30/10 kV power transformer Unit REQUIRED GUARANTEE

Technical performances D
Manufacturer - Name
Country of origin - country
Manufacturing place
Type Three phase oil
IEC standards - IEC 60076,
60354
Rated power ONAN
Substation RN1 MVA 10
Kabezi substation MVA 10
ITABA substation MVA 1
Rated voltage kV/kV 30/10
Maximum working voltage kV/kV 36/12
Nominal frequency Hz 50
Connection symbol
Substation RN1 - Dyn11
Kabezi substation Dyn11
ITABA substation Dyn11
Short-circuit voltage in middle position % 13
Insulation - uniform
Cooling mode - ONAN
Temperature rise (Rated power, 40 ° C maximum -
ambient temperature)
oil (Upper level) °C 50
Winding °C 60
Indoor / outdoor power frequency withstand kV 70/82
voltage, primary winding
Indoor / outdoor power frequency withstand kV 28/38
voltage, secondary winding
Internal / external shock wave withstand voltage, kV 170/200
primary winding
Internal / external shock wave withstand voltage, kV 75/95
secondary winding
Noise level (in no load / at 100% load) dB (A) 66
Idle current % In 0,2
No load losses kW
for 1 MVA transformer kW
for 10 MVA transformer kW
Losses (ONAN) kW
for 1 MVA transformer kW
for 10 MVA transformer kW
Short-circuit current (3s): kA 25
Homopolar impedance /ph
Connection mode
Primary side overhead
Secondary side cables
Dimensions
Length mm
Depth mm
Height mm
Weight
Total kg
30/10 kV power transformer Unit REQUIRED GUARANTEE
Technical performances D
of transport kg
of oil kg
Tap changers
Type (Kabezi, RN1) - In resistance load
Type (Itaba) without load
Rated current A
Current assigned for permissible short duration
Maximum kA 25
3 seconds kA
On-load tap-changer adjustment range - +-12%
+-1,25%
Mode of installation - MV side
Duration of the life of the switches cycles 200.000
Automatic tension control
Manufacturer -
Type -
Manufacturing place -
Tension Umax % of Un
Tension Umin % of Un
Max current x In
Sensitivity -%,+%