CEDD 3, Phase-IIIContract CE 10 Condenser Water Pumps at all Data Sheet


and CE-11 Stations

DATA SHEET FOR CONDENSER WATER PUMP

Type Horizontal Split Casing Condenser water pump

ISO : 9906
Reference Code / Standards
IS :1520
IS : 9137 & 10596
Tag No To Be Marked On Pump With Black Letter.
Tag No
SS Tag To Be Firmly Attached
Total Number As per BOQ
Service Continuous Duty
Capacity LPS 78.6 As per BOQ
Operating Head KPa 216 As per BOQ
Noise Criteria 85 dbA at 1 mtr. Distance
Acoustic Treatment As required to achieve the above
Number Of Stages Single Stage

Impeller
Material Bronze
Casing Material Cast Iron ASTM AI59 43000
Balancing Statically & Dynamically Balanced
Neck Ring Bronze
Lock Nut Bronze(ASTM A276 Type)
Logging Ring Brass
Pump Speed (nominal) 1450 RPM (Maximum)

Shaft
Seal Mechanical Type,
Bearing Drive End Roller Bearing/Ball Bearing
Bearing Non – Drive End Ball Bearing
Material EN-8 / High Tensile SS
Sleeve Renewable Sleeve
Mounting Shaft Key And Positive Locking Device
Packing Graphited Cotton
Stuffing Box Cast Iron / Mild Steel

Page 1 of 2
Delhi Metro Contract Mott MacDonaldCommon for all ECS
CEDD 3, Phase-IIIContract CE 10 Condenser Water Pumps at all Data Sheet
and CE-11 Stations

Connection
Suction Flange Type Horizontal
Discharge Flange Type Vertical
Flange Drilled To BS Standard, Suitable for ANSI 125
Flexible Yes – On Both Suction And Discharge Ends
Drive Arrangement Direct – With Flexible Coupling And Coupling Guard
Direction Of Rotation Anti Clock Wise / Clock Wise From Driving End

Motor
Type TEFC Induction Motor ( IP – 55 ), EFF-1
Design As Per IEC 34 – 1, IEC 72 – 1, BS – 4999
RPM 1440 (Max)
Power Supply Three Phase, 415 V, 50 Hz, AC Power Supply
Vibration Isolation Inertia Base, Spring Isolation
Mounting Arrangement Suitable Base Frame For Floor Mounting
Lifting Arrangement Lifting Eye At Suitable Location And Number
Paint Epoxy Paint, After Surface Treatment For Corrosion

Notes
1. Pumps shall be provided with common base frame, vibration isolation pads, suction & discharge
pressure gauges with isolation valves, test and / or air vent cocks, gland drain & other accessories
as required.
2. Pumps starters shall be star delta air break type
3. Pump head given is approximate and vendor shall do their own calculations and offer the pumps
accordingly.
4. Pump motor shall be EFF-1, non-overloaded up to the run out conditions riding over complete
curve.