Академический Документы
Профессиональный Документы
Культура Документы
Defrosting of
Air Coolers Various Methods
The evaporator being the coldest surface in the cold room, attracts moisture from the air. This
moisture condenses on the evaporator surface, and when the surface temperature is below
0OC frost is formed. If this frost is not removed, the performance of the evaporator deteriorates
since the frost acts as resistance to heat flow, as also increases the air side resistance reducing
the air flow. If the frost is not removed in time and plant is allowed to operate, the evaporator
may become totally ineffective, as there will be no air flow or heat transfer and un-evaporated
liquid ammonia coming back, is likely to damage compressor.
I
t is therefore essential to it again is estimated to be nearly 1.5 method can be adapted to any
defrost the coolers in time to kW/Kg of ice (iiar condenser temperature in the cold room. It
maintain efficiency levels and magazine May 2010 issue). One can requires ducting and personnel to
avoid damage to components. thus estimate, based on condensate carry out this defrosting. In colder
Improper and incomplete defrosting water amount collected as to how climates this method is either
can damage compressor and much extra energy and money one ineffective or less efficient. The
evaporator coil to the extent that is spending. outside air brings moisture and
irreparable refrigerant leaks develop There are various methods of additional heat load on the system.
when ice is allowed to build up and defrosting the coolers and these are Electric Defrost
crush one or more coil tubes. The described below with their This is one of the popular
fan blades are also likely to be advantages and disadvantages as methods for small size air coolers
damaged if ice builds up on the fan well as which method is more particularly for HFC/HCFC
ring. The drain pan gets totally suitable for the application under refrigerants. The method can be
blocked by ice slab and water spills consideration. applied to any cold room application
over to floor and ice is formed on operating at any temperature. While
the floor as well. Air Defrost manufacturing and assembling of
Defrosting is therefore necessary Off cycle defrost coils; the dummy tubes are inserted
but not in excess also. Defrosting is In the cold stores operating in the coil blocks in a particular
doubly expensive procedure because above 2OC, the evaporator coils can pattern and these tubes contain
energy is used to pump heat into be defrosted by simply turning off electrical heating elements.
cooler and its surroundings, after the refrigerant flow to the evaporator In some designs the heating
which further energy is used to while maintaining fans running and elements are strapped to the outside
extract the heat from the cooler and allowing room air to pass over the of the fin/tube assembly. The
its surroundings before the system evaporator, thus melting of frost. advantage of this method is the
gets back to its operating The disadvantage of this process is manufacturer does not have to
temperature. The energy is thus it is very slow; however it is of provide extra dummy tubes.
consumed twice, once for forming lowest cost and requires no additional The advantage of electric defrost
ice and second time for melting ice. controls or energy. This method also is - it does not interfere with the
Defrosting as the name suggests does not help in removing refrigerant circuit, and chances of
should be activated when frost is accumulated oil in the cooler. liquid coming to compressor or
formed and not wait till ice is formed Warm outside air hydraulic hammer are eliminated.
on the coil surface. The total energy Outside warm air can be ducted The system is low in initial cost
required to form the ice and defrost inside to defrost the coil. This but high in running cost since it
78 December 2012
Air Coole r s
also it does not help in oil removal be successfully used in many cycle. This system is popular in
from evaporator. In general for a applications for temperatures as truck/container refrigeration units
cooler of 30 to 40 kW capacity one low as -40OC. Hot Gas Defrost
requires heaters of nearly 18 kW • The water used for defrosting It is necessary to thoroughly
including drain pan heating and if needs to be with neutral PH understand details of working of this
defrost is done 4 times a day for 30 value so that it does not damage system before using the same
minutes each cycle then the cost of fins and filtered so as to prevent • Hot gas defrost is the best and
defrosting alone is 36kWhxRs.5.0/ choking of spray nozzles. most efficient alternative as heat
kWh=180 Rupees/day or 5400Rs/ • The quantity of water sprayed source acts from within whereas
per cooler per month. High and the velocity needs to be water/electrical defrost heat
maintenance due to frequent failure controlled to ensure that water source is from outside.
of resistance heating elements & droplets are not carried in the air • During hot gas defrost cycle,
replacement of burnt heaters is also stream and into cold room. evaporator acts as condenser
a tedious job. • A warm water from heat reclaim giving up the heat and converting
Water Defrost unit can also be used for defrost gas to liquid.
The second most popular method purpose. • Although hot gas defrost is the
of defrosting air coolers is spraying Brine Defrost most effective way of defrosting,
water on the coil. The mixture of In case of coils using brines it is equally complicated,
water and melted frost collects in instead refrigerant, the coils can troublesome & may be inefficient
the drain pan and taken outside the defrosted by remotely heating brine if not properly designed.
refrigerated space. The advantages for the defrost cycle. This system is • The basic procedure in hot gas
of water defrost over other methods effective since it provides heat from defrost method is to interrupt
are- inside and is therefore as rapid as the supply of liquid refrigerant to
• Inexpensive source of defrost hot gas-defrost. The heat source for evaporator, pump out the liquid
medium. brine could be steam, electricity or to empty the evaporator, restrict
• Short defrost time say 30 to 45 condenser water. the liquid outlet by closing the
minutes. Reverse Cycle Defrost valve, supply hot gas at high
• Provides automatic cleaning This defrosting method is used in pressure either from compressor
action of coil. air cooled applications where discharge or from high pressure
• Water defrost is most condenser and evaporator both work receiver to warm the evaporator
advantageous when there is only on air as cooling medium. The ideal coil & melt surface frost/ice
one or two coolers and out of defrosting should terminate the formation.
which one needs to be defrosted. defrost cycle when the whole cooler • During the operation the heat
In such cases enough hot gas is is sufficiently warmed above the from hot gas is absorbed by the
not available to defrost and the melting point of ice to ensure the metal in the coil/plate and its
hot gas defrost becomes cooler is dry and frost free. This is temperature rises. Once the
ineffective. done most easily in reversed cycle temperature is high enough, ice/
• Normally spiral freezers or blast defrosting system where the frost on the surface melts and is
freezers prefer this method since pressure within cooler gradually drained off.
these are many times single rises till the frost disappears and • Out of the total heat supplied by
compressor and single cooler then the defrost cycle may be the hot gas, nearly 50% is used
units. terminated. The reverse cycle for heating the metal and balance
• Water defrosting provides rapid defrost is very efficient but seldom 50% or even more is lost to
defrosting of coils for virtually all used since the very reliable four way space surrounding tubes/plates
room temperatures. Water is reversing valve is required in the since the temperature of
sprayed over the coil and the refrigeration circuit. Also this system surrounding air is much lower
mixture of water and melted is used where single cooler and than temperature of the unit.
frost flows in the drain pan. The single compressor are working in a • Typical freezer coils have internal
normal water temperature should system. Rotation of the four-way volume between 4-6 litres/kW. A
be around 16 to 18OC or more valve through 900 routes the hot coil of 35 KW will have
depending upon wet bulb gas to cooler instead to the approximately 27 to 50 kg of
temperature in the area and flow condenser. When multiple coolers ammonia liquid and with the
to be 1 to 3 litres per second per working on single compressor in the initial boil off rate of approximately
square meter of coil face. system this system cannot be used 1.2kg/min it will take about 20 to
• This method is less desirable for the obvious reason that all 40 minutes to boil out all the
when temperatures decrease coolers cannot be defrosted at a liquid from the freezer.
December 2012 79
80 December 2012
Air Coole r s
coil/plates can be gradually difference between returning low even when coil does not need
brought down to operating stage -40OC and intermediate defrosting the timer would
pressures before full liquid is vessel at -7OC is (172.34- automatically activate defrost
admitted. 19.17)=153.17 kJ/kg i.e. cycle. Many times when the
• A manual initiation of defrost for 153.17x132=20218.44 kJ=5.61 products are freshly loaded the
larger coils/freezers is kW or in 12 minutes required defrosting frequency is
recommended based on physical 5.61x60/12=28 kW removed more and once the products are
condition of freezer with respect from the -40 OC booster kept at desired temperatures, the
to amount of ice/frost formed on compressor for 12 minutes during defrosting frequency is less. This
the surface. each defrost. requires re adjusting timer
• It is recommended that • An excessive noise and shock or settings.
evaporator defrost liquid should vibrations observed during • Microprocessor controllers: They
be returned to intermediate defrost is not normal and if have mostly replaced mechanical
pressure vessel and not to low observed cause must be timer clocks. The use of
pressure vessel in case of two corrected. microprocessors reduces energy
stage system. This has two • Many times hot gas is taken from consumption and helps in
advantages. Firstly, it does not top of receiver instead from maintaining product quality.
disturb the LP vessel pressure/ compressor discharge, to ensure • Ice thickness sensor: An ice
temperature conditions during adequate amount of hot gas thickness sensor is attached to
defrost operation and thus other availability. the coil and when thickness
operating coolers work without builds to a particular size it
any disturbance. Secondly defrost Defrost Control Initiation touches the sensor and activates
liquid pressure and intermediate Alternatives defrost cycle. This method is
vessel pressure difference is Defrost initiation can be done used many times in ice bank/ice
much lower than defrost pressure once the frequency and duration of reserve units for dairies.
and LP vessel pressure and thus defrost cycle is established. Control • Air Temperature difference:
saves considerable energy. schemes are generally implemented Sensors are provided at coil inlet
• The non-return valve in main by means of an electric or electronic air path and outlet path and
supply line after solenoid valve is timer, or a computer based control defrost controller is set at
essential to ensure that high logic. particular ∆T. If the coil gets
pressure developed during • Mechanical Timer clock: This frosted this temperature
defrost in the coil does not exert allows coolers to be defrosted at difference reduces and the
back pressure at the outlet of fixed but adjustable set intervals. defrost sequence is activated.
solenoid valve, since the inlet The advantage is the operator • Air Pressure differential controls:
pressure is normally either equal does not have to remember when Instead of temperature
to evaporator pressure or pump
discharge pressure. A standard soft hot gas defrost cycle diagram is shown below
• Advantage of regulating pressure
to 7.0 barg in the equipment
room is, there is less chance of
coils getting damaged or bent or
ruptured as low side of the
system is normally designed for
10.0 barg and hot gas at 8.0 barg
or more pressure is dangerous to
the low side parts of the system.
To be safer it is recommended
that low side should be also
designed for 20 barg same as
high side design pressure for
condensers/receivers & pressure
tested to 1.25 time’s pneumatic
pressure.
• Example- a 70kW coil defrosting
for 12 minutes will condense up
to 11kg/min of ammonia of
December 2012 81
82 December 2012
Air Coole r s
the pressure in the coil to reduce available quantity of hot gas. particular evaporator model and size
slowly. This eliminates system The steps 1 to 10 are all built into since adjustable electronic timers
disruptions, which would occur if the control circuit of the controller. are provided in the controller.
warm refrigerant were released
quickly in to suction piping. This ❁
also reduces vapour propelled Ramesh Parashuram Paranjpey, Fellow Life Member ASHRAE,
liquid, and prevents sudden Member IIAR USA is MTech (Refrigeration), IIT Bombay and Fellow-Life
loading of compressor if suction Member, Institution of Engineers, India, and a Chartered Engineer. He was
pressure rises quickly. Ex-President, ISHRAE, Pune Chapter; Ex-President, ASHRAE Western
• Fan Delay time: The fan is not India Chapter and published more than 45 Papers in International/national
yet energized. Instead, the coil journals. he conducted corporate training on National level at various
temperature is allowed to drop, companies and ISHRAE, ASHRAE forums and on International level
freezing any water droplets that in US, Singapore, China, Germany, etc. Earlier he was Chief Executive
might remain on the coil surface Officer, Voltas Air International Ltd., Pune; Managing Director, Carrier
after the hot gas defrost phase, Refrigeration Ltd. Bangalore & Singapore; and Vice President, AC&R
thereby preventing the possibility Division, Kirloskar Pneumatics Ltd. Pune. He was also Examiner and
of blowing water droplets off the Paper setter in University of Pune for Master in Engineering and was in
coil in to refrigerated space. syllabus formulating committee. He was invited by German Chamber of
• Start of cooling cycle: After the Commerce to deliver lecture in Germany on “Ammonia Pump Circulation
fan delay has elapsed, the fan Systems for Low Temperature Applications” in 2008. He is winner of
gets energized automatically “Bry-Air Systems Design Award” for 2009 and published book on Cold
based on time setting. The room solutions for Emerson Climate Technologies. He is Refrigeration
refrigeration phase continues Specialist on NHB panel and has executed more than 700 projects for
until the next defrost cycle is cold storages, as well as air conditioning such as international air ports,
initiated. office buildings, and shopping malls. In last 5 years after retirement
from Voltas Air International, he is doing consultancy and is consultant
The entire process can take
for many projects/companies.
maximum 15 to 30 minutes
December 2012 83