Академический Документы
Профессиональный Документы
Культура Документы
PART 1 - GENERAL
A. Drawings and general provisions of the Contract, including Conditions of Contract and
Division 1 Specification Sections, apply to this Section.
0.2 SUMMARY
1. Division 7 Section "Manufactured Roof Specialties" for type and style of roof curbs
and equipment supports.
2. Division 15 Section "Mechanical Vibration Controls and Seismic Restraints" for
manufactured isolation bases.
0.3 SUBMITTALS
A. Product Data: Include manufacturer's technical data for each model indicated, including
rated capacities of selected model clearly indicated; dimensions; required clearances;
shipping, installed, and operating weights; furnished specialties; accessories; and installation
and startup instructions.
B. Shop Drawings: Detail equipment assemblies and indicate dimensions, weights, loadings,
required clearances, method of field assembly, components, and location and size of each
field connection. Detail mounting, securing, and flashing of roof curb to roof structure.
Indicate coordinating requirements with roof membrane system.
1. Wiring Diagrams: Detail wiring for power, signal, and control systems and
differentiate between manufacturer-installed and field-installed wiring.
A. Fabricate and label refrigeration system to comply with ASHRAE 15, "Safety Code for
Mechanical Refrigeration."
D. Listing and Labeling: Provide electrically operated components specified in this Section
that are listed and labeled.
E. Comply with listed and labeled as defined in latest and relevant IEC standard, by a testing
agency acceptable to the Engineer.
F. Paint finish shall be suitable for local hot and humid weather conditions. Unit shall be
capable of working at 50 deg. C ambient.
A. Deliver rooftop units as factory-assembled units with protective crating and covering.
C. Handle rooftop units to comply with manufacturer's written rigging and installation
instructions for unloading and moving to final location.
0.6 COORDINATION
A. Coordinate installation of roof curbs, equipment supports, and roof penetrations with roof
construction. Roof specialties are specified in Division 7 Sections.
0.7 WARRANTY
A. Furnish extra materials described below that match products installed, are packaged with
protective covering for storage, and are identified with labels describing contents.
PART 2 - PRODUCTS
A. Description: Factory assembled and tested; designed for roof or slab installation; and
consisting of compressors, condensers, evaporator coils, condenser and evaporator fans,
refrigeration and temperature controls, filters, and dampers.
C. Evaporator Fans: Airfoil, centrifugal, belt driven with adjustable sheaves and permanently
lubricated motor bearings.
D. Return-Air Fans: Airfoil, centrifugal, belt driven with adjustable sheaves and permanently
lubricated motor bearings.
F. Exhaust/Relief Fans: Forward curved, centrifugal, belt driven with adjustable sheaves and
permanently lubricated motor bearings.
G. Condenser Fans: Propeller type, directly driven with permanently lubricated motor
bearings.
H. Filters: 300 mm deep, Class 1 bag filters with 90 to 95 percent dust-spot efficiency in
galvanized steel frame; with 50 mm thick, permanent, washable, aluminum type prefilters.
I. Filters: 300 mm deep, Class 1 cartridge filters with 90 to 95 percent dust-spot efficiency in
galvanized steel frame; with 50 mm thick, fiberglass, throwaway prefilters.
J. Refrigerant Coils: Aluminum-plate fin and seamless copper tube in galvanized steel casing
with equalizing-type vertical distributor and thermal expansion valve; tested to 3110 kPa
and leak tested to 2070 kPa with air under water. Insulate coil section.
1. Refrigerant Circuits: Interlaced coil refrigerant circuiting with circuit for each
compressor.
2. Capacity Control: Cylinder unloaders with steps as scheduled.
3. Capacity Control: Hot-gas bypass valve and piping on one compressor.
4. Low-Pressure Cutout: Manual reset.
5. High-Pressure Cutout: Manual reset.
6. Compressor Motor Overload Protection: Manual reset.
7. Antirecycling Timing Device: Prevents compressor restart for 5 minutes after
shutdown.
8. Oil-Pressure Switch: Designed to shut down compressors on low oil pressure.
L. Economizer Dampers: Return-, relief- and outside-air dampers with damper operator and
control package.
1. Leakage: Maximum leakage 2.5 percent at nominal airflow of 54 L/s per kW with
250-Pa pressure differential.
2. Damper Operator: 24 V, with gear train sealed in oil with spring return.
M. Economizer Control: Return, relief and outside air dampers, outside air filter with
magnehelic gauge for dirty filter indication, fully modulating electronic control system with
adjustable mixed air thermostat and automatic changeover through adjustable enthalpy
control device.
P. Smoke Detectors: Photoelectric detector located in both supply- and return-air plenum, to
de-energize unit.
Q. Electrical Convenience Outlet: 230-V, AC fused outlet, separately fused, located in unit
cabinet or in roof curb perimeter.
1. Control Outputs: cooling; and automatic or continuous fan operation and economizer
damper operation.
2. Return-air-, discharge-air-, outdoor-air-, space-, control set-point temperature LCD.
3. Outdoor enthalpy LCD.
4. Filter pressure drop LCD.
5. Status: Airflow, fans, system, unit operation, operating mode.
6. Inlet-vane and economizer-damper position LCD.
7. Duct static-pressure LCD.
8. Alarm LCD.
ROOFTOP UNITS 15782 - Page 4/8
STD-SPC-DCA(A)-ME-DCA REV A
<Project Title>
0.4 MOTORS
A. Refer to Division 15 Section "Motors" for general requirements for factory-installed motors.
1. Sound Power Level Ratings: Comply with ARI 270, "Standard for Sound Rating of
Outdoor Unitary Equipment."
PART 3 - EXECUTION
0.1 EXAMINATION
A. Examine roof for compliance with requirements for conditions affecting installation and
performance of rooftop units. Do not proceed with installation until unsatisfactory
conditions have been corrected.
0.2 INSTALLATION
C. Curb Support: Install roof curb on roof structure level. Install and secure rooftop units on
curbs and coordinate roof penetrations and flashing with roof construction.
D. Unit Support: Install unit on structural curbs and level. Coordinate wall penetrations and
flashing with wall construction.
0.3 CONNECTIONS
D. Ground equipment.
0.4 COMMISSIONING
C. Complete manufacturer's installation and startup checks and perform the following:
1. Level unit on housekeeping base, and flash curbs to unit and to roof.
2. Inspect for visible damage to unit casing.
3. Inspect for visible damage to compressor, air-cooled condenser coil, and fans.
4. Verify that clearances have been provided for servicing.
5. Check that labels are clearly visible.
6. Verify that controls are connected and operable.
7. Remove shipping bolts, blocks, and tie-down straps.
8. Verify that filters are installed.
9. Adjust vibration isolators.
10. Check acoustic insulation.
11. Check operation of barometric dampers.
E. Check fan-wheel rotation for correct direction without vibration and binding.
H. Check and record performance of interlocks and protection devices; verify sequences.
J. Calibrate thermostats.
M. Check outside-air damper for proper stroke and interlock with return- and relief-air
dampers.
N. Check controls for correct sequencing of mixing dampers, refrigeration, and normal and
emergency shutdown.
P. Measure and record the following minimum and maximum airflows. Plot fan volumes on
fan curve.
1. Supply-air volume.
2. Return-air volume.
3. Relief-air volume.
4. Outside-air intake volume.
R. Verify operation of remote panel, including pilot-light operation and failure modes. Check
the following:
S. After starting and performance testing, replace filters with new, clean filters, change
vacuum heat exchanger and cooling and condenser coils, lubricate bearings, adjust belt
tension, and check operation of power vents.
0.5 DEMONSTRATION