Академический Документы
Профессиональный Документы
Культура Документы
mum simultaneously then the fan would not have enough air
output to meet the demand. The boxes closest to the fan would
get their required air while the boxes further downstream
“starve” for air. In Figure 9-1 all the boxes are set for a maximum
flow of 1000 cfm. The interior boxes have maximum shutoff at
75%. The minimum flow then is 250 cfm. The exterior boxes with
reheat coils have maximum shutoff at 50%. In other words, the
minimum flow is 500 cfm. If the airflow though these reheat
boxes falls below 50% the heat transfer may diminish, i.e., the
required heat from the steam, hot water or electricity may not be
picked up by the air if the airflow is too slow. Safety and fire may
be a concern, especially with electric reheats if not enough air is
moving across the electric resistance coil to remove the heat.
VAV Operation
Most VAV systems use a single duct, which supplies a con-
144 HVAC Fundamentals