Академический Документы
Профессиональный Документы
Культура Документы
INSTRUCTION: Study the lesson notes carefully. You will be required to answer an assignment
from the lesson.
A circuit breaker is a mechanical switching device capable of making, carrying and breaking
current under normal circuit conditions and also making current, carrying it for a specified time
and breaking it under abnormal circuit conditions.
A circuit breaker is not intended for frequent operation. Unlike the fuse, the circuit breaker
enables supply to be restored quickly.
The figure below shows the fault clearing process involving a circuit breaker;
BUSBAR
Relay contactor
When a fault occurs, current is increased due to reduced fault impedance. The CT energizes the
relay coil and the relay contacts are closed. The trip coil separates the circuit breaker contacts
and therefore opens the circuit.
1.3 CLASSIFICATION OF CIRCUIT BREAKERS
There are two modes of arc extinction techniques in circuit breakers and these are;
In high resistance interruption, the resistance of the arc is increased by lengthening and cooling
the arc so that the voltage is not able to maintain the arc.
High resistance interruption is employed in air-break circuit breakers and d.c circuit breakers.
In this method, the arc is extinguished at natural current zero of the a.c waveform, and is
prevented from restriking by rapid build-up of dielectric strength of the contact space.
Low resistance interruption method of arc extinction is employed in almost all a.c circuit
breakers.
This is the transient voltage of a higher natural frequency appearing across the contacts of a
circuit breaker after current zero. Restriking voltage tends to re-strike the arc.
Frequency of restriking voltage (TRV) is given by;
1
ftrv =
2 π √ (LC)
This is the power frequency system voltage on which the restriking voltage is superimposed
before it dies down.
Basically, the voltage appearing across the terminals of the circuit breaker after current zero is
composed of the restriking voltage and the recovery voltage.
This is the rate of increase of restriking voltage expressed in volts per microsecond.
de
RRRV = volts/µs
dt
em
RRRV = volts/µs
tm
Where
em
Amplitude factor =
Em
1.6 EQUATION OF RESTRIKING VOLTAGE
t
e = Em [1 – cos ]
√ ( LC)
Where
L = Inductance in Henry
C = Capacitance in Farad
t = Time in seconds
Therefore
de
RRRV =
dt
de Em t
= sin
dt √ (LC) √ (LC)
d2e
=0
dt 2
Em t
cos =0
LC √ ( LC)
Thus
t π
=
√ (LC) 2
π
t= √(LC)
2
de π
Therefore, maximum RRRV is the value of at t = √(LC)
dt 2
Em
∴ RRRVmax =
√ (LC)
de
Further, peak restriking voltage occurs when e is maximum i.e. when =0
dt
t
=π
√ ( LC)
Thus
t = π √(LC)
EXAMPLE
A 50 Hz, 3-phase alternator with grounded neutral has inductance of 1.6 mH per phase and is
connected to the busbar through a circuit breaker. The capacitance to earth between the
alternator and the CB is 0.003μF per phase. The circuit breaker opens when r.m.s value of
current is 7500 A. Determine;
SOLUTION
i. Erms = IXL
= 7500 X 2πfL = 7500 X 2π X 50 X 1.6mH = 3769.91 V
Em = √2 x 3769.91 = 5331 V
Em 5331
RRRV = = = 2434 V/μs
√ (LC) √ (1.6 mH X 0.003 μF)
d2e
ii. Maximum rate of rise of restriking voltage occurs when =0
dt 2
Thus
π
t= √(LC)
2
π
t = X 2.19 X 10-6 = 3.44 µs
2
iii. Frequency of oscillations is given by;
1 1
= = 72643.96 Hz
2 π √ (LC) 2 π √ (1.6 mH X 0.003 μF)
EXERCISE
A three phase alternator has the line voltage of 11 KV. The generator is connected to a circuit
breaker. The inductive reactance up to the circuit breaker is 5 Ω per phase. The distribution
capacitance up to the circuit breaker between phases and neutral is 0.01 μF. Determine;
i. Breaking capacity
ii. Making capacity
iii. Short-time capacity
Breaking capacity is the r.m.s current that a circuit breaker is capable of breaking
(interrupting) at a given recovery voltage and under specified conditions such as power
factor and rate of rise of restriking voltage
Recovery voltage is a power frequency system voltage on which the restriking voltage is
superimposed upon opening the contacts of the circuit breaker. The frequency of the
recovery voltage is 50 Hz.
Restriking voltage (or TRV) is a transient voltage of higher natural frequency appearing
across the contacts of the CB after current zero.
Rate of rise of restriking voltage (RRRV) is the rate of increase of restriking voltage
expressed in volts per microsecond.
The breaking capacity is always stated as the r.m.s value of fault current at the instance of
contact separation.
It is common practice to express the breaking capacity in MVA by taking into account the
rated breaking current and rated service voltage. Thus, if I is the rated breaking current in
amperes and V is the rated service line voltage in volts, then for a three phase circuit;
In Britain, it is usual practice to take breaking current equal to the symmetrical breaking
current. However, in America, breaking current is taken to be equal to the asymmetrical
breaking current. Therefore, the American rating given to a circuit breaker is higher than the
British rating.
Breaking capacity may be defined as the rated symmetrical breaking current at a rated
voltage.
There is always a possibility of closing or making the circuit under short circuit conditions.
The capacity of a breaker to make current depends upon its ability to withstand and close
successfully against the effects of electromagnetic forces.
Making capacity of a circuit breaker is the peak value of current during the first cycle of
current wave after the closure of the circuit breaker.
Making current is equal to the maximum value of asymmetrical current. To find this value,
multiply symmetrical breaking current by √2 to convert from r.m.s to peak, and then
multiply by 1.8 to include the ‘doubting effect’ of maximum asymmetry.
√2 x 1.8 = 2.55
Therefore
Short-time rating of a circuit breaker is the period for which the circuit breaker is able to carry
fault current while remaining closed.
Sometimes, a fault on the system is of temporary nature and will persist only for one or two
seconds after which it is automatically cleared. In the interest of continuity of supply, the
breaker should not trip in such situations. This means that the circuit breaker should be able to
carry high current safely for some specified period while remaining closed.
The short-time rating of a circuit breaker depends upon its ability to withstand the
electromagnetic force effects and the temperature rise.
Normal current rating is the r.m.s value of current which the circuit breaker is capable of
carrying continuously at its rated frequency under specified conditions.
EXAMPLE
A circuit breaker is rated as 1500 A, 1000 MVA, 33 KV, 3-second, 3-phase oil circuit breaker.
Find;
SOLUTION