Вы находитесь на странице: 1из 1

1 x 3 x 1.50 mm2 0.

6/1kV Cable

CONSTRUCTION CABLE STANDARDS


Conductor IEC 60502-1, IEC 60228
Annealed Copper Oil Resistant to ICEA S-82-552 4h, 70ºC
Flame Retardant to IEC 60332-3-24
Insulation
Sunlight Resistant to UL 1581-1200
XLPE 90 Degrees C

Inner Sheath
PVC FR
The electrical and dimensional properties of this product are measured by the
Metal Armour Technical and Quality Assurance department at the Eland Cables laboratory. Cable
performance in respect of conductor resistance, construction quality (workmanship),
Galvanised Steel Wire (90% Coverage)
dimensional consistency, and other parameters are verified to published standards
and approved product drawings. Conformance to RoHS (Restriction of the use of
Outer Sheath
Hazardous Substances) is determined and confirmed.
PVC FR

CHARACTERISTICS
Voltage Rating
0.6/1kV

Core Identification
Per Specification

Inner Sheath Colour


Black

Outer Sheath Colour


Black

DIMENSIONS

CONSTRUCTION NOMINAL CROSS SECTIONAL NOMINAL CONDUCTOR NOMINAL INSULATION NOMINAL CORES
AREA COMPOSITION THICKNESS DIAMETER
mm2 mm mm mm

1x3 1.50 7x.0.52 0.70 6.50


1x3 4 7x0.85 0.70 8.60

NOMINAL INNER NOMINAL WIRE NOMINAL OUTER NOMINAL OVERALL NOMINAL DIAMETER OF NOMINAL WEIGHT
SHEATH THICKNESS DIAMETER OF METAL SHEATH THICKNESS DIAMETER UNDER ARMOUR kg/km
mm ARMOUR mm mm mm
mm
1.00 0.90 1.80 13.90 8.50 394
1.00 1.25 1.80 16.70 10.60 644

ELECTRICAL CHARACTERISTICS
NOMINAL CROSS SECTIONAL AREA MAXIMUM RESISTANCE NOMINAL MUTUAL CAPACITANCE NOMINAL L/R RATIO
mm2 Ohm/km uF/km
1.50 12.100 - 40
4 4.610 - -

UK T 020 7241 8787 | F 020 7241 8700 | sales@elandcables.com | www.elandcables.com


technicalspecification
International T +44 20 7241 8740 | F +44 20 7241 8700 | international@elandcables.com