FireNET Plus Wiring Instructions

This manual provides wiring instructions for the 1 loop and 2 loop version of the FireNET
Plus panels, which supports our finest Hochiki’s DCP protocol.

Note: Refer to wiring diagrams for specific part numbers and descriptions of all fire control
panels covered in this manual. The operation of this product is intended for indoor use only.

Table of Contents
1. Front Panel View ................................................................................................................................ 2
2. Wiring Gauge ...................................................................................................................................... 2
3. Reference Documents ....................................................................................................................... 2
4. Terminal Connection .......................................................................................................................... 3
5. Model Description............................................................................................................................... 3
6. Power Supply Circuit ......................................................................................................................... 4
7. Battery Circuit ..................................................................................................................................... 5
8. Ground Fault ....................................................................................................................................... 5
9. Power Output Circuits ........................................................................................................................ 5
10. Limited Energy Circuit ................................................................................................................... 6
11. Supervised Circuits ........................................................................................................................ 6
12. SLC Circuits .................................................................................................................................... 6
13. NAC Circuits .................................................................................................................................... 6
1. Maximum Current Ratings ................................................................................................................ 7
2. Single and Dual Circuit Synchronization ........................................................................................... 7
14. Communication Circuits ................................................................................................................ 7
15. Relay Circuits .................................................................................................................................. 8
16. Auxiliary Voltage Circuits .............................................................................................................. 9

Version 1.01
Created: 02/07/2012
PN# 1700-10842

FireNET Plus Wiring Instruction 1 V1.01


1. Front Panel View
The figure below is the front panel view of the FireNET Plus Panel:

38 39 40 41

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37
P1R

P2R
L1R

L2R
P1T

P2T
L1T

L2T
E E + - + - + - + - + - + - NC C NO NC C NO NC C NO + - + - + - + - + -

24V OUT AUX 24V NAC 1 NAC2 SLC1 IN SLC1 OUT TROUBLE FIRE SUPERVISORY NET OUT NET IN COMMS SLC2 OUT SLC2 IN

Fire More Events


1
General
AC Power On
Disablement
4 ? 2
Pre-Alarm General Trouble

On Test Power Trouble 3

Supervisory JP1
Delay Active

AC Power On NAC Trouble Exit Enter

Enable Access
Re-Sound Alarm Panel Sounder Lamp Programmable More More
Reset Fire Drill
Alarm Silence Silence Test Function Fire Events Events

PC
PC / Dialer Reset Watchdog Watchdog Contrast
Operated Reset

Battery
Connection AC POWER
+ - L N E

Figure 1

2. Wiring Gauge
Use 18 to 14AWG wiring for all field terminations except for AC terminal block. Use
14AWG only for line, neutral and ground of the AC terminations.

3. Reference Documents
For additional information on installing and operating the FireNET Plus Panel, refer to
the following documents:

 FireNET Plus Installation and Operating Manual, 1700-10840, Version 1.04


 Operating Instruction, 1700-10850, Version 0.3
 Inner Door Label, 1700-04520, Version 1.04

FireNET Plus Wiring Instruction 2 V1.01


4. Terminal Connection
The figure below illustrates the terminal connections of the FireNET Plus Panel:

Earth Ground NAC 1 SLC 1 SLC 2


10K EOL Resistor Zero-Ohm Resistor Zero-Ohm Resistor
VF1544-00 VF1544-00 VF1544-00
TELCO 1

NAC 2 Network
TELCO 2 10K EOL Resistor IN
VF1544-00

24V OUT Network Comms


24 VDC OUT RS485

AUX 24V
Relays
24 VDC

38 39 40 41

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37
P1R

P2R
L1R

L2R
P1T

P2T
L1T

L2T

E E + - + - + - + - + - + - NC C NO NC C NO NC C NO + - + - + - + - + -

24V OUT AUX 24V NAC 1 NAC2 SLC1 IN SLC1 OUT TROUBLE FIRE SUPERVISORY NET OUT NET IN COMMS SLC2 OUT SLC2 IN

Figure 2

5. Model Description
The following are the details of the various FireNET Plus Models:

• FNP-1127 – 1 SLC Loop, Not Expandable


• FNP-1127D – 1 SLC Loop with Integrated DACT, Not Expandable
• FNP-1127E – 1 SLC Loop Expandable to 2 SLC Loops and Networkable
• FNP-1127DE – 1 SLC Loop with Integrated DACT, Expandable to 2 SLC Loops
and Networkable

FireNET Plus Wiring Instruction 3 V1.01


6. Power Supply Circuit
Following table is the electrical specification for the Power Supply Circuit:

Line Connection

Terminals Description Voltage Current

L AC Line 115 VAC @ 50/60 Hz 2.1 A max

230 VAC @ 50/60 Hz 1.1 A max

N AC Neutral

Earth Ground
G

Power Supply

Parameter Description

Rating 115 VAC @ 250 VA


230 VAC @ 250 VA

AC Input Fuse 3 A, 250 VAC, Slow-Blow, 5 x 20 mm

Input (Supervised) 115 VAC 50/60 Hz or


230 VAC 50/60 Hz

Transfer Voltage 115 VAC transfer @ 75 VAC


230 VAC transfer @ 160 VAC

FireNET Plus Wiring Instruction 4 V1.01


7. Battery Circuit
Following table is the electrical specification for the Battery Circuit:

Parameter Description

Standby-Battery Type Two 12 VDC, 50 AH, Sealed Lead Acid (SLA), batteries

Standby-Battery Charging Two standby batteries wired in series

Charge Current Fast charge: 1.25 A


Trickle charge: 1.25 A (voltage limited)

Output Current 0 - 4 Amps

Standby-Operating Time 24 Hours

Battery Charge Voltage 27.6 VDC

Fire Control Panel Current Draw D.P. - TBD mA with buzzer sounding
From Battery While In Mains Fail,
Standby And Not in Alarm

Maximum Current Draw D.P. - TBD mA (Current does not include loads from NACs, Solenoid, Remote
of FACP, In Alarm Annunciators, Ancillary Boards and Auxiliary equipment)

Maximum Current Draw 4 Amps


From Batteries

8. Ground Fault
A ground fault indication occurs when 30K Ohms or less is detected between earth
ground and the following field terminals of the FireNET Plus Panel:

 24V OUT
 AUX 24V
 NAC1 and NAC 2
 SLC1 and SLC2
 NET IN and NET OUT
 COMMS

9. Power Output Circuits


Special Application outputs are provided on the NAC1 and NAC2 terminals of the
FireNET Plus Panel.

FireNET Plus Wiring Instruction 5 V1.01


10. Limited Energy Circuit
All circuits are power limited except for AC input/output and the battery.

11. Supervised Circuits


All circuits of the FireNET Plus Panel are supervised except relay terminals for the
TROUBLE, FIRE, SUPERVISORY and the TELCO.

12. SLC Circuits


SLC circuits of the FireNET Plus Panel operates with Hochiki’s DCP-Protocol.

Terminals Description

SLC1 IN, SLC1 OUT Signaling Line Circuits are Class A, Style 7, Class A, Style 6 or Class B,
and SLC2 IN, SLC2 OUT Style 4.

13. NAC Circuits


Following table is the specification for the Notification Appliance Circuits (NAC1 and
NAC2):

Parameter Description

Fuse Self-resetting 1.6 A electronic

Regulated Continuous Current Continuous DC currents cannot exceed 1.6 A from NAC 1 and NAC with the
total DC current not to exceed 3.2 A.

Regulated Pulsed Current: Pulse DC currents cannot exceed 900 mA from NAC 1 and NAC with the total
DC current not to exceed 1.8 A.

Special Application 24 VDC @ 2.3 A continuous with the combined current of NAC 1 and NAC 2
not to exceed 3.1 A.

Supervision EOL Device, 0400-01023

FireNET Plus Wiring Instruction 6 V1.01


Parameter Description

Synchronization Synchronize the regulated output of NAC 1 and NAC 2 with authorized and
compatible synchronization modules from Gentex, Amseco, System Sensor or
Wheelock. Connect End-Of-Line-Device 0400-01023 to the output of each
Synchronization Module installed.
The FireNET Plus Panel provides internal device synchronization
between the outputs of NAC 1 and NAC 2 when operating NAC devices
from Gentex, Amseco, System Sensor or Wheelock.
External synchronization modules must not be used on the NAC outputs when
operating in the special application mode.

NFPA Operation Type Class B, Style Y

1. Maximum Current Ratings


The total sum of device loads in the NAC circuit must not exceed the maximum current
specified for the FireNET Plus Panel when operating in Continuous Regulated, Pulsed
Regulated, or Special Application mode.

Note: Reference NAC manufacturer datasheets for individual device loads and then
compare the total sum to the maximum current capability of the FireNET Plus Panel in
regulated or special application mode.

2. Single and Dual Circuit Synchronization


NAC channels 1 and 2 of the FireNET Plus Panel provides single and dual circuit
synchronization. Single circuit synchronization provides a synchronized output on one of
two NAC channels. Dual circuit synchronization provides a synchronized output on both
NAC channels.

14. Communication Circuits


Phone Line Terminal Connections:

Terminal Description

L1T TELCO Line 1 Tip

L1R TELCO Line 1 Ring

P1T TELCO Phone 1 Tip

P1R TELCO Phone 1 Ring

L2T TELCO Line 2 Tip

FireNET Plus Wiring Instruction 7 V1.01


Terminal Description

L2R TELCO Line 2 Ring

P2T TELCO Phone 2 Tip

P2R TELCO Phone 2 Ring

RS485 Serial Bus:

Terminal Rating

COMMS (+) (+) Data 3.3 VDC @ 30 mA max

COMMS (-) (-) Data

Network Terminals:

Terminal Rating

NET OUT (+) (+) Data 3.3 VDC @ 30 mA max

NET OUT (-) (-) Data

NET IN (+) (+) Data 3.3 VDC @ 30 mA max

NET IN (-) (-) Data

15. Relay Circuits


The following is the specification for the FireNET Plus Panel Relays:

Parameter Description

Operation Common: Operates for all of the signals relative to its type (such as alarm, trouble, supervisory).

Current 1A maximum, volt free change over contact

Voltage 30 VDC max

Power Factor 1.0 PF

FireNET Plus Wiring Instruction 8 V1.01


16. Auxiliary Voltage Circuits
The following is the specification for the FireNET Plus Panel Auxiliary Voltage Circuits:

Terminal Description

24V OUT Regulated 24 VDC @ 360 mA max

AUX 24V Regulated 24 VDC @ 360 mA max

If you have any questions regarding this matter please contact Technical Support.

Hochiki America Corporation

Technical Support

1-800-845-6692

Technicalsupport@hochiki.com