Compressor controller pro-Log – Parameters adjusting.


Keys:

Start Up or Increment Value

Stop Down or Decrement Value

Reset Enter

Escape

Display:
°
Operational Display Symbols:
°
ba
psF Unloading Loading Timer Pressure indicator Locked
C
kP
r
i p

a Fault Display Symbols:

General fault Emergency stop Excess pressure

Power failure Above set temperature limit Service due, maintenance

Menu Structure:

Access Code 0009

C> compressor status


P00: User
Td delivery air temperature

Pd delivery pressure

H1 total running hours

H2 loaded hours

H3 service hours

Access Code 0100

Pu unload pressure

PL load pressure

do drain open time

dt drain interval time

Rt standby run on time


P01: Operation
St stop run on time

Bt blowdown time

P> press. units bar/psi/kPa

T> temp. units oC/oF

P04: Alarm SD service due timer

1
For distributors use only!

Adjusting Parameters. Operational Menu – Access Code:


Distributor level 1- 0009
Distributor level 2- 0100
To access a menu stop the compressor first then press the Up and Down buttons simultainiously. After several
seconds the display will show four “0” characters; the first character will flash. Press Up or Down to adjust the first
character to match the first character of the required access code. Press Enter to increment to the second code
character. When all four access code characters have been set, and the last code character is flashing, press Enter. If
the access code is correct for access to one of the two menus the first menu item of the appropriate menu will be
displayed. If the access code is incorrect the display will return to the normal operational display. To select a menu
item for adjustment press Up or Down until the menu item is displayed. To adjust an item setting press Enter, the value
or option will flash. Press Up or Down to adjust as required then press Enter to store in memory. To exit a menu and
return to the normal operational display, at any time, press Reset.

Pos. Code Description Range Default


P00: User menu
Information Number of compressor switched on
1 P00:C> screen during last one hour 0
2 P00:Td Delivery air temperature -10 °C___+132 °C.
3 P00:Pd Delivery air pressure 0-16 bar.
4 P00:H1 Running hours (electric motor on) 0-99999 h.
5 P00:H2 Loaded hours 0-99999 h.
6 P00:H3 Service hours (countdown timer) 0-99999 h. 50
P01: Operation menu
7 P01:Pu Unload pressure PL+0,2____14 bar 7,0 bar
8 P01:PL Load pressure 5____Pu-0,2 bar 6,5 bar
9 P01:do Drain open time 5 sec.
10 P01:dt Drain interval time 60 sec.
11 P01:Rt Standby run on time 1____3600 sec. 300 sec.
12 P01:St Stop run on time 1____60 sec. 30 sec.
13 P01:Bt Blowdown time (separator tank) 1____600 sec. 10 sec.
14 P01:P Pressure units 0,1,2 0 = bar
15 P01:T Temperature units 0,1,/ 0 = °C
P04: Alarm
16 P04: SD Service due timer 0-10000 h. 50