SUMMARY
STEPS TO CERTIFY FAN PERFORMANCE
UNDER AMCA INTERNATIONAL’S CERTIFIED RATINGS PROGRAM

AMCA Seal can only be used in conjunction with AMCA Licensed Products.

This is a summary only. The Certified Ratings Program is fully described in AMCA Publications 11, 211 and 311.
Please read these Publications, particularly the Product Rating Requirement Subsections of Publication 211.

STEP 1 APPLY TO BECOME AN AMCA INTERNATIONAL MEMBER OR CRP AFFILIATE


(APPLICANT'S RESPONSIBILITY)

Newcomers to AMCA International’s Certified Ratings Program must first decide whether they
would like to become an AMCA International Member or a CRP Affiliate. Although it is usually
less costly to participate in the Certified Ratings Program as a Member, it is not necessary to
become an AMCA International Member in order to participate in the Certified Ratings Program.

Membership is limited to any business engaged in the design, fabrication, assembly and sale of
devices within the product scope of AMCA International. Information on membership can be
obtained by submitting a request to AMCA International’s Executive Director, or by completing the
Membership Interest Form located at http://www.amca.org/membership/join.asp, on AMCA
International's website.

If you are not eligible to become an AMCA International Member, or if you do not wish to become
an AMCA International Member, you must complete an application to become an AMCA
International CRP Affiliate. Applications are available from AMCA International upon request.

1 Rev. 9/07
STEP 2 SIGN LICENSE AGREEMENT – Publication 11, Section 6.1
(APPLICANT'S RESPONSIBILITY)

License Agreements are signed only once, prior to the first product being certified.

Upon approval of the application, AMCA International will mail two License Agreements to the
Licensee Representative. Sign, witness and seal both copies and return them to AMCA
International. AMCA International will then sign, witness and seal both copies and return one
copy to you along with the License Appendix for your first product line after Step 11 is completed.
A product is certified only after a License Appendix has been issued by AMCA International.
Each certified product will have a unique License Appendix Number.

STEP 3 TESTING – Publication 11, Section 7.3


(APPLICANT'S RESPONSIBILITY)

The fans may be tested in AMCA International’s Laboratory, an independent laboratory licensed
to perform tests for AMCA International, or in an AMCA International Accredited Laboratory.
Contact AMCA International’s Director of Laboratory Services to arrange for testing in AMCA
International’s Laboratory, or for information on AMCA International’s Laboratory Accreditation
Program.

Not every size of a product line needs to be tested. If there is a geometric proportionality
between several sizes, you may calculate the performance of the larger sizes from a smaller size
using the Fan Laws. Although the Licensee is responsible for selecting test sizes, the AMCA
International technical staff will assist in selection of test sizes.

STEP 4 APPLY FOR LICENSE AGREEMENT APPENDIX – Publication 11, Section 7.4 and 7.5
(APPLICANT'S RESPONSIBILITY)

SUBMIT TO AMCA INTERNATIONAL:

A. Completed CRP-8 Forms signed by the Licensee Representative. Please visit


http://www.amca.org/crp/documents.asp to download a form. Please submit a separate
CRP-8 form for each product line.

B. Test data in conformance with the test standard used. These results must be corrected
to standard air density.

C. Performance curves of the test results with the test points identified.

D. Photographs of each test setup.

E. Dimensional drawings giving the dimensions listed in AMCA Publication 211, Annex A.
Marked photocopies of the appropriate drawings from Annex A are acceptable, or contact
AMCA International for a PDF version.

F. Reverberant room qualification data for fans being certified for sound. For sound only –
not necessary of sound tests conducted in AMCA International’s Laboratory.

2 Rev. 9/07
STEP 5 STAFF REVIEW OF SUBMITTAL DATA – Publication 11, Section 7.6
(AMCA INTERNATIONAL'S RESPONSIBILITY)

AMCA INTERNATIONAL STAFF WILL CHECK THAT:

A. The completed CRP-8 form is signed by the Licensee Representative.

B. Every test listed on the CRP-8 form is contained in the submittal and in conformance with
the standard used.

C. Performance curves are included with the test results.

D. Photographs of the test(s) are included.

E. Drawings and dimensions are in conformance with AMCA Publication 211, Annex A and
Subsection A4.1.

If the submittal is in conformance, the AMCA International staff will select a Precertification Test
Unit and e-mail a Precertification Check Test Request to the Licensee Representative. A
Precertification Test is not necessary if all tests were run in AMCA International’s Laboratory or
an independent laboratory licensed to perform tests for AMCA International. If the submittal is not
in conformance, the AMCA International staff will notify the applicant by e-mail of the items
required to complete the application.

STEP 6 PRECERTIFICATION CHECK TEST – Publication 11, Section 7.7


(APPLICANT'S RESPONSIBILITY)

(Required if the tests were conducted in an AMCA International Accredited Laboratory)

A. Complete the Application and Agreement for Testing Service Form (TAF) using My
AMCA (unless otherwise instructed) and ship (prepaid) the Precertification Check Test
Unit to AMCA International. The Test Application Number should be marked on the
outside of the test unit and its crate.

(AMCA INTERNATIONAL'S RESPONSIBILITY)

B. Tests are scheduled after both the TAF and unit are received. AMCA International will
run the tests and notify the applicant of the results. If the test is unsatisfactory, AMCA
International will select an additional Precertification Check Test Unit.

STEP 7 SUBMIT PROPOSED CATALOG DATA – Publication 11, Section 7.8


(APPLICANT'S RESPONSIBILITY)

The data may also be submitted with the CRP-8 form in Step 4 above, or as part of the catalog
proof copy in Step 9 below.

STEP 8 AMCA INTERNATIONAL REVIEW OF PROPOSED CATALOG DATA – Publication 11,


Section 7.9 and 7.10
(AMCA INTERNATIONAL'S RESPONSIBILITY)

The AMCA International staff will review the proposed catalog data. If the proposed data is not
satisfactory, staff will notify the applicant by e-mail. If the proposed catalog data has been
verified as correct by AMCA International staff, a “Notice of Acceptability” will be sent by e-mail.

3 Rev. 9/07
STEP 9 SUBMIT CATALOG PROOF COPY – Publication 11, Section 7.11
(APPLICANT'S RESPONSIBILITY)

Submit a proof copy of the catalog and/or electronic media to AMCA International staff for
verification of the performance data and conformance to the requirements of the Certified Ratings
Program. AMCA International will retain the proof copy of the catalog. Electronic versions of the
AMCA International Seal are available from AMCA International for use in catalogs.

STEP 10 AMCA INTERNATIONAL REVIEW OF PROOF COPY – Publication 11, Section 7.12
(AMCA INTERNATIONAL'S RESPONSIBILITY)

The AMCA International staff will review the proof copy and notify the applicant by e-mail of any
necessary corrections or of the proof copy’s acceptability.

STEP 11 SUBMIT PRINTED CATALOG – Publication 11, Section 7.13


(APPLICANT'S RESPONSIBILITY)

Submit one copy of the printed catalog and/or electronic media to the AMCA International staff
immediately prior to being released to the public.

STEP 12 AMCA INTERNATIONAL REVIEW OF PUBLISHED CATALOG AND ISSUANCE OF


LICENSES – Publication 11, Section 7.14
(AMCA INTERNATIONAL'S RESPONSIBILITY)

The AMCA International staff will review the printed catalog and, if it is unchanged from the proof
copy shall issue an Appendix to the License Agreement for the product line.

In the event that the catalog does not meet the requirements of the program, the applicant shall
be notified immediately by e-mail of the discrepancy, advised not to distribute the catalog to the
public and a License Appendix shall not be issued. The applicant must then correct the
discrepancy and resubmit the catalog to the AMCA International staff for review and approval.

Note: This post-printing action will only happen if changes are made to the AMCA International
approved proof copy.

MANUFACTURING/PRODUCTION CHECK – Publication 11, Section 9.3

If the base tests are conducted on a prototype, AMCA International will request a Check
Test within one year after the License Appendix is issued. If the base tests are conducted
on a production model, the Check Test will be requested within three years after the License
Appendix is issued.

4 Rev. 9/07
CHECK LIST

Company_______________________________________ Model ____________________________________

‰ Step 1 Apply to Become an AMCA International Member or CRP Affiliate

‰ Step 2 Sign License Agreement

‰ Step 3 Testing

‰ Step 4 Apply for License Agreement Appendix

‰ Step 5 Staff Review of Submittal Data

‰ Step 6 Precertification Check Test

‰ Step 7 Submit Proposed Catalog Data

‰ Step 8 AMCA International Review of Proposed Catalog Data

‰ Step 9 Submit Catalog Proof Copy

‰ Step 10 AMCA International Review of Proof Copy

‰ Step 11 Submit Printed Catalog

‰ Step 12 AMCA International Review of Published Catalog and Issuance of Licenses

Revised 9/12/07

5 Rev. 9/07
AMCA Publication 211 Proportionality Dimensions
W

A Diameter at Blade Tip


B Diameter at Blade Heel
W Blade Width at Discharge D B A
D Minimum Diameter at Inlet Cone
N Number of Blades

Figure A-1 Backward inclined centrifugal impeller

Model No./Size Dimensions

A B W D N

10

11

12

Rev. 9/07
AMCA Publication 211 Proportionality Dimensions
W

A Diameter at Blade Tip


B Diameter at Blade Heel
W Blade Width at Discharge D B A
D Minimum Diameter at Inlet
N Number of Blades

Figure A-2 Forward curved centrifugal impeller

Model No./Size Dimensions

A B W D N

10

11

12

Rev. 9/07
AMCA Publication 211 Proportionality Dimensions
W

A Diameter at Blade Tip


B Diameter at Blade Heel
W Blade Width at Discharge D B A
D Inlet Diameter
N Number of Blades

Figure A-3 Radial centrifugal impeller

Model No./Size Dimensions

A B W D N

10

11

12

Rev. 9/07
AMCA Publication 211 Proportionality Dimensions

A Major Diameter at Discharge


1
A Minor Diameter at Discharge
1
B Major Diameter at Blade Heel D B A A
W Blade Width at Discharge
D Minimum Diameter at Inlet Cone
N Number of Blades

Figure A-4 Mixed flow impeller

Model No./Size Dimensions

A A1 B W D N

10

11

12

Rev. 9/07
AMCA Publication 211 Proportionality Dimensions

A Diameter at Blade Tip


"
H Hub Diameter
G Blade Width at Discharge A H
G
" Pitch Angle at Tip or at a Designated Radius
N Number of Blades

Figure A-5 Vaneaxial propeller

Model No./Size Dimensions

A H G α N

10

11

12

Rev. 9/07
AMCA Publication 211 Proportionality Dimensions

A Diameter at Blade Tip


"
H Hub Diameter
G Blade Width at Tip A H
G
" Pitch Angle at Tip or at a Designated Radius
N Number of Blades

Figure A-6 Tubeaxial propeller

Model No./Size Dimensions

A H G α N

10

11

12

Rev. 9/07
AMCA Publication 211 Proportionality Dimensions

A Diameter
H Blade Root Diameter, May be
20% less than Catalogued G
G Blade Width at a Designated Radius A H
" Pitch Angle at a Designated Radius
"
N Number of Blades

Figure A-7 Fabricated propeller

Model No./Size Dimensions

A H G α N

10

11

12

Rev. 9/07
AMCA Publication 211 Proportionality Dimensions
Tip Clearance

Design tip clearance is defined as the


difference between the design radius of
the impeller and the design internal Inside
radius of the fan casing. Measured tip Surface
clearance is defined as the average of of Casing
the tip clearance measurement for all
blades taken at eight locations
(45o intervals) around the fan casing.

Figure A-8 Tip clearance

Model No./Size Dimensions

Tip Clearance

10

11

12

Rev. 9/07
AMCA Publication 211 Proportionality Dimensions

A or A

A Width of Discharge
(or Evase, as applicable) C
B Height of Discharge
(or Evase, as applicable)
C Point of Inlet Radius or Inlet Collar or
B B
Diameter

Figure A-9 Centrifugal fan housing SI-DI

Model No./Size Dimensions

A B C

10

11

12

Rev. 9/07
AMCA Publication 211 Proportionality Dimensions
S Shaft Diameter if Shaft Extends L
A
Through Box
A Inlet Height
B Inlet Width B
L Inlet Box Length

Figure A-10 Inlet box

Model No./Size Dimensions

S A B L

10

11

12

Rev. 9/07
AMCA Publication 211 Proportionality Dimensions

Q Shaft Height above Base C


C Inlet Diameter at Tangent Point
of Inlet Radius or Inlet Collar Diameter
Q

Figure A-11 ARR. 3 plenum fan

Model No./Size Dimensions

Q C

10

11

12

Rev. 9/07
AMCA Publication 211 Proportionality Dimensions

Q Shaft Height above Base C

C Inlet Diameter at Tangent Point


of Inlet Radius or Inlet Collar Diameter Q

Figure A-12 ARR. 1 plenum fan

Model No./Size Dimensions

Q C

10

11

12

Rev. 9/07
AMCA Publication 211 Proportionality Dimensions

P Panel Size
C Inlet Diameter at Tangent Point P C
of Inlet Radius or Inlet Collar
Diameter

Figure A-13 Plug fan

Model No./Size Dimensions

P C

10

11

12

Rev. 9/07
AMCA Publication 211 Proportionality Dimensions
T J
U Drum Diameter or Square Size E
B1 Interior Drum Size
B2 Interior Drum Size at Discharge
T Length to Belt Tube
J Belt Tube Size U B2 B1
E Length of Vanes
NV Number of Vanes

NV

Figure A-14 In-line centrifugal fan

Model Dimensions
No./Size

U B1 B2 T J E NV

10

11

12

Rev. 9/07
AMCA Publication 211 Proportionality Dimensions
T J
U Diameter - ID E
B Interior Drum Diameter
T Length to Belt Tube
E Length of Vanes
U B
NV Number of Vanes
J Belt Tube Size

NV

Figure A-15 Vaneaxial fan belt drive

Model No./Size Dimensions

U B T E NV J

10

11

12

Rev. 9/07
AMCA Publication 211 Proportionality Dimensions
E

U Diameter - ID
B Inside Diameter of Vanes
E Length of Vanes
U B
NV Number of Vanes

NV

Figure A-16 Vaneaxial fan direct drive

Model No./Size Dimensions

U B E NV

10

11

12

Rev. 9/07
AMCA Publication 211 Proportionality Dimensions
T J

U Diameter - ID
B Size of Drive Tube
U B
T Length to Belt Tube
J Belt Tube Size

Figure A-17 Tubeaxial fan belt drive

Model No./Size Dimensions

U B T J

10

11

12

Rev. 9/07
AMCA Publication 211 Proportionality Dimensions

U Diameter U

Figure A-18 Tubeaxial fan direct drive

Model No./Size Dimensions

10

11

12

Rev. 9/07
AMCA Publication 211 Proportionality Dimensions
K

O Orifice Diameter
K Orifice Depth
P O
R Orifice Radius
P Panel or Ring Size

Figure A-19 Propeller fan

Model No./Size Dimensions

O K R P

10

11

12

Rev. 9/07
AMCA Publication 211 Proportionality Dimensions
V

N Hood Height
V Hood Diameter or Size
N
F Discharge Area or Size
C Inlet Collar Size (if provided)
I Recommended Inside Curb Dim. M
M Minimum Height Above Roof
C
F
I

Figure A-20 Centrifugal PRV exhaust-down discharge

Model No./Size Dimensions

N V F C I M

10

11

12

Rev. 9/07
AMCA Publication 211 Proportionality Dimensions
V
F
V Housing Diameter or Size
F Discharge Area or Size
C Inlet Collar Size (If Provided)
I Recommended Inside Curb Dim.

C
I

Figure A-21 Centrifugal PRV exhaust-up discharge

Model No./Size Dimensions

V F C I

10

11

12

Rev. 9/07
AMCA Publication 211 Proportionality Dimensions
V

O Orifice Diameter
V Hood Diameter or Size R
K
F Discharge Size or Area
M
C Inlet Collar Size (If Provided)
K Orifice Depth O
M Minimum Height Above Roof F
C
I Recommended Inside Curb Dim.
I
R Orifice Radius

Figure A-22 Axial PRV supply or exhaust

Model Dimensions
No./Size
O V F C K M I R

10

11

12

Rev. 9/07
AMCA Publication 211 Proportionality Dimensions
V

V Hood Size
F Intake Size or Area N
N Hood Height
Y Body Size
M Height Above Base
F
M
See A9 for Blower Dimensions Required

Figure A-23 Centrifugal supply PRV

Model No./Size Dimensions

V F N Y M

10

11

12

Rev. 9/07
AMCA Publication 211 Proportionality Dimensions
X

X Windband Diameter
C Inlet Collar Size (If Provided)
O Orifice Diameter R
K
K Orifice Depth
R Orifice Radius
I Recommended Inside Curb Dim.
O
C
I

Figure A.24 Axial upblast PRV

Model No./Size Dimensions

X C O K R I

10

11

12

Rev. 9/07
AMCA Publication 211 Proportionality Dimensions
X

C Inlet Collar Size (If Provided)


X Windband Diameter, Inside
I Recommended Inside Curb Dim.

See Tubeaxial and Vaneaxial for Dim.


Figures A-15 to A-18
C
I

Figure A-25 Axial upblast PRV

Model No./Size Dimensions

C X I

10

11

12

Rev. 9/07
AMCA Publication 211 Proportionality Dimensions
V
C Inlet Collar Size (If Provided)
V Hood Size
F Discharge/Intake Size or Area N
N Hood Height
M Height Above Roof
I Recommended Inside Curb Dim.
F
M
See tubeaxial Figure A-17 and A-18
for Required Fan Dim.

C
I

Figure A-26 Axial supply/exhaust PRV

Model No./Size Dimensions

C V F N M I

10

11

12

Rev. 9/07
AMCA Publication 211 Proportionality Dimensions
V

V Hood Size
N
F Discharge/Intake Size of Area
N Hood Height
M Height Above Roof M
Y Body Size
O Orifice Diameter F
K Orifice Depth R
R Orifice Radius
O

Figure A-27 Combination PRV exhaust-supply-circulate

Model Dimensions
No./Size
V F N M Y O K R

10

11

12

Rev. 9/07
AMCA Publication 211 Proportionality Dimensions
X

Y Body Size
K Orifice Depth
O Orifice Depth
R Orifice Radius
X Wind Band Diameter, Inside R
K
O

Figure A-28 Combination PRV exhaust-circulate

Model No./Size Dimensions

Y K O R X

10

11

12

Rev. 9/07
AMCA Publication 211 Proportionality Dimensions

See Figure A-19 for Dimensional Requirements for Propeller Fans


Provide All Dimensions Required to Define Inlet and/or Outlet Appurtenances

Figure A-29 Agricultural fans

Model No./Size Dimensions

10

11

12

Rev. 9/07
AMCA Publication 211 Proportionality Dimensions
L
Z2 Z1 B

L Interior Width A Interior Height


Z Fan Spacing B Interior Depth
Y Shaft Center Height

See Tubeaxial and Vaneaxial Figures A-15 to A-18


for Required Fan Dimensions

Figure A-30 Vane/tubeaxial air curtain

Model No./Size Dimensions

L Z A B Y

10

11

12

Rev. 9/07
AMCA Publication 211 Proportionality Dimensions
L B
Z3 Z2 Z1 X

W
V

A Interior Height W Centrifugal Fan/Housing Width


B Interior Depth X Shaft Center Depth
L Interior Width Y Shaft Center Heigfht
V Motor Spacing (where applicable) Z Centrifugal Fan/Housing Spacing

Figure A-31 Centrifugal/tangential air curtain

Model Dimensions
No./Size
A B L V W X Y Z

10

11

Rev. 9/07
AMCA Publication 211 Proportionality Dimensions
L B
Z 2 Z 1 K

O A

Y
R

W
A Interior Height
B Interior Depth
L Interior Width K Orifice Depth
Z Axial Fan Spacing R Orifice Radius
W Impeller Diameter at blade Tip O Min. Diameter of Inlet Cone
Y Shaft Center height

Figure A-32 Axial air curtain

Model Dimensions
No./Size
L Z W A B K R O Y

10

11

Rev. 9/07
AMCA Publication 211 Proportionality Dimensions
K W

K Inlet Orifice Depth


O Minimum Diameter
O of Inlet Orifice
W Tip Clearance

Figure A-33 Circulator fan

Model No./Size Dimensions

K O W

10

11

12

Rev. 9/07
AMCA Publication 211 Proportionality Dimensions
T1

N1

T2 S1

N2

N1 Number of Rings
N2 Number of Radial Supports
T1 Ring Thickness
T2 Radial Support Thickness
S1 Ring Spacing

Figure A-34 Circulator fan head with guard

Model No./Size Dimensions

N1 N2 T1 T2 S1

10

11

12

Rev. 9/07
AMCA Publication 211 Proportionality Dimensions
Li L Lo

Di Dfi D Dfo Do

Ri Ro
N

L Fan Length
Li Inlet Silencer Lenght
Lo Outlet Silencer Length
D Fan Diameter
Di Inlet Silencer Diameter
Do Outlet Silencer Diameter
Dfi Inlet Fairing Diameter
Dfo Outlet Fairing Diameter
Ri Inlet Bell Radius
Ro Outlet Bell Radius
N Number of Vanes

Figure A-35 Jet tunnel fan dimensions

Model Dimensions
No./Size
L Li Lo D Di Do Dfi Dfo Ri Ro N

Rev. 9/07
AMCA Publication 211 Proportionality Dimensions

Figure A-36 Induced Flow Fan Nozzle and Windband Dimensions

Model
No./Size
A B C D E F G
1

Rev. 9/07
CHECKLIST: AIR PERFORMANCE CATALOGS

CATALOG IDENTIFICATION_______________________ DATE OF CATALOG___________________

I. SEAL USAGE IN CATALOGS

A. Pick the correct AMCA Seal: [check all that apply]

□ Air Performance
□ Sound and Air Performance
□ CFM/Watt Air Performance
□ Positive Pressure Ventilator Air Performance
□ Efficiency Air Performance
□ Efficiency Sound and Air Performance
□ Induced Flow Fan Air Performance
□ Induced Flow Fan Air and Sound Performance
□ Smoke Management Fan Performance
□ Smoke Management Fan Performance Reversible Operation

B. Placement of AMCA Seal: [check all that apply]

□ 1. If the catalog contains all licensed products, the seal and qualifying statement shall be prominently
displayed either on the cover or in the catalog.

□ 2. If the catalog contains both licensed and unlicensed products, the AMCA Seal and qualifying
statement shall not be shown on the outside cover.

□ 3. In addition, the AMCA Seal may be shown on any page with licensed performance data.

C. Reproduction of AMCA Seal in Catalogs

□ 1. Size: No reproduction of the AMCA International Certified Ratings Seal in published material shall
be larger than 42 mm x 70 mm (1 5/8 in. x 2 3/4 in.), unless the AMCA International staff gives
specific permission.

□ 2. Color: When using one color reproduction, black is preferred. If light colored paper is used, regard
it as white for this purpose. The full color AMCA Seal may be used. The CRP Manager will email
reproductions of the AMCA Seal for use in the catalog upon request.

D. Member Logo

□ Other than the AMCA International Certified Ratings Seal, no logo or mark incorporating the acronym AMCA
International or initials A.M.C.A. such as the member logo shall be reproduced in any catalog or publication
containing performance ratings of any kind.

1 Rev. 12/07
II. QUALIFYING STATEMENT ADJACENT TO THE SEAL

□ In catalogs containing ratings of licensed products, the following statement shall be printed prominently and
immediately adjacent to the reproduction of the AMCA Certified Ratings Seal as required by I.B:

"(Licensee's name as shown on License Agreement) certifies that the (product description) shown
herein is (or are) licensed to bear the AMCA Seal. The ratings shown are based on tests and
procedures performed in accordance with AMCA Publication 211 (and AMCA Publication 311 if
sound is also certified) and comply with the requirements of the AMCA Certified Ratings
Program."

III. CATALOG IDENTIFICATION REQUIREMENTS

□ Catalogs containing performance ratings of licensed products shall be provided with a catalog identification
reference, and the month and year of publication shall be spelled out, e.g. "November 2004," on the outside
front or outside back cover of the product catalog.

□ The catalog identification may be any combination of letters and/or numbers. Where ratings are on separate
sheets or on loose leaf that may be removed from the cover, each sheet or loose leaf shall be identified and
dated as above. The final printed catalog shall have a current date.

IV. EFFICIENCY

The following statement shall be shown immediately adjacent to the efficiency ratings:

□ Efficiency ratings are fan static (or fan total) and include (or exclude) bearing and/or Power Transmission
Losses.

V. REQUIREMENTS FOR AIR PERFORMANCE

Rating Method (see last page of Publication 211 to determine rating method) [check one]

□A □B □C □D □E □F
□G □H □ I □J □K □L
Determine the rating method and then check the appropriate statements to be used. The statements shall be
shown immediately adjacent to the rating tables, graphs or charts.

A. Rating Method "A" (Constant Speed, Transmission Loss Not Included)

The performance ratings for each model number shall include:

□ Airflow rate

□ Static pressure and/or total pressure

□ Fan input power

2 Rev. 12/07
□ Impeller speed

□ Inlet air density (if other than standard air)

□ Fan static and/or fan total efficiency (optional)

Required Statements:

□ 1. Power rating (watts, kW or BHP) does not include transmission losses.


□ 2A. Performance ratings do not include the effects of appurtenances (accessories).
or

□ 2B. Performance ratings include the effects of [list appurtenances here].


B. Rating Method "B" (Constant Speed, Transmission Losses Included)

The performance ratings for each model number shall include:

□ Airflow rate

□ Static pressure and/or total pressure

□ Fan input power

□ Impeller speed

□ Inlet air density (if other than standard air)

□ Fan static and/or fan total efficiency (optional)

Required Statements:

□ 1. Power rating (watts, kW or BHP) includes transmission losses.


□ 2A. Performance ratings do not include the effects of appurtenances (accessories).
or

□ 2B. Performance ratings include the effects of [list appurtenances here].

3 Rev. 12/07
C. Rating Method "C" (As Run Speed, Transmission Losses Included, Low Slip Motor)

The performance ratings for each model number shall include:

□ Airflow rate

□ Static pressure and/or total pressure

□ Maximum fan input power over the range catalogued, or fan input power at the stated duty

□ Actual impeller speed at each point of ratings or a nominal speed

□ Inlet air density (if other than standard air)

□ Fan static and/or fan total efficiency (optional)

Required Statements:

□ 1. Power rating (watts, kW or BHP) includes transmission losses.


□ 2. Speed (RPM or RPS) shown is nominal. Performance is based on actual speed of test. Use this
statement only when nominal speed is catalogued.

□ 3A. Performance ratings do not include the effects of appurtenances (accessories).


or

□ 3B. Performance ratings include the effects of [list appurtenances here].


D. Rating Method "D" (Direct Drive, Constant Speed, Low Slip Motor)

The performance ratings for each model number shall include:

□ Airflow rate

□ Static pressure and/or total pressure

□ Maximum fan input power over the range catalogued, or fan input power at the stated duty, or
maximum motor input watts, voltage and frequency over the range catalogued, or motor input watts,
voltage, and frequency at the state duty

□ Impeller speed

□ Inlet air density (if other than standard air)

□ Fan static and/or fan total efficiency (optional)

4 Rev. 12/07
Required Statements:

□ 1A. Performance ratings do not include the effects of appurtenances (accessories).


or

□ 1B. Performance ratings include the effects of [list appurtenances here].


E. Rating Method "E" (Direct Drive, As Run Speed, Low Slip Motor)

The performance ratings for each model number shall include:

□ Airflow rate

□ Static pressure and/or total pressure

□ Maximum fan input power over the range catalogued, or fan input power at the stated duty, or
maximum motor input watts, voltage and frequency over the range catalogued, or motor input watts,
voltage, and frequency at the stated duty

□ Actual impeller speed at each point of rating or a nominal speed

□ Inlet air density (if other than standard air)

□ Fan static and/or fan total efficiency (optional)

Required Statements:

□ 1. Speed (RPM or RPS) shown is nominal. Performance is based on actual speed of test. Use this
statement only when nominal speed is catalogued.

□ 2A. Performance ratings do not include the effects of appurtenances (accessories).


or

□ 2B. Performance ratings include the effects of [list appurtenances here].


F. Rating Method "F" (Direct Drive, As Run Speed, High Slip Motor)

The performance ratings for each model number shall include:

□ Airflow rate

□ Static pressure

□ Maximum motor input watts, voltage and frequency over the range catalogued, or motor input watts,
voltage, and frequency at the stated duty (optional if less than 500 watts)

5 Rev. 12/07
□ Actual impeller speed at each point of rating or nominal speed

□ Inlet air density (if other than standard air)

□ Fan static and/or fan total efficiency (optional)

Required Statements:

□ 1. Speed (RPM or RPS) shown is nominal. Performance is based on actual speed of test. Use this
statement only when nominal speed is catalogued.

□ 2A. Performance ratings do not include the effects of appurtenances (accessories).


or

□ 2B. Performance ratings include the effects of [list appurtenances here].


G. Rating Method "G" (Air Curtains)

The performance ratings for each model number shall include:

□ Airflow rate

□ Average outlet velocity

□ Motor input power, voltage, and frequency

□ Outlet velocity uniformity

□ Inlet air density (if other than standard air)

□ Fan static and/or fan total efficiency (optional)

Required Statements:

□ 1. The AMCA Certified Ratings Seal applies to airflow rate, average outlet velocity, outlet velocity
uniformity, velocity projection and power rating at free delivery only.

□ 2. Rated data shown are only for base (unheated) units, as shown.

□ 3. Performance data obtained from the correction factors shown herein are only an approximation and
shall not be considered as part of the AMCA Certified Ratings.

6 Rev. 12/07
H. Rating Method "H" (Direct Drive, Jet Tunnel Fan, As Run Speed)

The performance ratings for each model number shall include:

□ Airflow rate

□ Nominal impeller speed

□ Thrust (N or Ibf)

□ Thrust/fan input power (N/kw or Ibf/bhp)

Required Statements:

□ 1. The AMCA Certified Ratings Seal applies to airflow rate at free delivery only. Speed (rps or rpm)
shown is nominal. Performance is based on actual speed of test.

□ 2. Performance ratings include the effect of [list appurtenances here].

I. Rating Method "I" (Agricultural Fan, As Run Speed, Transmission Losses Included, Low Slip Motor)

The performance ratings for each model number shall include:

□ Airflow rate at 10 Pa (0.05 in. wg) and 30 Pa (0.125 in. wg) static pressure (Ratings at other static
pressures are optional)

□ Actual impeller speed at each point of rating or a nominal speed

□ Airflow rate/motor input power (m3/s/watt or cfm/watt)

□ Motor nameplate voltage and frequency

□ Motor manufacturer and model number for all motors listed for use on the fan

□ Inlet air density (if other than standard air)

Required Statements:

□ 1. Speed (rpm or rps) shown is nominal. Performance is based on actual speed of test.

□ 2. Performance ratings include the effect of [list appurtenances here].

J. Rating Method "J" (Direct Drive, PPV, As Run Speed)

The performance ratings for each model number shall include:

□ Airflow rate

7 Rev. 12/07
□ Impeller speed

□ Setback distance

□ Tilt angle

□ Motor/engine manufacturer and model number (for all motors/engines listed for use on the PPV)

Required Statements:

□ 1. Performance ratings include the effect of [list appurtenances here].

K. Rating Method "K" (Direct Drive, Circulator Fan, As Run Speed)

The performance ratings for each model number shall include:

□ Airflow rate

□ Nominal impeller speed

□ Airflow rate/motor input power (m3/s/watt or cfm/watt)

□ Motor nameplate voltage and frequency

Required Statements:

□ 1. The AMCA Certified Ratings Seal applies to airflow rate at free delivery only.

□ 2. Speed (rpm or rps) shown is nominal. Performance is based on actual speed of test.

□ 3. Performance ratings include the effect of [list appurtenances here].

L. Rating Method “L” (Induced Flow Fans)

The performance ratings for each model number shall include:

□ Inlet airflow rate

□ Fan static pressure

□ Fan input power

□ Impeller speed

□ Inlet air density (if other than standard air)

8 Rev. 12/07
□ Fan static efficiency (optional)

□ Outlet airflow rate

□ Outlet area

□ Nozzle velocity (Inlet airflow rate divided by nozzle discharge area)

Required Statements:

□ 1. Power rating (watts, kW, or bhp) does not include transmission losses.

□ 2. Performance ratings do not include the effects of cross winds.


□ 3A. Performance ratings do not include the effects of appurtenances (accessories).

Or

□ 3B. Performance ratings include the effects of [list appurtenances here]:

M. Duct Statement

Installation Method [this is different from the rating method; see test report for installation method; check one]

For all rating methods, one of the following statements shall be shown immediately adjacent to the rating tables,
graphs and charts:

□A Performance certified is for installation type A – Free inlet, Free outlet.


□B Performance certified is for installation type B – Free inlet, Ducted outlet.
□C Performance certified is for installation type C – Ducted inlet, Free outlet.
□D Performance certified is for installation type D – Ducted inlet, Ducted outlet.
□ A&C Performance certified is for installation type A & C – Free or ducted inlet, Free outlet.
□ B&D Performance certified is for installation type B & D – Free or ducted inlet, Ducted outlet.

Note: Air curtains and air circulator fans do not require a duct statement.

VI. ADDITIONAL REQUIREMENTS FOR AIR CURTAINS

□ The velocity projection at standard inlet air density for one size of each product line shall be stated in the form
of a table. The distance from the nozzle will be listed with the average core velocity.

VII. ADDITIONAL REQUIREMENTS FOR AGRICULTURAL FANS

□ Each fan appurtenance(s) (accessories) assembly shall have a distinct model number different from one
without appurtenance(s) (accessories) or with a different group of appurtenance(s) (accessories).

9 Rev. 12/07
VIII. ADDITIONAL REQUIREMENTS FOR POSITIVE PRESSURE VENTILATORS

□ Each PPV appurtenance(s) (accessories) assembly shall have a distinct model number different from one
without appurtenance(s) (accessories) or with a different group of appurtenance(s) (accessories).

IX. ADDITIONAL REQUIREMENTS FOR CIRCULATOR FANS

□ Each fan-appurtenance(s) (accessories) assembly shall have a distinct model number different from one
without appurtenance(s) (accessories) or with a different group of appurtenance(s) (accessories).

X. ADDITIONAL REQUIREMENTS FOR INDUCED FLOW FANS

□ When electrical input power is cataloged, the tested motor shall be operated at the catalog voltage and
frequency, or where a voltage range is stated, it shall be the mean voltage. In addition, the temperature of the
motor winding has to be stable for each tested operating point.

XI. MISCELLANEOUS ITEMS FOR ALL CATALOGS

□ Where the ratings of licensed products are on the same page or "spread" as nonlicensed products, a clear
physical separation and statement shall differentiate licensed products from nonlicensed products.

□ Nonlicensed Sound Rating Statement


Where sound ratings of a product which is not licensed to use the AMCA Certified Ratings Seal for Sound and
Air are shown with licensed air performance ratings adjacent to the sound ratings, the following prominent
statement shall be shown adjacent to the ratings:

"The AMCA Certified Ratings Seal applies to air performance ratings only."

□ Partial Series of Sizes


When only a portion of a cataloged series of sizes are licensed, at least a majority of the sizes cataloged shall
be licensed.

□ The use of asterisks or similar marks to distinguish licensed products from nonlicensed products is
unacceptable.

□ In connection with nonlicensed products, the use of any phrase that is liable to be misinterpreted to mean that
such products are licensed to use the AMCA International Certified Ratings Seal shall be prohibited. Phrases
such as "tested and rated to AMCA International standards" or "rated to AMCA International standards" shall
not be used.

□ When a product is licensed for sound and air, the sizes shown for sound performance shall be the same as the
sizes shown for air performance.

□ There shall be no unauthorized use of AMCA International copyrighted material. See the AMCA International
website for the policy on using AMCA copyrighted material.

10 Rev. 12/07
CHECKLIST: SOUND CATALOGS

CATALOG IDENTIFICATION_____________________ DATE OF CATALOG_____________________

This check list should be used in conjunction with the air performance check list.

I. PRODUCT LINES LICENSED FOR SOUND

A. Octave Band and LWA Rating Qualifying Statements

The following are the qualifying statements that shall be used with Sections B and C.

1. Figure 1, Fan Total Sound Testing

“Values shown are for (total LW or total LWA) sound power levels for:

□ Installation Type A: free inlet, free outlet."

□ Installation Type B: free inlet, ducted outlet. Ratings include the effects of duct end correction for the
outlet duct."

□ Installation Type C: ducted inlet, free outlet. Ratings include the effects of duct end correction for the
inlet duct."

□ Installation Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction for
inlet and outlet ducts."

2. Figure 2, Fan Inlet Sound Testing

"Values shown are for (inlet LWi or inlet LWiA) sound power levels for:

□ Installation Type A: free inlet, free outlet."

□ Installation Type B: free inlet, ducted outlet."

□ Installation Type C: ducted inlet, free outlet. Ratings include the effects of duct end correction."

□ Installation Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction."

3. Figure 3, Fan Outlet Sound Testing

"Values shown are for (outlet LWo or outlet LWoA) sound power levels for:

□ Installation Type A: free inlet, free outlet."

□ Installation Type B: free inlet, ducted outlet. Ratings include the effects of duct end correction."

1 Rev. 12/07
□ Installation Type C: ducted inlet, free outlet."

□ Installation Type D: ducted inlet, ducted outlet. Ratings include the effects of duct end correction."

B. Octave Band Ratings

For a given rotational speed, a full set of octave band values may be presented for various points of rating. If only
one set is presented, the value in each octave band shall be the maximum at any point of rating.

□ The following statement shall be used:


"The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per
AMCA International Standard 301.”

In addition, the appropriate statement from Section A shall be used to clarify installation type and end reflection.

C. LWA Rating

□ The following statement shall be used:


"The A-weighted sound ratings shown have been calculated per AMCA International Standard 301."

In addition, the appropriate statement from Section A shall be used to clarify installation type and end reflection.

D. Fan Sone Rating Qualifying Statements

1. Fan Inlet Sone Rating

For fans rated by a single value (hemispherical sone rating) use the following sentence:

"The sound ratings shown are loudness values in fan sones at 1.5 m (5 ft) in a hemispherical free
field calculated per AMCA International Standard 301. Values shown are for:

□ Installation Type A: free inlet hemispherical sone levels."

□ Installation type B: free inlet hemispherical sone levels."

□ Installation type C: ducted inlet hemispherical sone levels. Ratings do not include the effect of duct
end correction."

□ Installation type D: ducted inlet hemispherical sone levels. Ratings do not include the effect of duct
end correction."

For fans rated using spherical sone values, use the following sentence:

“The sound ratings shown are for loudness values in spherical sones at 1.5 m (5 ft) in a spherical free
field calculated per Annex B of AMCA 311. Values shown are for:

□ Installation type A: free inlet spherical sone levels.”

2 Rev. 12/07
□ Installation type B: free inlet spherical sone levels.”
□ Installation type C: ducted inlet spherical sone levels. Ratings do not include the effect of duct end
correction.”

□ Installation type D: ducted inlet spherical sone levels. Ratings do not include the effect of duct end
correction.”

2. Fan Outlet Sone Rating

For fans rated by a single value (hemispherical sone rating) use the following sentence:

"The sound ratings shown are loudness values in fan sones at a distance of 1.5 m (5 ft) in a
hemispherical free field calculated per AMCA International Standard 301. Values shown are for:

□ Installation Type A: free outlet hemispherical sone levels."

□ Installation type B: ducted outlet hemispherical sone levels. Ratings do not include the effect of duct
end correction."

□ Installation Type C: free outlet hemispherical sone levels."

□ Installation type D: ducted outlet hemispherical sone levels. Ratings do not include the effect of duct
end correction."

E. Octave Band Ratings from In-Duct Tests

For fans rated in eight octave bands from tests in accordance with ANSI/AMCA 330, the following statement shall
be used:

“The sound power level ratings are shown in decibels, referred to 10-12 watts, in a duct connected to either the
inlet or the outlet of the fan, calculated per AMCA Standard 301. Values shown are sound power levels for:

□ total fan sound calculated from inlet and outlet tests.”


□ the fan inlet.”

□ the fan outlet.”


F. Presentation of Sound Values

□ For octave band and LwA ratings, round off the number to the nearest integer.
□ Hemispherical sone values less than twenty shall be rounded to one tenth of a sone. Values of twenty
or greater shall be rounded to the nearest integer.

□ Spherical sone values shall be at a fan static pressure of 25 Pa (0.1 in. wg). Ratings at other fan
pressures are optional.

3 Rev. 12/07
□ Spherical sone values greater than one and a half are rounded to the nearest one half sone.Spherical
sone values greater than three tenths and less than or equal to one and a half are rounded to one
tenth of a sone. Spherical sone values less than three tenths are rated as “<0.3 Sones”.

□ Cataloged sound power data shall not be lower than 1 dB less than the data developed from the CRP-
8 test data.

□ Cataloged hemispherical sone or spherical sone ratings shall not be lower than 1 sone (or 5%,
whichever is less) from the value calculated from the sound power level data developed from the
CRP-8 test data.

G. A-Weighted Sound Pressure Levels and dBA Ratings

□ If A-weighted sound pressure levels or dBA levels are displayed, the details of the calculation shall be shown,
and the following statement shall be used:

“dBA levels are not licensed by AMCA International.”

4 Rev. 12/07
AMCA CERTIFIED RATINGS SEAL
AIR MOVEMENT APPLICATION FORM CRP 8 & CRP T

TO: AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC.


We are submitting the enclosed test results (based on tests conducted in the AMCA Laboratory or in an AMCA
Accredited Laboratory in accordance with ANSI/AMCA 210/ASHRAE 51, ANSI/AMCA 230, AMCA 260, AMCA
300, ASHRAE 149 or an AMCA recognized test standard) along with the proposed catalog data, with a request
for license to use the AMCA Certified Ratings Seal on the below listed product.

Application for rating:

□ Air Performance □ Sound & Air Performance


□ CFM/Watt Air Performance □ Efficiency Sound & Air Performance
□ Efficiency Air Performance □ Induced Flow Fan Sound & Air Performance
□ PPV Air Performance □ Residential Sound & Air Performance
□ Induced Flow Fan Air Performance
□ Smoke Management Fan Performance □ Inlet Sound
(CRP-T) □ Outlet Sound
□ Smoke Management Fan Performance □ Total Sound
Reversible Operation (CRP-T) □ One-third Octave Bands
□ Residential Air Performance □ Octave Bands
□ Circulating Fan Performance □ Hemispherical sones
□ Spherical sones
□ LwA

Company Name ___________________________________________________ Date _____________________


Address ___________________________________________________________________________________
Authorized Signature ________________________________ Print Name _______________________________

PRODUCT INFORMATION
Product Name (As to be listed on License Appendix)

__________________________________________________________________________________________

SIZE MODEL NO. SIZE MODEL NO. SIZE MODEL NO.

Rev. 12/07
SUMMARY OF TEST DATA USED FOR RATINGS
□ Testing in an AMCA Testing Laboratory □ Testing in an AMCA Accredited Laboratory
Location ___________________________

FAN TYPE:
□ Agricultural Fan □ Circulating Fan □ Positive Pressure Ventilator
□ Air Curtain □ Energy Recovery Ventilator □ Propeller Fan
□ Axial Fan □ Evaporative Cooler □ Power Roof Ventilator
□ Ceiling Ventilator □ Induced Flow Fan □ Smoke Management Fan
□ Centrifugal Fan □ Jet Tunnel Fan □ Other _________________
□ Mixed Flow Fan

□ Production Sample □ Pre-Production Sample


Test Number
Test Standard
Figure No./Installation
Type
Date of Test
Model Number
Test Speed (rpm)
Impeller Diameter
Number of Blades
Blade Pitch Angle
(Curb Height
) (inches)
Sizes Rated from this Test
Other
Appurtenances Used During Testing
Inlet Bell
Shutter/Damper
Screen(s)
Other

Method used for calculating sound ratings (if applicable):


Full Octave Bands One-Third Octave Bands
Generalized Method □ □
Specific Method □ □

□ Belt Drive □ Direct Drive

Rating Method:
□ A - Constant Speed, Transmission Loss Not Included
□ B - Constant Speed, Transmission Losses Included
□ C - As Run Speed, Transmission Losses Included, Low Slip Motor
□ D - Direct Drive, Constant Speed, Low Slip Motor
□ E - Direct Drive, As Run Speed, Low Slip Motor
□ F - Direct Drive, As Run Speed, High Slip Motor
□ G - Air Curtain
□ H - Direct Drive, Jet Tunnel Fan, As Run Speed
□ I - Agricultural Fan, As Run Speed, Transmission Losses Included, Low Slip Motor
□ J - Direct Drive, PPV, As Run Speed
□ K - Direct Drive, Circulator Fan, As Run Speed
□ L – Induced Flow Fans
Rev. 12/07
AMCA CERTIFIED RATINGS SEAL
AERODYNAMICALLY SIMILAR APPLICATION FORM CRP A

TO: AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC.


Please accept this application to extend the license to use the AMCA Certified Ratings Seal to the product listed
hereon. This product is aerodynamically similar to our product ________________________, which is licensed to bear
the AMCA Seal under our License Appendix No. ________.

Application for rating:


Air Performance
Sound & Air Performance
Air Leakage
Efficiency Sound & Air Performance
CFM/Watt Air Performance
Induced Flow Fan Sound & Air
Efficiency Air Performance Performance
PPV Air Performance Residential Sound & Air Performance
Induced Flow Fan Air Performance Inlet Sound
Residential Air Performance Outlet Sound
Smoke Management Fan Performance Total Sound
Smoke Management Fan Performance One-Third Octave Bands
Reversible Operation
Octave Bands
Water Penetration
Hemispherical Sones
Wind Driven Rain
Spherical Sones

LwA

Company Name ___________________________________________________ Date __________________


Address ________________________________________________________________________________
Authorized Signature ______________________________ Print Name ______________________________

PRODUCT INFORMATION
Aerodynamically Similar Product Name: Originally Licensed Product Name:
(As to be listed in the Directory)

________________________________________ __________________________________

________________________________________ _________________________________

Rev. 12/07
SIZE AERODYNAMICALLY SIMILAR ORIGINALLY LICENSED PRODUCT
PRODUCT MODEL NUMBER MODEL NUMBER

Rev. 12/07
AMCA CERTIFIED RATINGS SEAL
NAMEPLATING APPLICATION FORM CRP B

TO: AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC.


Please accept our application for license to use the The Original Licensee is currently licensed to use the
AMCA Certified Ratings Seal on the product listed AMCA Seal on the product referenced hereon and is in
hereon. We are purchasing this product under brand full agreement with the content of this application. We
naming arrangement from understand that the license to use the AMCA Seal is
dependent on the Original Licensee maintaining full
______________________________________. compliance with AMCA's Certified Ratings Program.
(Original Licensee)

Application for rating:


Air Performance

Air Leakage Sound & Air Performance

CFM/Watt Air Performance Efficiency Sound & Air Performance

Efficiency Air Performance Induced Flow Fan Sound & Air


Performance
PPV Air Performance
Residential Sound & Air Performance
Induced Flow Fan Air Performance
Inlet Sound
Residential Air Performance Outlet Sound
Total Sound
Smoke Management Fan Performance
One-Third Octave Bands
Smoke Management Fan Performance Octave Bands
Reversible Operation Hemispherical Sones
Spherical Sones
Water Penetration LwA
Wind Driven Rain

Applicant Company

Company Address

Authorized Signature Date

Print Name Title

We have examined this application and its content and we fully endorse it.

Original Licensee ________________________________________________________________

Address ____________________________________________________________________

Authorized Signature _______________________________ Date ______________________

Print Name ____________________________________ Title _________________________

Rev. 12/07
PRODUCT INFORMATION

Applicant Company Original Licensee

Product Name (As to be listed in the Directory) Product Name (As to be listed in the Directory)

APPLICANT ORIGINAL LICENSEE


SIZE MODEL NUMBER SIZE MODEL NUMBER

Rev. 12/07
AMCA CERTIFIED RATINGS SEAL
ALTERNATE MANUFACTURER APPLICATION FORM CRP L

TO: AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC.


Please accept our application for license to use the We certify that our product is identical to that produced
AMCA Certified Ratings Seal on the product listed by the Original Licensee. The Original Licensee is
hereon. We are manufacturing this product licensing currently licensed to use the AMCA Seal on the
arrangement from product referenced hereon and is in full agreement with
the content of this application. We understand that the
______________________________________. license to use the AMCA Seal is dependent on the
(Original Licensee) Original Licensee maintaining full compliance with
AMCA's Certified Ratings Program.

Application for rating:


Air Performance
Sound & Air Performance
Air Leakage
Efficiency Sound & Air Performance
CFM/Watt Air Performance
Induced Flow Fan Sound & Air
Efficiency Air Performance Performance

PPV Air Performance Residential Sound & Air Performance

Induced Flow Fan Air Performance Inlet Sound


Outlet Sound
Residential Air Performance Total Sound
Smoke Management Fan Performance One-Third Octave Bands
Octave Bands
Smoke Management Fan Performance Hemispherical Sones
Reversible Operation Spherical Sones
Water Penetration LwA

Wind Driven Rain

Applicant Company

Company Address

Authorized Signature Date

Print Name Title

We have examined this application and its content and we fully endorse it.

Original Licensee ________________________________________________________________

Address ____________________________________________________________________

Authorized Signature _______________________________ Date ______________________

Print Name ____________________________________ Title _________________________

Rev. 12/07
PRODUCT INFORMATION
Applicant Company Original Licensee

Product Name (As to be listed in the Directory) Product Name (As to be listed in the Directory)

APPLICANT ORIGINAL LICENSEE


SIZE MODEL NUMBER SIZE MODEL NUMBER

Rev. 12/07
CATALOG CHECKING CHARGES
Effective December 15, 2007

PRINT CATALOGS

Performance Data Check (Per Product Line)


Air Performance .................................................................................................................... $180.00
Sound Performance .............................................................................................................. $180.00
Louver or Damper ................................................................................................................. $180.00
Airflow Measurement Station ................................................................................................ $225.00
Acoustical Duct Silencer........................................................................................................ $225.00

Format Check
4 Pages or Less .................................................................................................................... $135.00
5-50 Pages ............................................................................................................................ $225.00
50+ Pages ............................................................................................................................. $360.00

Catalog Revision, Performance Data Not Altered (Per Product Line)


Spot Check............................................................................................................................ $135.00

Brand Naming Products, CRP-B Forms (Per Product Line)


Performance data and format comparison ............................................................................ $180.00

Alternate Manufacturers, CRP-L Forms (Per Product Line)


OEM Catalog......................................................................................................................... $180.00
Own Catalog.......................................................................................................................... $270.00

ELECTRONIC CATALOGS

First Version .................................................................................................................................................... $900.00


Revised Version .............................................................................................................................................. $450.00

CATALOGS REQUIRING CORRECTIONS AS A RESULT OF 1ST REVIEW


Format Check
Second Review ....................................................................................................................... $75.00
Third Review ........................................................................................................................... $50.00
Data Check
Second Review ...............................................................................................50% of data check fee
Third Review ...................................................................................................25% of data check fee
FEES ARE SUBJECT TO CHANGE WITHOUT NOTICE
Rev. 12/15/07