Electrical Thumb Rules-(Part-6)


SEPTEMBER 5, 2013 14 COMMENTS Jignesh.Parmar

Transformer Earthing Wire / Strip Size:


Blog Stats
Size of T.C or DG Body Earthing Neutral Earthing
15,483,953 hits

<315 KVA 25×3 mm Cu / 40×6 mm GI Strip 25×3 mm Cu Strip

315 KVA to 500 KVA 25×3 mm Cu / 40×6 mm GI Strip 25×3 mm Cu Strip About Jignesh Parmar:
500 KVA to 750 KVA 25×3 mm Cu / 40×6 mm GI Strip 40×3 mm Cu Strip Jignesh Parmar has completed M.Tech (Power
System Control), B.E(Electrical). He is member
750 KVA to 1000 KVA 25×3 mm Cu / 40×6 mm GI Strip 50×3 mm Cu Strip
of Institution of Engineers (MIE) and CEng,India.
Membership No:M-1473586.He has more than
Motor Earthing Wire / Strip Size: 16 years experience in Transmission -
Distribution-Electrical Energy theft detection-
Size of Motor Body Earthing
Privacy & Cookies: This site uses cookies. By continuing to use this website, you agree to their use. Electrical Maintenance-Electrical Projects
(Planning-Designing-Technical Review- Close and accept
To find out more, including how to control cookies, see here: Cookie Policy Follow
< 5.5 KW 85 SWG GI Wire
coordination -Execution). He is Presently
associate with one of the leading business group
5.5 KW to 22 KW 25×6 mm GI Strip
as a Deputy Manager at Ahmedabad,India. He
has published numbers of Technical Articles in
22 KW to 55 KW 40×6 mm GI Strip “Electrical Mirror”, “Electrical India”, “Lighting
India”,”Smart Energy”, “Industrial
>55 KW 50×6 mm GI Strip Electrix”(Australian Power Publications)
Magazines. He is Freelancer Programmer of
Advance Excel and design useful Excel base
Panel Earthing Wire / Strip Size: Electrical Programs as per IS, NEC, IEC,IEEE
codes. He is Technical Blogger and Familiar with
Type of Panel Body Earthing English, Hindi, Gujarati, French languages. He
wants to Share his experience & Knowledge and
Lighting & Local Panel 25×6 mm GI Strip help technical enthusiasts to find suitable
solutions and updating themselves on various
Control & Relay Panel 25×6 mm GI Strip Engineering Topics.

D.G & Exciter Panel 50×6 mm GI Strip


Follow Blog via Email
D.G & T/C Neutral 50×6 mm Cu Strip Enter your email address to follow this blog and
receive notifications of new posts by email.

Electrical Equipment Earthing: Join 12,103 other followers

Enter your email address


Equipment Body Earthing
Follow This Blog by Email
LA (5KA,9KA) 25×3 mm Cu Strip

HT Switchgear 50×6 mm GI Strip Electrical Notes-…


22K likes
Structure 50×6 mm GI Strip

Cable Tray 50×6 mm GI Strip


Like Page

Fence / Rail Gate 50×6 mm GI Strip

BUY ELECTRICAL NOTES IN PDF

Earthing Wire (As per BS 7671)


Cross Section Area of Phase, Neutral Minimum Cross Section area of Earthing Conductor
Conductor(S) mm2 (mm2)

S<=16 S (Not less than 2.5 mm2)


BUY ELECTRICAL SOFTWARES
16<S<=35 16

S>35 S/2

Area for Transformer Room: (As per NBC-2005):


Transformer Min. Transformer Room Min. Total Sub Station Area( Min. Space Width BUY ELECTRICAL NOTE IN PDF
Size Area (M2) Incoming HV,LV Panel, T.C (Meter)
Roof) (M2)

1X160 14 90 9

2X160 28 118 13.5

1X250 15 91 9 BUY ELECTRICAL SOFTWARES.

2X250 30 121 13.5

1X400 16.5 93 9

2X400 33 125 13.5

Proud to be an IndiBlogger
3X400 49.5 167 18
electricalnotes.wordpress.c...

2X500

3X500
36

54
130

172
14.5

19
85 /100

2X630 36 132 14.5

3X630 54 176 19
SEARCH

2X800 39 135 14.5


Copyright © 2018
3X800 58 181 14 The content in electricalnotes.wordpress.com is
for personal, non-commercial use only. you can
2X1000 39 149 14.5 not reproduce,republish or communicate any of
the content , including files downloadable from
3X1000 58 197 19 this website, without the permission of the
copyright owner.The use of this content on any
other websites breaches copyright Act. If You
The Capacitor Bank should be automatic Switched type for Sub Station of 5MVA and Higher. find this content in any other site,it makes the
Transformer up to 25KVA can be mounted direct on Pole. page you are viewing an infringement of the
Transformer from 25KVA to 250KVA can be mounted either on “H” Frame of Plinth. copyright.
Transformer above 250KVA can be mounted Plinth only.
Transformer above 100MVA shall be protected by Drop out Fuse or Circuit Breaker.
Recent Posts
Span of Transmission Line (Central Electricity Authority):
Quick Reference -HVAC
Voltage Normal Span Thumb Rules-VENTILATION & CEILING FAN

Electrical Thumb Rules-Illumination-(Part-20)


765 KV 400 to 450 Meter
Quick Reference-Fire Fighting (Part-2)

400 KV 400 Meter Quick Reference-Fire Fighting (Part-1)

Electrical Thumb Rule- High Rise Building (As


220 KV 335,350,375 Meter per NBC)

Calculate Motor Pump Size


132 KV 315,325,335 Meter
Calculate Size of Cable for Motor (As NEC)

66 KV 240,250,275 Meter How to Design efficient Street lighting-(Part-6)

How to Design efficient Street lighting-(Part-5)

Max. Lock Rotor Amp for 1 Phase 230 V Motor (NEMA) How to Design efficient Street lighting-(Part-4)

How to Design efficient Street lighting-(Part-3)


HP Amp
How to Design efficient Street lighting-(Part-2)

1 HP 45 Amp How to Design efficient Street lighting-(Part-1)

Calculate Size of Pole Foundation & Wind


1.5 HP 50 Amp Pressure on Pole

Calculate Size of Circuit Breaker/ Fuse for


2 HP 65 Amp Transformer (As per NEC)

Selection of Various Types of UPS (Part-2)


3 HP 90 Amp
Selection of Various Types of UPS (Part-1)

5 HP 135 Amp Electrical Thumb Rules-Illumination-(Part-19).

Electrical Thumb Rules-Illumination-(Part-18).


7.5 HP 200 Amp

10 HP 260 Amp
Archives
December 2019 (1)

November 2019 (1)


Three Phase Motor Code (NEMA)
October 2019 (2)
HP Code
September 2019 (2)

August 2019 (2)


<1 HP L
July 2019 (2)
1.5 to 2.0 HP L,M June 2019 (1)

May 2019 (2)


3 HP K
April 2019 (3)

5 HP J March 2019 (2)

February 2019 (2)


7 to 10 HPPHPHPHHHHH H
January 2019 (3)

December 2018 (2)


>15 HP G
November 2018 (2)

October 2018 (1)


Service Factor of Motor:
September 2018 (2)
Synchronous Speed (RPM) August 2018 (3)

HP July 2018 (1)


3600 1800 1200 900 720 600 514
RPM RPM RPM RPM RPM RPM RPM June 2018 (1)

May 2018 (1)


1 HP 1.25 1.15 1.15 1.15 1 1 1
April 2018 (1)

March 2018 (1)


1.5 to 1.25 HP 1.15 1.15 1.15 1.15 1.15 1.15 1.15
February 2018 (2)

150 HP 1.15 1.15 1.15 1.15 1.15 1.15 1 January 2018 (1)

December 2017 (1)


200 HP 1.15 1.15 1.15 1.15 1.15 1 1
November 2017 (1)

> 200 HP 1 1.15 1 1 1 1 1 October 2017 (1)

September 2017 (1)

Type of Contactor: August 2017 (1)

July 2017 (2)


Type Application
June 2017 (1)

May 2017 (1)


AC1 Non Inductive Load or Slightly Inductive Load
April 2017 (1)
AC2 Slip Ring Motor, Starting, Switching OFF March 2017 (1)

February 2017 (1)


AC3 Squirrel Cage Motor
January 2017 (1)

AC4,AC5,AC5a, AC5b,AC6a Rapid Start & Rapid Stop December 2016 (1)

November 2016 (1)


AC 5a Auxiliary Control circuit
October 2016 (1)

AC 5b Electrical discharge Lamp September 2016 (1)

August 2016 (1)


AC 6a Electrical Incandescent Lamp July 2016 (1)

June 2016 (1)


AC 6b Transformer Switching
May 2016 (1)

AC 7a Switching of Capacitor Bank April 2016 (2)

March 2016 (2)


AC 7b Slightly Inductive Load in Household
February 2016 (2)

AC 5a Motor Load in Household January 2016 (2)

December 2015 (1)


AC 8a Hermetic refrigerant compressor motor with Manual Reset O/L Relay November 2015 (1)

October 2015 (2)


AC 8b Hermetic refrigerant compressor motor with Automatic Reset O/L Relay
September 2015 (1)

AC 12 Control of Resistive Load & Solid State Load August 2015 (1)

July 2015 (1)


AC 13 Control of Resistive Load & Solid State Load with Transformer Isolation
June 2015 (1)

AC 14 Control of small Electro Magnetic Load (<72 VA) May 2015 (1)

April 2015 (1)


AC 15 Control of Electro Magnetic Load (>72 VA)
March 2015 (2)

February 2015 (2)

Contactor Coil: January 2015 (2)

December 2014 (2)


Coil Voltage Suffix
November 2014 (2)
24 Volt T October 2014 (2)

September 2014 (2)


48 Volt W
August 2014 (3)

110 to 127 Volt A July 2014 (2)

June 2014 (2)


220 to 240 Volt B
May 2014 (2)

April 2014 (2)


277 Volt H
March 2014 (3)
380 to 415 Volt L February 2014 (4)

January 2014 (2)

December 2013 (1)


Rate this: November 2013 (1)
16 Votes October 2013 (2)

September 2013 (3)


Share this:
 Facebook  Email  LinkedIn  More
August 2013 (3)

July 2013 (3)


Like June 2013 (3)
Be the first to like this.
May 2013 (3)

April 2013 (2)


Related March 2013 (3)

Calculate Numbers of Thumb Rules-13 ( Quick Thumb Rule-12 (Quick February 2013 (2)
Plate/Pipe/Strip Earthings Reference Earthing -CPWD) Reference of DG Set) January 2013 (3)
(Part-3) With 6 comments With 13 comments
December 2012 (2)
With 30 comments
November 2012 (3)

October 2012 (1)


FILED UNDER UNCATEGORIZED
September 2012 (3)

August 2012 (7)

July 2012 (2)


About Jignesh.Parmar
Jignesh Parmar has completed M.Tech (Power System Control), B.E(Electrical). He is member of May 2012 (7)
Institution of Engineers (MIE) and CEng,India. Membership No:M-1473586.He has more than 16 April 2012 (2)
years experience in Transmission -Distribution-Electrical Energy theft detection-Electrical
March 2012 (3)
Maintenance-Electrical Projects (Planning-Designing-Technical Review-coordination -Execution). He is Presently
associate with one of the leading business group as a Deputy Manager at Ahmedabad,India. He has published February 2012 (2)
numbers of Technical Articles in “Electrical Mirror”, “Electrical India”, “Lighting India”,”Smart Energy”, “Industrial January 2012 (1)
Electrix”(Australian Power Publications) Magazines. He is Freelancer Programmer of Advance Excel and design
December 2011 (3)
useful Excel base Electrical Programs as per IS, NEC, IEC,IEEE codes. He is Technical Blogger and Familiar with
English, Hindi, Gujarati, French languages. He wants to Share his experience & Knowledge and help technical November 2011 (2)
enthusiasts to find suitable solutions and updating themselves on various Engineering Topics. October 2011 (4)

September 2011 (2)

August 2011 (1)


14 Responses to Electrical Thumb Rules-(Part-6)
June 2011 (5)

siva muthusamy says: May 2011 (3)


September 6, 2013 at 8:15 am
April 2011 (12)

Dear sir/madam l had received electrical thump rules 4,5,6. so i want electrical thump rules 1,2,3. so plase kindly March 2011 (17)
send me. thankyou M.SIVA

Reply
EEP

Jignesh.Parmar says:
September 6, 2013 at 2:23 pm

Is is already given in the Blog !!!!

Reply

Alex says:
September 10, 2013 at 11:21 am

Thank you for the valuable notes.

Reply

Amit Khari says:


September 10, 2013 at 7:41 pm

Pages
Dear Sir,
Thanks for valuable info.Kindly send me SLD of PCC in LT panel……. Abstract

Reply Abstract of CPWD-Part 1

Abstract of IE Rules

Abstract of IS Code.
KRISHNA R says:
September 12, 2013 at 9:45 am IS 1255

Sir .. Thank u for the Valuable information.. Can u pls upload details of Panel fabrication. IS 15652/11171/1445/1678

IS 3043 / 5039
Reply
IS 5613

IS 694 / 1554 / 11892


farooq ahmed rather says:
September 12, 2013 at 12:46 pm IE Rules for DP Structure

dear sir .
Electrical Notes
the thumb rule of electrical note is very help full
ElectRICAL. Q&A
Reply
Electrical Q&A Part-1

Electrical Q&A Part-2


abdul khadeer says:
Electrical Q&A Part-3
September 13, 2013 at 5:03 am
Electrical Q&A Part-4
thankx so much RESPECTED SIR
to share ur lot of experience with us Electrical.Tool

Reply
EXCEL TOOL

angelito Cortez says:


Top Clicks
October 10, 2013 at 7:11 am electricalnotes.files.wor…

Thank you so much for the very interesting information.More power and God Bless.Can you give me information gumroad.com/l/wzDt
on how to calculate cables size current capacity in meters. mediafire.com/file/5040ut…
Regards, Angelito mediafire.com/file/2v7lk1…

Reply instamojo.com/jiguparmar/…

mediafire.com/file/0qu8mt…

Yasir Liaquat says: mediafire.com/file/vc7vfk…


October 13, 2013 at 3:36 am
mediafire.com/file/1us8d4…

Sir Thanks alot for Shairing Such a Very very helpful Informative… ALLAH bless you… and keep on sir… Once mediafire.com/file/0e1g7r…
again Thanks
electricalnotes.files.wor…
Reply

Recent Comments
syed shahbaz hussain says: Peter Nena on Calculate Street Light Pole’s…
September 8, 2016 at 6:19 pm
shiv kumar on Electrical Thumbs Rules (…

Hi!Sir.Hope you are doing good.I’m very much thankful to you for this kind information regarding Electrical system. Muhammad Mohsin Ansa… on Quick
My question to you is my transformer is 315KVA so, what should be the size of the HT Cable.And also please let Reference -HVAC
me know that how to select the HT cable? Dr Mukesh Kumar on Thumb Rules-
VENTILATION &…
Thanks & Regards
Muhammad Mohsin Ansa… on Thumb Rules-
Shahbaz Hussain.
VENTILATION &…
Reply Muhammad Mohsin Ansa… on Electrical
Thumb Rules-Illumin…
Muhammad Mohsin Ansa… on Quick
Aravind says:
Reference-Fire Fighting…
April 8, 2017 at 1:49 am
Nikhil Garde on Quick Reference-Fire
Sir Fighting…
We have a cold storage with all the electrical load @ 197 hp. J.Sridharan on Electrical Thumb Rule- High
Right now we have a 185 Sq.mm cable from the transformer to the panel. Ri…
When we are operating at full load the 185Sq.mm cable is heating up & mains are getting burnt out. Can you Muhammad Mohsin Ansa… on Electrical
suggest suitable cable, & mains size. Thumb Rule- High Ri…

Reply

pradeep kumar says:


July 19, 2017 at 10:43 am

Dear Sir,

how we calculate earthing strip size and wire size for ESD (electrostatic discharge) and EPA (earth protection
area) in electronics assembly line. We are using ESD mat, ESd tile to discharge electrostatic charge.

Reply

nagendra says:
February 9, 2018 at 1:40 pm

in two same capacity dg synchronization, what should be the rating of between 2 dg bus coupler,.
is same of single dg or double of that.

Reply

shailendra sengar says:


December 20, 2018 at 4:32 pm

contactor voltage is ac or dc in contactor coil section as you indicated suffix

Reply

Leave a Reply

Enter your comment here...

This site uses Akismet to reduce spam. Learn how your comment data is processed.

Вам также может понравиться