2. Type designation
N J R 2-□ □
D: control unit
Soft-starter
AC motors
Company code
3. Technical data
NJR2-D series soft-starter requires external bypass 3.11 Environmental conditions: When the altitude is more
contactorwith voltage range of 380V, power than 1000m, used at reduced capacity, current is reduced
specifications for 7.5KW to 500KW; has characteristics by 0.5% for each additional 100m above 1000m;
of good load adaptability,stable and reliable operation,
3.12 When ambient temperature is between (-10 ~ 40) ℃,
and widely used in electrical drive equipment in the
current is reduced by 2% for each 1℃ more than 40 ℃;
fields of metallurgy, petroleum,fire, mining, water supply,
municipal, food, cement and petrochemical. It is an ideal 3.13 Relative humidity less than 95% (20 ~ 65) ℃;
updated product of traditionalstar - delta starter, and 3.14 No condensation, no flammable gas, no conductive
self-coupling voltage starting. dust, well ventilated.
4. Wiring diagram
KM1
W1
T
W
QF
CT
V1
Three-phase M
S
380V AC
Power
V
CT
U1
R
CT
Run RUN
Fault relay output
NJR2-D K3
Stop STOP
X1 spare
X2 Spare terminals
X1 Spare terminals
STOP Stopping terminal Can realize “two wire”and “three wire”control with COM
RUN Running terminal Can realize “two wire”and “three wire”control with COM
Fault relay output, normally open When there is a fault, the relay picks up
K3
Contact capacity (5A/250VAC) (0.2s pick-up time during power-up instant).
Programmable relay outputs, normally open The relay function can be defined programmatically,
K2
Contact capacity (5A/250VAC) when effective, the relay picks up.
5. Features
① ②
Removable
Patented
all-aluminum
F
Keyboard design
5.4 Removable keyboard,easy to operate outside remote 5.5 all-aluminum design patent (75kW and below) gives
operation control.(see ①) better heat dissipation, natural air cooling, and saves
space (see ②)
③ ④
RS485
Data display
communication
and memor y
function
5.6 RS485 communication function (requiring extended 5.7 Display of operating voltage and current; fault
RS485 communication module), facilitating networked description code display and memory function (see ④)
control and automation engineered; providing three 5.8 Unique master-slave linkage soft starting function,
relay outputs: operation, ramp-top and failure for beneficial to production process control.
external linkage control. (See ③)
P-035 Inverter & Soft-Starter Soft-Starter
72
118.2
115
18
69
NJR2-7.5D~45D
145
R3.5 190
128 Rated Power of
Weight
Model Current controlled
(kg)
(A) motor(kW)
R
NJR2-7.5D 15 7.5
NJR2-11D 22 11
READY RUN ERROR NJR2-15D 29 15
268
250
ENTER RUN
确定 运行 NJR2-18.5D 36 18.5
SET
设定
STOP
停止
5
NJR2-22D 42 22
NJR2-30D 57 30
NJR2-37D 70 37
NJR2-45D 84 45
NJR2-55D~75D
200
R3.5 183 215
R
Rated Power of
Weight
Model Current controlled
(kg)
(A) motor(kW)
READY RUN ERROR
NJR2-55D 103 55
270
310
ENTER RUN
确定 运行
8
SET
设定
STOP
停止 NJR2-75D 140 75
K1K2K3
U V W
Soft-Starter Inverter & Soft-Starter P-036
NJR2-90D~185D
253
220 241
Φ9
Rated Power of
Weight
Model Current controlled
(kg)
R
(A) motor(kW)
NJR2-90D 167 90
READY RUN ERROR
529
426
ENTER RUN
确定 运行
SET STOP
设定 停止
NJR2-220D~315D
293
240 253
Φ9
Rated Power of
Weight
R
Model Current controlled
(kg)
(A) motor(kW)
ENTER RUN
确定 运行
25
NJR2-280D 514 280
NJR2-315D 579 315
K1K2K3
F
NJR2-355D~500D
293
240 253
Φ9
Rated Power of
Weight
R
Model Current controlled
(kg)
(A) motor(kW)
ENTER RUN
确定 运行
52.5
NJR2-450D 810 450
NJR2-500D 900 500
K1K2K3
7. Ordering information
7.1 Please select the required model and specification according to the instructions on model and meaning when ordering.
Example: The controlled motor power of 45kW is installed and used with soft starting cabinet or matching distribution
cabinet.
Ordering model: NJR2-45D (to be connected with the bypass contactor with corresponding specifications)
7.2 When motor with more than 4 poles is used with soft starter, recommend to select one size larger.
Example: the controlled motor power 75kW is installed and used with soft starting cabinet or matching distribution
cabinet.Ordering model: NJR2-90D (to be connected with the bypass contactor with corresponding specifications)
7.3 When bipolar motor is used with soft starter, as the starting current is large, please set the parameters correct as per the
instruction manual before use.
7.4 For heavy load application, recommend the use of soft starter one grade larger.