SIPROTEC 5

Configuration
Aug 18, 2020 7:59 AM

Device: 6MD85 Bay Controller

Product code
Short: P1G153092
Long: 6MD85-DAAA-AA0-0AAAA0-AF0111-23111B-AAA000-000AC0-CB3BA1-CG0CG0-CG0

Firmware: Current version


Housing width: 5/6 x 19''
Housing type: Flush mounting
Binary inputs: 59
Binary outputs: 33 Relays (27 Standard, 6 Fast, 0 High-Speed, 0 Power)
Current transformers: 0 for protection
4 for measurement and sensitive ground-current detection
Voltage transformers: 4 standard
Measuring-transducer inputs: 0 (20 mA or 10 V, fast)
0 (20 mA, standard)
CPU: CP300
Modules in 19" row 1: IO202 , PS201 , IO207 , IO207 , IO207
Modules in 19" row 2:
LEDs/Push-buttons: 32 LEDs
Operation Panel: Integrated
Key switch: Without
Display type: Large display
Front Design: Standard
Power Supply: DC 60 V-250 V, AC 100 V-230 V
Redundant Power Supply: No

Communication/Plug-in modules:
Communications encryption: Normal
Integrated Ethernet port J: for DIGSI 5
Plug-in module position E: ETH-BA-2EL: 2x electric Ethernet 100 Mbit/s, RJ45 Communication Protocols:
applicable for DIGSI 5, IEC 61850-8-1 MMS and GOOSE, IEC 60870-5-104,
DNP3 TCP, Modbus TCP, Synchrophasor (IEEE C37.118 - IP), Profinet IO, SUP,
DHCP, SNTP, SNMP, etc. Redundancy protocols: Line Mode, RSTP, HSR, PRP
Plug-in module position F: Port is available but not assembled
SIPROTEC 5
Configuration
Aug 18, 2020 7:59 AM

Functions:
Function points class: Base + 50 function points

Note on function-points class


The function-points class results from the sum of the function points of the selected functions. You can apply these
functions as selected. The device allows also each other selection of functions as long as the sum of the required
function points is within the selected function-points class. With the maximum function-points class of 1400 it is
possible to activate all the functions in the device. The function-points exceeding 1400 are free of charge. In the
engineering phase DIGSI 5 checks that the selected configuration is suitable (capable of running in the device) before
loading it to the device.

Miscellaneous:
Warranty: 5 years
Firmware: Current version
SIPROTEC 5
Configuration
Aug 18, 2020 7:59 AM

Functional scope 6MD85 Bay Controller:


Always Add selected Result
ANSI Function Abbr. included Qty. x Value = Points Qty.
Protection functions for 3-pole tripping 3-pole

Hardware quantity structure expandable I/O

Process Bus Client Protocol (Note: This PB client x 100 =


function requires at least one dedicated
ETH-BD-2FO plug-in module, with
V8.0)
IEC61850-9-2 Merging Unit stream MU x 200 =
(Note: This function requires a
dedicated ETH-BD-2FO per stream,
with V8.0)
25 Synchrocheck, synchronization function Sync 1 x 50 = 50 1x
27 Undervoltage protection: "3-phase" or V< x 5 =
"universal Vx"
27R, Rate-of-voltage-change protection (from dV/dt x 5 =
59R V8.30)
32, 37 Power protection active/reactive power P<>, x 10 =
Q<>
38 Temperature supervision >

46 Negative-sequence overcurrent I2> x 10 =


protection
49 Thermal overload protection , I²t

50/51 Overcurrent protection, phases I> x 20 =


TD
Instantaneous tripping at switch onto SOTF
fault
50HS Instantaneous high-current tripping I>>>

50N/ Overcurrent protection, ground IN> x 20 =


51N TD
51V Overcurrent protection, voltage t=f(I,V) x 10 =
dependent
59 Overvoltage protection: "3-phase" V> x 5 =
or "positive-sequence system V1" or
"universal Vx"
67 Directional overcurrent protection, I>, (V,I) x 35 =
phases
SIPROTEC 5
Configuration
Aug 18, 2020 7:59 AM

Functional scope 6MD85 Bay Controller:


Always Add selected Result
ANSI Function Abbr. included Qty. x Value = Points Qty.
67N Directional overcurrent protection, IN>, (V,I) x 35 =
ground
74TC Trip-circuit supervision TCS

74CC Closed-circuit supervision (from V7.9) CCS x 5 =


81 Frequency protection: "f>" or "f<" or "df/ f<>; df/ x 5 =
dt" dt<>
81U Underfrequency load-shedding f<(UFLS) x 15 =
86 Lockout

90V Automatic Voltage controller for two- x 150 =


winding transformer
90V Automatic Voltage controller for two- x 180 =
winding transformer with parallel
operation
Number of two-winding transformers 2x x 5 = 2x
with parallel operation (Note: only
together with the function "Automatic
Voltage controller for two-winding
transformer with parallel operation")
90V Automatic Voltage controller for three- x 200 =
winding transformer
90V Automatic Voltage controller for grid x 175 =
coupling transformer
PMU Synchrophasor measurement PMU x 40 =
AFD Arc-protection (only with plug-in module
ARC-CD-3FO)
Measured values, standard

Measured values, extended: Min, Max, x 3 =


Avg
Basic PQ measurements: THD and
harmonics (from V8.01)
Switching statistic counters

Circuit-breaker wear monitoring Ix, I²t, 2P x 10 =


CFC (Standard, control)

CFC arithmetic x 40 =
SIPROTEC 5
Configuration
Aug 18, 2020 7:59 AM

Functional scope 6MD85 Bay Controller:


Always Add selected Result
ANSI Function Abbr. included Qty. x Value = Points Qty.
Switching sequences function x 5 =
Inrush current detection

External trip initiation

Control

Circuit-breaker 4x x 3 = 4x
Disconnector/Grounding switch 4x x 3 = 4x
Fault recording of analog and binary
signals
Monitoring and supervision

Protection interface, serial

Frequency-tracking groups (from V7.8)

Temperature acquisition via


communication protocol
Cyber Security: Role-Based Access x 25 =
Control (from V7.8)
Sum: 50