L’équipement PLC 1790 comprend une fonction d'égalisation de la bande BF. Deux
opérateurs sont nécessaires en cas d'absence de la carte INSU. Le logiciel IHM (voir la
section Interface homme-machine § 9) permet de générer huit tonalités test et de les
envoyer à l'équipement PLC opposé. L’opérateur distant, en choisissant les commandes
NEW EQUALISER (NOUVEL EGALISEUR) et Self-Training Equalisation (Égalisation
automatique), qui peut égaliser automatiquement les fréquences reçues du poste distant.
Une fenêtre affichera un graphique à barres représentant les 8 tonalités test pour l’opérateur
avant et après l’égalisation. Si la qualité des fréquences égalisées est suffisante, l’opérateur
peut activer la courbe d’égalisation en cliquant sur la commande "ACTIVER".
L’opérateur a la possibilité d’enregistrer l’égalisation affichée à l’écran via une boîte de
dialogue de fichier Windows standard.
Il peut ensuite dessiner une courbe d’égalisation manuellement en choisissant pour chaque
tonalité test une valeur d’affaiblissement comprise entre -6 et +6 dB.
Chaque courbe d’égalisation peut être enregistrée dans un fichier et imprimée à l’aide des
commandes décrites dans la section Interface homme-machine (IHM).
Afin d’évaluer la qualité de la transmission, l’opérateur peut contrôler la connexion avec
l'équipement PLC opposé en mesurant la fidélité de la liaison avec ou sans EGALISEUR.
1790B/FR CM/F11 Mise en service

Page 60/70 PLC 1790/B

3.7 Signal BF reçu


Une fois le test HF terminé, l’opérateur peut vérifier le niveau de sortie sur la bande BF.
L’opérateur à l’autre extrémité transmet les tonalités test, comme indiqué dans la section
consacrée à la transmission. Sur l'équipement PLC récepteur, l’autre opérateur vérifie le
niveau de sortie.
3.8 Indications des DEL
Voir précédemment.
3.9 Vérification BF point à point
3.9.1 Réponse de la ligne
Une fois le test de l'équipement PLC achevé, les opérateurs présents à chaque extrémité de
la liaison peuvent vérifier la réponse point à point de la liaison PLC.

• Phonie largeur de bande 300 ÷ 2000


Un signal de -3.5 dBm sera transmis à partir d'une extrémité sur l’entrée Phonie 4 fils.
Vérifier à la sortie correspondante de l’autre équipement que le niveau relatif n’excède pas
les limites indiquées ci-après.

• LIGNE-2 largeur de bande 300 ÷ 3720


Un signal de -18 dBm sera transmis à partir d’une extrémité sur l’entrée LIGNE-2.
Vérifier à la sortie correspondante de l’autre équipement que le niveau relatif n’excède pas
les limites indiquées ci-après.

• Télégraphe largeur de bande 2160 ÷ 3480


Un signal de -14 dBm sera transmis à partir d'une extrémité sur l’entrée Télégraphe.
Vérifier à la sortie correspondante de l’autre équipement que le niveau relatif n’excède pas
les limites indiquées ci-après.
Mise en service 1790B/FR CM/F11

PLC 1790/B Page 61/70

Équivalents PHONIE

3 dB

2 dB

1 dB

0.4 dB

0 dB

-0.4 dB
eq_s_170.vsd

0 300 400 800 1200 1500 1700 Hz


D0252XXa

FIGURE 32 – ÉQUIVALENT SIGNAL VOCAL 300 ÷2000 HZ

3 dB

2 dB
1.75 dB

1 dB
0.87 dB

0 dB

eq_t_216.vsd

-0.87 dB

2160 2220 3180 3420 3480 Hz


D0253XXa

FIGURE 33 – ÉQUIVALENT TÉLÉGRAPHE 2160 ÷3480 HZ


Les autres courbes de réponse BF se trouvent dans l’ANNEXE A.
1790B/FR CM/F11 Mise en service

Page 62/70 PLC 1790/B

3.9.2 Vérification de la signalisation


Activer le commutateur sur le panneau avant du module LFS et appuyer sur le bouton
d’appel téléphonique du service distant (C.Tx) afin de passer un appel à l’équipement PLC
opposé.
Sur l’équipement PLC opposé, vérifiez que la DEL-6 (C.Rx) est allumée et que l’avertisseur
sonore est activé pendant l’appel entrant.
Entrer une polarité de masse sur l’entrée signalisation du fil "M" (broche 9 du connecteur du
module LFS) et vérifier le fil de masse sur le poste distant (broche 10 du connecteur du
module LFS).
3.9.3 Critères de commutation automatique 2/4 fils
Afin de vérifier les fils de commutation automatique 2/4 fils, contrôler le mode phonie 2 ou 4
fils (Interface Homme-Machine, §8.3.2) et envoyer depuis l'équipement PLC opposé une
fréquence phonie avec un niveau nominal relatif (0 dBm 2 fils, -3.5 dBm 4 fils).
Sur l’équipement PLC local, raccorder un voltmètre sélectif, réglé sur la fréquence émise et
d’impédance d’entrée 600 ohm, aux broches 2 et 3 du connecteur du module LFS et vérifier
le niveau nominal.
Raccorder un fil de masse à la broche 25 du connecteur du module LFS et vérifier que le
niveau change de 3.5 dB par rapport au précédent.
3.9.4 Vérification des alarmes et des DEL
Après avoir effectué les précédents tests, l’équipement PLC étant en ligne, procéder au
contrôle des alarmes et des DEL.
Dans le programme Interface Homme-Machine (IHM), accéder à la fenêtre d’évaluation de la
carte MODAF ("Interface homme-machine" §10) et vérifier le niveau du CAG, le niveau de
bruit et les 12 indicateurs d’alarme (dans les mesures en ligne) ("ON LINE
MEASUREMENT").
La mesure en ligne du CAG doit détecter un gain CAG proche de 0. Pour cela, l’opérateur
peut modifier l’atténuateur de ligne HF supplémentaire situé sur la carte INRX.
Tous les indicateurs d’alarme doivent être affichés en vert.
L’opérateur a la possibilité de surveiller les mesures et les indicateurs d’alarme ; il peut
également les enregistrer à intervalles fixes (allant de 1" à 120') ou à chaque fois que la
position du contrôle automatique de gain (CAG), le niveau de bruit ou l’état des alarmes
changent. Les paramètres peuvent être enregistrés dans un fichier sur disque.
Mise en service 1790B/FR CM/F11

PLC 1790/B Page 63/70

Vérification des DEL


Pendant que l'équipement PLC est en ligne, vérifiez l’état des DEL situées sur le panneau
avant des cartes.

UNITE COULEUR ETAT


LFS Verte Verte o o
Verte Rouge ALLUMÉ ETEINT
Verte Jaune n ETEINT
MODAF 5 dB Rouge ETEINT
PLC1 Rouge p
Rx Rouge ETEINT
Tx Rouge ETEINT
PLC2 Rouge p
OVF LF0 Rouge ETEINT
OVF LF1 Rouge ETEINT
OVF A/D Rx Rouge ETEINT
–5 dB Rx Rouge ETEINT
+5 dB Rx Rouge ETEINT
SQUELCH Rouge ETEINT
BF n
Verte
DSP OK ETEINT
Jaune
BOUCLE ETEINT
Rouge
DSP non OK

TABLEAU 33 –DEL DU CPL (INACTIF)


o = Selon la programmation du modem
n = Clignotement rapide
p = Selon la programmation logicielle
1790B/FR CM/F11 Mise en service

Page 64/70 PLC 1790/B

Vérification des alarmes


Vérifier les contacts inverseurs des relais présentés sur la figure suivante avec un état
inactif.

13
25 MASSE
ALARME PLC COM
BOUCLE ACTIVE COM.
ALARME "OU" ALARME PLC N.O.
BOUCLE ACTIVE N.O. LOCAL
DE LA PLC &
ALARME PLC N.F.
BOUCLE ACTIVE N.F. DISTANT
5dB ALARME COM
PERTE ALARME S/B COM.
PORTEUSE Rx 5dB ALARME N.O. ALARME
ALARME S/B N.O.
NIVEAU 5dB 20 S/B
5dB ALARME N.F. ALARME S/B N.F. V.0/1
7
ALARME Tx COM ALARME SIGN. V.1 COM.
ÉCHEC
PORTEUSE Tx ALARME Tx N.O. ALARME SIGN. V.1 N.O. ALARME
ALARME Tx N.F. V.1
ALARME SIGN. V.1 N.F.
ALARME PWS COM
ALARME SIGN. V.0 COM
ALARMES ALARME PWS N.O.
ALIM. ALARME SIGN. V.0 N.O. ALARME
ALARME PWS N.F. V.0
14 ALARME SIGN. V.0 N.F.
1

D0262FRa

FIGURE 34 – CONNECTEUR DES ALARMES M8


Contrôler l’alarme signalisation du module LFS due à une baisse du niveau de -5 dB.
Connecter aux broches 13 et 7 du connecteur du module LFS un fil de suppression Tx BF
+24 Vcc et vérifier que les contacts inverseurs du relais (broches 20-21-22) du connecteur
M2 (LFS 0) et du connecteur M3 (LFS 1), le cas échéant, changent de position.
Contrôler également le contact relié à la terre (broche 11) du connecteur M2 (LFS 0) et du
connecteur M3 (LFS 1), le cas échéant.
Déconnecter les fils + 24Vcc et vérifier que les contacts du relais repassent à l’état inactif.

25lf_b.vsd

+
13
SUPPRESSION SERVICES BF "RX" - 25
INVERSION PHONIE 2/4 FILS
EXCLUSION COMPANSEUR
+
CRBLC1
SUPPRESSION SERVICES BF "TX"
ALARME BF -
CRBLC2
SC2A N.F.
M (TRON)
SC2C Commun ALARMES BF
SIGNALISATION
E (RON)
SC2B N.O.
20
7
LIGNE-2 RX Entrée
Entrée Phonie 4Fils Em.

Sortie Phonie 4Fils Rec.


ou Phonie. 2Fils LIGNE-2 TX Sortie

14
1

M2  BF - 0
M3  BF - 1 D0209FRa

FIGURE 35 – CONNECTEUR DU MODULE LFS M2 - LF0 OU M1 - LF1


Une fois le test de mise en route achevé, raccorder les connecteurs aux services clients, puis
remplir le rapport de mise en service. L’équipement PLC 1790 est maintenant prêt à fonctionner.
Mise en service 1790B/FR CM/F11

PLC 1790/B Page 65/70

4. ANNEXE
4.1 Voie phonie

3 dB

2 dB

1 dB

0.4 dB

0 dB

-0.4 dB
eq_s_170.vsd

0 300 400 800 1200 1500 1700 Hz


D0252XXa

FIGURE 36 – SIGNAL VOCAL 300 ÷1700 HZ

3 dB

2 dB

1 dB

0.4 dB

0 dB

-0.4 dB
eq_s_200.vsd

0 300 400 800 1600 1800 2000 Hz


D0254XXa

FIGURE 37 – SIGNAL VOCAL 300 ÷2000 HZ


1790B/FR CM/F11 Mise en service

Page 66/70 PLC 1790/B

3 dB

2 dB

1 dB

0.4 dB

0 dB

-0.4 dB
eq_s_220.vsd

0 300 400 800 1400 1800 2200 Hz


D0255XXa

FIGURE 38 – SIGNAL VOCAL 300 ÷2200 HZ

3 dB

2 dB

1 dB

0.4 dB

0 dB

-0.4 dB
eq_s_240.vsd

0 300 400 800 1600 2000 2400 Hz


D0256XXa

FIGURE 39 – SIGNAL VOCAL 300 ÷2400 HZ


Mise en service 1790B/FR CM/F11

PLC 1790/B Page 67/70

3 dB

2 dB

1 dB

0.4 dB

0 dB

-0.4 dB
eq_s_340.vsd

0 300 400 800 2400 3000 3400 Hz


D0257XXa

FIGURE 40 – SIGNAL VOCAL 300 ÷3400 HZ


1790B/FR CM/F11 Mise en service

Page 68/70 PLC 1790/B

4.2 Voies télégraphiques

3 dB

2 dB
1.75 dB

1 dB
0.87 dB

0 dB

eq_t_216.vsd

-0.87 dB

2160 2220 3180 3420 3480 Hz


D0258XXa

FIGURE 41 – VOIE TÉLÉGRAPHIQUE 2160 ÷3480 HZ

3 dB

2 dB
1.75 dB

1 dB
0.87 dB

0 dB

eq_t_228.vsd

-0.87 dB

2300 2340 3180 3420 3480 Hz


D0259XXa

FIGURE 42 – VOIE TÉLÉGRAPHIQUE 2300 ÷3480 HZ


Mise en service 1790B/FR CM/F11

PLC 1790/B Page 69/70

3 dB

2 dB
1.75 dB

1 dB

0.5 dB

0 dB

eq_t_240.vsd
-0.5 dB

2400 2460 3180 3600 3720 Hz


D0260XXa

FIGURE 43 – VOIE TÉLÉGRAPHIQUE 2400 ÷3720 HZ

3 dB

2 dB
1.75 dB

1 dB

0.5 dB

0 dB

eq_t_264.vsd
-0.5 dB

2640 2700 3180 3600 3720 Hz


D0261XXa

FIGURE 44 – VOIE TÉLÉGRAPHIQUE 2640 ÷3720 HZ


1790B/FR CM/F11 Mise en service