Вы находитесь на странице: 1из 7

Substation Ground Grid Analysis Using Commercial Software – A Case Study

James K. Niemira, P.E.


S&C Electric Company
6601 North Ridge Boulevard
Chicago, Illinois 60626
773-338-1000, Fax 773-338-4254
jniemira@sandc.com

touch voltages to new (lower) tolerable levels;


Abstract elimination of some ground rods could be
Ground resistance, ground fault current, and allowed by addition of more grid wires. Several
potential gradients all play a role in assuring that alternative designs were proposed with selection
step and touch potentials in substations will not from among the alternatives to be based on
exceed acceptable levels. This presentation will construction considerations.
discuss the safety considerations in substation
ground grid design and will present an example Reason for Ground Grid
of a substation ground grid design using The ground grid serves to provide an
commercially available analysis software. Use adequate path to convey ground fault current to
of the computer model facilitates iterative ground, limits the ground potential rise during a
modifications of the ground grid design to fault, and controls the surface potential gradient
assure effectiveness of the grid design while to limit touch and step potentials to safe values
reducing cost. during fault conditions.
Fault Current, Ground Resistance, and
Introduction Ground Potential Rise
Installation of a 69 kV switching substation The ground potential rise (GPR) is the
at an industrial plant required design and maximum voltage the ground grid may assume
analysis of a ground grid for the station to with respect to remote earth. This voltage is
assure safety of operating personnel. The open- determined by the ground resistance and the grid
air switchyard included 15 circuit breakers rated current (the fraction of the ground fault current
2000 A arranged as 5 breaker-and-a-half that flows from the grid to earth). A multiplying
schemes for 10 sets of cables. Two main busses factor is applied to the symmetrical grid current
were included, each rated 4000 A. The initial to account for the effect of the dc offset that can
ground grid design was laid out based on the occur. This decrement factor depends on the
placement of the circuit breakers and buswork. fault circuit X/R ratio and the fault clearing
The soil was modeled as a two layer composite. time. An additional multiplying factor may be
Analysis of the initial grid indicated deficient applied to the fault current to allow for future
areas where step and touch potentials were growth of the power system.
above allowable levels. These areas were Safety Concerns – Body Current
addressed by adding ground rods to reduce the Physiological effects caused by electric
Ground Potential Rise and by including a layer current flow through the human body is the
of crushed rock on the surface of the ground. basic concern. Effects range from perception of
The computer program used, CYMGRD for the current as a slight tingling sensation to
Windows, allowed the modifications to be made impairment of breathing, ventricular fibrulation,
and the analysis to proceed with each iterative and death. The threshold of perception is
step. Different design trade-offs were generally taken as approximately 1 mA.
investigated: use of a thinner layer of crushed Currents in the range of 1 to 6 mA are termed
rock could be accommodated by addition of grid “let-go currents”; these may be unpleasant, but
wires and ground rods to further reduce step and generally the person can still control the
muscles and release an energized component. between one foot and another, the distance
Higher currents in the range of 9 to 25 mA may between the feet being 1 meter. Touch voltage
be painful, may impair voluntary muscular is the voltage between the hand and feet or one
response preventing release of a grasped object, hand to the other; for the substation grounding
and may temporarily impair breathing; at this problem, touch voltage is taken as the difference
current range, these effects are not permanent between the surface voltage (where the feet
and cease when the current is interrupted. As would be) and the grid voltage (to which
current approaches 60 to 100 mA, ventricular equipment will be bonded). Since a person may
fibrillation can occur, heart may stop beating, or be standing anywhere within a mesh and could
breathing may be stopped. Actual current that touch the metal frame of a piece of equipment
may cause these problems will depend on the connected to the grid, the mesh voltage is
individual involved, and the duration of the defined as the maximum touch potential within
current. Statistically, the current that can be a mesh of the ground grid. This is usually the
safely tolerated (that is, without ventricular worst case touch voltage in a conventional
fibrillation) by 99.5% of the human population substation, however, the possibility of metal-to-
is related to body mass. Body mass can usually metal contact hand-to-hand or hand-to-feet
safely be assumed to be at least 70 kg for areas should be investigated where such conditions
not accessible to the general public, such as may occur as in gas-insulated substation, for
fenced switchyards; outside the fence, a 50 kg example. Transferred potential is a special case
assumption may be appropriate, depending on of touch potential where a voltage from a remote
particular circumstances. location is brought into the substation, or the
Maintain voltages to tolerable levels. GPR of the substation is transferred to some
The IEEE Standard 80 [1] derives equations remote location. For example, pipes, static
for maximum permissible step and touch wires, neutral wires, railroad rails, or
voltages based on conservative estimates of communications circuits may be grounded at
contact resistance between the feet and ground, some remote location or, if connected to the
length of stride, and permissible current through station ground grid, can create a transfer
the body to avoid ventricular fibrillation. The potential hazard at a remote location. Special
equations so derived include the insulating precautions to isolate or neutralize this sort of
effects of a layer of crushed rock. Note that it is hazard are often required.
the body current that is the safety hazard and
not the voltage per se. The amount of current Soil Resistivity
flow for a given voltage will depend on the Soil resistivity obviously has an important
impedance and, more specifically, the effect on the ground resistance and GPR. Soil
resistance. The human body itself has some resistivity varies with type of soil, moisture
resistance, there is contact resistance between content, and temperature, so variation with
the feet and the ground, and there may be some seasons of the year are to be expected in most
intentionally introduced resistance such as the locations. The soil may be modeled as uniform
layer of crushed stone. The resistance of each resistivity, ignoring variation of resistivity with
of these will also vary depending on the depth. Typically, the soil is comprised of
particular situation as well. For example, dry several layers, each having a different
skin may present a fairly high contact resistance, resistivity. Thus, a more accurate model can be
but if the skin is wet, sweaty, or broken a much achieved by assuming a two-layer soil model.
lower resistance is presented. The layer of
crushed stone will also likely have a lower Computer Program Features
resistance when it is wet as compared to dry, so The CYMGRD program includes many
the worst cases should be considered. Thus, in features that simplify the analysis of a ground
some situations, 1500 volts or more may be grid.
tolerable while in others 400 volts or even less
may be too high. Step voltage is the voltage
An analysis routine to match a two-layer IF
soil model to measured resistivity data is
included. Values of soil apparent resistivity
measured using the Wenner technique can be
entered along with the probe spacing used to
make each measurement, and the program
calculates a best fit model determining the
resistivity of each of the two layers and the Primary Return
thickness of the top layer (the lower layer
extends to infinite depth). Alternatively, if the
parameters for the two-layer soil model are
Figure 1: Primary and Return Electrodes.
known from previous analysis, the resistivity of
each layer and the thickness of the upper layer simple as a single ground rod. Distinct
can be entered directly. electrodes can also be included. Distinct
Safety assessment calculations are also electrodes are conductive structures such as
included. Based on the soil model and surface pipelines or cable sheaths that are near the
covering (rock layer) thickness, body weight, ground grid but not connected to the power
and shock duration, the program will calculate system. It is also possible to include a
permissible step and touch potentials using the resistance in parallel with the primary electrode
equations from IEEE 80-1986. Data is to account for current conveyed back to the
automatically transferred between the soil source via other remote parallel paths, such as
model, the safety assessment, and the grid overhead ground wires and counterpoises.
analysis routines.
Analysis of the ground grid is accomplished Initial Design of the Grid
using a finite element technique. Conductors, Available line to ground short-circuit
ground rods and grid wires, are divided into current had been determined to be 40 kA with
smaller segments called “elements.” Current is 24 kA returning to the source via the ground
diffused from the elements into the surrounding grid. Fault clearing time was 0.25 seconds
ground and the resulting voltages at the surface maximum. Customer standards required the
of the soil are calculated. Increasing the number grid to be buried 0.5 meter below the soil
of elements can give greater accuracy in the surface and to extend 1.5 meter outside the
solution, but the program is limited to 1500 total fence line. Local conditions indicated that the
elements [2]. Usually, good accuracy is soil could be modeled appropriately using a
obtained when the element size is equal to the 2-layer model, using soil resistivity of 200 •m
length between junctions of the grid wires, and for the top 5-ft layer and 100 •m below 5 ft.
further increase of the number of elements does The initial design of the grid was determined by
not significantly affect accuracy [3,4]. equipment layout and was based on experience
Electrodes can be one of three types: primary,
with other substations of similar type. It was
return, or distinct. The ground grid being
desired to avoid use of layer of crushed rock, if
analyzed is comprised of primary electrodes; requirements could be met without it, and to
any metal objects directly bonded to the grid,
minimize the number of ground rods.
such as fence posts, would also be part of the The substation enclosed area was 208 ft by
primary electrode system. Return electrodes 184 ft. The initial model included 11 grid wires
convey the current from the ground back to the running North-South and 10 running East-West
power system. If the return is nearby, the (see Figure 2). This grid indicated a GPR of
surface gradients at the station under study may approximately 22,200 volts and touch potentials
be influenced. For example, if the source for on the order of 6500 volts. Because there was
the ground fault is another nearby substation, no layer of crushed rock included, allowable
the source-substation grid is the return electrode touch potential was relatively low, about
– see Figure 1. Return electrodes may be as
410 volts. The addition of a
layer of crushed rock does
not significantly affect the
surface potentials or gradient,
but the high resistance of the
rock layer greatly increases
the allowable step and touch
potentials. Also, the addition
of ground rods, especially
when they penetrate the
lower resistance soil layers,
helps to limit the ground
resistance and resulting
ground potential rise.
Addition of Ground
Rods. The next step in the
design of the of the grid was
the location of ground rods.
Perimeter rods are most
effective in uniform soil; Figure 2: Initial grid design, without ground rods.
rods on the interior plane are
shielded somewhat by the perimeter rods and tolerated for a given current flow through the
thus are less effective. In the case of stratified body. A 9-inch layer of rock was modeled, with
soil, as in the present example, ground rods an assumed minimum resistivity of 3000 •m.
penetrating the lower, less-resistive soil layers A contour plot showing touch potentials of one
for a significant depth are most effective [5]. corner of the grid is shown in Figure 3. It is
Best performance of the deep rods is obtained seen that the touch voltage does not exceed the
by distributing the rods, again to avoid a increased tolerable voltage level except at the
shielding effect between the rods. Initially, rods perimeter of the grid.
were dispersed throughout the plane of the grid. Additional details were then included in the
The rods were 10 ft long, and thus penetrated model. Fence posts near the perimeter of the
the basement, lower resistance, soil layer for grid will act as auxiliary ground rods. These
half of their length. This configuration was also were included by modeling as 2.5-inch diameter
analyzed and was again found lacking. Ground ground rods driven 3-feet deep and spaced
resistance and GPR were reduced approximately roughly every 20-feet along the perimeter.
7 % compared to the base case with no ground Additional primary ground rods along the
rods, and maximum touch voltage was reduced perimeter were still needed to further decrease
about 22 %. Increasing the length of the ground the touch voltage along the fence line. These,
rods was the next step. Increasing rod length to too, were added and the resulting grid was seen
30 ft decreased the GPR by an additional 15 % to meet the safety requirements. A surface
and decreased the maximum touch voltage by potential plot of this solution to the design
44 % compared to the 10 ft rods. Although this problem is shown in Figure 4. Particular
was much improved, the touch voltage was still attention should be paid to areas where hazards
too high by a factor of more than 6. are more likely. For example, it is very likely
Recognizing that it is sometimes easier to that people will be walking and touching the
raise the bridge rather than lower the water, a fence in the area of the gates. Special
layer of rock was added to the model. The rock consideration should be given as to whether
layer does not significantly affect the surface increased grid density may be desirable in such
voltages, but does add a high resistance in series areas.
with the feet, allowing higher voltages to be
The color contour
plotting feature of the
computer program quickly
identified areas of the
modified grid in need of
attention. Grid wires or
ground rods could be added
to areas having excessive
touch voltages. Conversely,
ground rods could be
eliminated from areas
identified as having voltages
lower than the maximum
tolerable levels.
A final design option to
eliminate some of the ground
rods was also analyzed. By
adding N-S and E-W grid
wires, ground rods within the
Figure 3. Touch potential contour plot. plane of the grid could be
eliminated while still
Having completed a workable design, it was maintaining voltages within tolerable limits.
then desired to explore other possible trade-offs The resulting grid and equipotentials are shown
in the design solution. For example, a thinner in Figure 7a and 7b. “What-if” analysis was
layer of crushed rock (4 inches)
was desired. As expected, the
surface voltage distribution is
not affected by the change in
thickness of this layer, but the
maximum tolerable voltage is
reduced. With this lower
tolerable threshold, the
maximum limit was exceeded
in the area of the fence line.
The thinner layer of rock
covering could be used if
additional grid wires were
added near the fence line and at
the aprons in front of the
entrance gates to control the
touch voltages to the resulting
lower tolerable limit. Voltage
profiles, showing step and
touch voltages along a diagonal
of the grid both before and after
addition of perimeter grid wires
along the fence line are shown
in Figure 5a and 5b. The
modified grid is shown in
Figure 6. Figure 4: Touch voltage 3-D contour plot of first design solution.
(a)

(b)
Figure 5. Voltage profiles across grid diagonal with 4-inch rock covering, (a) before and (b)
after addition of grid wires near the fence line.
further simplified by the ability to “turn off” the data file; the elements can later be “turned
selected grid wires and ground rods. This on” for subsequent analyses, if desired.
feature allows eliminating the selected elements
from the analysis without deleting them from
and Systems, vol. PAS-103, No. 3, pp. 631-639,
March 1984.
[4] R.J. Heppe, “Computation of Potental at
Surface Above an Energized Grid or Other
Electrode, Allowing for Non-Uniform current
Distribution,” IEEE Transactions on Power
Apparatus and Systems, vol. PAS-98, No. 6,
pp. 1978-1989, Nov/Dec 1979.
[5] H. Lee, et al., “Efficient Ground Grid
Designs in Layered Soils,” IEEE Transactions
on Power Delivery, vol. 13, No. 3, pp. 745-751,
July 1998.

Figure 6: Modified grid for voltage profile of


5b.

Conclusion
As with any design problem, there are
many different alternative solutions that
can achieve a safe substation ground grid
design. Ground rods may be eliminated at
the expense of adding more grid wires.
Higher voltages may be tolerated by
adding a relatively high resistance layer of
crushed stone. Trade-off between the
various options are most often made as a
result of non-technical requirements such
as cost of materials, cost of labor, and ease
of construction. Use of the CYMGRD
computer program allows for rapid (a)
analysis of various design alternatives to
choose an economical solution for any
particular installation.

References
[1] ANSI/IEEE Standard 80-1986, IEEE
Guide for Safety in AC Substation
Grounding, IEEE Inc., New York, 1986.
[2] CYMGRD for Windows User’s Guide
and Reference Manual, CYME
International Inc., Quebec, Canada, March
1998
[3] K.A. Ewey, H.A. Smolleck, “A
Graphical Explanation of the Resistance
and Surface-Potential Calculation for
Grounding Systems in Two-Layer Earth,” (b)
IEEE Transactions on Power Apparatus Figure 7: (a) Alternative ground grid. (b) Equipotentials in
corner area.

Вам также может понравиться