EFBW series -
BiWire Ultra control panel
Benefits
EFBW2ZONE EFBW4ZONE EFBW8ZONE • Tailored to the size and need of the building
No. of zones 2 4 8 • Reduced cost of installation
Detectors per 32 32 32 • Simple system testing by a single fire alarm technician
zone
• Capability to sound class change bell in schools
Maximum loading 200mA 200mA 200mA
per zone
• Interlink relay allows for greater system flexibility
Repeater Port
• Comprehensive protection for safety of building
occupants
• .PEFSOEFTJHO
EATON - SPECIFIER’S GUIDE - FIRE AND VOICE ALARM SYSTEMS SGTEXT ©November 2015
Specifier’s guide
4.2 Control panels and repeater panels
Maximum 200mA
Loading Per Zone
Standby Zone Min: 22V DC, Max: 24V DC
Voltage
Alarm Zone Min: 31V DC, Max: 33V DC
Voltage
Fuse Protection 250mA PTC
Per Zone
End of Line EOLM-3 Only
Termination (Do not use EOLM-1 or EOLM-2) Description Height (mm) Width (mm) Depth (mm)
Fire, Fault & Type: Volt-Free, Single Pole Double Throw, Complete Panel 336 375 134
Interlink Relay Rating: 30V DC, 1A,
Fuse 1.1A PTC Backbox 273 338 88
Auxiliary Output V: 0V DC (Standby)/30V DC (Alarm +/-10%),
Imax: 50mA,
Fuse: 50mA PTC
Status indication
Class Change Short circuit to trigger input,
open circuit to clear input
Mains rating 230V Ah +10%/-15% 50Hz
Battery rating 2 x 12V 5Ah
Changeable Mains 1A anti surge
power fuses Battery 6-3A anti surge
Repeater Port Yes
Environmental
Operating -5 °C to +40°C
temperature
Relative humidity 93% +/-3% non-condensing
IP Rating IP30 1. When the fire panel enters a fault condition it will turn on the Gen-
Physical eral Fault indicator and the appropriate fault indicator (refer to 8 for
more details). The panel buzzer will sound a slow pulsing tone.
Weight (excluding 2.25kg
batteries) 2. System Fault – Severe failure of the panel, the service company
must be contacted immediately.
Material PC ABS Front and Rear
Repeater Fault – Communication with a repeater panel has been
Cabling lost
Cable access 29 x 20mm drill positions 3. Battery Fault – Battery voltage missing
Slots for rear cable entry Mains Fault – Mains supply missing
Cable type Firetuf FT120 / FP200 4. Battery Failure – Battery impedance failure
2 core 1.5mm, 2 screened fire rated cable, 500m (max Charger Fault – Charger voltage missing
per zone) 5. Sounder Fault – Short circuit or open circuit condition detected on
the zone will prevent the activation of sounders if fitted on that
zone
Standard panel connections 6. FRE Fault – Short circuit or open circuit condition detected on the
FRE output
7. FPE Fault – Short circuit or open circuit condition detected on the
FPE output
8. Detector Removed Fault – A detector head has been removed
Zone Fault – Short circuit or open circuit condition detected on the
zone.
Catalogue numbers
Description Code
Eaton 2 zone BiWire Ultra panel EFBW2ZONE
Eaton 4 zone BiWire Ultra panel EFBW4ZONE
Eaton 8 zone BiWire Ultra panel EFBW8ZONE
BiWire End of line module BWEOLM
2 zone relays + FRE/FPE BW0B2Z
4 zone relays + FRE/FPE BW0B4Z
8 zone relays + FRE/FPE BW0B4Z
EATON - SPECIFIER’S GUIDE - FIRE AND VOICE ALARM SYSTEMS SGTEXT ©November 2015
Specifier’s guide 4.3 Accessories
EFBW5IN1DET -
BiWire Ultra detector 5 in 1
EATON - SPECIFIER’S GUIDE - FIRE AND VOICE ALARM SYSTEMS SGTEXT ©November 2015
Specifier’s guide
4.3 Accessories
Performance
Optical Photo-
smoke thermal Rate of rise Fixed heat Fixed heat
Feature mode mode mode 77 ˚C mode 92 ˚C mode
Area coverage 100m2 100m2 50m2 50m2 50m2
(subject to local standards)
Heat class N/A A2S A1R BS CS
Alarm temperature N/A 60 ˚C 60 ˚C 77 ˚C 92 ˚C
Installation
1. Detectors are fixed and wired via common mounting base.
2. Cable entry into base can be rear or side.
3. A locking facility is provided which can be activated if required
to prevent unauthorised detector removal without the use of a
special tool.
4. Positive click mechanism incorporated to provide clear indication
when detector is correctly located in base.
User interface
1. Red LED to indicate alarm condition.
2. Amber LED to indicate chamber fault/drift compensation limit.
3. All wiring connections are via a common mounting base (supplied
separately).
Catalogue numbers
Description Code
Detector 5 in 1 EFBW5IN1DET
Standard base FXN520
EATON - SPECIFIER’S GUIDE - FIRE AND VOICE ALARM SYSTEMS SGTEXT ©November 2015
Specifier’s guide 4.3 Accessories
The base sounder and base sounder VAD are certified • Certified to EN54-3 & EN54-23
to EN54-3 and EN54-23 respectively. • Cover plate (optional)
EATON - SPECIFIER’S GUIDE - FIRE AND VOICE ALARM SYSTEMS SGTEXT ©November 2015
Specifier’s guide
4.3 Accessories
4 4
Conventional
Compatible
EOLM-1
ZONE
body. 2 E 2 E
- 3 3
System functionality - VE
Catalogue numbers
Description Code
BiWire Ultra base sounder EF5021BWS
BiWire Ultra base sounder VAD EF5021BWSB
Cover Plate (Pack of 5) CASC
EATON - SPECIFIER’S GUIDE - FIRE AND VOICE ALARM SYSTEMS SGTEXT ©November 2015
Specifier’s guide 4.3 Accessories
The BiWire Ultra wall sounder and wall sounder VAD Features
offer low current consumption and high sound output.
• Ultra low current consumption
The BiWire Ultra range of sounders has been
• Certified to EN54-3 and EN54-23
designed to meet the latest European Standards -
EN54-3 and EN54-23. • High sound output
• Weatherproof option
It is offered in two variants, sounder only or a
combined sounder VAD. Benefits
EATON - SPECIFIER’S GUIDE - FIRE AND VOICE ALARM SYSTEMS SGTEXT ©November 2015
Specifier’s guide
4.3 Accessories
Technical specification
Installation Dimensions
1. First fix mounting plate is fixed to wall.
2. Cable entry is from rear, or top/bottom. D
Interface options
Sounder operates from nominal 24V dc supply and can be connected W
+ + - -
Compatible
Conventional
Control Panel
WARNING:
Do NOT use high voltage testers if ANY equipment is
connected to the system.
Catalogue numbers
Description Code
BiWire Ultra wall sounder EF009
BiWire Ultra wall sounder, weatherproof EF009WP
BiWire Ultra wall sounder VAD EF009SB
BiWire Ultra wall sounder VAD, weatherproof EF009SBWP
EATON - SPECIFIER’S GUIDE - FIRE AND VOICE ALARM SYSTEMS SGTEXT ©November 2015
Specifier’s guide 4.3 Accessories
EF201BWCP, EF203BWCPWP -
BiWire Ultra callpoints
EATON - SPECIFIER’S GUIDE - FIRE AND VOICE ALARM SYSTEMS SGTEXT ©November 2015
Specifier’s guide
4.3 Accessories
Technical specification
COMMON
680Ω
H + + - -
Compatible
Conventional
Control Panel
D
WARNING:
Description H (mm) W (mm) D (mm) Do NOT use high voltage testers if ANY equipment is
Flush mounted 87 87 36 connected to the system.
Surface mounted 87 87 57 Screen (Earth) must be continuous along entire length of cable
Weatherproof 87 87 59
Catalogue numbers
Description Code
Callpoint, surface/flush EF201BWCP
Callpoint, weatherproof EF203BWCPWP
Protective hinged cover CXPC
Spacer plates (pack of 10) MBGSP
Recessing bezels (pack of 10) MBGBEZ
Resettable element kit (pack of 10) MBGREKIT
Spare break glasses (pack of 5) FX5G
Callpoint keys (pack of 10) MFBGKEY3