Automatic sash controllers
Table of contents
1.1 Introduction
If the sash is manually pushed in the direction UP or in The FC500 or iCM fume hood controllers immediately
the direction DOWN, the internal touch sensor (only when reduce the exhaust air volume flow, while ensuring minimal
activated) automatically recognizes the desired direction escape of contaminants. The required exhaust air volume
and opens or closes the sash via the motor. flow (sash = SHUT) can be reduced, depending on the
requirement by about 70 % in relation to the maximum
An infrared light barrier IRL100 mounted on the sash exhaust air volume flow (sash= fully OPEN). A fume hood
handle bar automatically stops the sash if an obstacle with a required exhaust air of 500 m3/h when the sash is
is detected during the closing process. Objects, such as fully open can be reduced to an exhaust air volume flow of
measuring probes, electrical cables, etc., that lead out 150 m3/h when the sash is fully shut without compromising
of the fume hood are recognized with a resolution of ≥ safety.
1mm. It is essential to cover transparent glass bulbs in the
detection range of the infrared light barrier, as these can
otherwise not be detected. 3.1.1 Easy installation
Manual movement of the sash is possible at all times. The SCHNEIDER FC500/iCM fume hood controllers and
This also applies to manual intervention in the closing the SC500 automatic sash controller ideally complement
process. Restrictive obstacles are recognised by constant one another. The SC500 is suitable for fitting in all fume
monitoring of the current of the drive unit. As soon as hood models and constructions and is thus ideally suited
the sash runs into a restrictive obstacle, the current for retrofitting.
consumption is increased and results in shut-off of the
electrical drive unit.
The current consumption of the drive unit is monitored 4.2.1 Network connection via field bus
when the sash is automatically opened or closed. If the
sash touches an obstacle or cannot move smoothly, the The SC500 automatic sash controller can easily be
current consumption of the motor increases. As soon integrated in a network via a field bus module on the fume
as a freely programmable current threshold (maximum hood controller (e.g. FC500). This ensures that connection
threshold value) is exceeded, the motor immediately to the building services management is possible. Thus,
switches off. This protection circuit offers additional safety the sash can easily be closed automatically when a fire
for the user. or smoke alarm is activated. Remote maintenance via the
network is also easy and efficient to implement.
6
1
M
Fault alarm
Fume 2 SC500 230 VAC Power
hood UP
STOP
RS485
DOWN
CLOSED RS 232
4 3
5
Service module
SVM100
F1 F2 F3
1 2 3
4 5 6
1 Passive-Infrared-Detection PIR 7 8 9
* 0 ,
2 Control panel Laptop
Passive infrared
movement detector
Figure 4.6 shows the schematic diagram of the entire In addition to a CPU kernel, there is also a D/A (Digital/
SC500 automatic sash controller. Analogue converter) as well as an input and an output
interface on the control board. The peripheral sensors
and acutators are connected to the corresponding port
5.2.1 Power supply cables.
All SCHNEIDER products have their own 230V AC power The parameters are saved mains voltage failure-free in
supply, which eliminates the need for a 24V AC power the EE-PROM.
supply via an external transformer. The integrated power
supply makes planning easier, generates no additional
costs and considerably improves system safety and 5.2.3 Two independent watchdog circuits
stability of the electronics. With an external 24 V power
supply the entire supply line would fail in the case of a The SC500 controller hardware has two independent
short circuit or other defect. watchdog circuits. The microcontroller is checked for errors
at regular intervals and in the case of an error in the CPU,
one or both of the watchdog circuits trigger a hardware
5.2.2 CPU set-up reset, which restarts the CPU. This unique watchdog
concept additionally increases operating safety.
The CPU consists of a microcontroller with integrated
RAM (Random Access Memory), a ROM (Read Only
Memory) for the application software, a UART (Universal
Asynchronous Receiver Transmitter), internal timers, Input/
Output-Ports and an A/D (Analogue/Digital converter).
Watchdog 2 EE-PROM
Relay
Relay: Alarme
Output
TTL: Actuator
TTL
Optocoupler OC: Up
Down
RS 232
Voltage
Input
Backup
230/115 V AC batterie
Power supply
Serial interface
All cables are pre-assembled and fitted with screw 4. Connection of the foot switch (optional) to terminal
terminals. When mounting, you only have to plug the X6.
screw terminals into the slots provided and the wiring is
complete. This ensures that wiring is easy, cost-efficient 5. Connection of the IRL100 light barrier to terminal X4.
and error-free.
6. Connection of the limit switch "Sash DOWN" (not
The following points must be completed when carrying out included in the scope of delivery) to terminal X5.
the wiring:
7. Connect the 230 VAC to terminal X1.
1. Connection of the electrical motor and the encoder
cable to the drive unit and plug X8. After the self-test the set-up is complete and the automatic
sash controller functions automatically.
2. Connection of the passive infrared sensor to terminal
X3 (ensure the correct polarity).
3
2
4
5 6
7
JP3 JP3
F2
T 3,15A/250V X4
X4
Transformer
Prim.: 230V AC/115V AC Run
Sek.: 20V AC
11 12 13 11 12 13
SC500 Controller
Figure 4.7: Terminal diagram SC500
F1
T 500mA/250V
T 1A/115V
X 13
Relay 1 RS 232
X8 RS485-1 RS485-2
X7
K1 SC500 Connector X11 X12
JP3 X9 X10
X6 Service module
X3 X4 X5
34 35 36 37 38 39
16 18 20 22 24 26 28 30 32
F1 F2 F3 Laptop
1 2 3 X2 7 8 9 10 11 12 13 14 15
X1 4 5 6 17 19 21 23 25 27 29 31 33 1 2 3
PE 4 5 6
7 8 9
* 0 ,
SUPPLY 230V AC
PIR
Pulley
SUPPLY 115V AC
Drive unit
Drive roll
rubber or tooth belt
7
Automatic sash controllers
Chapter 4.0
Microprocessor controlled automatic closing system Figure 4.8: Automatic sash controller SC500
for fume hood sashes
Integrated power supply 230V AC
All system data are saved mains voltage failure-safe
in the EEPROM
Programming of all system values via service module
SVM100 or laptop computer software PC2500
Automatic adjustment of the sash position via buttons
(UP, DOWN, STOP), foot switch or manually
Automatic adjustment of the sash position directly via
touch control mode on the window (UP, DOWN)
10 freely selectable speeds with soft stop
Motor current control with automatic shutoff (manual
intervention)
Monitoring of closing time
Teach-in mode for easy commissioning of different
fume hood types
start of the closing process by passive infrared
movement detector
Monitored closing process via infrared light barrier
and automatic shutoff on obstruction recognition
Reduced cabling effort through the use of a 2-wire
light barrier using both sash cables is possible
Lowering delay time adjustable from 10 sec to 30 min
Optionally connectable time extension button for
extending the lowering delay time (fume hood setup)
Automatic, electronic adjustment of the drive when
free movement of the sash is changed
Progamming of the system via the FAZ on the fume
hood (RS 485 – together with the FC-500 controller)
improvement in safety and reduction of the air
requirement by the predominant operating state sash
closed
Suitable for all fume hood constructions, independent
of the opening or closing method
The diagram shows an overview of the products that are Technical data sheets, further information and tender
available from SCHNEIDER in the product group Sash specifications for the SC500 automatic sash controller are
controllers. available for download on the Internet at www.schneider-
elektronik.de.
See Chapter 1, Section 6.1 for the full LabSystem product
overview.