Академический Документы
Профессиональный Документы
Культура Документы
TRAINING MANUAL
TK50390-4-TM (08-01).
Introduction & Safety Precautions
THERMO KING
INGERSOLL-RAND
Introduction
A. Table of Contents
B. Safety Precautions
1. Refrigeration Theory
5. Evacuation
7. AC Electricity
9. Microprocessor Controllers
17. Notes
1
Introduction & Safety Precautions
7. Be sure all mounting bolts are tight and are the correct Refrigerant Oil
length for their particular application. Observe the following precautions when working with or
around refrigerant oil: Do not allow refrigerant oil to contact
8. Use extreme caution when drilling holes in the unit. The your eyes. Do not allow prolonged or repeated contact with
holes may weaken structural components. Holes drilled skin or clothing. To prevent irritation, you should wash thor-
into electrical wiring can cause fire or explosion. Holes oughly immediately after handling refrigerant oil. Rubber
drilled into the refrigeration system may release refriger- gloves are recommended when handling Polyol Ester based
ant. refrigerant oil.
9. Use caution when working around exposed coil fins. The First Aid
fins can cause painful lacerations. Eyes: Immediately flush eyes with large amounts of water
for at least 15 minutes while holding the eyelids open. Get
10. Use caution when working with a refrigerant or refrigera- prompt medical attention.
tion system in any closed or confined area with a limited
Skin: Remove contaminated clothing. Wash thoroughly with
air supply (for example, a trailer, container or in the hold
soap and water. Get medical attention if irritation persists.
of a ship). Refrigerant tends to displace air and can cause
oxygen depletion, resulting in suffocation and possible Inhalation: Move victim to fresh air and restore breathing if
death. necessary. Stay with victim until arrival of emergency person-
nel.
Ingestion: Do not induce vomiting. Immediately contact a
local poison control center or physician.
2
Introduction & Safety Precautions
3
Introduction & Safety Precautions
1. Disconnect all power to the unit. 1. Disconnect all power to the refrigeration unit.
2. Avoid wearing clothing that generates static electricity 2. Disconnect all quick-disconnect wire harnesses from the
(wool, nylon, polyester, etc.). back of the µP-D controller. Also disconnect the wire
3. Do wear a static discharge wrist strap (TK P/N 204-622) harness from the Output module.
with the lead end connected to the microprocessor’s 3. If the unit is equipped with an Integrated Remote Moni-
ground terminal. These straps are available at most elec- tor Unit (IRMU)/Remote Communications Device
tronic equipment distributors. DO NOT wear these straps (RCD), disconnect all wire harnesses from the IRMU/
with power applied to the unit. RCD circuit board.
4. Avoid contacting the electronic components on the circuit 4. Switch all of the electrical circuit breakers in the control
boards of the unit being serviced. box to the OFF position.
5. Leave the circuit boards in their static proof packing 5. Weld unit and/or container per normal welding proce-
materials until ready for installation. dures. Keep ground return electrode as close to the area
6. If a defective microprocessor is to be returned for repair, to be welded as practical. This will reduce the likelihood
it should be returned in the same static protective packing of stray welding currents passing through any electrical
materials from which the replacement component was or electronic circuits.
removed. 6. When the welding operation is completed, the unit power
7. After servicing the circuit board and any other circuits, cables, wiring and circuit breakers must be restored to
the wiring should be checked for possible errors before their normal condition.
restoring power.
4
SECTION 1
Refrigeration Theory
1-1
Section 2-Basic Refrigeration System Operation
1-2
Section1 - Refrigeration Theory
Refrigeration Fundamentals
In this section you will learn the fundamental principles of heat transfer. These principles are the
foundation for your understanding of temperature control.
1-3
Section1 - Refrigeration Theory
Heat Is Everywhere!
The total absence of heat is 460 degrees below zero Fahrenheit
(-273°C). This is called absolute zero. It is unlikely that you will ever
experience "no heat". Even ice cream at -20°F (-29°C) contains heat
energy. We know this by the simple fact that the ice cream can be
made even colder by removing additional heat energy. Thermo King
units don’t make coldthey remove heat!
Heat enters a temperature controlled compartment from many
sources
• Product that is loaded too warm
• Heat from the sun and high outside temperatures
• Door openings during loading and unloading
• Heat generated by the cargo as it ripens
A Thermo King unit simply removes unwanted heat from a temperature-controlled compartment. If heat is
removed faster than it enters, the compartment gets colder. If heat is removed at the same rate it enters, compart-
ment temperature remains the same.
Heat Transfer
Heat energy normally transfers from one molecule to the next. But this movement of heat energy can only occur if
there is a difference in temperature between the two molecules. If two molecules (or any objects, for that matter)
are the same temperature, no heat transfer occurs. Heat energy always moves from higher energy areas (hot) to
lower energy areas (cold).
For example, if you hold an ice cube in your hand, heat energy transfers
from your warm hand to the cool ice. Your hand becomes colder (loses
heat energy) and the ice becomes warmer (gains heat energy).
1-4
Section1 - Refrigeration Theory
The speed of heat transfer from one object to another is affected by the
temperature difference between the two objects. Heat energy travels
fast when there is a great temperature difference between two objects.
For example, that ice cube would melt quickly in boiling water, more
slowly in your hand, and very slowly in a cool refrigerator.
Thermo King unit operation relies on these two principles of heat transfer:
• Heat energy always move from “hotter” to “colder”.
• Heat transfer occurs quickly when there is a large temperature difference between two objects
Radiation
Radiation is a method of heat energy transfer. Radiant energy travels through empty space.
The sun’s energy is an example. Energy from the sun must pass through 93 million miles
of space before reaching our atmosphere. It does not warm the emptiness of outer space; it
only becomes heat energy when absorbed by an object. Even when painted white to help
reflect the sun’s radiant energy, refrigerated trucks, trailers, and containers absorb
unwanted heat energy from the sun.
Conduction
Conduction occurs when heat energy moves through a solid object, through a fluid, or when it moves directly from
one substance to another in direct contact. In our earlier example, heat energy was conducted directly from the
warm hand to the ice cube
If a warm spoon is placed in ice water, heat energy will be quickly conducted from
the spoon to the surrounding water (hot to cold). If a cool spoon is placed in hot
water, heat energy will be quickly conducted from the water to the spoon (hot to
cold).
The principle of conduction moves the sun’s heat energy through the ceiling and
walls of a refrigerated truck or trailer. Although insulation is used in the walls and
ceiling to reduce heat conduction, some heat passes into the refrigerated compart-
ment. Chapter three will help you understand how a Thermo King unit uses the
principle of conduction to move unwanted heat from the inside to the outside of the refrigerated box.
1-5
Section1 - Refrigeration Theory
Convection
Convection is the movement of heat within a moving fluid. The fluid can be a liq-
uid (such as water) or a gas (such as air). For example, in an engine cooling sys-
tem, convection contributes to coolant flow between the engine and radiator.
A pump, fan or blower is often used to increase fluid movement. Thermo King
units include powerful fans to force air movement throughout the temperature
controlled compartment.
1-6
Section1 - Refrigeration Theory
Heat Measurement
Heat measurement is part of our daily lives. When someone says, "It’s too hot today", you understand what
they mean. But the words "hot" and "cold" are relativetheir meaning is defined by the subject at hand.
For example, a hot load of lettuce may be 65°F (18°C), but a hot load of ice cream is 0°F (-18°C). (Ice
cream is normally transported at -20°F/-29°C). Some people would consider a bus coach hot when it’s
75°F (24°C) and cold when it’s 65°F (18°C).
Heat Intensity
A thermometer, scaled in degrees Fahrenheit or degrees Celsius, is commonly
used to measure and communicate heat intensity. If an object contains a great
deal of heat energy, the temperature is high. If an object contains little heat
energy, the temperature is low. The formulas below show how to convert
between the two temperature scales.
____°C x 1.8 + 32 = ____°F ____°F - 32 ÷ 1.8 = ____°C
Heat Quantity
A thermometer can only indicate heat intensityit cannot indicate heat quantity. A candle flame and a camp fire
may be the same temperature (intensity) but the camp fire contains much more heat energy. The quantity of heat
energy is commonly measured with a unit known as the British Thermal Unit (Btu) or the metric equivalent, gram-
calorie. One Btu is the amount of heat required to raise the temperature of one pound of water one degree
Fahrenheit. One gram-calorie is the amount of heat required to raise the temperature of one gram of water one
degree Centigrade.
1-7
Section1 - Refrigeration Theory
Cooling Capacity
To warm an object, add BTUs. To cool an object, remove BTUs. Most Thermo King units can add BTUs in the
operating mode called HEAT. However, they’re usually called upon to remove BTUs in the operating mode called
COOL. The cooling capacity of a Thermo King unit is measured in BTUs per hour (BTU/hr) or in Watts. This is a
measure of the unit's ability, per hour of operation, to move BTUs (or Watts) from the inside to the outside of an
enclosure. For example, a refrigeration unit may be rated at 10,000 Btu's per hour. In one hour, it can move 10,000
Btu's from inside the box to the outside. If the box contained 10,000 pounds of water, the temperature of the water
can be reduced one degree Fahrenheit in one hour. (Remember, one Btu is the amount of heat required to change
the temperature of one pound of water one degree Fahrenheit).
Unit capacity:----------------------------------------------------------------------- 10,000 Btu’s / hr
Cargo:-------------------------------------------------------------------------------- 10,000 lbs. water
Btu’s required to change load temperature one degree Fahrenheit: -------- 10,000 Btu’s
Calculation: ------------------------------------------------------------------------- 10,000 Btu’s÷10,000 Btu/hr unit capacity = 1 hr
To lower the water temperature by 10°F, the unit must be operated for ten hours. (Of course, that assumes that no
additional heat is entering the water through the box walls, floor and ceiling!)
1-8
Section1 - Refrigeration Theory
Specific Heat
You learned that a very specific amount of heat must be moved (one Btu) to change the temperature of one pound
of water one degree Fahrenheit. It is important to know that water does not change temperature as easily as most
other substances. In other words, compared to water, most substances require less heat movement to change tem-
perature.
To compare the “willingness” of various substances to change temperature, substances have been given a numeric
value to compare them to water. This value is called specific heat. Water is the standardthe specific heat of water
is 1.0. The table below provides the specific heat value for several common foods. Note that the specific heat of
bacon is 0.5. This means that bacon absorbs (or releases) heat energy two times easier than water. The specific heat
of butter is 0.33it changes temperature three times easier than water.
Commodity Specific Heat Above Freezing
BTU/Pound/°F
Water 1.00
Watermelons 0.97
Lettuce, iceberg 0.96
Strawberries 0.93
Milk (whole) 0.92
Carrots 0.90
Beef (fresh) 0.75
Cheese, cheddar 0.62
Bacon 0.50
Milk Chocolate 0.41
Butter 0.33
The specific heat value of a perishable load affects the amount of time required to change product temperature.
Referring again to our example, a 10,000 pound load of water can be cooled 1°F in one hour by a unit rated at
10,000 Btu/hr. The same unit will cool 10,000 pounds of carrots ten percent quicker (0.9 hours) because the spe-
cific heat of carrots is 0.9. Carrots change temperature 10% quicker than water. The formula for computing time
required to change load temperature may be written as:
SPECIFIC HEAT x WEIGHT x DEGREES CHANGE = HOUR REQUIRED TO CHANGE
UNIT CAPACITY (Btu’s / hour)
1-9
Section1 - Refrigeration Theory
Heat of Respiration
Melons, strawberries and other fresh produce create heat energy as they ripenheat of respiration. Heat of respi-
ration is calculated in BTUs per hour, per ton. The chart below provides a few common examples.
For example, a ton (2000 pounds) of strawberries, at 32°F, produces 113-158 BTUs per hour. At 40°F, the straw-
berries produce 150-283 BTUs per hour. At 60°F, the same strawberries produce up to 846 BTUs per hour! This
additional heat will extend the time required to lower product temperature. It may take many days to reduce the
temperature of these strawberries to the recommended storage temperature. Unfortunately, the strawberries would
be spoiled beyond recognition before they reached the recommended temperature.
The appendix of this manual contains a chart listing moisture content, initial freezing point, and specific heat of
foods.
Heat of Respiration?
Of course, bus passengers can hardly be compared to a load of strawber-
ries. Like strawberries, however, each passenger gives off heatabout 580
BTUs per hour. Add the heat of each passenger to the heat entering when
the doors open and passengers stream in and out. Now add the sun’s heat
coming through the glass and engine heat being conducted through the
coach body. You can see why bus air conditioning requirements range up
to 125,000 BTUs per hour!
1-10
Section1 - Refrigeration Theory
Terms To Remember
Refrigeration
Air Conditioning
Absolute Zero
Radiation
Conduction
Convection
Heat Transfer
Heat Intensity
Fahrenheit
Celsius
Gram-Calories
Watts
Cooling Capacity
Specific Heat
Heat of Respiration
1-11
Section1 - Refrigeration Theory
1. True or False
The main difference between refrigeration and air conditioning is the temperature in the controlled area.
2. What’s the preferred term for the transport heating and cooling business?
a. Transport refrigeration
b. Mobil cooling
c. Transport air conditioning
d. Transport temperature control
1-12
Section1 - Refrigeration Theory
7. If heat is removed from a box faster than heat enters the box, box temperature
a. goes up.
b. goes down.
c. remains the same.
8. Which method of heat transfer occurs when heat moves through trailer, truck, or container walls?
a. Conduction
b. Radiation
c. Convection
9. The amount of heat required to raise the temperature of one pound of water one degree Fahrenheit. This is
the definition of
a. British Thermal Unit.
b. specific heat.
c. heat of respiration.
d. ambient temperature.
10. What is the approximate time necessary to reduce this load of bacon one degree Fahrenheit?
a. 30 minutes
b. 50 minutes Product: Bacon
Weight: 1,000 pounds
c. 60 minutes Specific Heat: 0.50
d. 4 hours Unit Capacity: 1,000 Btu’s /Hr.
1-13
Section 1-Refrigerqtion Theory
Latent Heat
Earlier you learned about heat measurement. You learned that the intensity of heat can be measured with a ther-
mometerthis is sensible heat. There is another type of heat that cannot be measured with a thermometerlatent
heat. Latent heat is heat absorbed or released when a substance changes its physical state.
Understanding latent heat is your key to understanding refrigeration systems. To explain this concept, let’s begin
with the physical behavior of something familiarwater!
Water, like many substances, can exist in three physical statessolid, liquid and vapor
(gas). If you add heat to a block of ice it becomes water. It changes from the solid state to
the liquid state. (Some call it a phase change.) If you add enough heat to water, the water
boils and becomes steam. The water changes state from liquid to vapor (gas).
It works the other way, too. If you remove heat from steam (if you cool it), the steam
returns to water. If you continue to remove heat from the water, it becomes ice.
As you add heat to a block of ice, a thermometer will clearly indicate a temperature rise. And as the temperature
rises, the ice will change from solid, to liquid, to vapor. But if you watch the thermometer very carefully, you will
notice something strange. Although you continue to add heat energy, the thermometer stops rising during each
change of state!
During each change of state, the heat is being absorbed to make the phase change possible. This heat, that cannot
be measured on the thermometer, is latent heat. A large amount of latent heat is absorbed or released as a sub-
stance changes state.
1-14
Section 1-Refrigerqtion Theory
This illustration will help you understand how heat energy is used to convert one pound of ice at 0°F (-17.7°C)
to steam at 212 °F (100°C) .
1. We begin with a bock of ice, at 0°F (-17.7°C), weighing one pound (0.45 kilograms). Sixteen BTUs of heat
raises the ice temperature from 0°F (-17.7°C) to 32°F (0°C). The sixteen BTUs added here are called sensible
heat heat energy that can be “sensed” or measured with a thermometer and results in temperature change.
Ice has a specific heat of “0.5”. The BTUs required to raise the temperature 32 degrees is .5 X 32 or 16 BTUs.
2. When the ice temperature reaches 32°F (0°C), it begins to melt. However, the temperature rise stops while 144
additional BTUs are absorbed by the ice. This heat cannot be sensed with a thermometerthis is latent heat.
Latent heat is always involved in a change of state. While the 144 Btu's of latent heat are absorbed, the ice
changes to water.
144 BTUs of latent heat are required to change one pound of ice from solid to liquid.
3. After the ice becomes water, we continue to add Btu's and the water temperature rises. As we add 180 BTUs of
sensible heat, the water temperature steadily rises from 32°F (0°C) to 212°F (100°C).
Remember, one Btu is the amount of heat required to raise the temperature of one pound of water one
degree Fahrenheit. Here we have one pound of water being raised 180 degrees (from 32°F to 212°F).
180 BTUs of sensible heat are absorbed.
4. When the water temperature reaches 212°F (100°C), it begins to boil. However, the temperature rise stops
while 970 additional BTUs are absorbed by the water. 970 BTUs of latent heat are absorbed while water
changes to steam.
970 BTUs of latent heat are required to change one pound of water from liquid to vapor.
5. If we continue adding heat to the steam, the steam becomes super heated. Super heated vapor contains heat
beyond the amount required to maintain it as a vapor. Super heated water vapor is steam with a temperature
above 212°F (100°C).
1-15
Section 1-Refrigerqtion Theory
.
Every change of state absorbs or releases large amounts of heat energy.
All refrigeration units use these two principles to move heat from one place to another. Latent heat of vaporization
is used to absorb large amounts of heat inside the box. Latent heat of condensation is used to release large amounts
of heat outside the box. The evaporator absorbs heat. The condenser releases heat.
1-16
Section 1-Refrigerqtion Theory
.
At sea level, water in an open container boils when it reaches 212°F (100°C).
However, the temperature of water in a closed container can rise above 212°F (100°C).
Trapped vapor builds pressure on the water’s surface. Increased surface pressure raises the
boiling point of liquidthe water must get hotter than 212°F (100°C) before it can boil and
release excess heat energy.
CAUTION!
Boiling liquid in a closed container may cause the container to explode causing serious injury
or death!
.
Raising pressure on a liquid raises the boiling point.
1-17
Section 1-Refrigeration Theory
.
Lowering pressure on a liquid lowers the boiling point.
1-18
Section 1-Refrigeration Theory
1-19
Section 1-Refrigeration Theory
Let’s see how much you remember about sensible heat, latent heat, and the affect of
pressure on boiling points.
1. Sensible heat
a. can be measured with a thermometer.
b. absorbs a large amount of heat energy as liquid changes to gas.
c. absorbs a large amount of heat energy as solid changes to liquid.
d. absorbs a large amount of heat energy as solid changes to gas.
2. Latent heat
a. cannot be measured with a thermometer.
b. absorbs a large amount of heat energy as liquid changes to gas.
c. releases a large amount of heat energy as gas changes to liquid.
d. All of the above.
5. True or False
At sea level, atmospheric pressure is 14.7 psi (101.3 kPa) and the boiling point of water is 212°F (100°C).
Reducing the pressure on water will raise its boiling point; increasing pressure will lower the boiling point.
1-20
Section 1-Refrigeration Theory
REFRIGERATION THEORY sea level of 29.2 inches of mercury. At pressures above that,
boiling would not take place. Pressures from 1,500 to 2,000
The table below illustrates the reduction of the boiling point microns are required for effective dehydration.
of water with a reduction of pressure. At normal room tem-
peratures, dehydration by evacuation requires pressures below NOTE: It is important to remember that gauge pressure has
0.40 psia, which means a corresponding vacuum reading at no relationship to absolute pressure.
Pounds Per
Boiling Boiling Inch of
Inches of Square Inch
Temperature Temperature Mercury kPa Microns
Mercury (PSI)
of H20 in F. of H20 in C. Vacuum
(Pressure)
1-21
Section 1-Refrigeration Theory
Temperature - Pressure Chart temperatures above those given for the corresponding pres-
sures. This is true of any substance which can exist in liquid
The chart shows the temperature at which this substances will
or gaseous states, but the change-of-state points are different
change from a liquid to a gas, or vice-versa, at various pres-
for each substance. It is by virtue of these properties that
sures. Two important points must be remembered when con-
mechanical refrigeration is possible.
sidering this pressure-temperature relationships; Refrigerant-
12 cannot exist as a gas at temperatures below those given for
corresponding pressures, neither can it exist as a liquid at
1-22
Section 1-Refrigeration Theory
Glossary Convection
The method of heat transfer by the circulation of heated por-
Absolute Pressure tions of a fluid. As heat is transferred to a gas, it causes it to
Absolute pressure expressed in pounds per square inch abso- expand. Cooler and more dense air will settle and push the
lute (psia) or kilopascals (kPa) is the pressure existing above a less dense (warmer) air upward.
perfect vacuum.
Dehydration
Ambient Temperature Removing moisture from a refrigeration system or produce.
Ambient temperature is the temperature of the air surrounding
an object. Density
The density of a substance is defined as weight per unit vol-
Atmospheric Pressure ume and is normally expressed in pounds per cubic foot.
The atmosphere surrounding the earth extends many miles Since density is directly related to specific volume, the den-
above the surface of the earth. The weight of that atmosphere sity of a gas may vary greatly with changes in pressure and
pressing down on the earth is relatively constant except for temperature.
minor changes due to changing weather conditions. As a basic
reference for comparison, the atmospheric pressure at sea Desiccant
level has been universally established at 14.7 psi (100 kPa) A chemical used in removal of moisture from refrigerant.
and is equivalent to the pressure exerted by a column of mer- Additional requirements are: Allow oil to pass without affect-
cury 29.92 inches high. ing the efficiency of the desiccant; Remain chemically stable
during operation and idle or storage periods; Retain its origi-
At altitudes above sea level, the depth of the atmospheric nal shape so as not to plug up and restrict the flow of refriger-
blanket surrounding the earth is less; therefore, the atmo- ant.
spheric pressure is less. Evacuation
The removal of air, non-condensable gas and moisture from
Back Seating
inside a refrigerant system through the use of a vacuum pump.
Turning the valve stem all the way out (counter clockwise)
backseats the valve. In this position the valve outlet to the sys- Evaporation
tem is open and the gauge connection closed. A change of state from a liquid to a vapor.
Boiling Point Flash Gas
The temperature at which a liquid vaporizes upon the addition The instantaneous vaporization of refrigerant caused by the
of heat or by the reduction of pressure. reduction of pressure in liquid refrigerant when it passes
British Thermal Unit though a pressure reducing device.
The amount of heat required to produce a temperature change Fluid Flow
of one degree Fahrenheit in one pound of water. In order for a fluid to flow from one point to another, there
must be a difference in pressure between the two points to
Calorie
cause the flow. Fluids may be either liquids or gases. Fluid
The amount of heat required to raise temperature of one gram
flow through pipes or tubing is governed by the pressure
of water one degree Celsius.
exerted on the fluid, the effect of gravity due to the vertical
Capacity rise or fall of the pipe, restrictions in the pipe resisting flow,
Rate of heat transfer measured in tons, BTU per hour, K cal and the viscosity of the fluid.
per hours, or Watts.
Foaming
Change Of State A condition caused by refrigerant boiling out of the compres-
A change from one phase to another, such as a solid to a liquid sor oil.
or liquid to a gas.
Force
Charge Force is a word used to denote total pressure or influence to
The amount and type of refrigerant in a system. cause motion or movement.
Conduction Freeze-up
The method of heat transfer from molecule to molecule. 1. The formation of ice at the expansion valve.
When an object is heated on one end heat will flow to the 2. The formation of a solid ice mass over the evaporator coil
other end. reducing air flow.
1-23
Section 1-Refrigeration Theory
Heat Measurement (Metric) When one pound of ice melts, it absorbs 144 BTU (151 905
The basic unit of heat measurement in this system will be joules), and if one pound of water is to be frozen into ice, 144
either joule or watts: BTU (151 905 joules) must be removed from the water.
The joule can be defined as a unit of energy or work. The
joule is the work done when the point of application of force Latent Heat Of Sublimation
of one Newton is displaced a distance of one meter in the A change in state directly from a solid to a vapor without
direction of the force. The watt (unit of power). The watt is going through the liquid phase can occur in some substances.
the power that in one second gives rise to energy of one joule. The most common example is the use of “dry ice” or solid
carbon dioxide for cooling.; the same process can occur with
Heat Of Compression ice below the freezing point, and is also utilized is some
The heat of compression is the heat added to the refrigerant freeze-drying processes at extremely low temperatures and
gas as a result of the work energy used in compression. high
vacuums. The latent heat of sublimation equal to the sum of
Heat Of Respiration the latent heat of fusion and the latent heat of evaporation.
The living process in which plants continue to age. Often car-
bon dioxide and water are given off by the product.
1-24
Section 1-Refrigeration Theory
Load PSIA
1. The product that is being refrigerated. Pound per square inch - Absolute.
2. The amount of heat that is being removed by the system.
PSIG
Pressure And Fluid Head Pound per square inch - Gauge.
It is frequently necessary to know the pressure created by a
column of liquid, or possibly the pressure required to force a Purging
column of refrigerant to flow a given vertical distance Releasing a vapor through a refrigeration system, to remove
upwards. contaminants from the system. The common vapors used for
purging are dry nitrogen and refrigerants.
Densities are usually available in terms of pounds per cubic Radiation
foot, and it is convenient to visualize pressure in terms of a Radiation is the transfer of heat by waves similar to light
cube of liquid one foot height, one foot wide, and one foot waves or radio waves. For example, the sun is energy is trans-
deep. Since the base of this cube is 144 square inches, the ferred to the earth by radiation.
average pressure in pounds per square inch is the weight of
the liquid per cubic foot divided by 144. For example, since Saturation Temperature
water weighs approximately 62.4 pounds per cubic foot, the The conditions of temperature and pressure where both liquid
pressure exerted by 1 foot of water is 62.4. (144 =.433 pounds and vapor exist simultaneously is termed saturation. A satu-
per square inch. Then feet of water would exert a pressure of rated liquid or vapor is one at its boiling point, and for water
10 x.433 pounds per square inch. The same relation of height at sea level, the saturation temperature is 212 F (100 C). At
to pressure holds true, no matter what the area of vertical liq- higher pressure, the saturation temperature increases, and
uid column. The pressure exerted by other liquids can be cal- with a decrease in pressure the saturation temperature
culated in exactly the same manner if the density is known. decreases.
Fluid head is a general term used to designate any kind of Saturated Vapor
pressure exerted by a fluid which can be expressed in terms of The condition when a refrigerant has liquid present with the
the height of a column of the given fluid. Hence a pressure of vapor. This occurs in the evaporator when refrigerant is mak-
1 psi may be expressed as being equivalent to a head of 2.31 ing the change from liquid to vapor or in the condenser when
feet of water. (1 psi (.433 psi/ft of water). In air flow through the refrigerant is condensing.
ducts, very small pressures are encountered, and these are Sensible Heat
commonly expressed inches of water. 1 inch of water = Sensible heat is defined as the heat involved in a change of
.433 12 =.036 psi. temperature of a substance. When the temperature of water is
Pressure Drop raised from 32 F (0 C) to 212 F (100 C), an increase in sensi-
The amount of pressure lost while passing through a compo- ble heat content is taking place.
nent. It is the difference between the pressure in and the pres- Short Cycling
sure out. 1. Improper air circulation in a trailer or container causing
Pressure Gauge unit to operate for brief periods.
A pressure gauge is calibrated to read 0 pounds per square 2. Thermostats set with improper differential causing it to
inch when not connected to a pressure producing source. sequence too rapidly from cool to heat or from cool to off
Therefore the absolute pressure of a closed system will position.
always be gauge pressure plus atmospheric pressure. Pres- Slugging
sures below 0 psig are actually negative readings on the The return of liquid refrigerant or oil to the compressor. This
gauge, and are referred to as inches of vacuum. condition will cause knocking and possible damage to com-
Pressure - Temperature Relationship pressor.
The boiling temperature of a liquid is dependent on the pres-
sure being exerted on it. Reducing the pressure reduces the
boiling temperature and increasing the pressure increases the
boiling temperature.
1-25
Section 1-Refrigeration Theory
1-26
Section 1-Refrigeration Theory
Pounds Per
Temperature Square Inch
F (PSI)
(Pressure)
205 F 96 C 12.279
194 F 90 C 10.162
176 F 80 C 6.866
158 F 70 C 4.519
140 F 60 C 2.888
122 F 50 C 1.788
104 F 40 C 1.066
86 F 30 C .614
80 F 27 C .491
76 F 24 C .442
72 F 22 C .393
69 F 21 C .344
64 F 18 C .295
59 F 15 C .246
53 F 12 C .196
45 F 7C .147
32 F 0C .088
21 F -6 C .049
6F -14 C .0245
1-27
Section 1-Refrigeration Theory
Cabbage. late 32 F (0 C) 95-100 3-4 months 92.4 30.4 F (-.88C) 0.94 0.47 132
Carrots. topped. mature 32 F (0 C) 98-100 5-9 months 88.2 29.5 F (-1.38C) 0.90 0.46 126
Cauliflower 32 F (0 C) 95 2-4 weeks 91.7 30.6 F (-.77C) 0.93 0.47 132
Celery 32 F (0 C) 95 1 -2 months 93.7 31.1 F (-.5C) 0.95 0.48 135
Cherries. sour 31-32 F (-1-0 C) 90-95 3-7 days 83.7 29.0 F (-1.6C) 0.87 — 120
Sweet 30-31 F (-2 --1 C) 90-95 2-3 weeks 80.4 28.8 F (-1.7C) 0.84 — —
Chocolate (Coating) 50-65 F (10-18 C) 40-50 2-3 months 55.0 95-85 F (35-29.4C) 0.30 0.55 40
Cocoa 32-40 F (0-5 C) 50-70 1 year. plus — — — — —
Coconuts 32-35 F (0-2 C) 80-85 1-2 months 46.9 30.4 F (-.88C) 0.58 0.34 67
Coffee (Green) 35-37 F (2-7 C) 80-85 2-4 months 10-15 — 0.30 0.24 14-21
Collards 32 F (0 C) 95 10-14 days 86.9 30.6 F (-.77C) 0.90 — —
Corn Sweet (Fresh) 32 F (0 C) 95 4-8 days 73.9 30.9 F (.61C) 0.79 0.42 106
Cranberries 36-40 F (2.2 - 4.4 C) 90-95 2- 4 months 87.4 30.4 F (.88C) 0.90 0.46 124
Cucumbers 50-55 F (10-13 C) 90-95 10-14 days 96.1 31.1F (-.5C) 0.97 0.49 137
Currants 31-32 F -1-0 C) 90-95 10-14 days 84.7 30.2 F (-1C) 0.88 0.45 120
Dairy Products
Cheddar Cheese 40 F (4.4C) 66-70 6 months 37.5 8.0 F (-13.3C) 0.50 0.31 53
Processed Cheese 40 F (4.4 C) 65-70 12 months 39.0 19.0 F (-7.2C) 0.50 0.31 56
Butter 40 F (4.4 C) 75-85 1 month 16.0 -4 F- 31 F (15.5-.55C) 0.60 0.25 23
Cream 35-40 F (2 - 4.4 C) — 2- 3 weeks 55-75 31.0 F (-.55C) 0.66-0.80 0.36-0.42 79-107
Ice Cream -20 to -15 (C) — 3-12 months 58-63 21.0 F (-6.1C) 0.66-0.70 0.37-0.39 86
Milk, Fluid Whole
Pasteurized. Grade A 32-34F (0-1 C) — 2- 4 months 87.0 31.0 F (-.55C) 0.93 0.46 125
Condensed. Sweetened 40 F (4.4 C) — 15 months 28.0 5.0 F (-15C) 0.42 0.28 40
Evaporated 40 F (4.4 C) — 24 months 74.0 29.5 F (-1.38C) 0.79 0.42 106
Dates (Dried) 0 or 32 F (-18 or 0 C) 75 or less 6-12 months 20.0 3.7 F (-15.72C) 0.36 0.26 29
Dewberries 31-32 F (-1-0 C) 90-95 3 days 84.5 29.7 F (-1.27C) 0.88 — —
Dried Fruits 32 F (0 C) 50-60 9-12 months 14-26 — 0.31-0.41 0.26 20-37
Eggplant 45-50 F (7.2 -10 C) 90-95 7-10 days 92.7 30.6 F (-.77C) 0.94 0.48 132
Eggs. shelf 29-31 F (-2-0 C) 80-85 5- 6 months 66.0 28.0 F (-2.2C) 0.73 0.40 96
Shelf. farm cooler 50-55 F (10-13 C) 70-75 2- 3 weeks 66.0 29.0 F (-1.6C) 0.73 0.40 96
Frozen. whole 0 or below (-18 C or below) — 1 year, plus 74.0 28.0 F (-2.2C) 0.73 0.42 106
Endive (Escarole) 32 F (0 C) 95 2- 3 weeks 93.3 31.9 F (-.05C) 0.94 0.48 132
Figs. dried 32-40 F (0 -4.4 C) 50-60 9-12 months 24.0 — 0.39 0.27 34
Fresh 31-32 F (-1-0 C) 85-90 7-10 days 78.0 27.6 F (-2.4C) 0.82 0.43 112
Fish. fresh 33-35 F (.5 -2 C) 90-95 5-15 days 62-85 28.0 F (-2.2C) 0.70-0.86 0.38-0.45 89-122
Smoked 40-50 F (4.4 -10 C) 50-60 6- 8 months — — 0.70 0.39 92
Shellfish. fresh 30-33 F (-1 -.5 C) 85-95 3- 7 days 80-87 28.0 F (-2.2C) 0.83-.90 0.44-0.46 113-125
Furs and Fabrics 34-40 F (1 -4.4 C) 45-55 several years — — — — —
1-28
Section 1-Refrigeration Theory
Nectarines 31-32 F (-.5 - 0C) 90 2- 4 weeks 81.8 30.4 F (-.88C) 0.90 0.49 119
Nuts (Dried) 32-50 F (0 - 10 C) 65-75 8-12 months 3-6 — 0.22-0.25 0.21-0.22 4-8
Okra 45-50 F (7.2 - 10 C) 90-95 7-10 days 89.8 28.7 F (-1.83C) 0.92 0.46 128
Oleo margarine 35 F (1.66 C) 60-70 1 year, plus 15.5 — 0.32 0.25 22
Olives, fresh 45-50 F (7.22 - 10 C) 85-90 4-6 weeks 75.2 29.4 F (-1.44C) 0.80 0.42 108
Onions (Dry) and Onion sets 32 F (0 C) 65-70 1-8 months 87.5 30.6 F (-.77C) 0.90 0.46 124
Green 32 F (0 C) 95 3- 4 weeks 89.4 30.4 F (-.88C) 0.91 — —
Oranges 32-48 F (0 - 8.8C) 85-90 3-12 weeks 87.2 30.6 F (-.77C) 0.90 0.46 124
Orange Juice. chilled 30-35 F (-1.1 - 1.6 C) — 3- 6 weeks 89.0 — 0.91 0.47 128
Papayas 45 F (7.22 C) 85-90 1- 3 weeks 90.8 30.4 F (-.88C) 0.82 0.47 130
Parsley 32 F (0 C) 95 1 - 2 months 85.1 30.0 F (-1.1C) 0.88 0.45 122
Parsnips 32 F (0 C) 98-100 4-6 months 78.6 30.4 F (-.88C) 0.84 0.44 112
Peaches and Nectarines 31-32 F (-.5 -0 C) 90 2- 4 weeks 89.1 30.3 F (-.94C) 0.90 0.46 124
Pears 29-31 F (-1.6 - -.5C) 90-95 2-7 months 82.7 29.2 F (-1.55C) 0.86 0.45 118
Peas. green 32 F (0 C) 95 1 - 3 weeks 74.3 30.9 F (-.61C) 0.79 0.42 106
Peppers, sweet 45-50 F (7.2 - 10 C) 90-95 2-3 weeks 92.4 30.7 F (-.72C) 0.94 0.47 132
Peppers. Chili (Dry) 32-50 F (0 - 10 C) 60-70 6 months 12.0 — 0.30 0.24 17
Persimmons 30 F (-1.1 C) 90 3-4 months 78.2 28.1 F (-2.16C) 0.84 0.43 112
Pineapples. ripe 45 F (7.2 C) 85-90 2-4 weeks 85.3 30.0 F (-1.11C) 0.88 0.45 122
Plums. including fresh prunes 31-32 F (-.5 - 0 C) 90-95 2-4 weeks 82.3 30.5 F (-.83C) 0.88 0.45 118
Pomegranates 32 F (0 C) 90 2-4 weeks 77.0 26.6 F (-3C) 0.87 0.48 112
Popcorn. unpopped 32-40 F (0 - 4.4 C) 85 4-6 months 13.5 — 0.31 0.24 19
Potatoes. Early crop 50-55 F (10-12.7 C) 90 0-2 months 81.2 30.9 F (-.61C) 0.85 0.44 116
Late crop 38-50 F (3.3 - 10 C) 90 5-8 months 77.8 30.9 F (-.61C) 0.82 0.43 111
Poultry. Fresh Chicken 32 F (0 C) 85-90 1 week 74.0 27.0 F (-2.7C) 0.79 0.42 106
Fresh Goose 32 F (0 C) 85-90 1 week 47.0 27.0 F (-2.7C) 0.57 0.34 67
Fresh Turkey 32 F (0 C) 85-90 1 week 55.0 27.0 F (-2.7C) 0.64 0.37 79
Pumpkins 50-55 F (10 - 12.7C) 70-75 2-3 months 90.5 30.5 F (-.83C) 0.92 0.47 130
Quinces 31-32 F (-.5 - 0 C) 90 2-3 months 85.3 28.4 F (-2C) 0.88 0.45 122
Radishes-Spring. prepackaged 32 F (0 C) 95 3-4 weeks 93.6 30.7 F (-.72C) 0.95 0.48 134
Raisins (dried) 40 F (4.4 C) 60-70 9-12 months 35.0 — 0.47 0.32 43
Rabbits. fresh 32-34 F (0 - 1.1 C) 90-95 1-5 days 68.0 — 0.74 0.40 98
Raspberries. black 31-32 F (-.5 - 0 C) 90-95 2-3 days 81.6 30.0 F (-1.11C) 0.84 0.44 122
Red 31-32 F (-.5 - 0 C) 90-95 2-3 days 84.1 30.9 F (-.61C) 0.87 0.45 121
Rhubarb 32 F (0 C) 95 2-4 weeks 94.9 30.3 F (-.94C) 0.96 0.48 134
Rutabagas 32 F (0 C) 98-100 4-6 months 89.1 30.1 F (-1.05C) 0.91 0.47 127
Salsify 32 F (0 C) 98-100 2-4 months 79.1 30.0 F (-1.1C) 0.83 0.44 113
Spinach 32 F (0 C) 95 10-14 days 92.7 31.5 F (-.27C) 0.94 0.48 132
Squash, summer 32-50 F (0 - 10 C) 85-90 5-14 days 94.0 31.1 F (-.5C) 0.95 0.48 135
Winter 50-55 F (10 - 12.7 C) 70-75 4-6 months 88.6 30.3 F (-.94C) 0.91 0.48 127
Strawberries. fresh 31-32 F (-.5 - 0C) 90-95 5-7 days 89.9 30.6 F (-.77C) 0.92 0.42 129
Sugar. Maple 75-80 F (23.8 - 26.6 C) 60-65 1 year. plus 5.0 — 0.24 0.21 7
Sweet Potatoes 55-60 F (12.7 - 15.5 C) 85-90 4-7 months 68.5 29.7 F (-1.27C) 0.75 0.40 97
Syrup, Maple 31 F (-.55 C) 60-70 1 year plus 35.5 — 0.48 0.31 51
Tangerines 32-38 F (0 - 3.3 C) 85-90 2-4 weeks 87.3 30.1 F (-.55C) 0.90 0.46 125
Tobacco. Cigarettes 35-46 F (1.6 - 7.7 C) 50-55 6 months — 25.0 F (-3.8C) — — —
Cigars 35-50 F (1.6 - 10 C) 60-65 2 months — 25.0 F (-3.8C) — — —
Tomatoes. Mature green 55-70 F (12.7 - 21.1 C) 85-90 1- 3 weeks 93.0 31.0 F (-.55C) 0.95 0.48 134
Firm ripe 45-50 F (7.2 - 10 C) 85-90 4-7 days 94.1 31.1 F (-.5C) 0.94 0.48 134
Turnips. roots 32 F (0 C) 95 4-5 months 91.5 — — — —
Vegetables (mixed) 32-40 F (0 -4.4 C) 90-95 1-4 weeks 90.0 30.0 F (C) 0.90 0.45 130
Yams 60 F (15.5 C) 85-90 3-6 months 73.5 28.5 F (C) 0.79 0.40 105
Yeast. compressed baker’s 31-32 F (-.55 - 0C) — — 70.9 — 0.77 0.41 102
*Not based on maintaining nutritional value. Extracted by permission from 1974 ASHRAE APPLICATIONS HANDBOOK.
1-29
Section 1-Refrigeration Theory
HEAT OF RESPIRATION
Approximate rates of evolution of heat by certain fresh fruits, vegetables and cut flowers
when stored at the temperatures indicated.
Bananas
Holding 54° 138
Ripening 68° 380
Chilling 70 - 56° 1000
Beans, green or snap 383 - 475 1338 - 1838
Beans, lima 96 - 133 179 - 254 917 - 1142
Beets, topped 112 170 300
Blueberries 54 - 91 83 - 113 313 - 541
Broccoli, sprouting 312 458 - 733 1408 - 2083
Brussels sprouts 137 - 345 275 - 458 550 - 1145
Cabbage 50 71 171
Carrots, topped 87 146 337
Cauliflower 150 - 175 175 - 200 392 - 450
Celery 66 100 341
Cherries 54 - 75 117 - 121 458 - 550
Corn, sweet 300 - 470 442 - 550 1600
Cranberries 25 - 29 38 - 47
Cucumbers 137 - 304
Grapefruit 16 - 41 29 - 54 92 - 166
Grapes, American 25 50 14
Grapes, European 13 - 17 29 - 54 92 - 108
Lemons 21 - 38 25 - 79 96 - 208
Lettuce, head 96 113 329
Lettuce, leaf 188 267 600
1-30
SECTION 2
Basic Refrigeration
System Operation
2-1
Section 2-Basic Refrigeration System Operation
2-2
Section 2-Basic Refrigeratrion System Operation
.
Refrigerant is the vehicle that absorbs, carries and releases heat energy.
Refrigerant is the vehicle that absorbs, carries and releases heat energy.
2-3
Section 2-Basic Refrigeration System Operation
The Compressor
The compressor performs two important functions:
1. It moves refrigerant through the system to carry heat energy.
2. It creates high pressure on one side of the refrigeration system and low
pressure on the other. These two pressures help control the boiling
point of the refrigerant, causing refrigerant to boil in the evaporator and
condense in the condenser.
2-4
Section 2-Basic Refrigeratrion System Operation
The Condenser
The condenser is similar to the radiator in an automobile. The automobile’s
radiator transfers heat from the engine to the ambient air. This keeps the
engine cool. In a refrigeration system, the condenser releases heat to the
outside air. The condenser is always on the outside of the refrigerated com-
partment.
The condenser relies on two key principles of heat transfer:
• Heat energy always moves from "hotter" to "colder".
• Heat energy transfers quickly between objects having a large tempera-
ture difference.
The condenser consists of copper tubes to contain the hot refrigerant and
hundreds of delicate fins to transfer heat from the copper tubes to the cool air
passing around the fins. These fins are tightly attached to the copper tubes to
provide excellent heat transfer. They also provide an extremely large surface
area for maximum exposure of heat to the cool ambient air. Copper or alu-
minum fins are used because they are good conductors of heat energy. The
condenser (often called the condenser coil) is a very efficient heat transfer
component.
As the hot refrigerant vapor passes through the condenser, it loses heat and changes from vapor to liquid (it con-
denses.) In chapter two you learned that a large amount of latent heat energy is released as vapor cools and changes
to the liquid state. The condenser makes good use of the Latent Heat of Condensation principle. The boiling point
of refrigerant in the condenser must always be above ambient temperature so that the "cool" ambient air causes the
refrigerant vapor to condense. If the refrigerant vapor fails to condense, only a small amount of heat will transfer
to the ambient air.
Refrigerant vapor condenses in the condenser.
The latent heat of condensation is vital to system efficiency.
2-5
Section 2-Basic Refrigeration System Operation
2-6
Section 2-Basic Refrigeratrion System Operation
2-7
Section 2-Basic Refrigeration System Operation
.
After passing through the condenser, the high
pressure liquid refrigerant travels to the expansion
valve. The expansion valve restricts and controls
the flow of liquid refrigerant to the evaporator.
This restriction helps maintain high pressure in the
condenser to keep the boiling/condensation point
high (above ambient).
This restriction also allows low pressure to
develop on the outlet side of the expansion valve.
This low pressure reduces refrigerant pressure,
refrigerant temperature, and the refrigerant’s boil-
ing point in the evaporator. The boiling point of
refrigerant in the evaporator can be reduced so
much that refrigerant in the evaporator boils at
temperatures below -20°F (-28.8°C).
The expansion valve assembly constantly responds to changes in evaporator outlet temperature and pressure to pre-
cisely meter the correct amount of refrigerant through the evaporator.
Too much refrigerant will "flood" the evaporator. This will reduce or eliminate the important boiling effect that
must occur for efficient operation. It also may damage the compressor.
Too little refrigerant will not provide the volume of moving refrigerant necessary to absorb large amounts of heat
from the refrigerated compartment.
2-8
Section 2-Basic Refrigeration System Operation
The Evaporator
Like the condenser, the evaporator consists of copper tubes and hundreds of delicate fins that transfer heat very
efficiently. While the condenser releases heat to the outside air, the evaporator absorbs heat from the refrigerated
compartment. The evaporator is always inside the refrigerated compartment.
Like the condenser, the evaporator relies on the same two key principles
of heat transfer:
• Heat energy always moves from "hotter" to "colder".
• Heat energy transfers quickly between objects having a large temper-
ature difference.
As low pressure, liquid refrigerant passes through the evaporator, it
absorbs heat from the refrigerated compartment and begins to boil. Even
if the evaporator temperature is well below zero degrees Fahrenheit, the
refrigerant boils and takes full advantage of the principle discussed in
chapter twoLatent Heat of Vaporization. As the refrigerant boils, the
evaporator surface is normally about ten degrees colder than the box air
passing through it. (On bus climate control systems, evaporator tempera-
ture is maintained at approximately 35°F.) Evaporator pressure and
refrigerant boiling point must be lower than the temperature of air pass-
ing through it. (That's opposite to the conditions required in condenser.)
.
Refrigerant liquid evaporates in the evaporator.
The latent heat of evaporation is vital to system efficiency.
2-9
Section 2-Basic Refrigeration System Operation
2-10
SECTION 3
Container
Refrigeration
Components & System
Diagrams
3-1
Section 3-Container Refrigeration Unit & System Diagrams
Product Overview
Over the years, Thermo King has produced several different marine container unit models. The CSR and CRR series
units shown here have been selected as ‘representative’ and will be used to explain system components and compo-
nent functions.
3-2
Section 3-Container Refrigeration Unit & System Diagrams
3-3
Section 3-Container Refrigeration Unit & System Diagrams
Thermo King marine container units are designed for 40-foot or 20-
foot marine containers. Depending on unit model and age, the com-
pressor used may be a Thermo King X426 or X430, a Copeland
3DS/3DF (like the one pictured here), or a Copeland scroll
compressor. Thermo King CRR marine container units use the
Copeland reciprocating compressor; CSR models use the Cope-
land scroll compressor.
CSR scroll compressors have two (2) scrolls, a stationary scroll and an
orbiting scroll, that compress the refrigerant and circulate it throughout
the refrigeration system.
3-4
Section 3-Container Refrigeration Unit & System Diagrams
3-5
Section 3-Container Refrigeration Unit & System Diagrams
Microprocessor controllers have been the standard on Thermo King container units
since 1984 when the original Thermoguard µP was introduced on the CF-II con-
tainer unit.
3-6
Section 3-Container Refrigeration Unit & System Diagrams
In the year 2000, Thermo King became the first reefer unit man-
ufacturer to introduce internal capacity control with a scroll
compressor. The CSR ‘Magnum’ unit’s unique Modulated
Vapor Injection (MVI) scroll compressor has an internal
unloading mechanism that allows variable compressor capacity
from 0% to 100%. Loading and unloading is accomplished by
opening and closing a ‘Pulse Width Modulation (PWM) sole-
noid valve. Opening the valve reduces cooling capacity. The
duration of valve-open time affects how much the cooling
capacity is reduced. The longer the valve is open, the more
cooling capacity is reduced.
3-7
Section 3-Container Refrigeration Unit & System Diagrams
CRR Components
As previously discussed, Thermo King has provided a variety of different models and options over the years to meet
customer requirements. The following illustration provides an overall view of the refrigeration system components
used in the CRR unit.
3-8
Section 3-Container Refrigeration Unit & System Diagrams
3-9
Section 3-Container Refrigeration Unit & System Diagrams
CSR Components
The following illustration provides an overall view of the refrigeration system components used in the CSR unit.
3-10
Section 3-Container Refrigeration Unit & System Diagrams
3-11
Section 3-Container Refrigeration Unit & System Diagrams
3-12
Section 3-Container Refrigeration Unit & System Diagrams
(Item numbers below correspond to the item numbers on the preceding page.)
1. Moves refrigerant and increases refrigerant gas temperature and pressure.
2. Protects compressor from overheating and can control operation of the condenser fan motor.
3. Shuts refrigeration system down in case of high refrigerant pressure.
4. Used for adding / removing refrigerant and evacuating the refrigeration system’s high side.
5. Causes refrigerant to condense by transferring heat from refrigerant to ambient air flowing through it.
6. Collects condensed refrigerant and stores it during low load conditions and during low side repair.
7. Relieves extremely high-pressure refrigerant from the system.
8. Acts as a filter to remove dirt and debris from the system, absorbs moisture from the system and filters and cleans
the compressor oil.
9. Pre-cools liquid refrigerant being delivered to evaporator TXV1.
10. Controls / meters refrigerant flow to the evaporator coil during cooling.
11. Senses evaporator outlet pressure and helps control operation of the expansion valve.
12. Senses evaporator outlet temperature and helps control operation of the expansion valve.
13. Equally distributes refrigerant to each circuit within the evaporator.
14. Absorbs heat from the cargo space into the refrigerant flowing through its tubes / circuits.
15. Protects the compressor and system from low refrigerant charge conditions.
16. Used for adding / removing refrigerant and evacuating the refrigeration system’s low side.
17. Controls the physical loading and unloading of the compressor.
18. Controls the flow of refrigerant to the economizer circuit.
19. Controls / meters refrigerant flow to the economizer circuit.
20. Senses economizer heat exchanger outlet pressure and helps control operation of TXV2.
21. Senses economizer heat exchanger outlet temperature and helps control operation of TXV2.
22. Provides heat necessary to raise container temperature during heat mode and melt frost and ice off the evaporator
coil during defrost mode.
23. Controls all aspects of unit operation, records and displays data, alarms, events and is the user interface.
24. Senses temperature of air returning to the unit from the cargo area and helps control operation of the unit.
25. Senses evaporator coil temperature and is used to control initiation and termination of defrost.
26. Senses temperature of the air being delivered (supplied) to the cargo space.
27. Senses temperature of the surrounding / outside (ambient) air.
28. Senses temperature of the condenser coil.
29. Optional sensor that provides input to microprocessor and controls operation of dehumidify solenoid valve.
30. Optional solenoid valve that shuts off half of evaporator coil to remove moisture in the cargo air space.
3-13
Section 3-Container Refrigeration Unit & System Diagrams
Terms to Remember
Shore Power
Land Bridge
Clip-On
Center-Mount
Side-Mount
Resistance Heaters
CRR
CSR
Scroll Compressor
Hermetic
PWM Valve
Unloader
3-14
Section 3-Container Refrigeration Unit & System Diagrams
3-15
CF-II M34, M36
Refrigeration System Components
1. Compressor
2. Discharge Service Valve (DSV)
3. High Pressure Cutout Switch (HPCO)
4. Condenser Coil
5. High Pressure Relief Valve
6. Water Cooled Condenser / Receiver Tank 13
7. Condenser Water Inlet
14
8. Water Pressure Switch (WPS) 19
9. Condenser Water Outlet
10. Receiver Tank Outlet Valve
11. Filter Drier 20 15
12. Liquid Line Solenoid (LLS) 16
17
13. Expansion Valve (TXV)
14. Distributor 22 18
15. Evaporator Coil 21
16. TXV Power Element
17. TXV Equalizer Line
18. Electric Heaters 12
19. Return Air Sensor
20. Coil Sensor 4
3-16
21. Discharge / Supply Air Sensor
Section 3-Container Refrigeration Unit & System Diagrams
22. Controller
23. Low Pressure Cutout Switch (LPCO)
24. Modulation Valve (MV) 11
25. Compound Gauge 23
26. Suction Service Valve (SSV)
5
24
25 8
3 10
7
2 9
26 6
1
AJA478
Section 3-Container Refrigeration Unit & System Diagrams
3-17
It CLOSES at 5 ± 3 PSIG (35 ± 21 kPa), returning the
unit to condenser fan operation. 21
If (CFPS) opens during water cooled operation, the
condenser fan will run.
22. Controller
12
Thermoguard (P-A with digital thermostat,
thermometer and fault indicator monitor. 4
Null Mode Operation
During Null Mode Operation, the compressor does not
run. Condenser fan runs for 2 minutes and stops. Evap- 11
orator blowers are running. (Speed is controlled by the
23
return air sensor temperature.)
5
High pressure gas 24
High pressure liquid
Low pressure gas 8
25 3
Low pressure liquid 10
7
Condensing high pressure gas 2 9
Low pressure vaporizing liquid
26 6
1
AJA479
Flow and Pressure Diagram
CF-II M34, M36
Modulated Cool
12. Liquid Line Solenoid (LLS)
Is a normally CLOSED solenoid.
It OPENS when energized.
18. Electric Heaters
During DEFROST operation, the Electric heaters
are energized. The compressor does not run. Evapo-
rator blowers and the condenser fan are off. During
HEAT operation, the Electric Heaters are energized.
The compressor does not run. Condenser fan is off. 13
Evaporator blowers running. (Speed is controlled by
the return air sensor temperature.) 19 14
23. Low Pressure Cutout Switch (LPCO)
Is a normally CLOSED switch.
It OPENS (cuts-out) at 5 to I I in he vacuum (-17 to
-34 kPa). 20 15
16 17
It CLOSES (cuts-in) at 4 to 7 PSIG (28 to 48 kPa).
24. Modulation Valve (MV)
Is a normally OPEN valve. It CLOSES when ener- 22 18
3-18
gized. As the signal strength is increased, the valve
CLOSES more. The controller controls the signal to 21
Section 3-Container Refrigeration Unit & System Diagrams
3-19
18. Electric Heaters
19. Return Air Sensor
20. Coil Sensor 11
21. Discharge/Supply Air Sensor 27
22. Controller 5
23. Low Pressure Cutout Switch (LPCO)
24. Modulation Valve (MV)
25. Suction Service Valve (SSV) 10
26. Compressor Head (Discharge
23
Temperature) Sensor (CDTS)
27. Liquid Injection Module (LIM) 6
28. Liquid Injection Valve 26 4
24
w/Restrictor (LIV)
8
3 9
2
25 7
28
1
AJA481
Flow and Pressure Diagram
CF-II M37, M37.1
Full Cool
1. Compressor
Compressor operation has a three (3) second
delay on initial unit start-up or when the unit
shifts to cooling mode requiring compressor
start up.
3. High Pressure Cutout Switch (HPCO)
Is a normally CLOSED switch.
It OPENS (cuts-out) when pressure is 325 + 25
/-0 PSIG (2242 + 172 /0 kPa).
It CLOSES (cuts-in) when pressure is 200 ± 20 12 13
PSIG (1379 ± 138 kPa).
4. Condenser Fan Pressure Switch (CFPS) 19 14
Is a normally closed switch.
It OPENS at 200 ± 7 PSIG
(1379 ± 48 kPa).
It CLOSES at 160 ± 7 PSIG 20 15
(1103 ± 48 kPa).
16 17
6. High Pressure Relief Valve
OPENS at 500 +50/-15 PSIG 22 18
3-20
(3447+ 345/-104 kPa)
Resets (CLOSES) at 400 PSIG (2758 kPa). 21
Section 3-Container Refrigeration Unit & System Diagrams
22. Controller
Thermoguard (P-A with digital thermostat,
thermometer and fault indicator monitor). 11
27
High pressure gas 5
High pressure liquid
Low pressure gas
Low pressure liquid 10
Condensing high pressure gas 23
Low pressure vaporizing liquid
Liquid refrigerant injection
6
26 4
24
8
3 9
2
25 7
28
1
AJA482
Section 3-Container Refrigeration Unit & System Diagrams
3-21
Is a normally OPEN valve.
It CLOSES when energized.
21
As the signal strength is increased, the valve
CLOSES more. The controller controls the signal
to the valve as it monitors the temperatures and
11
power limit to the compressor. 27
28. Liquid Injection Valve (LIV) 5
Is a normally CLOSED valve.
It OPENS when energized. The valve is energized
when the compressor head temperature is above
292F (144.4C) or when the modulation valve 10
closes 62% or more (75% or more on temperature
pull down).
23
6
High pressure gas 26 4
24
High pressure liquid
Low pressure gas 8
Low pressure liquid 3 9
Condensing high pressure gas 2
Low pressure vaporizing liquid 25 7
Liquid refrigerant injection
28
1
AJA483
CF-II M19.7, M19.8, M19.9
M37.3, M37.5 Refrigeration System Components
1. Compressor
2. Discharge Service Valve (DSV)
3. High Pressure Cutout Switch (HPCO)
4. Condenser Fan Pressure Switch (CFPS)
5. Condenser Coil
6. High Pressure Relief Valve
7. Receiver Tank (M37.5 has water cooled
12 13
condenser/receiver tank)
8. Sight Glass 14
9. Receiver Tank Outlet Valve 19
10. Filter Drier
11. Liquid Line Solenoid (LLS)
20 15
12. Heat Exchanger 16 17
13. Expansion Valve (TXV)
14. Distributor 22 18
15. Evaporator Coil
3-22
16. TXV Power Element 21
Section 3-Container Refrigeration Unit & System Diagrams
3-23
Thermoguard (P-A+ with digital thermostat, 21
thermometer and fault indicator monitor.
Null Mode Operation 11
During Null Mode Operation, the compressor does
not run. Condenser fan runs for 2 minutes and
stops. Evaporator blowers are running. (Speed is 5
controlled by the return air sensor temperature.)
Water Pressure Switch (WPS) (M37.5 only)
Is a normally CLOSED switch, and automatically
10
selects air-cooled OR water-cooled condenser 23
operation. It OPENS at 17 ± 3 PSIG (117 ± 21
kPa), condenser fan stops. It CLOSES at 5 ± 3 6
PSIG (35 ± 21 kPa), returning the unit to condenser 26 4
fan operation. If (CFPS) opens during water cooled
24
operation, the condenser fan will run. 25 8
3 9
High pressure gas Low pressure gas
2
High pressure liquid Low pressure liquid
Condensing high pressure gas
29 7
27 28
Low pressure vaporizing liquid 1
Liquid refrigerant injection AJA485
Flow and Pressure Diagram
CF-II M19.7, M19.8, M19.9,
M37.3, M37.5
Modulated Cool
11. Liquid Line Solenoid (LLS)
Is a normally CLOSED solenoid.
It OPENS when energized.
18. Electric Heaters
During DEFROST operation, the Electric Heaters
are energized. The compressor does not run.
Evaporator blowers and the condenser fan are off.
During HEAT operation, the Electric Heaters are 12 13
energized. The compressor does not run. Condenser
fan is off. Evaporator blowers running. (Speed is
controlled by the return air temperature.)
19 14
23. Low Pressure Cutout Switch (LPCO)
Is a normally CLOSED switch.
It OPENS (cuts-out) at 5 to 17 in hg vacuum (-17 20 15
16
to -57 kPa). 17
It CLOSES (cuts-in) at I to 7 PSIG (7 to 48 kPa).
24. Modulation Valve (MV) 22 18
Is a normally OPEN valve.
3-24
It CLOSES when energized. As the signal strength 21
is increased, the valve CLOSES more. The
Section 3-Container Refrigeration Unit & System Diagrams
3-25
19
18. Coil Sensor 20
19. Discharge/Supply Air Sensor (Squashed)
20. Ambient Sensor
21. Controller
22. Suction Line Solenoid (SLS) 4
23. Modulation Valve (MV)
24. Suction Service Valve (SSV)
25. Compressor Head Discharge 23
9
Temperature Sensor (CDTS)
26. Liquid Injection Valve w/Restrictor (LIV)
27. Condenser Fan Pressure Switch (CFPS) 22
5
25
7
3 8
2
24 6
26
1
AJA487
Flow and Pressure Diagram
CF-II M38, M39, M39.2, M39.3
Full Cool
1. Compressor
Compressor operation has a three (3) second delay on
initial unit start-up or when the unit shifts to a cooling
mode requiring compressor start up.
3. High Pressure Cutout Switch (HPCO)
Is a normally CLOSED switch.
It OPENS (cuts-out) when pressure is 450 ±10 PSIG
(3105 ± 69 kPa).
It CLOSES (cuts-in) when pressure is 375 ± 38 PSIG
(2588 ± 262 kPa). 11
10
5. High Pressure Relief Valve
OPENS at 500+50/-15 PSIG (3447+345/-104 kPa).
Resets (CLOSES) at 400 PSIG (2759 kPa). 17 12
21. Controller
Thermoguard (P-A+ with digital thermostat,
thermometer and fault indicator monitor.)
18 13
14 15
Null Mode Operation
During Null Mode Operation, the compressor does not
run. Condenser fan runs for 2 minutes and stops. 16
Evaporator blowers are running. (Speed is controlled by 21
3-26
the return air sensor temperature.) 19
27. Condenser Fan Pressure Switch (CFPS) 20
Section 3-Container Refrigeration Unit & System Diagrams
3-27
and power the limit to the compressor.
26. Liquid Injection Valve (LIV) 19
Is a normally CLOSED valve.
20
It OPENS when energized. The valve is
energized when the compressor head
temperature is above 280F (137.8C) or
when the modulation valve closes 62% or 4
more (75% or more on temperature pull down).
23
High pressure gas 9
High pressure liquid
Low pressure gas
22
5
Low pressure liquid 25
Condensing high pressure gas
Low pressure vaporizing liquid 7
Liquid refrigerant injection
3 8
Modulated pressure
2
24 6
26
1
AJA489
CF-II M40, M40.1 M41
Refrigeration System Components
1. Compressor
2. Discharge Service Valve (DSV)
3. High Pressure Cutout Switch (HPCO)
4. Condenser Fan Pressure Switch (CFPS)
5. Condenser Coil
6. High Pressure Relief Valve
7. Water Cooled Condenser / Receiver Tank
8. Condenser Water Inlet
9. Water Pressure Switch (WPS) 14 15
10. Condenser Water Outlet
11. Receiver Tank Outlet Valve 21 16
12. Filter Drier
13. Liquid Line Solenoid (LLS)
14. Heat Exchanger 22 17
18
15. Expansion Valve (TXV) 19
16. Distributor
24 20
17. Evaporator Coil
3-28
18. TXV Power Element 23
19. Equalizer Line
Section 3-Container Refrigeration Unit & System Diagrams
3-29
select air-cooled OR water-cooled condenser 23
operation. It OPENS at 17 ± 3 PSIG (17 ± 21 kPa),
condenser fan stops. It CLOSES at 5 ± 3 PSIG
(35 ± 21 kPa), returning the unit to air cooled 13
condenser fan operation. If (CFPS) opens during water
cooled operation the condenser fan will run.
24. Controller 5
Thermoguard up-A+ with digital thermostat,
thermometer and fault indicator monitor.
27
Null Mode Operation 12
During Null Mode Operation, the compressor does not 25
run. Condenser fan runs for 2 minutes and stops. 26
Evaporator blowers are running. (Speed is controlled
6
by the return air sensor temperature.)
29
3 4
High pressure gas
9
High pressure liquid 2 11 8
Low pressure gas 10
Low pressure liquid
28 32 7
Condensing high pressure gas 30 31
Low pressure vaporizing liquid 1
Liquid refrigerant injection AJA491
Flow and Pressure Diagram
CF-II M40, M40.1, M41
Modulated Cool
13. Liquid Line Solenoid (LLS)
Is a normally CLOSED solenoid.
It OPENS when energized.
20. Electric Heaters
During DEFROST operation, the Electric Heaters
are energized. The compressor does not run.
Evaporator blowers and the condenser fan are off.
During HEAT operation, the Electric Heaters are
energized. The compressor does not run. Condenser 14 15
fan is off. Evaporator blowers running. (Speed is
controlled by the return air sensor temperature.) 21 16
25. Low Pressure Cutout Switch (LPCO)
Is a normally CLOSED switch.
It OPENS (cuts-out) at 5 to 17 in hg vacuum 17
(-17 to -57 kPa). 22 18
It CLOSES (cuts-in) at I to 7 PSIG (7 to 48 kPa). 19
26. Suction Line Solenoid (SLS)
Is a normally CLOSED solenoid. It OPENS when 24 20
energized.
23
3-30
27. Modulation Valve (MV)
Is a normally OPEN valve. It CLOSES when
Section 3-Container Refrigeration Unit & System Diagrams
3-31
16. Heat Exchanger
17. Expansion Valve (TXV) 25
26
18. Distributor
19. Evaporator Coil
20. TXV Power Element 15
21. Equalizer Line 8
22. Electric Heaters
23. Return Air Sensor
24. Coil Sensor 13
25. Supply Air Sensor 14
26. Ambient Sensor 28
27. Controller 6 5 9
28. Suction Line Solenoid (SLS) 29 4
(Not Used on M48.1) 30
29. Modulation Valve (MV)
7 11
30. Liquid Injection Valve w/Restrictor (LIV)
31. Suction Service Valve (SSV)
31
2 10
3 AJA493 12
1
Flow and Pressure Diagram
CF-II M46.1, M48.1, M49
Full Cool
1. Scroll Compressor
Compressor operation has a three (3) second delay on
initial unit start-up or when the unit shifts to a cooling
mode requiring compressor start up.
5. High Pressure Cutout Switch (HPCO
Is a normally CLOSED switch.
It OPENS (cut-out) when pressure is 450± 10 PSIG
(3105±69kPa).
It CLOSES (cut-in) when pressure is 375± 38 PSIG
(2588±262kPa). 16 17
6. Condenser Fan Pressure Switch (CFPS)
Is a normally CLOSED switch. 23 18
It OPENS at 200±7 PSIG (1379±48 kPa).
It CLOSES at 160±7 PSIG (1103±48 kPa).
9. High Pressure Relief Valve
OPENS at 500+50/-15 PSIG (3447+345/-104 kPa). 24 19
20 21
Resets (CLOSES) 400 PSIG (2758 kPa).
22. Electric Heaters
During DEFROST operation, the Electric Heaters are 27 22
3-32
energized. The compressor does not run.
25 26
Evaporator blowers and condenser fan are off.
Section 3-Container Refrigeration Unit & System Diagrams
3-33
It OPENS when energized.
The valve is energized when the compressor
25
26
head temperature is above 280 F (137.8 C) or
when the modulation valve closes 62% or more
(75% or more on temperature pull down).
15
8
13
14
28
6 5 9
High pressure gas 4
29
High pressure liquid
30
Low pressure gas
7 11
Low pressure liquid
Condensing high pressure gas
Low pressure vaporizing liquid 31
Liquid refrigerant injection 2 10
Modulated pressure 3 AJA495 12
High pressure gas injection 1
CF-II M37.6, M37.7, M37.9,
M52 M52.1, M53
Refrigeration System Components
1. Compressor
2. Discharge Service Valve (DSV)
3. High Pressure Cutout Switch (HPCO)
4. Compressor Head Discharge
Temperature Sensor (CDTS)
5. Condenser Fan Pressure Switch (CFPS)
6. Condenser Check Valve (CCV) 15 16
7. Discharge Pressure Regulator Valve (DPRV) 25
8. Condenser Coil 21 17
9. High Pressure Relief Valve
10. Receiver Tank
11. Sight Glass 22 20
12. Receiver Tank Outlet Valve 18
19
13. Filter Drier
14. Liquid Line Solenoid (LSS) 26 24
3-34
15. Heat Exchanger 23
16. Expansion Valve (TXV)
Section 3-Container Refrigeration Unit & System Diagrams
17. Distributor
18. TXV Power Element 14
19. Equalizer Line
20. Evaporator Coil 8
21. Return Air Sensor
22. Coil Sensor 7
23. Discharge/Supply Air Sensor (Squashed) 28
13
(Used on M53) 27
24. Electric Heaters 29 6
25. Humidity Sensor 9
26. Controller
4
27. Low Pressure Cutout Switch (LPCO) 3 5
28. Modulation Valve (MV)
11
29. Suction Line Solenoid (SLS) 2 12
30. Liquid Injection Valve w/ Restrictor (LIV)
31. Suction Service Valve (SSV)
(Not used on M53) 10
32. Compressor Bypass Oil Filter 30
(Not used on M53) 1
33. Check Valve (Not used on M53) AJA496
Section 3-Container Refrigeration Unit & System Diagrams
3-35
discharge pressure at 70 PSIG (478.4 kPa) into the 23
compressor.
9. High Pressure Relief Valve
OPENS at 500 ± /-15 PSIG 14
(3447+345/-104 kPa).
Reset (CLOSES) at 400 PSIG (2758 kPa).
26. Controller 8
Thermoguard µP-A+ with digital thermostat,
thermometer and fault indicator monitor.
7
Null Mode Operation
28 13
During Null Mode Operation, the compressor does 27
not run. Condenser fan run for 2 minutes and stops. 29 6
Evaporator blowers are running. (Speed is
9
controlled by the return air sensor temperature.)
High pressure gas 4
3 5
High pressure liquid 11
Low pressure gas 2 12
Low pressure liquid
Condensing high pressure gas
Low pressure vaporizing liquid 10
30
Liquid refrigerant injection
1
AJA497
Flow and Pressure Diagram
CF-II M37.6, M37.7, M37.9,
M52, M52.1, M53
Modulated Cool
24. Electric Heaters
During DEFROST operation, the Electric Heaters
are energized. The compressor does not run.
Evaporator blowers and the condenser fan are off.
During HEAT operation, the Electric Heaters are
energized. The compressor does not run.
Condenser fan is off. Evaporator blowers running.
(Speed is controlled by the return air temperature.)
27. Low Pressure Cutout Switch (LPCO) 15 16
Is a normally CLOSED switch. 25
It OPENS (cut-out) at 5 to 17 in hg vacuum 17
21
(-17 to -57 kPa).
It CLOSES (cut-in) at 1 to 7 PSIG (7 to 48 kPa).
28. Modulation Valve (MV)
Is a normally OPEN valve. 22 20
It CLOSES when energized. As the signal strength 18 19
is increased, the valve CLOSES more. The
controller controls the signal to the valve as it
monitors the temperatures and power limit to the 26 24
3-36
compressor. 23
29. Suction Line Solenoid (SLS)
Section 3-Container Refrigeration Unit & System Diagrams
3-37
20. Fusible plug
21. Sightglass/moisture indicator
22. Sightglass 12
2
23. Fusible plug
24. Service adapter
25. Adapter incl. schraeder valve 15 13 23
26. High pressure switch
24, 25
27. Condenser
27
14 22
1
26
21
16
AJA499
TNE 508 w/ Unloaders
1. Evaporator coil
2. Condenser coil 1
3. Receiver
4. Dehumidifying solenoid valve
5. TX Expansion valve
6. Drier refrigerant
7. Hand valve
4
8. Indicator moisture
9. Heat exchanger 5
10. Constant pressure regulator
11. Crankcase pressure regulator 13
12. Compressor
13. Liquid solenoid valve
9
14. Non return valve
2
6 7
8
3-38
Section 3-Container Refrigeration Unit & System Diagrams
3
10
11
14
12
AJA500
Section 3-Container Refrigeration Unit & System Diagrams
3-39
High pressure gas
High pressure liquid
Low pressure gas
Low pressure liquid
Condensing high pressure gas
Low pressure vaporizing liquid
Liquid refrigerant injection
Modulated pressure
Flow and Pressure Diagram
CRR-40
Full Cool
1. D3DS Compressor
Compressor operation has a variable delay on initial start-up. A
sequence start of the compressor occurs when the compressor has
been OFF for more than 18 hours.
4. High Pressure Cutout Switch (HPCO)
Is a normally CLOSED switch.
OPENS at 2240 +/- 70 kPa, 22.4 +/- 0.7 bar 325 +/- 10 psig.
It CLOSES at 1590 +/- 70 kPa, 15.9 +/- 0.7 bar, 230 +/- 10 psig.
9. High Pressure Relief (Fusible Plug)
BLOWS at 100 C (212 F).
16. Liquid Line Solenoid (LLS)
Is a normally CLOSED solenoid.
It opens when energized, when the compressor operates.
22. Electric heaters
During the DEFROST mode, the electrical heaters are pulsed ON
and OFF.The compressor, condenser fan and evaporator fans are
OFF.
During the HEAT mode, the electric heaters are pulsed ON and
OFF. The compressor and condenser fans are OFF. The evapora-
tor fans continoue to operate (evaporator fan speed is determined
by the setpoint and economy mode setting).
28. Controller
3-40
Microprocessor with digital thermostat, thermometer and fault
indicator monitor.
Section 3-Container Refrigeration Unit & System Diagrams
3-41
reducecooling capacity by about 50%, the controller will
pulse the electric heaters ON and OFF. This increases the
cooling
load of the evaporator coil, thereby lowering the
temperature of the entire coil and condensing more
moisture from the container air.
33. Humidity Sensor (rH)
The humidity sensor is located at the top right hand side
of the evaporator fan deck and measures the humidity of
the return air from the cargo space.
High pressure gas
High pressure liquid
Low pressure gas
Low pressure liquid
Condensing high pressure gas
Low pressure vaporizing liquid
Liquid refrigerant injection
CSR-40
Refrigeration System Components
1. Scroll compressor
2. Sight Glass
3. Oil Fill / Drain Fitting
4. Compressor Head Discharge Temperature Sensor 33
(CDTS) 19 23
18
5. High Pressure Cutout Switch (HPCO)
6. Condenser Fan Pressure Switch (CFPS) 24
7. Discharge Service Valve (DSV)
8. Condenser Coil (Circular)
18 22
9. High Pressure Relief Valve
32 25
10. Receiver Tank
11. Receiver Tank Sight Glasses 20
12. Receiver Tank Outlet Valve
13. Receiver Bypass Valve 17 28
21
14. Compressor Oil Filter
15. Filter Drier (Dehydrator) 13
3-42
9
16. Heat Exchanger
27
Section 3-Container Refrigeration Unit & System Diagrams
3-43
28. Controller (µP-D) 9 11
Thermoguard (µP-D) with digital thermostat,
27
thermometer and fault indicator monitor.
Null Mode Operation 10
During the Null mode, the compressor does not
operate. If the condenser fan is ON (based on 16 11
condensing pressure) when the unit shifts to Null,
the condenser fan operates for 30 seconds and stops.
Evaporator fans continue to operate (evaporator fan 14
speed is determined by return air temperature and
economy mode setting). 12
15
5 6 8
26
High pressure gas 29 AJA506
High pressure liquid 7
Low pressure gas 4
Low pressure liquid 31
Condensing high pressure gas 30 2
Low pressure vaporizing liquid 3
Liquid refrigerant injection
1
Flow and Pressure Diagram
CSR-40
Modulation Cool
13. Receiver Bypass Valve
Is a normally CLOSED solenoid.
It OPENS when energized to reduce cooling
capacity when the temperature is close to setpoint.
22. Electric Heaters 18 19 23
During the defrost mode, the electric heaters are
pulsed ON and OFF. The compressor does not
24
operate. The condenser fan and evaporator fans
remain OFF.
During the HEAT mode, the electric heaters are 18
pulsed ON and OFF. The compressor does not
22
32 25
operate. The condenser fan is OFF. The
evaporator fans continue to operate (evaporatro fan
20
speed is determined by return air temperature and
economy mode setting).
29. Modulation Valve (MV) 21 17 28
Is a normally OPEN valve. 13
It OPENS when energized. When liquid injection
9
3-44
is required, the valve is pulsed open and closed on 11
a 10 second cycle. 27
Section 3-Container Refrigeration Unit & System Diagrams
3-45
side of the evaporator fan deck and measures the 9
humidity of the return air from the cargo space. 11
27
10
16 11
14
12
15 8
5 6
26 AJA508
High pressure gas 29
High pressure liquid 7
Low pressure gas 4
Low pressure liquid 31
Condensing high pressure gas 30 2
3
Low pressure vaporizing liquid
Liquid refrigerant injection
1
Flow and Pressure Diagram
CSR-20 & CSR-40
Modulation Cool
7. Warm Gas Bypass Valve
Is a normally CLOSED solenoid.
It OPENS when energized to reduce cooling
capacity when the temperature is close to
setpoint.
16. Modulation Valve (MV)
Is a normally OPEN valve.
It CLOSES when energized. As the signal
strength is increased, the valve closes more. The
controller regulates the signal to the valve based
on sensor temperatures and power limit
requirements.
18. Liquid Injection Valve (LIV)
Is a normally CLOSED valve.
It OPENS when energized. When liquid injection
is required, the valve is pulsed open and closed
on a 10 second cycle.
3-46
The valve is energized when the compressor head
temperature is above 138 C (280 F) or when the
Section 3-Container Refrigeration Unit & System Diagrams
3-47
The humidity sensor is located at the top right hand side of
the evaporator fan deck and measures the humidity of the
return air from the cargo space.
High pressure gas
High pressure liquid
Low pressure gas
Low pressure liquid
Condensing high pressure gas
Low pressure vaporizing liquid
Liquid refrigerant injection
Modulated pressure
Section 3-Container Refrigeration Unit & System Diagrams
CRR DF
3-48
Section 3-Container Refrigeration Unit & System Diagrams
3-49
Section 3-Container Refrigeration Unit & System Diagrams
3-50
Section 3-Container Refrigeration Unit & System Diagrams
3-51
Section 3-Container Refrigeration Unit & System Diagrams
3-52
SECTION 4
Thermostat Sequence
Diagrams
4-1
Section 4-Thermostat Sequence Diagrams
8.0 F (4.5 C)
Condenser Fan
Controlled by Full Cool
Pressure Switch
Full Cool
Defrost
Defrost
Unit Function
Heat
Null
Null
4-2
Section 4-Thermostat Sequence Diagrams
Cool Cool
+9.0 F (5.0 C)1
Modulation Cool
Null
+0.5 F (+.03 C)1
Set point 1 Set point4 +0.5 F (+.03 C)4
In-Range
- 1.0 F (-.06 C)1
Heat2 -2.0 F (-1.1 C)3 Null
In-Range
- 3.0 F (-1.7 C)3
Cool Cool
1
+5.4 F (+3.0 C)
Modulation Cool
+4.0 F (+2.2 C)3 +4.0 F (+2.2 C)3
Out-of-Range
3
+3.0 F (+1.7C)3 +3.0 F (+1.7C)
Null
+0.5 F (+.03 C)1 Out-of-Range
+0.5 F (+.03 C)4
Set point1 Set point4
In-Range
-1.0 F (-.06 C)1
Heat2
-2.0 F (-1.1 C)3
In-Range
-3.0 F (-1.7 C)3
Null
4-3
Section 4-Thermostat Sequence Diagrams
1
A
+4.5 F4
(+2.5 C)
A
+4.5 F5
+3.0 F5
(+2.5 C) +4.5 F6
(+1.7 C)
B (+2.5 C)
C
E +0.5 F +3.0 F6
4 (+0.3 C4) (+1.7 C)
2 +1.8 F6,8
E (+1.0 C)
-1.0 F4 -3.0 F5 -3.6 F6,7
(-0.6 C) D (-1.7 C) (-2.0 C)
-4.5 F5 C
AJA798
(-2.5 C)
3 AJA707
Fresh Load Control Sequence 3
(Setpoints at 14.1 F (-9.9C) and Above)
Frozen Load Control Sequence
A. Cool 1. Decreasing Temperature (Setpoints at 14F (-10C) and Below)
B. Modulation Cool 2. Setpoint Economy Mode ON
C. Null 3. Increasing Temperature
A. Cool 1. Decreasing Temperature
D Heat 4. Calculated Temperature Differential
C. Null 2. Setpoint
E. In Range 5. Supply Air Temperature
E. In-Range 3. Increasing Temperature
6. Return Air Pressure
7. ECMIN (default setting is
1 3.6F (2.0C) below
setpoint) Setting is
adjustable from 0F to
18F (0C to 10C)below
setpoint.
A 8. ECMAX (default setting
is 1.8F (1.0C). Setting is
+4.5 F6 adjustable from 0F to
(+2.5 C) 18F (0C to 10C) above
setpoint.
+3.0 F6
(+1.7 C)
+1.8 F6
E (+1.0 C)
-1.8 F6
(-1.0 C)
C
AJA709
3
Frozen Load Control Sequence
(Setpoints at 14F (-10C) and Below)
Economy Mode OFF
A. Cool 1. Decreasing Temperature
C. Null 2. Setpoint
E. In-Range 3. Increasing Temperature
6. Return Air Pressure
4-4
SECTION 5
Evacuation
5-1
Section 5-Evacuation
5-2
Section 5-Evacuation
5-3
Section 5-Evacuation
TESTING FOR AIR AND OTHER 3. Close the high side gauge valve to isolate the micron
gauge and pump.
NON-CONDENSABLES IN A
THERMO KING CONTAINER 4. Open the receiver tank service valve to a count of four
(4). Then close the valve and count to four (4) again.
REFRIGERATION UNIT
5. Then close the low side gauge valve.
MANIFOLD SET HOOKUP PROCE- 6. Place the sample bottle into the ice bath for 15 to 20 min-
utes. Stir the ice bath occasionally.
DURE
Attach manifold set as follows: NOTE: An ice water bath must be 75% ice in small
pieces and it should completely cover the sample bottle.
1. Connect low side hose to sample bottle. The smaller the sample bottle, the faster the
temperature will equal that of the ice water bath.
2. Connect center hose to receiver tank service valve. 7. Compare the low side gauge reading with your pressure/
temperature chart for 32 F (0 C).
3. Connect high side hose to evacuation pump. R-12 = 30.2 psig (208 kPa)
R-134a = 27.3 psig (188 kPa)
R-404a = 72.5 psig (499.5 kPa)
CAUTION: If hoses are not connected properly, gauge
readings will be inaccurate.
READING MUST BE PLUS/MINUS
ICE BATH TEST PROCEDURE ONE (1) psig (7 kPa)
If pressures exceed specifications, the refrigerant must be
1. Open manifold gauges and evacuate all hoses, manifold
reclaimed and the unit totally evacuated according to proper
and sample bottle to 500 microns.
evacuation procedures. After the system has been evacuated,
leak tested, and recharged with clean refrigerant, reconfirm
CAUTION: Ensure that there are no leaks in the system.
the system operation. If system operation is satisfactory,
return the unit to service.
2. Run the unit to circulate any air that may be in the sys-
tem.
5-4
Section 5-Evacuation
5
6
1 8
5-5
SECTION 6
R12 to R134a Conversion
6-1
Section 6-R12 to R134a Conversion
Tool List - Reference 3. Operate unit in full cool with the container temperature
above 50 F (10 C) for one (1 hour) to get the maximum
Van Steenburgh or other U.L. approved refrigerant reclama- amount of oil back to the compressor.
tion system
In ambient conditions below 50 F (10 C) it may be necessary
Thermo King Evacuation Station to use supplemental heat sources to raise the container (box)
110 VAC P/N 204-725 temperature above 50 F (10 C).
220 VAC P/N 204-744
In ambients ABOVE 50 F (10 C) opening the container doors
may be sufficient to keep the unit operating in the full cool
Adapters for the Evacuation Station for use with mode.
R-134a fittings.
High Side Couplers (2 needed)P/N 204-791 4. Leak check unit (repair leaks before continuing).
Low Side CouplerP/N 204-792
Vacuum Pump Oil 1 US GallonP/N 203-419 5. Turn unit off and reclaim R12 with U.L approved recla-
Leak Detector for R-134a refrigerant mation system. Pull system down to 10î vacuum.
12VDC/110 VACP/N 204-756
12VDC/220 VACP/N 204-765 NOTE: While refrigerant is being reclaimed see attachment
Manifold gauge set for R-134aP/N 204-758 on assembly and use of the compressor oil drain and fill
Electronic programmable charging scale tool.
110 VACP/N 204-760
220 VACP/N 204-795 6. With the unit still in a vacuum install the oil drain tool,
Compressor oil sump drain and fill toolP/N 204-750 this will minimize oil spillage.
Oil Sump Adapter (included with 204-750 Kit)
P/N 204-796 7. Return unit pressure to 0 to 2 psig (O to 14 kPa) using dry
125# Cylinder valve adapter (converts 3.4’NPS nitrogen.
on the valve to 1/4” male flare)P/N 204-169
R-134a ACME Coupler (converts 1/4” male flare to 8. FIRST OIL CHANGE. Drain oil from compressor sump.
1/2”male ACME) (permanent application) Refill with 1 US gallon (3.78 liters) of polyolester oil.
P/N 204-793
R-134a ACME Coupler, (converts 1/4” male flare to
1/2” male ACME (with swivel nut)P/N 204-794
6-2
Section 6-R12 to R134a Conversion
9. Install the following new parts. 15. Charge system with R-134a (see unit data plate for proper
charge weight). Operate the unit at 50 F (10 C) (or above)
• Replace the expansion valve thermostatic element. Hand box temperature for 20 minutes. Turn unit off.
tighten element and then tighten an additional 1/6 turn (1
flat on the nut). 16. Leak check unit (make any repairs as needed).
• Clean suction line and install TXV sensor bulb with new NOTE: While unit is operating between oil changes, install
clamps and insulation wrap. the new decals. See attached CF-11 decal positioning.
17. SECOND OIL CHANGE. Pump down the compressor to
Suggestion: To make the installation of the insulation eas- 0 psig. Adjust pressure to 1 to 2 psig (7-14 kPa) positive.
ier, cut the long strip into 4 short pieces. Drain the compressor oil. Refill with 1 US gallon of new
polyolester oil. Operate unit for 20 minutes at 50 F (10 C)
10. Remove schrader valve depressors from the 1/4î flare fit- (or above) box temperature.
tings on the discharge side of the system only.
18. THIRD OIL CHANGE. Pump down the compressor to 0
11. Install Two Discharge (red) and One Suction (blue) R- psig. Adjust pressure to 1 to 2 psig (7-14 kPa) positive.
134a access fitting using provided Locktight on the Drain the compressor oil. Refill with 1 US gallon of new
threads. polyolester oil. Operate unit for 20 minutes at 50 F (10 C)
(or above) box temperature.
NOTE: Do Not over tighten adapters. The adapters have an 19. FINAL OIL FILL. Pump down the compressor and drain
integral o-ring seal. Torque to 5 to 6 ft/lbs. (60-72 in/lbs.) the oil. Refill the compressor new with polyolester oil to
maximum. the BOTTOM of the sight glass. Operate the unit in full
cool for 20 minutes and check oil level. Oil level should
12. Remove any remaining 1/4î flare fittings and plug the
be 1/2 sight glass. Make adjustments as needed.
hole(s) with 1/8î pipe plug(s) using the provided Lock-
tight on the threads.Install new Oil Fill Plug and O-Ring.
20. Pump down the compressor and remove the oil fill/drain
tool and install the new oil drain plug and o-ring pro-
13. Install new Filter Drier.
vided.
14. Evacuate refrigeration system using the Thermo King
21. Isolate and evacuate the compressor to remove any air
Evacuation Station.
that may have entered the compressor during installation
of the drain plug.
6-3
Section 6-R12 to R134a Conversion
6-4
Section 6-R12 to R134a Conversion
26. After this is complete, replace the K 3 (Evap. Fan High) CAUTION: WHEN ADJUSTING SUPERHEAT, DO NOT
relay and operate the unit in MAXIMUM COOL until ADJUST VALVE STEM ANY MORE THAN ONE (1)
Return Air is 0 F (-18 C) again. COMPLETE TURN (4 FLATS) AT A TIME.
27. With the unit continuing to operate in MAXIMUM If the proper Superheat WAS NOT achieved using the above
COOLING, read the Suction Pressure on the compound procedure further adjustment of the TXV is required. To
gauge and Suction Temperature on the thermometer. adjust the TXV, use the following procedure:
Make several readings approximately every two (2) min-
utes. • If the Superheat is TOO LOW (potential liquid return to
the compressor), turn the valve stem IN (clock wise when
28. If measuring evaporator outlet pressure between the viewed from the stem end) approximately 1/4 turn (1 flat
evaporator coil outlet and modulation valve, skip step 34 on stem). 1/4 turn of the stem provides approximately 1 F
and go to step 35. (0.5 C) change in Superheat.
29. IF MEASURING SUCTION PRESSURE AT THE • REPEAT AS NECESSARY UNTIL THE PROPER
COMPRESSOR, ADD I PSIG to the pressure gauge SUPERHEAT IS ACHIEVED.
reading BEFORE converting that pressure to the corre-
sponding Saturation Temperature using an R-134a Pres- • If the Superheat is TOO HIGH (lack of cooling capacity),
sure / Temperature chart. turn the valve stem OUT (counter clock wise when
viewed from the stem end) approximately 1/4 turn (1 flat
30. Subtract the Saturation Temperature from P/T chart from on stem). 1/4 turn of the stem provides approximately 1 F
the Suction Vapor (Thermometer) Temperature. The dif- (0.5 C) change in Superheat.
ference is the Superheat.
• REPEAT AS NECESSARY UNTIL THE PROPER
Note: If the proper amount of Superheat was achieved using SUPERHEAT IS ACHIEVED.
the above procedures the conversion is complete and the
31. Pre-Trip unit and return to service.
unit may be placed back into service. If the proper amount
of Superheat was not achieved, perform the following
procedures for the conditions obtained.
6-5
Section 6-R12 to R134a Conversion
1. Inlet
2. Equalizer Line
3. To Distributor
6-6
SECTION 7
AC Electricity
7-1
Section 7-AC Electricity
DEFINITIONS OR TERMS USED IN CURE: The word cure embraces all theoretical and practical
aspects of the term Vulcanization of rubber or neoprene com-
THE WIRE AND CABLE INDUSTRY pounds.
A.S.T.M.: American Society for Testing Materials. CURRENT CARRYING CAPACITY: The current carrying
A.W.G.: American Wire Gauge. The wire gauge universally capacity of an electrical conductor is the maximum current
used in the U.S to designate the size of wire or conductors. the conductor can carry without heating beyond a safe limit.
The number designating wire sizes are retrogressive. The DUPLEX CABLE: A duplex cable is a cable composed of
larger the number the smaller the wire. two insulated conductors twisted together with no sheath or
BRAID: A woven covering of cotton or other type of yarn, outer covering.
used on some types of insulated wires. Braids provide some DIRECTION OF LAY: The direction of lay is the lateral
mechanical strength and serve as a means of polarity identifi- direction in which the strands of a cable run over the top of
cation. the cable as they recede from an observer looking along the
BUNA RUBBER: Man-made rubber used as replacement axis of the cable. This is the same designation used for thread
for natural rubber. direction of screws.
BUNCH STRANDING: A Bunch Strand is a collection of DIELECTRIC: A medium having the required properties that
wires or strands twisted together in the same direction without the energy required to establish an electric field (voltage
regard to geometrical arrangement. stress) is recoverable, in whole, or in part, as electrical energy.
The establishment of the field or voltage stress is accom-
BUTYL RUBBER: Man-made rubber used for special appli- plished by displacement of charging currents. A vacuum is the
cations. Has excellent resistance to heat, sunlight, weather, only known perfect dielectric.
aging and ozone.
DIELECTRIC STRENGTH: The voltage stress required to
C.M.: Circular Mil. puncture a specimen of known thickness, expressed as volts
CABLE: A cable is a standard insulated single conductor or per unit thickness.
an assembly of insulated conductors usually with an outer G.R.S.: Same as Buna Rubber.
covering. Small single conductors are often called wires and
small flexible cables are called cords. There are numerous I.P.C.E.A.: Insulated Power Cable Engineers Association.
deviations from these definitions resulting from traditional INSULATION: Any substance of such low conductivity that
names for items used for a long time. the flow of electrical current through it can usually be
CIRCULAR MIL: The circular mil area of a round conductor neglected.
is obtained by squaring its diameter measured in thousandths INSULATION RESISTANCE: The insulation resistance of
of an inch. For instance, a 0.010 inch wire has an area of 100 an insulated conductor is the resistance offered by its insula-
circular mils: a 0.001 inch wire has an area of 1 circular mil, tion to current flow from impressed d.c.
etc.
JACKET: An outer sheath or covering, extruded or tubed
COMPACT STRANDING: A compact stranded conductor over an insulated conductor, or over an assembly of insulated
is a round or sector conductor having all layers of wires conductors.
within it stranded in the same direction and rolled to the
LAY: The lay or pitch of any helical element of a cable is the
desired shape. The finished conductor has a relatively smooth
axial length of a turn of the helix of that element.
surface and the individual strands are no longer round.
CONCENTRIC STRANDING: A concentric stranded con- LEAD-CURE: A vulcanization process for wires and cables
ductor consists of a central wire or core surrounded by one or during which unvulcanized insulated wires or cables are run
more layers of helically laid wires. Each layer of wires is through a lead press which forms a lead pipe snugly around
applied in the reverse direction to the layer of wires under it. the cable. The lead cure process consists of vulcanizing the
insulated cable while it is enclosed in this tight fitting pipe.
CONDUCTOR: A conductor is a wire or a group of wires When vulcanization is complete, the lead pipe is removed
uninsulated from one another, suitable for transmitting elec- from the cable.
tric current. A conductor may be bare of insulated.
MCM: 1000 Circular Mils.
CORD: A cord is a small very flexible cable, having two or
MIL: “MIL” is a term universally used in the United States to
more conductors insulated from one another, covered by an
measure wire or cable diameters. It is a unit of length equal to
outer sheath or suitable covering.
one-thousandth of an inch.
7-2
Section 7-AC Electricity
N.E.C.: National Electric Code. copper and insulation. It also facilitates soldering the wire to a
terminating connection.
N.E.M.A.: Abbreviation for National Electrical Manufactur-
ers Association. TINSEL: Tinsel wire is an extra flexible conductor made by
wrapping thin flat ribbons on copper or bronze around fine
NEOPRENE: A man-made rubber having superior resis-
cotton or textile yarns of other fibrous materials. This type of
tance to oils, alkalies, acids and most solvents. Has high abra-
conductor has a low current carrying capacity.
sion resistance and will not support combustion.
PLASTIC: A physical condition characterized by permanent TRACER: A means of identifying polarity,e.g., a thread or
change of shape of a material upon application of force. group of threads of contrasting color or size in a braid, a ridge
on insulation surface, a colored stripe on insulation.
ROPE STRANDING: A rope stranded conductor is a
TRIPLEX CABLE: A triplex cable is a cable having three
stranded conductor, formed by cabling together groups of
insulated conductors twisted together without a sheath over
wires which are themselves stranded.
all.
SAFETY FACTOR: The safety factor of assurance of wire
TWIN CABLE: A twin cable is a cable having two insulated
or cable insulation is the ratio of the voltage at which it is
conductors, laid parallel and having a protecting sheath or
tested to that at which it is used or designed for.
jacket over them.
SELENIUM: A finely ground form of an elementary metal:
TWISTED PAIR: A twisted pair comprises two insulated
used as a vulcanizing agent in rubber compounds.
conductors twisted together without a common covering.
SHIELDED CABLES: A shielded cable is a cable in which
the insulated conductor or conductors is/are enclosed within VULCANIZATION: Vulcanization or cure is a permanent
an envelope of conducting material. The shield of conducting chemical and mechanical change in Rubber or Neoprene
metal or other material is so applied that substantially every Compounds. After application of heat and pressure, the com-
point on the surface of the insulation is at ground potential. pound is no longer plastic; but now, has the familiar property
of stretching and returning to its original shape upon the
STRAND: A strand is a single uninsulated wire used in com- application and removal of force.
bination with other strands or groups of strands to form a con-
WIRE: A wire is a rod or filament of drawn metal, usually of
ductor.
circular cross section.
STRANDED CONDUCTOR: A stranded conductor is com-
posed of a group of wires, or a combination of groups of
wires.
ELECTRICAL DEFINITIONS
SYNCHRO-CURE: An improved, perfected method of vul- AMPACITY: Current carrying capacity of conductors
canizing rubber insulated cables, which makes it possible to expressed in amperes.
balance the “cure” of the rubber insulated conductors with the ALTERNATING CURRENT: Alternating current (ac) is
“cure” of the Neoprene or rubber outer sheath. By eliminating current which reverses direction rapidly, flowing back and
the possibility of “over-cure”, maximum physical properties forth in the system with regularity. This reversal of current is
and electrical characteristics are maintained. due to reversal of voltage which occurs at the same frequency.
TELLURIUM: A finely ground form of an elementary metal; In alternating current, any one wire is first positive, then neg-
used as a vulcanizing agent in rubber compounds. ative, then positive and so on. With commercial power, the
change from positive to negative to positive occurs 60 times
THERMOPLASTIC: A physical condition in which the per second resulting in 60 Hertz current.
plasticity is increased by increased temperatures and
decreased by decreased temperatures. Any change of shape ALTERNATOR: An electric generator designed to supply
resulting from the application of force at elevated tempera- alternating current. Some types have a revolving armature and
tures is permanent. in other types a revolving field.
THERMOSETTING: A term applied to any type of material AMPERE: The ampere is the unit of measurement for elec-
which, although originally in a plastic condition, undergoes tric current. It represents the rate at which current flows
permanent change at increased temperature, so that subse- through a resistance of one ohm by a pressure of one volt.
quent changes of shape resulting from applications of force CAPACITOR OR CONDENSER: A capacitor is an electri-
exist only during the period the force is effective and the orig- cal device which causes the current to lead the voltage, oppo-
inal shape is restored when the force is removed. site in effect to inductive reactance. Capacitors are used to
TINNED CONDUCTOR: A bare copper wire with a thin neutralize the objectionable effect of lagging current (induc-
coating of tin. The tin coating acts as a separator between the tive reactance) which overloads the power source. It also acts
7-3
Section 7-AC Electricity
as a low resistance path to ground for currents of radio fre- cotton, enamel and paraffin are called insulators because they
quency thus effectively reducing radio disturbances. are practically non-conducting. However, no material is a per-
fect insulator.
CONDUCTOR: Substances which offer little resistance to
the flow of electric current (such as metals). Silver, copper KVA: The abbreviation of kilovolt-amperes which is the
and aluminum are especially good conductors although no product of the volts times the amperes divided by 1000. This
material is a perfect conductor. Each of the wires lying in the term is used in rating alternating current machinery because
armature slots of an electric generator is referred to as a con- with alternating currents, the product of the volts times the
ductor. amperes usually does not give the true average power. See
Reactance and Power Factor.
CURRENT: The flow of electricity in a circuit (similar to the
flow of water in a pipe). It is expressed in amperes and repre- KVAR: The abbreviation of kilovolt-ampere reactance which
sents an amount of electricity, similar to gallons per minute of is a measurement of reactive power that generates power
water flow, regardless of the pressure (voltage). within induction equipment (motors, transformers, holding
CYCLE: One complete period of flow of alternating current coils, lighting ballasts, etc.).
in both directions. One cycle represents 360×. See Frequency. KW: The abbreviation for kilowatt is a unit of measurement
DIRECT CURRENT: Current (dc) which flows in one direc- of electrical power. A kilowatt (kw) equals 1000 watts and is
tion only. One wire is always positive, the other negative. the product of the volts times the amperes divided by 1000
when used in rating direct current machinery. It is also the
ELECTRICAL GENERATOR: An electrical generator is a term used to indicate true power in an ac circuit.
machine so constructed that when its rotor is driven by an
KILOWATT HOUR: A kilowatt hour is the amount of elec-
engine or other prime mover, a voltage is generated.
trical power represented by 1000 watts for a period of 1 hour.
EXCITER: An exciter is a direct-current generator which Thus a generator which delivered 1000 watts for a period of 1
supplies direct current to excite or magnetize the fields of an hour would have delivered 1 kilowatt hour of electricity.
alternator. An exciter may be a separate machine or be com-
OHM: The ohm is the unit of measurement of electrical resis-
bined with the alternator.
tance and represents the amount of resistance that permits cur-
FARAD: A farad is a measure of electrical capacity of con- rent flow at the rate of one ampere under pressure of one volt.
densers. A microfarad is one-millionth of a farad and is abbre- The resistance (in ohms) equals the pressure (in volts) divided
viated “mfd”. by the current (in amperes).
FREQUENCY: Frequency of alternating current is the num- POWER FACTOR: When the current waves in an alternat-
ber of cycles per second. A 60-Hertz alternating current ing-current circuit coincide exactly in time with the voltage
makes 60 complete cycles of flow back and forth (120 alter- waves, the product of volts times amperes gives volt amperes
nations) per second. A conventional alternator has an even which is true power in watts (or in kw if divided by 1000).
number of field poles arranged in alternate north and south When the current waves lag behind the voltage, due to induc-
polarities. Current flows in one direction in an ac armature tive reactance (or lead due to capacitive reactance), they do
conductor while the conductor is passing a north pole and in not reach their respective peak values at the same time.
the other direction while passing a south pole. The conductor
passes two poles during each cycle. A frequency of 60 Hertz Under such conditions, the product of volts and amperes does
requires the conductor to pass 120 poles per second. In a 6- not give true average watts. Such a product is called volt
pole alternator, the equivalent speed would be 20 revolutions amperes or apparent watts. The factor by which apparent
per second or 1200 revolutions per minute. In a 4-pole alter- watts must be multiplied to give the true watts is know as the
nator, the equivalent speed would be 30 revolutions per sec- power factor (PF).
ond or 1800 revolutions per minute.
HERTZ: A unit of frequency, one cycle per second. Written Power factor depends on the amount of lag or lead, and is the
as 50-Hertz or 60-Hertz current, etc. percentage of apparent watts which represents true watts.
With a power factor of 80%, a fully loaded 5KVA (80% PF)
IMPEDANCE: Effects placed on alternating current by alternator will produce 4KW (true watts). When the rating of
inductive capacities (current lags voltage), capacitor reactance a power unit is stated in KVA at 80% PF, it means that with an
(current leads voltage) and resistance (opposes current but 80% PF load, the generator will generate its rated voltage pro-
does not lag or lead voltage) or any combination of two. It is viding the load does not exceed the KVA rating.
measured in ohms like resistance.
INSULATOR: Substances which offer great resistances to An engine-driven alternator with automatic voltage regula-
the flow of electric current such as glass, porcelain, paper, tion, the KVA rating usually is determined by the maximum
7-4
Section 7-AC Electricity
current which can flow through the windings without injuri- at the rate of one ampere. In a dc circuit or in an ac circuit at
ous overheating or by the ability of the engine or other prime unity (100%) power factor, the number of watts equals the
mover to maintain the normal operating speed. A resistance pressure (in volts) multiplied by the current (in amperes).
load such as lamp bulbs, irons, toasters and similar devices is
a unity power factor load. Motors, transformers and various ELECTRICAL POWER SUPPLY
other devices cause a current wave lag which is expressed in
the power in the power factor of the load. The preceding section dealt with Direct Current power. This
source was primarily from a battery which was maintained by
REACTANCE: Reactance is opposition to the change of cur-
the generator or alternator. This section will deal with alter-
rent flow in an ac circuit. The rapid reversing of alternating
nating current that is supplied to run the motor or operate
current tends to induce voltages that oppose the flow of cur-
other components.
rent in such a manner that the current waves do not coincide
in time with the voltage waves. The opposition of self induc-
Alternating current is different from direct current in that the
tance to the flow of current is called “inductive reactance” and
current flow is constantly reversing in the circuit while direct
causes the current to lag behind the voltage causes the current
current flows only in one direction.
wave to lead the voltage wave. This is called “capacitive reac-
tance.” The unit of measurement for either inductive reac-
The alternating current that is supplied has voltage character-
tance or capacitive reactance is the ohm.
istics as follows:
RESISTANCE: Electrical resistance is opposition to the
flow of electric current and may be compared to the resistance If the electric service is a two-wire system of any voltage, the
of a pipe to the flow of water. All substances have some resis- current will flow first in one direction and then the other
tance but the amount varies with different substances and with direction. The current flow will alternate or charge direction
the same substances under different conditions. at a rate of 120 times a second, or 60 cycles per second. This
cycling or frequency is call Hertz (Hz). In some locations this
RESISTOR: A resistor is a poor conductor used in a circuit
may be only 50 Hz as in European and Asian countries.
to create resistance which limits the amount of current flow. It
may be compared to a valve in a water system.
SINGLE PHASE: A single phase, alternating-current sys-
tem has a single voltage in which voltage reversals occur at
the same time and are of the same alternating polarity
VOLTS
throughout the system.
THREE PHASE: A three phase, alternating-current system
has three individuals circuits or phases. Each phase is timed
so the current alternations of the first phase is 1-3-cycle ZERO 0° 180° 360°
(120°) ahead of the second and 2-3-cycle (240°) ahead of the
third.
VOLTAGE: Voltage is the force, pressure or electromotive
force (EMF) which causes electric current to flow in an elec-
tric circuit. Its unit of measurement is the volt, which repre-
sents the amount of electrical pressure that causes current to
flow at the rate of one ampere through a resistance of one
ohm. Voltage in an electric circuit may be considered as being
similar to water pressure in a pipe or water system.
BASIC ALTERNATING CURRENT
VOLTAGE DROP: The voltage drop in an electrical circuit
is the difference between the voltage at the power source and Electrical power, how does it originate? Many times we over-
the voltage at the point at which electricity is to be used. The look the very basic requirements of electrical power genera-
voltage drop or loss is created by the resistance of the con- tion.
necting conductors.
1. A magnetic field created by one or more permanent mag-
WATT: The watt is the unit of measurement of electrical
nets each having a North and South Pole.
power or rate of work. 746 watts is equivalent to 1 horse-
power. The watt represents the rate at which power is
2. A conductor in effect with the magnetic force.
expended when a pressure of one volt causes current to flow
7-5
Section 7-AC Electricity
4. The external conductor to complete the circuit with mod- It should be understand that none of our units are designed to
ifications. These basic requirements are in use in all gen- use the system ground in lieu of the system neutral in control
erators. or power circuits. Units which require a neutral connection
for satisfactory operation will not operate safely and reliably
The magnetic field is maintained using coils which use d.c. if a connection to ground is used in lieu of a connection to
power or permanent magnets for excitation. neutral. Most power companies ground their neutral when
they have one, but this fact does not alter the above.
The field may rotate, as in an alternator, or be stationary as in Whenever the standby system is worked on, the control power
a generator, or may be a combination. transformer leads must be wired as shown on the unit wiring
diagram. This means that they must be wired for proper volt-
A rotating or stationary field virtually has no difference as to age and into the correct supply conductors. They must not be
output. wired from one of the supply phase wires, through the trans-
former, unit circuitry, switches, control contacts to ground.
This is the EXCITATION CIRCUIT. By varying the amount
of excitation, output is changed. With the unit disconnected from the power source, you should
be able to check with an ohmmeter or a “megger” and find no
If a single conductor is in motion through a magnetic field connection between ground and any part of the high voltage
(magnetic lines of force), it has no practical use. system for electric standby.
1. If the number of conductors is increased, the voltage will Conditions within the A.C. Circuit: there are three basic con-
increase. ditions that can take place within any electrical circuit resis-
tance, inductions, and capacitance.
2. If the size of the conductor is increased, the amperage Resistance: With this type of load, the voltage and amper-
will increase. age sine wave are in phase.
This normally accounts for the physical size of any unit. By Inductive: With an inductive load, the voltage leads the
combining the proper turns and size of wire, the manufacturer amperage. This is referred to as lag.
can have any output of voltage and amperage required. Capacitance: With this type of load, the current leads the
voltage. This is referred to as lead.
The movement of the conductor through the lines of force or
the movement of the lines of force around the conductor
makes virtually no difference as to output.
7-6
Section 7-AC Electricity
ZERO
0° 90° 180° 270° 360° 90° 180° 270° 360°
VOLTS
C B
POWER SUPPLIES AVAILABLE PHASE PHASE
FROM ELECTRIC COMPANIES
There are two basic 3-phase systems for supplying industrial 480 V.
power. One system is called WYE, the other DELTA. Neither Figure 1: 480V, 4-Wire, 3-Phase Wye
one is standard. The same system may be used at more than
one nominal voltage. Actual operating voltage is usually
somewhat higher than the nominal voltage. (Figure 1): The neutral wire is usually grounded (to a water
pipe) on such systems and there will be 277 V between any
The most up-to-date but least common system is the 3-phase, phase wire and either the grounded conductor or metal part of
4-wire Wye, sometimes called 4-wire star. Voltages on a nor- the building, conduit system, etc. The system which is preva-
mal 440 V system will be approximately 480 V between any lent in downtown areas of cities, 120/208 V, 3-phase, 4-wire
two of the 3-phase wires, and at the same time approximately Wye is similar.
277 V between any phase wire and the fourth or neutral wire.
7-7
Section 7-AC Electricity
C 120 V.
LIGHTING B 480 V.
PHASE PHASE
416 V.
208 V.
480 V.
120/280 V, 4-Wire, 3-Phase Wye
7-8
Section 7-AC Electricity
NEC REFERENCE
A
4 WIRE, 240 V.,
SECTION 200-10: “Identification of terminals - All devices
3 PH. DELTA (HIGH LEG)
provided with terminals for the attachment of conductors and
intended for connections to more than one side of the circuit
shall have terminals properly marked for identification...”
7-9
Section 7-AC Electricity
except the prongs, blades or pins. The cover for wire termina-
tions shall be mechanically secured, or an integral of the 2
1 2 1
attachment plug or connector.”
SECTION 410-54: “Receptacles in Damp or Wet Loca-
3 4 4 3
tions.”
a. Damp Locations. A receptacle outlet installed outdoors MALE OUTPUT FEMALE OUTPUT
in a location protected from the weather or in other damp
locations shall have an enclosure for the receptacle which
is weather-proof when the receptacle is covered (attach-
2 2
ment plug cap not inserted and receptacle covers closed).
Twist the strands of wire and simultaneously insert all the “Y” Terminal (No specific lettered terminal is
wires into all proper wiring chambers as noted. for any
specific colored conductor)
Examine cable to be sure you have proper end of cable for
correct alignment of wires and pass cable through cord
clamp and cover of device in the proper direction as AC VOLTMETER OPERATION
illustrated. Ac measuring instruments have different characteristics than
dc instruments have because the ac current flow is constantly
reversing. The procedure for using the ac voltmeter differs
from the dc voltmeter.
7-10
Section 7-AC Electricity
3. AC voltage reading to line ground would be an indication NOTE: Voltage test made at this location should be
of type of power supply from the generator or power compared to nameplate or data plate. If not within the 10%
transformer. Voltage readings should be taken between allowable range, corrective steps must be taken.
lines or across components.
AC AMMETER OPERATION
Before using the ac voltmeter, it should be zeroed, the voltage
selector turned one voltage scale higher than the anticipated Amperage readings on ac circuits are done with a wraparound
voltage the test leads and probes should be in good condition, ammeter.
an electrical shock could be fatal. Then test the circuits by
first checking between legs as shown in the diagram of a This meter converts the strength of the magnetic field around
three-phase system. the wire to a meter reading. The ammeter must be zeroed
before use. The amperage selector should be turned to a scale
CAUTION: Always use a disconnect switch to shut off the higher than anticipated. The procedure for using ac ammeters
power to a unit before working on it. Do not use the plug for is to place the pickup clamp around a single conductor. It will
not read more than one wire at a time because the current will
a switch.
be flowing in both directions at once, and the amperage flow
in the conductors would cancel each other. The pickup clamp
jaws should mate firmly. Any air gap would cause error in
readings. A reading should be taken from each conductor to
check for balance of load.
G
ON
WR
VM
VM
VM
7-11
Section 7-AC Electricity
L2
NOTE: Any voltage reading between legs that is one half or
less that the required voltage indicates an open circuit and
the wiring or fuses should be corrected before proceeding
with any further testing.
L3
L1
L2
Three-Phase Plug
L1
22
0V
0V
22
Single-Phase Plug
L3 L2 100 V
OR MORE
220 V
7-12
Section 7-AC Electricity
2. These rotors are called squirrel cage rotors. The magnetic ZERO
field induced in the loops of these rotors by the rotating VOLTS 0° 90° 180° 270° 360° 90° 180° 270° 360°
5.0 L1
L3 L2
2.5 2.5
5A
L1
L3 2.5 L2
2.5
7-13
Section 7-AC Electricity
3. Larger motors may have 9 to 12 or even more external NOTE: There is only one way to wire a motor otherwise
leads. This allows the motor to be wired to different volt- damage could occur: refer to the data plate below for
ages. Proper wire configuration at a 12 lead motor would example.
be:
6. RPM at full load.
NAMEPLATE DATA 7. Frequency.
A. Alternating-Current Single-Phase and Polyphase Squirrel-
Cage Motors, NEMA Standard 8. Number of phases.
4. Maximum ambient for which motor is designed. 12. For motors equipped with thermal protection, the words
“thermally protected” and, for motors rated more than 1
5. Insulation system designation. (if stator and rotor use dif- horsepower, a type number. (See MG1-171 and MG 1-
ferent classes of insulation system, both insulation sys- 1.72). (For their own convenience, motor manufacturers
tem designations should be given on the nameplate, for may use letters, but not numbers, preceding or following
the stator being given first.) the words “thermally protected” for other identification
purposes.)
CYCLES KVA
PHASE
HZ CODE SERIAL
3 60
K
7-14
Section 7-AC Electricity
10 11
12
10 11 12 10 11 12
4 5 6 4 5 6
7 8 9 7 8 9
1 2 3 1 2 3 2
1
4 5
7
8
2
1 7
8
10 5 10
4 11
11
12
6 12
9
6
3 9 3
7-15
Section 7-AC Electricity
CONTACTORS
Contact material used in the contactor must meet the follow-
ing basic requirements:
These are a few of the requirements that enter into the life of
1. Manual reset with control circuit interrupt. the contact. Replacement components will require the same
quality.
CAUTION: When used as part of the load circuit, voltage
may be present at the contactor or even to the motor. CONTROL TYPE
The voltage used to control the contactor is normally of low
voltage-12vdc; 24 vdc; or 12 to 25 vac. This is supplied by a
transformer or the battery. The voltage from the transformer
output may be rectified to be compatible with the other com-
ponents within system. If line voltage is use in the contactor
coils, it will be isolated from the remaining circuit by a line
starter actuator.
This device carries high voltage across the contact and the
coil will be supplied low voltage.
NAMEPLATE DATA
The information consists of:
F.L. - Full Load Amps: The maximum amps that the con-
tactor contacts can conduct continuously.
L.R. - Locked Rotor Amps: The maximum amperage
load the contactor contact can conduct for motor start up.
7-16
Section 7-AC Electricity
Coil Voltage: The voltage and type of power for which the MOTOR PROTECTORS
pull in coil is designed.
The motor protectors are of individual line units or of multi-
line units. The protectors have a very high degree of reliabil-
Contact Voltage Ratings: The voltage and amperage for ity. Failures, if at all, most times are caused by open circuits
which the contacts are designed. within the device. Check for opens across the connection with
a voltmeter.
Inductive Per Pole: Amperage for motor operation.
NOTE: When changing voltages, motor protectors must be
Resistive Per Pole: Amperage for heaters. changed.
VM
INDIVIDUAL
LINE UNIT
VM
1. 10-12 VDC
VM
2. 15 AMP - 300 V.
10 AMP - 100 V. Contactor Voltmeter Check
15 AMP - 80 V.
Multi-Line
AC CONTACTOR CHECKS Unit
The contacts conduct between the power supply and the load.
VM
Check for burnt contacts by visual inspection and the voltage
drop across the contact with an ac voltmeter. This must be VM
Low Voltage
done for each contact under load. The lower the voltage read-
Check
ing, the better the contact has completed the circuit.
VM
7-17
Section 7-AC Electricity
7-1/2 22 11
10 28 14
1
2
3
15 42 21
7-1/2 132 66
FULL LOAD AMPERAGE
10 162 84
1/2 9.8 4.9 2 1 NOTE: The amperage values given are approximate. The
voltage difference will cause amperage values to vary.
3/4 13.8 6.9 2.8 1.4
7-18
Section 7-AC Electricity
440
(220) (220)
TRANSFORMER DEFINITION
A transformer is an electric device without continuously mov-
ing parts, which with electro-magnetic induction transfers
electric energy from one or more circuits to one or more at the
same frequency, usually with changed values of voltage and
current.
(16) (16)
32 V
220
COOLING
Transformers used are of the fry type, self-cooled, which are
cooled by the natural circulation of air.
RATINGS
16 V
Input Voltage: The voltage at which the primary side of the
transformer is designed to operate.
Output Voltage: The voltage at the secondary side of the TRANSFORMER EVALUATION
transformer is designed to maintain at rated load.
CHECKS
Output Ampacity: This is the current-carrying capacity
expressed in amperes. The transformer assembly used is of single-phase type and
can be checked for proper operation with a voltmeter and
Output KVA: This is the voltage x amperage indicating a ammeter. Set the voltmeter on the proper scale and take read-
total output. ings on the primary and secondary side of the transformer. A
line voltage reading should be obtained on the primary side,
CIRCUIT and control voltage should be read on the secondary side. Any
readings not within specification indicate a defective trans-
A single-phase circuit, energized by single alternating electro-
former, power supply, or excessive load on circuit. The watt-
motive force.
7-19
Section 7-AC Electricity
18 10 7
220 Volts
.075 Amps 16 13 10
VM
L1 (Example)
L2 14 20 15
Primary Side
12 25 20
10 40 25
8 65 35
16 Volts 6 95 45
Secondary Side 4 125
VM 10 Amps (Example)
Ratings: All heaters are rated in watts. The heaters also
16 Volts specify the maximum voltage that may be applied to the
Transformer Evaluation Check heater.
TRANSFORMER LOAD
RESISTANT HEATERS
Definition: Resistant heaters use wires which oppose the
flow of electricity; this causes the wire to heat excessively.
The heat generated by the wire is conducted to the object.
Circuit: Heater of the type used in our units are of single-
phase type which requires two conductors to each heater. The
back of heaters may be wired. Wye or Delta configuration to
utilize all three phases.
7-20
Section 7-AC Electricity
Maximum
Type Trade Maximum Voltage Kind of
Operating Outer Covering Application
Letter Designation Rating Insulation
Temperature
AMPERAGE VM
Watts Each
230 V 460 V
L2 - 5 Amps (Example)
500 3.6 1.8
VM
3 HEATERS WIRED “DELTA”
VM
7-21
Section 7-AC Electricity
GREEN GREEN
RED RED
WHITE
BLACK
WHITE
BLACK
BLK RD
BLK
GRN
WH R
WH
DC+
A single three-phase bridge rectifier uses three terminals for
ac input and one terminal for dc positive output.
AC
Three-Phase
Rectification - L3
Two, Single-Phase Bridges
7-22
Section 7-AC Electricity
Another disadvantages of the direct-current system becomes evident when the direct current from the generating station must be
transmitted a long distance over wires to the consumer. When this happens, a large amount of power is lost due to the resistance
of the wire. However, this loss can be greatly reduced if the power is transmitted over the lines at a very high voltage level and a
low current level. This is not a practical solution to the power loss in the d.c. system since the load would then have to be oper-
ated at dangerously high voltage. Because of the disadvantages related to transmitting and using direct current, practically all
modern commercial power companies generate and distribute alternating current (a.c.)
Unlike direct voltages, alternating voltages can be stepped up or down by a device called a TRANSFORMER. Use of the trans-
former permits efficient transmission of electrical power over long-distance lines. At the electrical power station, the transformer
output power is at high voltage and low current levels. At the consumer end of the transmission lines, the voltage is stepped
down by a transformer to the value required by the load. Due to its inherent advantages and versatility, alternating current has
replaced direct current in all but few commercial power distribution systems.
CONDUCTORS PARALLEL TO
LINES OF FORCE, EMF MINIMUM DIRECTION OF
CURRENT
ROTATION ROTATION
N N N N
N
(B) S (E) S
(A) S S (C) S (D)
EMF
ONE ALTERNATION
ZERO
ONE CYCLE
ONE ALTERNATION
AJA515
7-23
Section 7-AC Electricity
CHECKING AC VOLTAGE
AC measuring instruments have different characteristics than dc instruments have because the ac current flow is constantly
reversing. The procedure for using the ac voltmeter differs from the dc voltmeter.
2. AC voltage readings should always be made between the one or more power supply wires.
+ 01 02 03
0
120° 120° 120°
-- VM
AJA271
VM AJA272
VM
7-24
Section 7-AC Electricity
120° 120°
AJA273
120°
Three-phase AC power generation.
+
01 02 03
0
120° 120° 120°
-- AJA274
7-25
Section 7-AC Electricity
With the component values selected, the circuit wye point is Measure the voltages on the components as indicated in the
shifted away from neutral or zero volts such that unbalanced diagram.
voltages are relatively high on one resistor/contactor coil
phase and relatively low on the other resistor/contactor coil Compare the voltages with the proper voltages as indicated on
phase. The contactor with the higher coil voltage is then ener- the diagram which is appropriate for the applied voltage.
gized.
If the voltage values are correct, the phase reversal assembly
The energized contactor connects the phase voltage straight is good, or the contactor may have a mechanical problem.
thru for positive phase sequence or swaps two of the phases
for negative sequence. Verify proper mechanical operation by manually energizing
each contactor and by verifying both conductors can’t simulta-
neously pull in.
Visually verify that the contactor contacts are good and that
contactor return spring and contact overtravel springs have
normal force and travel. Verify that the movable contacts slide
freely.
7-26
Section 7-AC Electricity
7-27
Section 7-AC Electricity
7-28
Section 7-AC Electricity
7-29
Section 7-AC Electricity
7-30
SECTION 8
Refrigeration Unit
Schematic/Wiring Diagrams
8-1
8-2
Section 9
Microprocessor Controllers
9-1
Section 9-Microprocessor Controllers
MP3000 CONTROLLER
DESCRIPTION
Controller Description
The MP3000 is an advanced microprocessor controller that
has been specially developed for control and monitoring of
refrigeration units. The controller contains the following basic
features:
1. LED display for TEMPERATURE:
• Five alpha numeric, 20.32 MM. high characters:
Numerical hundredths, tens, ones and tenths position, a C
for Celsius or F for Fahrenheit for temperature display.
• LED display shows controlling (return or supply) sensor-
temperature. Sensor temperature shown in LED display
is indicated by status indicator lights. If a sensor is out of
range the display shows “+Err” or “Err”. The +/sign indi-
cates whether the sensor temperature is out of range high
or low.
• The LED display also shows the test stage of a Pretrip
(PTI) or Function test.
2. LCD display for SETPOINT, MESSAGES and MENU:
• 4 line, 20 character LCD display shows setpoint tempera-
ture during normal operation.
• Alarms, messages and the controller menu also appear in
the LCD display when special keys are pressed.
3. Sixteen general purpose keys are used to enter text and
scroll through the controller menu tree.
a. Text Input: The keyboard supports both numerical
and text input. Each key can have more than one mean-
ing.
Use the special text keys F1, F2, F3 and F4 to enter AJA730
text in an information screen:
• F1 key: Press the F1 key, then press another general pur-
pose key to enter the number shown on the key.
• F2 key: Press the F2 key, then press another general pur-
pose key to enter the first letter shown on the key. 1. LED display for TEMPERATURE. Status
• F3 key: Press the F3 key, then press another general pur- indicator LEDs identify controlling sensor
pose key to enter the second letter shown on the key. temperature (return or supply) that appears
• F4 key: Press the F4 key, then press another general pur- in display.
pose key to enter the third letter shown on the key.
NOTE: When the F1, F2, F3 or F4 key is pressed 2. LCD display for SETPOINT, MESSAGES
to enter a character in the display, the keypad and MENU. Use the keypad to scroll
remains on that “character level” until another through messages and the controller menu.
“level” is selected by pressing the F1, F2, F3 or 3. 3. General purpose keys are used to enter
F4 key. text and scroll through menus.
9-2
Section 9-Microprocessor Controllers
Text Input Example: To enter THERMO in an information • Control circuit fuse and circuit breaker protection: 7 amp
screen: manual reset circuit breaker protects the 24 Vdc
a. Enter “T” by pressing F3 key, then pressing STU key. • control circuit. 2 amp fuse protects the 28V ac control
b. Enter “H” by pressing GHI key. power circuit to the controller. 2 amp fuse protects the
c. Enter “E” by pressing DEF key. battery charger output circuit to the controller.
d. Enter “R” by pressing F4 key, then pressing PQR • Electronics for measuring phase sequence.
key. • Electronics for measuring amperage.
e. Enter “M” by pressing F2 key, then pressing MNO • Electronics for measuring voltage.
key. • Zero current transformer for earth leaking measurement
f. Enter “O” by pressing F4 key, then pressing MNO (option).
key. 8. Replaceable sensors: Return air, left hand supply air,
b. Menu Scrolling: General text keys F1, F2, F3 and right hand supply air, evaporator coil (defrost), condenser
F4 also include directional arrows for entering and coil, ambient air and compressor discharge line tempera-
scrolling through the controller Main Menu: ture sensors are field replaceable. Three (replaceable)
• • F1 key: ESC indicates that pressing the K1 key moves spare sensor receptacles are also provided for USDA
the cursor out of (exits) a menu list. temperature recording.
• • F2 key: FORWARD/UP ARROWS indicate that press- 9. Probe Test (see “Probe Test” in this chapter).
ing the K2 key scrolls the cursor forward and/or upward 10. Defrost cycle control (see “Defrost System” in this chap-
through text boxes and menu lists. ter).
• • F3 key: BACKWARD/DOWN ARROWS indicate that 11. Pretrip (PTI) test capability (see “PTI (Pretrip) Test” in
pressing the K3 key scrolls the cursor backward and/or this chapter).
downward through text boxes and menu lists. 12. Function test capability (see “Function Test” in this chap-
• • F4 key: ENTER ARROW indicates that pressing the K4 ter).
key moves the cursor into the next menu level or into a 13. Data recording capability (see “Data Recording and
menu item text box. Downloading Data” in this chapter).
4. Four special function keys (see illustration on page 1): 14. Electronic phase selection: The microprocessor relay
• C/F key: Press to view alternate temperature scale in board monitors the phase of the power supply to ensure
LED display. proper rotation of the condenser fan and evaporator
• DEFROST key: Press to initiate defrost. Evaporator coil fans.The controller determines the correct phase
temperature must be below 10 C (50 F). sequence for the compressor and energizes the correct
• SUP/RET key: Press to view alternate return/supply sen- compressor contactor.
sor temperature in LED display. 15. Power limit control (see “Power Limit Mode” in this
• SETPOINT key: Press to enter Setpoint Menu. The first chapter)
line of the Setpoint Menu is the setpoint temperature. 16. Sequential component startup control: A sequence star of
• Press F2 or F3 key to scroll up or down through the menu the required loads occurs during initial startup of the con-
list. troller and when a control mode shift requires the com-
NOTE: Press the “5” key to increase the display time of the pressors to start (see “Sequence of Operation” in this
current LCD data screen by 5 minutes. Maximum display chapter).
time is 30 minutes for data screens and 100 minutes for 17. Compressor refrigerant injection cycle control (see Com-
manual tests. pressor Liquid Injection” in this chapter).
5. Status indicator LEDs (see “Status Indicator LEDs and 18. Hourmeters: The MP3000 controller has multiple built-in
Alarm Codes” in this chapter). hourmeters that can be accessed through the Main Menu.
6. Control Transformer: Low voltage control power and 19. Manual emergency control capability. Manual control
ground is supplied to the MP3000 controller and the main settings in the control box allow the unit to operate even
relay board. in the event of a fatal failure of the controller. Manual
7. Main Relay Board: High voltage supply power and low control offers three operating functions: Heat, Defrost
voltage control power and ground are supplied to the and Cool (see “Manual Emergency Mode Operation” in
main relay board. The main relay board contains: this chapter).
• Relays to energize and deenergize unit contactors and 20. Flash memory: Flash program memory allows the appli-
• solenoids. Component relays include the heater, evapora- cation software to be updated without replacing a
tor fan motor, condenser fan motor, and phase reversalre- EPROM chip on the controller. Application software can
lays. be updated in the field using a portable computer and the
• Supply power circuit protection: 20 amp fuses (3) protect MP3000 Loader program. Consequently, the field
the high voltage circuits on the main relay board. installed application software version may have a differ-
9-3
Section 9-Microprocessor Controllers
ent revision number and may include control features not Status Indicator LEDs
included in the original factory installed software. If the
operation of your unit differs from the Sequence of Oper- Eight status indicator LEDs are located in the top LED dis-
ation described for the unit in this manual, enter “Misc. play and signal the following:
Functions” in the Main Menu to check that the program • Supply (Air Temperature)
version is correct (see “Menu Operating Instructions” in • Return (Air Temperature)
this chapter). • Humidity Mode (Humidification set to On in Setpoint
21. Display menus: The MP3000 controller contains an menu)
extensive display menu that can be navigated via keypad. • Compressor (Cooling On)
22. The display menu is organized into eight (8) Main • Heat (On)
Menus: • Defrost
• • Setpoint Menu: Menu screens in this group are used to • InRange (Temperature)
enter the temperature setpoint and set the economy mode. • Alarm
Setpoint menu option functions include: set humidify or The indicator LEDs stay ON continuously to indicate sensor
dehumidify operation, enter humidity setpoint, set air- temperature display, unit operating mode or condition. The
flow, set custom airflow, set bulb mode, set AFAM opera- Alarm LED flashes ON and OFF continuously when a Check
tion, set AFAM delay, set AFAM rate, set O 2 Minimum Alarm (Level 2 Alarm) or Shutdown Alarm (Level 1 Alarm)
and set CO 2 Maximum. occurs. Less serious Log Alarms (Level 3 Alarm) are
• Data Menu: Menu screens in this group are used to dis- recorded but do not activate the Alarm LED (see Alarms
play unit operating information including sensor temper- Menu on page 417 for more information).
atures, voltage, current and frequency information.
• Alarm List Menu: Menu screens in this group display a Data Recording and
list of alarm code(s).
• Commands Menu: Menu screens in this group are used to
Downloading Data
activate defrost, function tests, pretrip (PTI) tests and The MP3000 datalogger can record sensor temperatures as
manual function test. well as loss of power, alarms, sensor failure, setpoint change
• Miscellaneous Functions Menu: Menu screens in this and unit shutdown events. All data logs include the time and
• group display date/time, C/F, cargo data, program version date; setpoint temperature; supply, return, ambient, USDA1,
and run time (hourmeters) information. USDA2 and USDA3 sensor temperatures; and humidity sen-
• Configuration Menu: Menu screens in this group display sor. All temperature logs can be viewed from the controller’s
refrigerant type, ingrain setting, container ID, contrast LCD message display.
(screen), language, unit type, reefer type and zero current Data logging intervals are selectable from 1 minute or 1/2,
status. 1, 2 or 4 hours. When a 1 hour logging interval is selected, the
• Datalogger Menu: Menu screens in this group display datalogger memory can store approximately 512 days of
temperature log, event log, set log time and PTI log. information.
• Refcon Remote Monitoring (RMM) State: Menu screen- The logging of USDA sensors is fixed at 1 hour intervals
show current remote monitoring state (Offline, Zombie to comply with USDA requirements. A logging test of USDA
or Online). sensors at 1 minute intervals is possible for 72 minutes.
USDA data can be downloaded during the logging test. After
72 minutes, controller returns to previous logging interval and
clears USDA test data from datalogger memory.
If the unit power supply is disconnected, the datalogger
will continue to register 120 temperature logs (except humid-
ity sensor) when battery voltage is above 11.4 volts. These
will be maintained until the unit is reconnected to power, and
the battery automatically recharged.
Trip data can be retrieved (but not erased) from the datalogger
memory using a DRUII or Smart Sponge handheld data
retriever. DRUII data transfer rate based on a 1 hour log.
9-4
Section 9-Microprocessor Controllers
for event logs only and about 45 seconds for temperature logs Chill Loads (Setpoint at 9.9 C
only.
Trip data from separate units is denoted by the identification [14.1 F] and Above)
information entered into the controller at the beginning of The unit operates on Cool with Modulation and Heat to pro-
the trip via the general purpose keypad. Identification data vide accurate control of chill loads. During Cool with Modu-
may include the container ID number, location B.R.T., con- lation, the controller uses a proportional integral derivative
tent, loading data, voyage no., ship, load port, discharge port (PID) algorithm and a stepper motor valve to provide accurate
and comments. The container ID number is stored in the control of the container temperature in direct response to load
Configuration submenu. demand.
The stepper motor valve is installed in the suction line and
controls the amount of refrigerant returning to the compres-
General Theory Of Operation sor. The valve opens and closes in response to a controller
The MP3000 controller uses advanced solid state integrated voltage signal based on a control temperature differential. The
circuits to monitor and control unit functions. The controller controller uses the setpoint temperature, supply air sensor
monitors inputs from: temperature (left and/or right hand sensors) and pull-down
• Return air sensor rate for the last 10 seconds, last 20 seconds and last 180 sec-
• Supply air sensor, left hand onds to calculate the control temperature differential.
• Supply air sensor, right hand
• Evaporator coil sensor Supply Air Sensor Control
• Condenser coil sensor Temperature control accuracy and protection against frost
• Ambient sensor damage is provided by using two separate sensors (left hand
• Humidity sensor and right hand) to determine the supply temperature used to
• USDA (Spare) sensors 1, 2 and 3 calculate the control temperature differential:
• Compressor discharge line temperature sensor • At setpoints below 1 C (30 F), the controller uses the
• Phase measuring circuits lowest supply air sensor temperature.
• Current measuring circuits • At setpoints above 0 C (32 F), the controller uses the
• Voltage measuring circuits average temperature of the left hand and right hand sup-
Output signals from the controller automatically regulate all ply air sensors.
unit functions including: • At setpoints between 1 C and 0 C (30 F and 32 F), the
• Compressor operation controller uses a sliding temperature scale from the low-
• Condenser fan operation est supply air sensor temperature to the average tempera-
• Evaporator fan motor operation ture of the left hand and right hand supply air sensors.
• Liquid line solenoid valve If one supply air sensor fails, the controller uses the tempera-
• Stepper motor valve ture of the other supply air sensor for temperature control. If
• Liquid injection valve both supply air sensors fail, the controller uses the tempera-
• Dehumidify valve ture of the return air sensor plus an offset for temperature con-
• Electric heaters trol.
• Phase selection Temperature Control Accuracy
and Frost Protection
The PID algorithm generally minimizes container tempera-
ture fluctuations to +/ 0.1 C (+/ 0.2 F). Additional frost pro-
tections is provided by pulsing the electric heaters ON and
OFF on a 60 second duty cycle to increase the supply air tem-
perature if the return air temperature decreases to within 0.3 C
(0.5 F) of setpoint.MP3000 Controller
9-5
Section 9-Microprocessor Controllers
9-6
Section 9-Microprocessor Controllers
Condenser Fan Control The unit remains in Null until the return air temperature
increases to ECMAX temperature at the expiration of a 45
The controller also uses a proportional integral derivative minute Null state time sequence. Default ECMAX setting is.2
algorithm to control the condenser temperature and ensure a C (0.4 F) above setpoint. ECMAX setting is adjustable from 0
constant liquid pressure at the expansion valve. In low ambi- to 5 C (0 to 8.9 F) above setpoint through the Configuration
ent conditions, the controller pulses the condenser fan ON and menu of the controller.
OFF to maintain a minimum condenser temperature. The con- NOTE: On Frozen loads, supply and return air
troller maintains a minimum 30 C (86 F) condenser tempera- temperatures may vary considerably during Economy mode
ture on Chill loads and a minimum 20 C (68 F) condenser operation due to long periods of no air circulation.
temperature on Frozen loads.
Probe Test
Economy Mode Operation
The controller constantly monitors the left hand and right
The Economy Mode reduces unit power consumption by hand supply sensors, return sensor and defrost (evaporator
reducing evaporator fan operation on both chill and frozen coil) sensor to determine when to initiate a demand defrost. If
loads. The use of the Economy Mode should be established a demand defrost is requested and defrost has occurred within
by the shipper and the type of cargo. The Economy Mode last 90 minutes, the controller initiates a Probe Test to check
option is turned on from Setpoint menu of the controller. for a defective sensor.
NOTE: Enter Setpoint temperature before turning ON the During a Probe Test, the LCD display shows “Probe Test
Economy mode. The controller automatically turns the Please Wait”. The controller operates the unit on high speed
Economy mode OFF when the setpoint is changed. evaporator fans only for 5 minutes. All sensor temperatures
Chill Loads (Setpoints of 9.9 C (14.1 F) and Above) are then compared:
Evaporator fans operate on low speed whenever the container • Sensors with large temperature differences are discarded
temperature is Inrange. from the control algorithm. The controller then activate
NOTE: On Chill loads, container air temperatures may vary the appropriate Alarm codes to identify the defective sen-
1 C to 3 C (1.8 F to 5.4 F) above setpoint in high ambient sor(s).
temperatures. • If no sensors are found defective, controller LCD display
shows “Running with High Supply Difference” message.
Frozen Loads (Setpoints of 10 C (14 F) and Below) Sensor errors recorded during a Probe Test are cleared
The evaporator fans stop during the Null mode. A null state when the next Defrost is initiated or Unit On/Off switch
timer automatically restarts the evaporator fans on low speed is turned OFF.
for 5 minutes every 45 minutes. NOTE: A manual Probe Test can be performed by a
The Economy Mode also modifies the temperature control technician by selecting Sensor Check from the Manual Test
algorithm on frozen loads to extend the Null mode. The unit Function menu.
continues on Cool operation until return air temperature
reaches ECMIN temperature. Default ECMIN setting is 2.0 C
(3.6 F) below setpoint. ECMIN temperature is adjustable
from 0 to 5 C (0 to 8.9 F) below setpoint through the Configu-
ration menu of the controller.
9-7
Section 9-Microprocessor Controllers
9-8
Section 9-Microprocessor Controllers
Continuous Temperature Control • Controller pulses electric heaters ON and OFF for addi-
tional frost protection if the return air temperature
Operation decreases to within 0.3 C (0.5 F) of setpoint.
Chill Loads — Controller Setpoint at 9.9 C (14.1 F)
and Above
The controller regulates the compressor, stepper motor valve
and electric heaters based on a Control Temperature Differen- 1
tial (see “General Theory of Operation” in this chapter for
more detail). This means the unit operating mode can NOT be
predicted based ONLY on the setpoint and supply air temper-
ature. A
At setpoints of 9.9 C (14.1 F) and above, the controller
operates the unit on:
• Cool mode with Modulation
• Controller energizes the liquid injection valve continu-
+1.5C
ously when the modulation percent is 75% or less.
(+2.7)F
• Controller energizes the warm gas bypass valve on a 30
second duty cycle when the modulation percent is 75% or C
less. The amount of ON (open) time increases as the 2
modulation percent decreases.
B
• Heat mode (electric heaters pulse On and Off on a 60 sec-
-1.5C
ond duty cycle)
(-2.7)F
• Defrost mode (electric heaters On, evaporator fans Off)
• Evaporator fans operate on high speed (except when
3
Economy mode is ON and temperature is Inrange) and
continuously circulate air inside the container (except AJA731
during defrost)
• Controller LED display shows the supply air sensor tem-
perature.
• Controller LCD display shows the setpoint temperature. Table 1: Chill Load Control Sequence
• Controller uses the condenser coil temperature and a PID (Setpoints at 9.9 C [14.1 F] and Above)
algorithm to cycle a single speed condenser fan between
ON and OFF on a 30 second duty cycle. A. Cool with Modulation* (control temperature dif-
• Power limit is active when the unit is operating in the ferential is above setpoint)
Cool mode.
B. Heat (electric heaters pulse ON and OFF on a 60
second duty cycle if return air temperature decreases
Cool with Modulation within 0.3 C [0.5 F] of setpoint or supply air temper-
• Controller calls for the Cool mode whenever the Control ature is too low)
Temperature Differential (based on supply air tempera-
C. InRange (based on supply air temperature)
ture) is above setpoint.
1. Decreasing Temperature
• Controller turns ON the Compressor LED when the
2. Setpoint
• compressor is operating.
3. Increasing Temperature
• Controller opens and closes stepper motor valve to regu-
late the flow of refrigerant to the compressor. The posi-
tion of the stepper motor valve balances the unit cooling *NOTE: Controller also energizes liquid injection
capacity against the actual load requirements. valve and warm gas bypass valve as modulation
• Controller turns ON the In-range LED when the supply percent decreases.
air sensor temperature is within 1.5 C (2.7 F) of setpoint.
• Supply air sensor control algorithm increases temperature
control accuracy and protection against frost damage (see
“Chill Loads” under General Theory of Operation in this
chapter).
9-9
Section 9-Microprocessor Controllers
• Chill Mode: When the modulation percent is 25% or less. The amount of OPEN (energized) time increases as the modula-
tion valve closes until the bypass valve remains energized continuously (modulation = 0%).
4
Condenser fan operation is determined by a control algorithm so ON/OFF operation can not be predicted. In low ambient con-
ditions, controller pulses the condenser fan ON and OFF on a 30 second duty cycle to maintain a minimum condenser tempera-
ture:
• Chill Loads: Controller maintains a minimum 30 C (86 F) condenser temperature.
• Frozen Loads: Controller maintains a minimum 20 C (68 F) condenser temperature.
NOTE: The condenser fan operates continuously if the compressor or condenser temperature sensor is defective.
5
Stepper motor valve MODULATES:
• Chill Loads: Whenever the unit is in a cooling mode.
• Power Limit: Whenever the unit is in Power Limit mode.
6
Controller energizes electric heaters for frost protection, heat and defrost modes:
• Frost Protection (during compressor operation): If return air temperature decreases to within 0.3 C (0.5 F) of setpoint, con-
troller PULSES heaters ON and OFF on a 30 second duty cycle.
• Heat mode (compressor OFF): If supply air temperature is too low, the controller PULSES heaters ON and OFF on a 60 sec-
ond duty cycle.
• Defrost mode: Controller turn heaters ON until evaporator coil temperature increases to:
Chill Loads: 30 C (86 F) or exceeds 18 C (65 F) for 15 minutes.
Frozen Loads: 18 C (65 F) or exceeds 8 C (46 F) for 15 minutes.
9-10
Section 9-Microprocessor Controllers
Frozen Loads — Controller Setpoint • Controller uses the condenser coil sensor temperature
at 10 C (14 F) and Below and PID algorithm to cycle a single-space condenser fan
ON and OFF on a 30 second duty cycle.
At setpoints of 10 C (14 F) and below, the controller locks out
the Modulation and Heat modes. The controller regulates • Power limit is active during initial startup and pull-down
compressor operation based the return air sensor and setpoint
temperatures. when the unit is cooling at return air temperatures
At setpoints of 10 C (14 F) and below, the controller above 10 C (14 F).
operates the unit on:
9-11
Section 9-Microprocessor Controllers
Cool Defrost
• After initial startup and pull-down to 1.0 C (1.8 F) below
setpoint, the controller calls for the Cool mode whenever: The evaporator coil sensor temperature must be below 18 C
Return air temperature increases more than 1.0 C (1.8 F) (65 F) to initiate a Demand Defrost or Manual Defrost. The
above setpoint; or evaporator coil sensor temperature must be below 10 C (50 F)
Compressor has been OFF for 15 minutes (maximum). to initiate a Timed Defrost.
• Controller turns ON the Compressor LED when the com- • Demand defrost function initiates defrost immediately
pressor is operating. when:
• Compressor must operate for a minimum of 5 minutes Temperature difference between the return air sensor and
after startup. defrost (evaporator coil) sensor is too large
• After initial pull-down to setpoint, controller keeps the Temperature difference between the left hand and right
Inrange LED ON as long as the return air temperature hand supply air sensors is too large and unit has operated
remains less than 1.5 C (2.7 F) above setpoint. for more than 90 minutes since last defrost
Temperature difference between the supply sensors and
Null return air sensor is too large.
• The controller calls for Null when the Return Air Tem- • • Manual Defrost may be initiated immediately by press-
perature decreases more than 1.0 C (1.8 F) below set- ing the Defrost key or by Refcon Remote Monitoring
point. Modem (RMM).
• The controller stops the compressor and condenser fan. • A Timed Defrost always starts at 1 minute past the hour
• The evaporator fans continue to operate (except when immediately following a defrost timer request for defrost.
Economy mode is ON). For example, if the defrost timer requests a defrost cycle
• Compressor remains OFF for a minimum of 5 minutes at 7:35, the defrost cycle will start at 8:01. The datalogger
and a maximum of 15 minutes. will record a Defrost event for each log interval in which
a Defrost cycle is pending or active (i.e. both the 8:00 and
1 9:00 data logs on 1 hour logging interval).
On Chill Loads (setpoints at 9.9 C [14.1 F] and above),
the initial time interval is:
• 8 hours of compressor operation at supply air tempera-
A tures of 5.1 C (41.2 F) or above.
+1.5C • 2.5 hours of compressor operation at supply air tempera-
(+2.7F) tures of 5.0 C (41.0 F) or below. One half (0.5) hour is
+1.0C added to the time interval each timed defrost interval.
C (+1.8F) Defrost synchronization creates step intervals of 3, 4, 4,
2 5, 5, 6, 6 and 7 hours. Maximum time interval is 7 hours.
On Frozen Loads, the initial time interval is 8 hours. Two
-1.0C D
(2) hours are added to the time interval each timed
(-
defrost interval. Maximum accumulated time interval is
1.8F)
24 hours.
Defrost timer resets if the unit is Off more than 12 hours,
AJA732 setpoint is changed more than 5 C (8.9 F) or PTI Pretrip
test occurs.
NOTE: If unit operating conditions do not allow the unit to
enter a defrost cycle, “Defrost Not Activated” appears on
A. Cool LCD display when the DEFROST key is pressed.
C. InRange
D. Null
1. Decreasing Temperature
2. Setpoint
3. Increasing Temperature
9-12
Section 9-Microprocessor Controllers
9-13
Section 9-Microprocessor Controllers
9-14
Section 9-Microprocessor Controllers
9-15
Section 9-Microprocessor Controllers
AJA738
9-16
Section 9-Microprocessor Controllers
3. To enter a new setpoint, press the F4 key. An Enter • Voltage 3 (Main Power Supply)
Arrow appears in the menu line and the current setpoint- • Frequency (Main Power Supply)
disappears. • Zero Current
4. Enter (type) the new setpoint in the LCD display using • Current Phase 1 (Main Power Supply)
the general purpose keypad. The cursor moves to the • Current Phase 2 (Main Power Supply)
right of the screen as each key entry is acknowledged and • Current Phase 3 (Main Power Supply)
displayed. • O2
NOTE: Always check that the setpoint entered in the LCD • CO 2
display is correct before proceeding. • Fresh Air Exchange Rate
5. Press and hold the F4 key until the cursor stops flashing. • Evaporator Fan Speed
The new setpoint is recorded in the controller and • Supply Air Temperature, Left Hand
appears in the LCD display.
6. Press ESC key to exit the SETPOINT screen. NOTE: Press the “5” key to lock a Data screen in the LCD
display for 5 minutes. Press any key to unlock the display.
Data Menu
NOTE: Controller returns to previous menu level or LCD
NOTE: Information can ONLY be displayed using the
Standard Display after 30 seconds.
Data menu. Items can NOT be changed.
The Data menu displays general unit operating information
including sensor temperatures, unit electrical data, etc. NOTE: All screens are
NOT present on all units.
Viewing the Data Menu The screens that display
on the controller are
With the unit On/Off switch ON and the LCD display show- determined by the Unit
ing the standard display (setpoint): Configuration setting.
1. Press F4 key for directly enter the Data menu. Menu
items appear in LCD display.
2. Press F3 to scroll the cursor down through the menu list.
The Data menu displays the following functions:
• Supply Air Temperature, Right Hand
• Return Air Temperature
• Evaporator Coil (Defrost) Temperature
• Condenser Coil Temperature
• Modulation
• Ambient Temperature
• Low Pressure
• High Pressure
• High Pressure Temperature (Compressor Discharge Line
Temperature)
• Relative Humidity
• Battery Voltage
• Voltage Average (380/460V Power Supply)
• Voltage 1 (Main Power Supply)
• Voltage 2 (Main Power Supply)
AJA739
9-17
Section 9-Microprocessor Controllers
NOTE: All screens are NOT Viewing the Alarm List Menu
present on all units. The
With the unit On/Off switch ON and the LCD display show-
screens that display on the
ing the standard display (setpoint):
controller are determined by
1. Press F2 key to directly enter the Alarms menu. The first
the Unit Configuration
alarm code number, alarm state and alarm description
setting.
appears in LCD display.
NOTE: Alarm codes are displayed in sequential order, not
in the order of occurrence.
2. Write down the first alarm code. Then press F2 key to
view the next alarm code when more than one alarm code
has been recorded.
3. Repeat step 4 until all alarm codes have been recorded.
To scroll backward to return to a previous alarm code,
press F3 key.
4. To clear all alarm codes from the current display list and
turn off the Alarm LED, all problems must be corrected
and the alarm code “acknowledged” in the Alarm List
menu. NOTE: To acknowledge an alarm, press F4 while
the alarm code appears on the screen. The alarm state will
change from ACTIVE or NOT ACTIVE to ACKNOWL-
EDGE. NOTE: If no key is pressed for 30 seconds, the
AJA740 controller returns to the previous menu level or the LCD
Standard Display.
Alarms Menu Screen Flow Diagram
9-18
Section 9-Microprocessor Controllers
9-19
Section 9-Microprocessor Controllers
9-20
Section 9-Microprocessor Controllers
• Function Test: LCD display shows functional test cur- Pretrip (PTI) Test
rently being performed. Function test ends automatically.
Unit automatically returns to normal operation. CAUTION: The PTI test should only be performed on
• PTI (Pretrip): LCD display shows PTI Test currently an empty container!
being performed. PTI test ends automatically. Press any
key on the controller to return the unit to normal opera- NOTE: Units equipped with a water-cooled condenser must
tion. be set to operate on air cooled condensing to perform a
• Manual Function Test: LCD display shows list of unit complete system capacity test.
components. Test the operation of individual components
or turn several components ON at the same time to per- The MP3000 controller contains a special PTI pretrip test that
form a system test. automatically checks unit refrigeration capacity, heating
• Power Management: LCD display shows current Power capacity, temperature control, and individual components
Limit setting and Power Time setting. Turn Power Limit including the controller display, contactors, fans, protection
feature ON and OFF, change power limit setting or devices and sensors. The test includes measurement of com-
change power limit time. ponent power consumption and compares test results to
expected values. The test takes about 2 to 2.5 hours to com-
plete, depending on the container and ambient temperature.
Defrost
For a description of the Defrost function, see “Initiating a NOTE: Correct all existing alarm conditions and
Manual Defrost” on page 13. clear the alarm codes before performing a PTI test.
The controller will automatically clear all existing
alarms before beginning the PTI test.
Function Test
The MP3000 controller contains a special function test that For a detailed description of the PTI Test, see pages 23
automatically tests individual components including the con- through 27. Detailed PTI test results are stored in the MP3000
troller display, sensors, condenser fan, evaporator fan, com- Datalogger for later viewing. Any alarm codes recorded
pressors, etc. The test includes measurement of component during the test can be viewed through the controller’s Alarm
power consumption and compares test results to expected val- List menu at the end of the test.
ues.
For a detailed description of the Function Test, see pages
21and 22. Any alarm codes recorded during the test can
be viewed through the controller’s Alarm List menu at the end
of the test.
9-21
Section 9-Microprocessor Controllers
LCD Display
LED
(Shows Approx. Possible Duration
Display Test Description
Amps for 460V, Alarms (Time)
(Test No.)
60 Hz Unit)
F1.00 Display Test Event Log for Function Test begins. None 10 Seconds
Activated All alarms are turned OFF.
0.1 A 0.0 A 0.1 A Alarm list is cleared.
All lights and bars in display turn ON.
F1.01 Sensor Test All sensors must have values within their mea- 00, 01, 02, 2 Seconds
Activated suring range. 03, 04, 05,
0.1 A 0.0 A 0.1 A 28, 31, 32,
33, 34, 35,
97, 98, 112
F1.02 Evaporator Fan Low Amp draw is measured and compared to voltage 14, 15 10 Seconds
Activated and frequency.
1.1 A 1.0 A 1.1 A • CSR40 PS: 0.8 Amps approx. at 50 Hz,
1.1 Amps approx. at 60 Hz
• CSR20 PS and CSR40SL PS:
1.2 Amps approx. at 50 Hz,
1.6 Amps approx. at 60 Hz
F1.03 Evaporator Fan High Amp draw is measured and compared to voltage 12, 13 10 Seconds
Activated and frequency.
2.4 A 2.3 A 2.4 A • CSR40 PS: 2.2 Amps approx. at 50 Hz,
2.6 Amps approx. at 60 Hz
• CSR20 PS and CSR40SL PS:
3.0 Amps approx. at 50 Hz,
3.6 Amps approx. at 60 Hz
F1.04 Condenser Fan Amp draw is measured and compared to voltage 16, 17 10 Seconds
Activated and frequency: 1.2 Amps Maximum.
0.8A 0.7 A 0.8 A
F1.05 Reverse Phase Condenser fan stops. Reverse phase selector 58 30 Seconds
Activated relay is energized and condenser motor is started
0.8 A 0.7 A 0.8A in reverse. Amps measured must be approx.
equal to previous test (F1.04).
F1.06 Compressor Test With condenser fan ON and compressor ON, 06, 07, 31 14 Seconds
Activated compressor is operated at 25% capacity. Amp
7.1 A 7.0 A 7.1 A draw is measured and compared to voltage.
Evaporator temperature and condenser coil tem-
perature are measured and stored.
F1.07 Injection Valve Test Condenser fan and compressor remain ON. Liq- 29, 31 10 Seconds
Activated uid injection valve is turned ON. Amp draw is
7.6 A 7.5 A 7.6 measured and verified to be a minimum of .02
amps higher that test F1.06.
9-22
Section 9-Microprocessor Controllers
LCD Display
LED
(Shows Approx. Possible Duration
Display Test Description
Amps for 460V, Alarms (Time)
(Test No.)
60 Hz Unit)
F1.08 Low Pressure Test Condenser fan, compressor and liquid injection 31 10 Seconds
Activated valve remain ON. Stepper valve is closed and
0.8 A 0.7 A 0.8 A low pressure cutout is verified to open.
F1.09 Warm Gas Bypass With condenser fan and compressor ON, com- 30 10 Seconds
Valve Activated pressor is operated at 25% capacity. Liquid
8.3 A 8.2A 8.3A injection valve is OFF. Bypass valve is turned
ON. Amp draw measured and verified to be a
minimum of 0.2 amps higher that test F1.06.
F1.10 Heat Test Amp draw is measured and compared to volt- 10, 11 10 Seconds
Activated age:
5.2 A 5.1 A 5.2 A • 4.4 Amps approx. at 400V;
• 5.2 Amps approx. at 460 V.
F1.11 Humidify Valve Test Dehumidify valve is turned ON for 2 seconds, None 6 Seconds
Activated OFF for 2 seconds and ON for 2 seconds to ver-
0.1 A 0.0 A 0.1 A ify valve operation.
Function Test log ends.
Alarms (if any) are cleared from data logger.
However, alarms (if any) remain in alarm list as
not active until acknowledged.
P1.00 Display Test Event Log for PTI begins. None 10 Seconds
Activated All alarms are turned OFF.
0.1 A 0.0 A 0.1 A Alarm list is cleared.
All lights and bars in display turn ON.
P1.01 Sensor Test All sensors must have values with in their mea- 00. 01, 02, 10 Seconds
Activated suring range. 03, 04, 05,
0.1 A 0.0 A 0.1 A When CONTAINER ID begins with MAE, 28, 31, 32,
MSF or MWC prefix, at least 1 USDA sensor 33, 34, 35,
must be installed or USDA No. 1 OPEN alarm 97, 98, 99 112
will be logged.
P1.02 Heat Test Electric heaters are turned ON. 10, 11 10 Seconds
Activated Amp draw is measured and compared to volt-
5.2 A 5.1 A 5.2 A age:
• 4.4 Amps approx. at 400V;
• 5.1 Amps approx. at 460V.
heater amperes are recorded in PTI log.
P1.03 Defrost If evaporator sensor is below +10 C (50 F), heat 20 1 Hour
Activated remains on until evaporator sensor reaches _18 Maximum
5.2 A 5.1 A 5.2 A C (65 F).
P1.04 PreCool If the evaporator sensor is above +20 C (68 F), 22 1 Hour
Activated unit operates in Cool until sensor temperature is Maximum
15.2 A 15.2 A 15.2 below +15 C (59 F).
A
9-23
Section 9-Microprocessor Controllers
LCD Display
LED
(Shows Approx. Possible Duration
Display Test Description
Amps for 460V, Alarms (Time)
(Test No.)
60 Hz Unit)
P1.05 Evaporator Fan High Condenser fan and compressor are turned OFF. 12, 13 10 Seconds
Activated With evaporator fan on high speed, Amp draw is
2.4 A 2.3 A 2.4 A measured and compared to voltage and fre-
quency:
• CSR 40 PS: 2.2 Amps approx. at 50 Hz,
2.6 Amps approx. at 60 Hz
• CSR20 PS and CSR40Sl PS:
3.0 Amps approx. at 50 Hz
3.6 Amps approx. at 60 Hz
Evaporator fan high speed amperes are recorded
in PTI log.
P1.06 Probe Test Evaporator fans operate on high speed for 3 52 3 Minutes
Activated minutes. Then probe test runs until temperature Minimum to
2.4 A 2.3 A 2.4 A difference between sensors stops increasing. 13 Minutes
Maximum temperature difference allowed: Maximum
• Return/Evaporator: 1.5 C (2.7 F); return air
sensor temperature must be 0.5 C (1.0 F) above
evaporator sensor temperature
• Return/Supply: 0.8 C (1.4 F); return air sensor
temperature must be 0.5 C (1.0 F) above supply
air temperature
• LH Supply/RH Supply (if equipped): 0.5 C
(0.9F)
P1.07 Condenser Fan Condenser fan is turned ON. Amp draw is mea- 16, 17 10 Seconds
Activated sured and compared to voltage and frequency:
0.8 A 0.7 A 0.8 A 1.2 Amps Maximum. Condenser fan amperes
are recorded in PTI log.
P1.08 Reverse Phase Condenser fan stops. Reverse phase selector 58 30 Seconds
Activated relay is energized and condenser motor is started
in reverse. Amps measured must be approx.
equal to test P1.07.
P1.09 Compressor Test With condenser fan ON and compressor ON, 06, 07 14 Seconds
Activated compressor is operated at 25% capacity. Amp
7.1 A 7.0 A 7.1 A draw is measured and compared to voltage.
Evaporator temperature and condenser coil tem-
perature are measured and recorded in PTI log.
P1.10 Injection Valve Test Condenser fan and compressor remain ON. Liq- 29 10 Seconds
Activated uid injection valve is turned ON. Amp draw is
7.6 A 7.5 A 7.6 measured and verified to be a minimum of 0.2
amps higher that test P1.09.
P1.11 Low Pressure Test Condenser fan, compressor and liquid injection 31 10 Seconds
Activated valve remain ON. Stepper valve is closed and
0.8 A 0.7 A 0.8 A low pressure cutout is verified to open.
9-24
Section 9-Microprocessor Controllers
LCD Display
LED
(Shows Approx. Possible Duration
Display Test Description
Amps for 460V, Alarms (Time)
(Test No.)
60 Hz Unit)
P1.12 Warm Gas Bypass With condenser fan and compressor ON, com- 30 10 Seconds
Valve Activated pressor is operated at 25% capacity. Liquid
8.3 A 8.2 A 8.3 A injection valve is OFF. Bypass valve is turned
ON. Amp draw measured and verified to be a
minimum of 0.2 amps higher that test P1.09
P1.13 Compressor High Stepper valve opened to 50% capacity. With 53 10 to 300
Pressure Activated compressor ON, evaporator fan operates on high Seconds
12.2 A 12.0 A 12.2 speed until high pressure cutout occurs, causing
A significant amps drop. Maximum time depends
on condenser coil temperature at start of test.
P1.13 Compress High With compressor OFF, condenser fan starts and 54 3 to 50 Sec-
Pressure Activated operates until compressor starts, causing a sig- onds plus 60
4.5 A 4.4 A 4.5 A nificant amps increase. Compressor is then Seconds
turned OFF. Condenser fan operates 60 seconds
more to lower condenser temperature.
P1.14 Evaporator Fan Low Condenser fan and compressor are turned OFF. 14, 15 10 Seconds
Activated With evaporator fan on low speed, Amp draw is
1.1 A 1.0 A 1.1 A measured and compared to voltage and fre-
quency:
• CSR 40 PS: 0.8 Amps approx. at 50 Hz,
1.1 Amps approx. at 60 Hz
• CSR20 PS and CSR40Sl PS:
1.2 Amps approx. at 50 Hz
1.6 Amps approx. at 60 Hz
P1.15 Capacity Test 1 With condenser fan ON, compressor ON, and 22 3 Minutes
Activated evaporator fans on low speed, stepper valve is (4 Minutes
12.1 A 12.0 A 12.1 set to 50% capacity. Liquid injection valve is on CSR20)
A turned ON. A difference of approx. 4.5 C (8.0 F)
is required between return and supply air tem-
peratures, depending on return air and con-
denser coil temperatures.
P1.16 Capacity Test 2 With condenser fan ON, compressor ON, liquid 23 2 Minutes
Activated injection valve ON and stepper valve set to 50%
13.2 A 13.0 A 13.2 capacity, evaporator fans are changed to high
A speed. A difference of approx. 3.0 C (5.4 F) is
required between return and supply air tempera-
tures, depending on return air and condenser
coil temperatures. However, temperature differ-
ence must be less than in test P1.15.
9-25
Section 9-Microprocessor Controllers
LCD Display
LED
(Shows Approx. Possible Duration
Display Test Description
Amps for 460V, Alarms (Time)
(Test No.)
60 Hz Unit)
P1.17 Capacity Test 3 Stepper valve is almost closed (set to 250 24 4 Minutes
Activated value). With condenser fan ON, compressor ON (5 Minutes
11.2 A 11.1 A 11.2 A liquid injection ON, bypass valve ON and evap- on CSR20)
orator fans on high speed, alarm is recorded if
temperature difference exceeds:
• CSR40 PS: 1.5 C (2.7 F)
• CSR20 PS and CSR40SL PS: 3.0 C (5.4 F)
P1.18 Heat Test With heaters ON and evaporator fans on high 27 4 Minutes
Activated speed, alarm is recorded if supply temperature is
7.3 A 7.2 A 7.3 A not at least 0.4 C (0.7 F) above the return air
temperature.
P1.19 Evaporator Stepper valve is set to 50% capacity. With con- 25 5 Minutes
Temperature Test denser fan ON, compressor ON, and liquid Maximum
Activated injection valve ON, evaporator fans are turned
12.3 A 12.1 A 12.3 OFF. The evaporator coil temperature must
A decrease to approx. 15 C (+5 F), depending on
the return air temperature.
P1.21 PTi Part 1 End “PTI Part 1 End” is recorded in PTi log. Return/ None 5 Minutes
supply air temperature difference from tests
2.4 A 2.3 A 2.4 A P1.15, P1.16, P1.17 and P1.18 are recorded in
PTI log. Condenser fan and compressor stop.
Evaporator fans start and operate on high speed.
P1.22 PreHeat If return air temperature is below 5 C (41 F), None 120
Activated evaporator fans operate on high speed and heat- Minutes
7.9 A 7.9 A 7.9 A ers turn ON. Unit operates until return air tem- Maximum
perature is above 5 C (41 F).
Supply PTI Running Unit operates in normal cool mode with 0 Cl (32 23 120
Temp. Setpoint: 0 C (32 F) F) setpoint. When supply air temperature Minutes
decreases to setpoint, “Chill Arrival” tempera- Maximum
tures are recorded in PTI log.
Supply PTI Running Unit operates in normal mode with 0 C (32 F) None 30
Temp Setpoint: 9 C (32 F) setpoint for 30 minutes after previous test is Minutes
completed. At the end of 30 minutes, “Chill
End” temperatures are recorded in PTi log.
Return Defrost Activated Unit operates in normal mode with 18 C (0 F) 20 90
Temp. 4.5 A 4.4 A 4.5 A setpoint. When return air temperature decreases Minutes
to 18 C (0 F), defrost is initiated. Defrost termi- Maximum
nates when evaporator temperature increases to
18 C (65 F).
9-26
Section 9-Microprocessor Controllers
LCD Display
LED
(Shows Approx. Possible Duration
Display Test Description
Amps for 460V, Alarms (Time)
(Test No.)
60 Hz Unit)
Return PTI Running Unit operates in normal mode with 18 C (0 F) 22, 60 180
Temp. Setpoint: 18 C (0 F) setpoint. When return air temperature decreases Minutes
to setpoint, “Frozen Arrival” temperatures are Maximum
recorded in PTi log.
Return PTI PASS: If alarms (errors) occurred during PTI test, LCD NONE __
Temp. Press (Any) Key display shows PTI FAIL.
Press any key to clear display.
9-27
Section 9-Microprocessor Controllers
9-28
Section 9-Microprocessor Controllers
9-29
Section 9-Microprocessor Controllers
2. Press F2 key to scroll through Main Menu until “MISC. 7. With the correct time entered in the menu line, press F4
FUNCTIONS” appears in LCD display. key. Then press EXIT key to enter time in controller
3. Press F4 key to access the Misc. Functions menu. The memory. Cursor stops blinking and new time appears in
first command in the submenu appears in the LCD dis- display.
play: Date Time. 8. To enter a new date, press F3 key to move cursor to Date
4. 4. Press F2 or F3 key to scroll to the desired function: menu line. Display shows date in and date in
• Date Time “YY.MM.DD” where Y = year, M = month and D = day.
• C/F Mode 9. Press F4 key with cursor in Date menu line. An Enter
• Cargo Data Arrow appears in the menu line and the previous date dis-
• Program Version appears.
• Run Time 10. Enter new date in “YY.MM.DD” where Y = year, M =
5. Press F4 key to access the function selected. month and D = day. Decimal points must be included in
the entry between the year, month and day.
Setting the Date and Time 11. With the correct date entered in the menu line, press F4
key. Then press EXIT key to enter date in controller
1. Press the F1 key to retrieve current unit performance data memory. Cursor stops blinking and new date appears in
before entering Main Menu. the display.
2. Press F2 key to enter the menu list. Press F2 key to scroll 12. Press ESC key to exit the Date Time screen.
to “MISC. FUNCTIONS”.
3. Press F4 key to access the Misc. Functions menu. “Date
Time” appears in the LCD display.
Changing the Temperature Display
4. Press F4 key to access the Date Time screen. Date Time Value (C/F)
screen appears with cursor in the Time menu line. Dis-
1. Press the F1 key to retrieve current unit performance data
play shows time in “HH.MM.SS” where H = hour, M =
before entering Main Menu.
minute and S = second.
2. Press F2 key to enter the menu list. Press F2 key to scroll
5. To enter a new time, press F4 key with cursor in Time
to “MISC. FUNCTIONS”.
menu line. An Enter Arrow appears in the menu line and
3. Press F4 key to access the Misc. Functions menu. “Day-
the previous time disappears.
time” appears in the LCD display. Press F2 key to scroll
6. Enter new time in “HH.MM.SS” format. Decimal points
to “C/F MODE”.
must be included in the entry between the hour, minute
4. Press F4 key to access the C/F Mode screen. C/F Mode
and second.
screen appears with cursor in the temperature value menu
NOTE: To scroll backward in the Time or Date menu line,
line. Display shows “C/F MODE o C” where C = Celsius
press and hold the F4 key, then press F3 key. Press F1 key to
and F = Fahrenheit.
return keyboard to “numerical” entry before typing again.
5. To change the temperature value, press F4 key. Cursor
moves to end of menu line and flashes.
6. Press F2 key to toggle temperature value in the menu line
between C and F.
7. With the desired temperature value in the menu line,
press and hold F4 key until cursor stops flashing. Cursor
stops blinking and new temperature value appears in dis-
play.
8. Press ESC key to exit the C/F Mode screen.
9-30
Section 9-Microprocessor Controllers
9-31
Section 9-Microprocessor Controllers
NOTE: All screens are NOT present on all units.The screens that display
on the controller are determined by the Unit Configuration setting.
9-32
Section 9-Microprocessor Controllers
• Reefer Type: Sets the unit model state to CSR20 PS or Datalogger Menu
CSR40SL PS/CSR40 PS. Must be manually set to unit
type on unit serial number plate. The Datalogger menu contains a list of functions that display
• Zero Current: View display ON or OFF value (factory unit operating information recorded in the MP3000 datalog-
default = ON). However, no errors occur if a Zero Cur- ger. The following functions are available:
rent transformer is not installed and configuration is set • Inspect Temperature Log: Displays temperature logs by
to ON. time and date for the Setpoint; Supply (Controlling Tem-
• Supply LH: View display ON or OFF value (factory perature), Return, USDA1, USDA2, USDA3 and Ambi-
default = OFF). Controller automatically activates when ent sensors; humidity sensor; and event flags.
a left hand supply sensor is installed for more than 1 • Inspect Event Log: Displays important event logs by time
minute. Setting this value is not necessary. and date for events such as unit alarms, power On/Off,
• Controlled Atmosphere Option: View display value (fac- setpoint change, clock reset, trip start, defrost, etc.
tory default = NO). Controller automatically activates • Set Log Time: Sets the data log interval (1 minute or 1/2,
when a O 2 or CO 2 sensor is installed for more than one 1, 2 or 4 hours).
minute. • Activate Tripstart: Sets the date and time of the trip start.
• Evaporator Fans: Sets the number of evaporator fans to 2 • Inspect PTI Log: Displays results of last PTI test includ-
or 3. Must be manually set. ing component volt and amps data and sensor tempera-
• AFAM Option: View display ON or OFF value (factory tures. Test values are recorded at the start and end of the
default = ON). Set value to OFF when customer want Chilled and Frozen Mode test.
AFAM door to remain closed.
• Auto Configuration: View display ON or OFF value (fac- Viewing the Datalogger Menu
tory default = OFF). Set value to ON to automatically
With the unit On/Off switch ON and the LCD display show-
configure unit to installed components. See “Automatic
ing the standard display (setpoint):
Configuration of Spare Parts Controller” in this chapter
1. Press the F1 key to retrieve current unit performance data
for additional information.
before entering Main Menu.
• Serial Number: Sets the unit serial number. Enter up to 11
2. Press F2 key to enter the menu list. Press F2 key to scroll
characters (number or letters). Must be manually set.
through Main Menu until “DATALOGGER” appears in
Required to enable automatic detection of USDA sensors
LCD display.
units with serial number beginning with MAE, MSF or
3. Press F4 key to access the Datalogger menu. The first
MWC prefix.
function appears in the LCD display: Inspect Temp Log.
5. To set a new Configuration screen value:
4. Press F2 or F3 key to scroll to the desired function:
a. Press F4 key with cursor in the desired menu line. The
Inspect Temp Log
Password screen appears.
Inspect Event Log
b. Press F2 key, “A” key (password is “A”), F4 key and
Set Log Time
then EXIT key. An Enter Arrow appears in the hourmeter
Activate Tripstart
line.
Inspect PTI Log
c. Use the general purpose keypad to enter the desired
5. Press F4 key to access the function selected.
value; or press the F3 key to toggle the value to the
desired setting.
d. When the entry is complete, press and hold the F4 Inspect Temp Log
key until the cursor stops flashing. The new value With the unit On/Off switch ON and the LCD display show-
appears in the menu line. ing the standard display (setpoint):
6. Repeat steps 4 and 5 to reset additional configuration val- 1. Press F2 key to enter the menu list. Repeatedly press F2
ues. key to scroll through Main Menu until “DATALOGGER”
7. Press ESC key to exit the Configurations screen. appears in LCD display.
2. Press F4 key to access the Datalogger menu. “Inspect
Temp Log” appears in the LCD display.
3. Press F4 key to enter Temp Log. LCD display shows the
Log Time and the Setpoint, Supply and Return tempera-
tures of the most recent log in the first screen.
9-33
Section 9-Microprocessor Controllers
• To scroll through previous logs of the sensor tempera- Inspect Event Log
tures currently in the display, press F3 key. All tempera-
ture logs recorded in the datalogger memory may be With the unit On/Off switch ON and the LCD display show-
viewed on the LCD display. ing the standard display (setpoint):
4. To view additional sensor log and event flag screens, 1. Press F2 key to enter the menu list. Repeatedly press F2
press F4 key again. LCD display shows USDA1, key to scroll through Main Menu until “DATALOGGER”
USDA2, USDA3, Relative Humidity (rH), Ambient, etc. appears in LCD display.
sensor readings, and flags. 2. Press F4 key to access the Datalogger menu. “Inspect
• To scroll through previous logs of the sensor tempera- Temp Log” appears in the LCD display.
tures currently in the display, press F3 key. 3. Press F2 or F3 key to scroll through submenu until
“Inspect Event Log” appears in LCD display.
Event Flags for Temperature Log 4. Press F4 key to enter Event Log. LCD display shows the
T = Tripstart Activated Log Time and the most recent event.
P = Primary Power Off • To scroll through previous event log screens, press F3
D = Defrost in Last Interval key. All event logs recorded in the datalogger memory
O = Temperature Not Inrange may be viewed on the LCD display.
h = Humidity Control Active
E = Evaporator High Temperature Event Examples
H = High Refrigeration Pressure • Controller alarm status (alarms set/cleared)
d = Defrost terminated on time limit • Main power On/Off status (humidity On/Off, temperature
e = Economy mode activated setpoint, and main power Hz)
s = Reefer unit stopped (after PTI) • 12 Vdc battery discharge test (battery voltage, total unit
w = Water-cooled operation (Condenser Fan switch is in and compressor hours if main power On) — this event
the WATER position) logged at once a day
A = Alarm in last interval • Change temperature setpoint (new/old setpoint)
NOTE: All event flags that occurred during a log • Change RH setpoint (new/old RH setpoint)
interval are displayed. • Change RH status (On/Off)
5. Press ESC key to exit the Temp Log. • Event log retrieval
• Temperature log retrieval
NOTE: All screens are NOT present on all units. The screens that display on
the controller are determined by the Unit Configuration setting.
9-34
Section 9-Microprocessor Controllers
9-35
Section 9-Microprocessor Controllers
AJA746
AJA745
RMM State Menu Screen Flow Diagram Manual Emergency Control Connections
9-36
Section 9-Microprocessor Controllers
9-37
Section 9-Microprocessor Controllers
power up, the controller turns the Auto Configuration feature Flash Loading Controller Software
Off. The Auto Configuration feature detects the following
options and sets the correct value in Configuration menu: Controller software must be flash loaded when software has
• Number of Supply Air Sensors (1 or 2): Controller been revised. To flash load software:
detects left hand and right supply air sensors. 1. Turn the unit On/Off switch OFF.
• Number of Evaporator Fans (2 or 3) 2. Plug cable from a portable computer with controller soft-
• Dehumidify (On or OFF): If controller detects a humidity ware into the data retrieval connector on the control box.
sensor, it then checks for current draw on a dehumidify 3. Press one of the special functions keys to activate con-
valve. troller LCD display on battery power; or turn the Unit
• Humidification (On or OFF): If controller detects a On/Off switch ON.
humidity sensor, it then checks for current draw on an air 4. Press and hold the “7” key and F1 key at the same time.
compressor. LCD display will show “FLASHLOAD ”.
• Position 7: Unit testing and service only. NOTE: Installing new software does not change any
Changing Software Selection Dial Position configuration settings or the setpoint setting, or
erase the data log currently stored in the controller.
1. Turn Unit On/Off switch OFF.
2. Set dial indicator to correct position.
3. Turn Unit On/Off switch ON. New software selection is
loaded during controller startup.
9-38
Section 9-Microprocessor Controllers
AJA748 A
B 1 to 1.2 in.
(25 to 30 mm)
9-39
Section 9-Microprocessor Controllers
• Evaporator coil (defrost) sensor must be placed in the Diagnosis and Repair
middle of the coil and at least 75 mm deep between the
fins. If the unit appears to be operating incorrectly, view any alarm
• Condenser sensor must be placed on the upper left side of codes that may be stored in the controller display memory.
the condenser coil and at lest 70 mm deep between the Diagnose and correct the problem associated with each alarm
fins. code (see “Alarm Codes, Alarm Types and Corrective
• Ambient sensor must be placed on the bottom plate of the Actions” in this chapter).
right forklift pocket.
• Compressor sensor must be placed in the manifold on the NOTE: Defrost can be delayed for 24 hours during unit
discharge tube before the discharge service valve. diagnosis or testing: Press “7” key and F1 key at the same
time from any controller screen display. Press F3 key to
scroll cursor down to DELAY DEF menu line. Then press
Resistance Values for Compressor Discharge Line F4 key, F2 key, “A” key, F4 key and EXIT key. Cursor
Sensor moves to end of line and flashes. Pressure F3 key to toggle
TEMP. C OHMS TEMP. C OHMS OFF to ON. Then press and hold F4 key until cursor stops
flashing.
0 351017 70 15502
2 315288 72 14410 If you have viewed and corrected these problems and the
4 283558 74 13405 unit still appears to be operating incorrectly, eliminate any
6 255337 76 12479 possibility that the problem is caused by failure of compo-
8 230210 78 11625 nents other than the controller.
10 207807 80 10837
12 187803 82 10110 External Cause Checks
14 169924 84 9438 • Poor contact between male and female connector plugs
16 153923 86 8817 (loose connection).
18 139588 88 8242 • Defective wire harness (broken wires, loose connec-
20 126729 90 7710 tions).
22 115179 92 7216 • External electrical causes such as faulty (open or stuck)
24 104796 94 6759 contactors.
26 95449 96 6335 • Malfunction of refrigeration system components.
28 87023 98 5941
30 79428 100 5574
32 72567 102 5234
34 66365 104 4917
36 60752 106 4623
38 55668 108 4348
40 51058 110 4092
42 46873 112 3854
44 43071 114 3631
46 39613 116 3423
48 36465 118 3229
50 33598 120 3047
52 30983 122 2877
54 28595 124 2718
56 26413 126 2569
58 24419 128 2430
60 22593 130 2299
62 20921 132 2176
64 19388 134 2118
66 17961 136 1953
68 16689 138 1852
9-40
SECTION 10
Container
Service Bulletins
10-1
Section 10-Container Service Bulletins
SERVICE BULLETIN
C-001 Procedure for Converting Thermo King CF-11 C-018 Supply (Discharge) Air Sensor Position in
Sensor Tube on CSR-40, CRR-40, TNE 508 and
Container Units from R-12 to R-401 B (MP66)
C-002 Compressors Oils TNE 508 SCII Units
C-003 New Pocket Reference Cards C-019 PVC Breather Vent on se 2.2 Engines
C-020 Revised Operating Instructions for
C-004 Unit Sight Glass Balls Sticking on HFC Units,
Thermo King P/N 66-7420 Communications Tester/Amplifier (P/N 204-901)
C-005 Refrigeration System Cleanup When Compressor C-021 CSR and CRR Leak Charts
C-022 Operating Instructions for µP-D Tester, P/N 204-911
Oil is Contaminated (Dark or Discolored)
C-006 Copeland Bypass Oil Filter C-023 Use Separate, Dedicated Service Tools for
(Thermo King P/N 66-7462) -Change Requirements HCFC/CFC Refrigerants and HFC Refrigerants
C-024 µP-D Controller Emergency Bypass Procedure
C-007 Thermo King Expansion Valve (TXV)
Setting: After Unit Conversion from R-12 to R-134a; C-025 Normal Operating System Pressures for CSR Units
All Units Factory Equipped with R-134a; C-026 Auto-Restart Operation on Smart Generator Sets
C-027 Sealed Expansion Valve on Sea-Land CSR Units
All Units Including Standard R-12 Units
C-008 Thermo King Refrigeration System Cleanup C-028 New Dehydrator, P/N 66-9015, for All CF-11
Procedure Series Units
C-029 CSR Versus CRR Service Guide and
C-009 Leak Checking Compressor Shaft Seal on
Thermo King X426 and X430 Compressors Refrigeration System Service Procedures
C-010 µP-A+ Controller Configuration Setting and C-030 Injection Pump Timing Bolt Change to Provide
Positive Fuel Shutoff on CG and SG (Smart)
Minimum Software Version Requirement
C-011 CF-11 Sight Glass Moisture Indicators with Generator Sets
R-134a and R-404A C-031 Thermo King 11.71 (or above) Software Release
C-032 Check Mounting Bolt Torque of Suction Flange
C-012 Operating Instructions for Communications
Tester/Amplifier (P/N 204-901) with Power Connections on CRR Units with “29K” in the Serial
Cable/Battery Number (xxx29Kxxx)
C-033 Procedures for Belt Tension Adjustment on
Connector (P/N204-937)
C-013 Operating Instructions for Communications Thermo King Gensets
Tester/Amplifier (P/N 204-901) with Power C-034 Use the Thermo King EXTRANET Site on the World
Wide Web to View and Download Files for Container
Cable/Battery
Connector (P/N204-938) Products
C-014 µP-G Controller Unit Operating Information for C-035 PC-PAC V3.3 Upgrade Now Available from the Public
CG-11 Generator Sets File Download Center at the Thermo King
C-015 CF-11 Heaters EXTRANET Site
C-037 µP-D Controller Replacement
C-016 CF-11 Condenser Coil Cleaning
C-017 Measuring Compressor Crankshaft End Play C-038 Unit and Customer Configuration Settings for
on Thermo King X426 and X4340 Compressors µP-D Controller
C-039 Unit Health Check for CSR Hermetic
Used in CF-11
and CF-111 Container Refrigeration Units Refrigeration Systems
10-2
Section 10-Container Service Bulletins
SERVICE BULLETIN
10-3
Section 10-Container Service Bulletins
SERVICE BULLETIN
TK PIN 203-433, Mobil EAL 22 CC (POE) Oil TK P/N 203-426, Mobil EAL 32 (POE) Oil
• CF-II units equipped with 3DS Copeland compressors • CF-II refrigeration units equipped with an X426 or X430
require polyol ester (POE) oil, TK P/N 203-433. ONLY compressor and R-134a must use a polyol ester (POE)
Mobil EAL Arctic 22 CC compressor oil contains the oil. Both Thermo King polyol ester (POE) oils, TK P/N
additive package required all 3DS Copeland compres- 203-426 and TK P/N 203-433 are approved and recom-
sors. mended for use in X426 and X430 compressors.
CAUTION. DO NOT add or mix ANY other CAUTION: DO NOT use TK PIN 203-426 or 203433
compressor oil to units equipped with a 3DS (POE oils) with R-12 refrigerant.
Copeland compressor. Other Thermo King polyol
ester (POE) oils (i e. TK PIN 203-426) DO NOT CAUTION: DO NOT use TK P/N 203-426 (POE oil) in
contain the Copeland required additive and should a Copeland 3DS compressor
NOT be used.
TK P/N 67-404, Alkyl Benzene (AB) Oil
• Through laboratory and field testing, Thermo King has • CF-II refrigeration units equipped with an X426 or X430
determined that Mobil EAL Arctic 22 CC compressor oil compressor and R-12 use synthetic alkyl benzene (AB)
also performs satisfactorily in CF-II units equipped with oil, TK P/N 67-404.
X426 and X430 compressors and R-134a.
CAUTION: DO NOT use alkyl benzene (AB) oil with
NOTE: TK P/N 203-433 pol ester (POE) oil is R-134a refrigerant. DO NOT use alkyl benzene (AB)
designed for use with HFC refrigerants like R-134a. oil in a Copeland 3DS compressor.
Therefore, this oil is PREFERRED for use in ALL
Thermo King CF-II units that use R-134a.
AJA516
10-4
Section 10-Container Service Bulletins
SERVICE BULLETIN
Three (3) Quick Reference Pocket Guide cards have been printed by Thermo King to make dealers and customers more familiar
with proper CF-11 container unit service procedures. All technicians should have one of each card to use for reference. Refer-
ence cards can be ordered from the Thermo King Publications Department, 314 W. 90th Street, Minneapolis, MN 55420.
de
G ui
et
ock 085
P 41
S ee TK
de
Gui
et
ock 081
P 41
S ee TK
e
uid
tG
c ke 52
o 08
e e P TK4
S
10-5
Section 10-Container Service Bulletins
SERVICE BULLETIN
It has been reported that receiver tank sight glass ball(s) have been “sticking” on some units charged with HFC refrigerant R-
134a. This sticking may occur in a refrigeration system that contains residue. The residue accumulates on the sight glass ball(s),
causing the ball(s) to “stick” to the sight glass (es).
If this sticking occurs on newer units that are under warranty, the sight glass (es) (Thermo King P/N 66-7420) should be changed
and handled as a standard warranty claim.
NOTE: The refrigerant charge level may be verified in a system with a “stuck” sight glass ball by shining a light on the sight
glass to view the refrigerant level.
Two Sight Glass Receiver Tank Single Sight Glass Receiver Tank
10-6
Section 10-Container Service Bulletins
SERVICE BULLETIN
Copeland 3DS
Compressor
Bypass Oil Filter
10-7
Section 10-Container Service Bulletins
SERVICE BULLETIN
The Expansion Valve (TXV) settings have been changed by After converting a unit from R-12 to R-134a:
some technicians in an attempt to achieve lower box tempera- Use this quick reference pocket card, TK41085, to assure that
tures. This is NOT a recommended Thermo King mainte- the expansion valve is correctly set. After the correct setting is
nance practice! verified, use Loctite on the expansion valve cap threads to
Expansion valves come pre-set from the Thermo King fac- seal cap in place!
tory and rarely require adjustment
One of the times adjustment IS required is after a unit conver- ALL Units Factory Equipped with R-134a:
sion from R-12 to R-134a. Thermo King has created a quick If an expansion valve is suspected of being set incorrectly,
reference pocket guide card “Checking and Adjusting CF- CHECK the setting per the procedure on pocket guide card
11 Expansion Valve Superheat Setting” (TK 41085) which (TK 41085) mentioned above. After the correct setting has
outlines and illustrates the correct method of checking and been verified, use Loctite on the expansion valve cap threads
setting the expansion valve. to seal cap in place!
10-8
Section 10-Container Service Bulletins
SERVICE BULLETIN
10-9
Section 10-Container Service Bulletins
Special
self-sealing,
quick connect
V-4 couplers are
required for
Sensor R-134a units
V-3
Micron Meter
V-2
Calibration Standard V-1
Gas Ballast Valve
Iso Valve
Evacuation Station
and Unit Hookup AJA517
Two Stage Vacuum Pump
To 110 VAC or 220 VAC Power
Unit Evacuation When the system reaches 1,000 microns, close the Gas
1. Turn on the Vacuum Pump. Open the Gas Ballast Valve Ballast Valve.
located on top of the pump housing in front of the handle
(the valve is fully open at two turns counterclockwise). Evacuate the system to 500 microns to achieve a final equilib-
rium pressure of 2000 microns or less. The final equilibrium
pressure is determined with the Thermo King Evacuation Sta-
NOTE: The Gas Ballast Valve is opened to purge a small
tion using the following procedure (called a pressure-rise
amount of atmospheric air through the pump’s exhaust
test):
chamber This extra volume of air helps exhaust moisture in
the form of vapor from the pump and will substantially a. Evacuate the system using the Evacuation Station until
extend the life of the pump oil. the vacuum level reaches 1000 microns. Then close the
pump Gas Ballast Valve.
b. Continue evacuation to 500 microns or until vacuum
stabilizes at its lowest level. Contamination may delay
10-10
Section 10-Container Service Bulletins
reaching the lowest level for a period of several or more • system that rises above 2000 microns but stabilizes
hours. below atmospheric pressure is probably contaminated
with moisture or has refrigerant out-gassing from the
c. Close valve Vl to isolate the vacuum pump from the compressor oil. Additional evacuation is required.
system. • A system that continues to rise without stabilizing has a
leak and must be repaired.
d. Observe the vacuum level on the Micron Meter. 5. If the vacuum level remained below 2000 microns for
five minutes, the unit is ready to charge.
When the Meter has stabilized, the value indicated on the
Micron Meter is the equilibrium pressure. This reading must Pressure Rise Test
be 2000 microns or less. 1. Evacuate the system and close valve Vl. With valves V3
and V4 open, the pump is isolated and the system is held
under a vacuum. If the Micron Meter rises, one of the fol-
NOTE: The presence of refrigerant in the compressor oil
lowing conditions exists.
may prevent a low vacuum reading from being achieved
Compressor oil can continue to out-gas for long periods of Leak: Watch the movement of the Micron Meter needle.
time. If the needle continues to rise until it reaches atmospheric
2. If the vacuum level appears to stall above 500 microns, pressure, it is an indication that a leak exists somewhere
back seat the discharge service valve (if so equipped) or in the system. When a leak is in a system, the vacuum
rotate the discharge hose coupler wheel counterclockwise will eventually stabilize at atmospheric pressure. See the
to back the stem out of the discharge service fitting. Then diagram below.
back set the suction service valve (if so equipped) or
rotate the suction hose coupler wheel counterclockwise to Moisture: When the needle indicates a rise and then sta-
back the stem out of the suction service fitting. This iso- bilizes at a level below atmospheric pressure, it is an indi-
lates the compressor from the Micron Meter. Observe the cation that the system is vacuum tight, but is still wet and
Micron Meter. requires additional dehydration and pumping time. See
• A drop in pressure indicates that the compressor oil is the diagram below.
out-gassing and further evacuation is necessary.
• An increase in pressure indicates that a leak exists or Pressure Rise Test Evaluation
there is moisture in the system. Perform a “Pressure Rise
Test” and evaluate. Factors Affecting the Speed of System Evacuation
3. Close valve Vl when desired vacuum level has been It is almost impossible to state the exact amount of time
reached. required to evacuate any system. Some factors that can influ-
4. Wait five minutes and read the Micron Meter. ence evacuation time are listed below.
• A system that is leak free and dry will remain below 2000 • How large the system is
microns for five minutes. • The amount of moisture contained in the system
• The ambient temperature
• Internal restrictions within the system
• External restrictions between the system and the vacuum
Atmospheric pump
Pressure
Atmospheric
Pressure
Vacuum level
stabilizes at
atmospheric pressure
Absolute
Vacuum level
Vacuum
stabilizes below
Time Absolute
atmospheric pressure
Vacuum
Time
Pressure Rise Test Evaluation
10-11
Section 10-Container Service Bulletins
Hose size, both diameter and length, affect evacuation times. 10. Set the refrigerant tank for liquid removal. Open the hand
Laboratory tests show that the evacuation time can be signifi- valve on the tank.
cantly reduced by larger diameter hoses and shorter hoses. To 11. With the unit OFF, open the gauge manifold hand valve
obtain optimum pumping speed, keep hoses as short as possi- and charge liquid refrigerant into the system.
ble and as large in diameter as possible. For example, it takes 12. Close the refrigerant tank hand valve when the correct
eight times as long to pull a given vacuum through a 1/4-inch amount (by weight) of refrigerant has been added or if
(6 mm) diameter hose as it does through a 1/2-inch (12 mm) the system will take no more liquid.
diameter hose. It takes twice as long to pull a vacuum through The unit is now ready to have the Evacuation Station removed
a 6-foot (1.8 m) long hose as it does through a 3-foot (0.9 m) (described in the following steps, “Evacuation Station
long hose. Removal”).
NOTE: If the refrigerant tank and gauge manifold hoses do • If the unit is fully charged, perform a functional check
not have seal-sealing, low loss fittings, be sure to purge the out.
hoses.
• If the unit has a partial charge, add refrigerant to the unit
8. Weigh the tank of refrigerant. per the procedure on pocket guide card (TK 41081) men-
9. Check the unit data plate for the required weight of tioned above.
refrigerant charge then subtract the amount of the charge
to be input to your unit from the total weight of the tank
of refrigerant. This provides final tank weight after the
unit receives a full system refrigerant charge.
10-12
Section 10-Container Service Bulletins
SERVICE BULLETIN
• The technician must be able to differentiate between normal oil seepage which is usually dirty or dusty and a fresh stream of
oil which continues to appear and flow until it drips.
• A seal may gradually leak enough refrigerant to cause a system failure with no evidence of heavy oil seepage.
• The compressor seal on a unit that has not been operated for extended periods of time may leak small amounts of refrigerant.
However, the seal often recovers its normal sealing capability after the unit is operated and lubrication occurs.
• Like other refrigerant leaks, a shaft seal leak can be masked by the presence of oil in the leak passage. It can take as long as
30-45 minutes for the leak to appear in a large enough quantity to be measured.
• A high quality, very accurate leak detection device (TK P/N 204-712, 11 OV) and the discipline to follow proper leak test
procedures are essential. A unit with a low refrigerant charge should be thoroughly leak checked.
2. Calibrate your leak detector (TK P/N 204-712) for the medium setting (1/2 oz./year).
3. Start below the seal plate and slowly move the probe up towards the compressor seal. Avoid getting dirt or oil in the probe.
4. If the leak detector senses a leak on the medium setting, withdraw the probe, allow the leak detector to stabilize and check
again.
5. Re-calibrate the leak detector for the large setting (5 oz./year) and repeat steps 3 and 4.
6. If the leak detector senses a leak on the large setting, the unit should be operated in MAXIMUM COOL for 10 minutes or
more. Stop the unit and blow out the seal plate area. Allow unit to stand for 1/2 hour.
NOTE: This time can be used to leak check the rest of the unit.
7. Repeat steps 2, 3, 4, and 5. If the leak detector does not sense a leak on the large setting, the shaft seal is okay unless a fresh
stream of oil reappeared.
10-13
Section 10-Container Service Bulletins
SERVICE BULLETIN
The configuration select function has now been moved into the user “Guarded Access” menu. To change the configuration of the
µP-A+ controller:
NOTE: To set the configuration block using the µP-A + controller keypad, the controller MUST be equipped with software
version 05.00.14 or above.
1. Install a new or remanufactured µP-A+ controller.
2. Connect unit to 230V or 460V main power and turn Unit On/Off switch ON position.
NOTE: If power source is not available, operate the controller using battery power if necessary, connect 12 Vdc battery to
battery jack and press [SELECT] key on controller keypad.
3. a. Determine which security code you must enter to access the Guarded Access submenu.
Code Unit
0007 All units (except those listed for code 0013)
0013 CF-II M32E, M32F, M32G and M32H
b. Determine which configuration number is required for your unit:
10-14
Section 10-Container Service Bulletins
4. Press [SELECT] key on controller keypad to enter the MAIN MENU. The display will show
6. Press the [SELECT] key with “GrAc” appearing in the SET POINT display. The display will show “0000” in the TEMP
CODE display with the left digit flashing on and off.
8. Press the [ENTER] key with the correct security code entered in the display. The display will show “Cld 6 XXXX”.
9. Press the [UP] or [DOWN] arrow key to scroll to the “Cb XX” display.
10. Press the [SELECT] key with “Cb XX” appearing in the display to change the configuration number. The EDIT LED will
flash.
11. Press the [UP] or [DOWN] arrow key to scroll to the required configuration number (see step 3b).
12. With the required configuration number appearing in the TEMP/CODE display, press [ENTER] key. The display will show
“LOAD” for 3 seconds. The controller will then perform a shutdown and restart. After unit start-up, the controller will return
to display the current set point and controlling air sensor temperature.
13. To verify that the correct configuration block setting was loaded, press the [ENTER] key. The controller will display the
application software version, configuration block version and boot block software version currently stored in the micropro-
cessor memory.
10-15
Section 10-Container Service Bulletins
SERVICE BULLETIN
300
Refrigerant (ppm)
200
Moisture in
Wet
100
Dry
0
(C) 0 5 10 15 20 25 30 35 40 45 50 55 (°C)
(F) 32 41 50 59 68 77 86 95 104 113 122 122 (°F)
Temperature
10-16
Section 10-Container Service Bulletins
SERVICE BULLETIN
10-17
Section 10-Container Service Bulletins
Communications Tester/Amplifier
Adapter, PN 204-901, MUST Be
Ribbon Cable, PN 204-936, for Installed in SERIES with (P Con-
Easy Viewing of Communications troller and Laptop Computer to
Tester/Amplifier LEDs Amplify Communication Signals
Figure 4.
Using Communications Tester/Amplifier
with µP Controllers
Laptop computer and
Communications Cable
10-18
Section 10-Container Service Bulletins
NOTE: The communications tester/amplifier adapter If the RXD or TXD LED does not flicker or stays on con-
MUST receive 12 VDC power from the communications stantly, and you have verified that the communications tester/
signals between a laptop computer and µp controller. amplifier assembly is good on another controller, the UP con-
troller is defective and should be replaced.
If the PWR indicator DOES NOT light, recheck the power
supply. Also, check to be sure the power cable connectors are Using the Communications Tester/Amplifier with
properly connected. µP-A and µP-A+ Controllers to Monitor Communications.
NOTE: The PWR LED MUST light before attempting NOTE: Communication signals between a µP-A or µP-A +
communications with µP controller. controller and a laptop computer do NOT require
6. Initiate a data exchange with the controller. The GREEN amplification.
TXD LED should flicker briefly, indicating that the lap-
1. Install the ribbon cable on the 15-pin female serial port
top computer is sending a signal to the controller. If the
connector on the controller.
data exchange requires a reply from the µP controller, the
RED RXD LED should flicker, indicating that a reply 2. Then insert the communications tester/amplifier in one of
message (download) is being sent by the controller to the the 15-pin female connectors on the ribbon cable.
laptop computer.
7. If the GREEN TXD or RED RXD indicator does not
NOTE: The communications tester/amplifier adapter may
flicker, verify that the laptop computer and communica-
be plugged in while the controller is powered.
tions tester/amplifier assembly are working properly on
another µP controller.
Figure 5.
Using Communications Tester/Amplifier
with µP-A or µP-A + Controllers
10-19
Section 10-Container Service Bulletins
3. Connect the communications cable from a laptop com- 7. Initiate a data exchange with the controller. The GREEN
puter to the OTHER 15-pin female connector on the rib- TXD LED should flicker briefly, indicating that the lap-
bon cable as shown in Figure 5. top computer is sending a RS232 signal to the controller.
If the data exchange requires a reply from the controller, the
NOTE: The communications tester/amplifier adapter RED RXD LED should flicker, indicating that a reply mes-
MUST be installed in PARALLEL with a (µP-A or (µP-A + sage (download) is being sent by the controller to the laptop
controller and the laptop computer Otherwise, the computer.
communications tester/amplifier adapter may INTERFERE 8. If the GREEN TXD or RED RXD indicator does not
flicker, verify that the laptop computer and communica-
with the communication signals and cause a
tions tester/amplifier assembly are working properly on
communications fault. This is because the communication
another µP-A or µP-A + controller.
signals between a (µP-A or (µP-A + controller and a laptop
computer do NOT require amplification. If the RXD or TXD LED does not flicker or stays on con-
stantly, and you have verified that the communications tester/
4. a. If the Unit On/Off switch is ON and the unit is operat- amplifier assembly is good on another controller, the µP-A or
ing, check to see that the communication tester’s PWR µP-A + controller is defective and should be replaced.
LED is ON to verify 12 Vdc has been supplied to the
communications tester/ amplifier adapter through the Using the Communications Tester/Amplifier with
VREC circuit of controller (µP-A or µP-A + controllers IRMU Remote Monitor Units to Monitor Communications
ONLY).
NOTE: Communication signals between a µP-A or µP-A +
NOTE: The communications adapter MUST receive 12
controller and IRMU do NOT require amplification.
VDC power from either the controller or the power cable/
battery connector in older to operate the LEDs. LED 1. To make it easier to view the communications tester/
operation is required to monitor communications. amplifier LEDs, install the ribbon cable on the 15-pin
female serial port connector on the controller.
b. If the Unit On/Off switch is OFF or the unit has been 2. Then insert the communications tester/amplifier adapter
disconnect from a 3-phase power supply, connect the in one of the 15-pin female connectors on the ribbon
power cable/battery connector to a 12 Vdc power source. cable.
• If the microprocessor has an on-board backup battery,
insert the controller battery connector plug into the bat- NOTE: The communications tester/amplifier adapter may
tery socket on the (µP-A or (µP-A + controller. be plugged in while the controller is powered.
• If the on-board battery is not working or not installed,
connect a portable 12 Vdc battery to the battery pack
NOTE. The communications tester/amplifier adapter MUST
connector.
be installed in PARALLEL with a µP-A or µP-A+ controller
5. Connect the power cable/battery connector lead to the 12
and IRMU Otherwise, the communications tester/
Vdc power receptacle on the communications tester/
amplifier adapter may INTERFERE with the
amplifier adapter.
communications signals and cause a communications fault
6. Check to see that the communication tester’s PWR indi-
This is because the communication signals between a µP-A
cator is ON to verify 12 Vdc has been supplied to the
or µP-A + controller and IRMU do NOT require
communications tester/amplifier adapter.
amplification.
If the PWR indicator DOES NOT light, recheck the power
supply. Also check to be sure the power cable connectors are 3. Turn the Unit On/Off switch to ON and operate the unit
properly connected. to establish communications between the controller and
the IRMU.
NOTE: The PWR LED MUST light before attempting to
monitor communications with a µP-A or µP-A + controller.
10-20
Section 10-Container Service Bulletins
IRMU Remote
Monitor Box
4. Check to see that the communication tester’s PWR LED As the controller sends the IRMU a complete download of the
is ON to verify 12 Vdc has been supplied to the commu- data logger memory, the RED RXD LED should flicker, indi-
nications tester/amplifier adapter through the VREC cir- cating the controller is sending a RS232 signal to the IRMU.
cuit of controller (µP-A or µP-A + controllers ONLY).
6. If the RED RXD or GREEN TXD indicator does not
flicker, verify that the communications tester/amplifier
NOTE: The communications tester/amplifier adapter
assembly is working properly on another controller.
MUST receive 12 VDC power from the controller in order to
operate the LEDs. LED operation is required to monitor If the RXD or TXD LED does not flicker or stays on con-
communications. stantly, and you have verified that the communications tester/
amplifier assembly is good on another controller, the control-
5. Approximately 30 seconds after turning the Unit On/Off ler or IRMU is defective and should be replaced.
switch ON, the IRMU requests operating information
from the controller. The GREEN TXD LED should
flicker, indicating the IRMU is sending an RS232 signal
to the controller.
10-21
Section 10-Container Service Bulletins
Plug Power Cable/Battery Connector, Plug the Lead of the 12 Vdc Power Cable/Battery Connec-
PN 204-937, into Battery Receptacle on tor into the communications tester/amplifier adapter after
SRMU Data Pac Communications connecting power cable/battery connector to either the on-
Panel f the Unit has a working, on- board backup battery socket or a portable 12 Vdc battery.
board backup battery.
Connect Power Cable/Battery connector
Ribbon Cable, to portable 12 Vdc battery when on-
PN 204-936 board backup battery is NOT working or
NOT installed.
SRMU Remote Communications Tester/Amplifier
Monitor Box Adapter, PN 204-901, MUST be
Installed in PARALLEL with the SRMU
and Laptop Computer to monitor
communications signals.
Using the Communications Tester/Amplifier with 4. Connect the power cable/battery connector to a 12 Vdc
SRMU Remote Monitor Units to Monitor power source.
Communications • If the unit has an on-board backup battery, insert the con-
1. Install the ribbon cable on the 15-pin female serial port troller battery connector plug into the battery socket on
connector on the SRMU Data Pac communications 15- the SRMU Data Pac communications panel in the unit
pin female connector. control box.
• If the on-board battery is not working or not installed,
2. Connect the communications cable from a laptop com- connect a portable 12 Vdc battery to the battery pack
puter to one of the 15-pin female connectors on the rib- connector.
bon cable.
5. Connect the power cable/battery connector lead to the 12
3. Then insert the communications tester/amplifier in the Vdc power receptacle on the communications tester/
OTHER 15-pin female connector on the ribbon cable as amplifier adapter.
shown in Figure 7.
6. Check to see that the communication tester’s PWR indi-
NOTE: The communications tester/amplifier adapter may cator is ON to verify 12 Vdc has been supplied to the
be plugged in while the controller is powered. communications tester/amplifier adapter.
NOTE: The communications tester/amplifier adapter NOTE: The communications tester/amplifier adapter
MUST be installed in PARALLEL with a unit controller and MUST receive 12 VDC power from the power cable/Battery
laptop computer. Otherwise, The communications tester/ connector in order to operate the LEDs to monitor
amplifier adapter may INTERFERE with the communications. If the PWR indicator DOES NOT light,
communication signals and cause a communications fault. recheck the power supply. Also, check to be sure that the
This is because the communication signals between a laptop power cable connectors are properly connected.
computer and a SRMU do NOT require amplification.
10-22
Section 10-Container Service Bulletins
NOTE: The PWR LED MUST light before attempting to 8. If the RED RXD or GREEN TXD indicator does not
monitor communications. flicker, verify that the laptop computer and communica-
tions tester/amplifier assemblies are working properly on
7. Turn the laptop computer ON and initiate a data another controller.
exchange with the SRMU. The GREEN TXD LED
should flicker briefly, indicating that the laptop computer If the RXD or TXD LED does not flicker or stays on con-
is sending an RS232 signal to the SRMU. stantly, and you have verified that the communications tester/
amplifier assembly is good on another controller, the control-
If the data exchange requires a reply from the SRMU, the ler or SRMU is defective and should be replaced.
RED RXD LED should flicker, indicating that a reply mes-
sage (download) is being sent by the SRMU to the laptop
computer.
10-23
Section 10-Container Service Bulletins
SERVICE BULLETIN
• Communications Tester/Amplifier Adapter, PN 204-901 The Power Cable/Battery Connector provides 12 Vdc power
• Power Cable/Battery Connector, PN 204-938 from a portable battery pack or the on-board backup battery
through the receptacle located on the microprocessor control-
PURPOSE ler (if the unit is equipped with a data logger battery and bat-
tery charger) to the Communications Tester/Amplifier
• Amplify serial communication signals to download data
Adapter.
from a µP controller.
12 Vdc Power Receptacle
DESCRIPTION
Communications Tester/Amplifier Adapter
10-24
Section 10-Container Service Bulletins
• If the microprocessor has an on-board backup battery, NOTE: The PWR LED MUST light before attempting
insert the controller battery connector plug into the bat- communications with a µP controller
tery socket on the (µP controller. If the on-board battery
6. Initiate a data exchange with the controller. The GREEN
is not working or not installed, connect a portable 12 Vdc
TXD LED should flicker briefly, indicating the laptop
battery to the battery pack connectors.
computer is sending a signal to the controller.
Plug Power Cable/Battery Connector, PN
204-938, into Battery Receptacle on (µP
µP Controller
Controller if the Unit Has a Working, On-
Board Backup Battery
Connect Power Cable/Battery Con-
nector to Portable 12 Vdc Battery
when On-Board Backup battery Is
NOT Working or NOT Installed
Figure 3.
Using Communications
Tester/Amplifier with
µP Controllers
Laptop Computer and
Communications Cable
10-25
Section 10-Container Service Bulletins
If the data exchange requires a reply from the µP controller, NOTE: Communication signals between a (P-A or (P-A+
the RED RXD LED should flicker, indicating that a reply controller and a laptop computer do NOT require
message (download) is being sent by the controller to the lap- amplification.
top computer.
1. Install the laptop computer communications cable
7. If the GREEN TXD or RED RXD indicator does not directly into the 15-pin female serial port connector on
flicker, verify that the laptop computer and communica- the controller.
tions tester/amplifier assembly are working properly on
another µP controller. 2. If the on-board backup battery is not working or not
installed, connect the power cable/battery connector to a
If the RXD or TXD LED does not flicker or stayson con- portable 12 Vdc battery (see Figure 4). Then plug the
stantly, and you have verified that the communications tester/ power cable/battery connector into the battery socket on
amplifier assembly is good on another controller, the µP con- the µP-A or µP-A+ controller.
troller is defective and the power cable/battery connector into
the battery should be replaced.
µP-A or µP-A+ Controller Plug Power Cable/Battery Connector, PN 204-938, into Bat-
tery Receptacle on µP-A or µP-A+ Controller and Connect
the 12 vdc Battery Terminals to Portable 12 Vdc Battery if
On-Board Backup Battery Is NOT Working or NOT Installed
Communications Tester/Amplifier
Adapter Is NOT Used
10-26
Section 10-Container Service Bulletins
SERVICE BULLETIN
3. If the protection device repeatedly trips after testing 5. Isolate and check the resistance of each individual heater
heater element operation (step 2), test the insulation of element if the connections appear secure.
each individual heater element: a. Disconnect and isolate each heater. Check the resis-
tance of each heater with an insulation tester between
a. Turn unit power supply OFF. each heater and ground. If the resistance between each
heater and ground is 0.8 Meg ohms, replace the defective
b. Remove unit power plug from power supply recepta- heater.
cle.
NOTE: When replacing heaters or repairing heater
c. Open control box high voltage tray. connections, protect the new connections from the ingress
of moisture with heat Shrink tubing. All heaters should be
secured to prevent contact with sharp metal edges.
10-27
Section 10-Container Service Bulletins
SERVICE BULLETIN
The condenser coil on CF-II units should be cleaned every Where CF-II units are repeatedly subjected to excessive
1,000 hours to ensure proper refrigeration system perfor- amounts of salt water spray due to vessel design or unusually
mance and coil protection. heavy sea conditions, Thermo King recommends that the
1,000 hour cleaning interval be reduced to 500 hours.
Use low pressure compressed air or a medium pressure warm
water spray. Direct the air or water spray from the inside of If salt deposits have corroded the condenser coil to the point
the coil outward (opposite direction of normal airflow). where the header plates no longer properly secure the coil
tubes from structural movement, the coil must be replaced.
If a build up of salt is present on the condenser coil, Thermo
King recommends that the coil be cleaned using a mild alka-
line cleaner with a pH of 9.5 to 10.5; Follow any cleaning
solution application with a fresh water rinse.
10-28
Section 10-Container Service Bulletins
SERVICE BULLETIN
The Thermo King Warranty Department has recently received main bearing can have lateral (axial) movement during startup
several “good” X430 compressors that were changed out and shut down. However, the refrigerant pressure and crank-
because of suspicion that excessive crankshaft endplay was shaft torque forces prevent the main bearing from spinning
contributing to a shaft seal leak. The crankshaft endplay on radically during compressor operation.
these compressors was measured and found to be well within
normal limits. NOTE: Crank end play up to OX47 inch (12 mm) has NOT
been shown to be a factor in crankshaft seal leaks in testing
Compressor crankshaft endplay on a warm compressor can be conducted by THERMO KING.
as much as 0.047 inch (1.2 mm) as measured with a dial indi-
cator. As much as, 0.012 inch (0.03mm) of this endplay can Crankshaft endplay should NOT be considered to be factor in
be to the accumulated internal clearances in the crankshaft contributing in a shaft seal leak unless it is correctly measured
main bearings. The balance of this endplay is a result of the and found to be more than 0.047 inch (12 mm).
crankshaft main bearing outer races moving laterally in the
bores in the compressor body and oil pump housing. The following guidelines apply when measuring compressor
crankshaft endplay on X426 and X430 compressors:
This end play is necessary because of the different expansion/
contraction rates between aluminum and steel. Endplay pre- • A dial indicator gauge MUST be used.
vents the compressor from locking up at low ambient temper-
atures. Endplay increases with temperature. This means the • Dial indicator gauge must be securely damped or bolted
to the drive coupling housing or compressor body.
10-29
Section 10-Container Service Bulletins
Tools Required: 7. Repeat step 6 three times. Then average the three read-
• Wrench and Socket Set ings together obtain an accurate crankshaft endplay mea-
• Soft Hammer or Soft Punch surement.
• Small Pry Bars (2)
• Torque Wrench If total crankshaft end play measures 0.047 inch (1 2 mm) or
• Dial Indicator Gauge with Mounting Adapters less, the crankshaft and compressor bearings are considered to
be in good condition. Thermo King testing has determined
End Play Measurement Procedure that a crankshaft end play of 0.047 inch (1.2 mm) is NOT a
1. Close the receiver tank outlet valve and pump down the factor in crankshaft seal leaks.
low side to 10 inch Hg vacuum (-33.8 kPa).
8. Remove dial indicator from compressor drive housing/
2. Turn unit On/Off switch to Off. Then disconnect the unit seal plate or compressor body.
power cable from the main power source. Close (front
seat) the discharge service valve. Break the vacuum with
NOTE: If the drive housing/seal plate was removed from the
nitrogen between 1 and 3 psig (7 and 21 kPa).
compressor body, refer to Service Bulletin No. 493-1 for
detailed instructions on reassembly of crankshaft seal and
CAUTION: Any time the discharge valve is front seated,
drive housing/seal plate to compressor body. Be sure to
disconnect the unit power source to prevent accidental
observe the following guidelines.
compressor start-up.
• Clean the compressor shaft and housing thoroughly
3. Disconnect motor and slide away from compressor.
before reassembly.
NOTE: Disconnecting the 3-phase motor harness may not
• Use only lintless cloth when handling or cleaning the
be necessary. compressor shaft, housing or seal assembly.
4. Remove drive coupling from compressor shaft.
• Never touch the polished contact surfaces of the crank-
5. Install dial indicator gauge. shaft seal or the seal plate hard ring with your fingers.
• Clamp or bolt the dial indicator gauge to the Compressor • Carefully inspect the contact surfaces of the seal and hard
drive housing/seal plate if no additional service of the ring for any nicks, scratches or foreign material. Use a
compressor or compressor crankshaft seal is planned. lintless cloth and denatured alcohol to remove debris
from the seal or hard ring. Replace any seal or hard ring
• Remove the compressor drive housing/seal plate from the that has been damaged in any way.
compressor body if the compressor crankshaft seal
requires replacement. Then clamp or bolt the dial indica- • Always apply only CLEAN compressor oil to the hard
tor gauge to the drive end of the compressor body. ring and contact surface of the new seal before reassem-
bly of the seal and drive plate.
NOTE: For guidelines on how to determine when a
compressor crankshaft seal should be changed, see
Container Service Bulletin C-009.
6. Measure the crankshaft endplay.
10-30
Section 10-Container Service Bulletins
SERVICE BULLETIN
The supply (discharge) air sensor MUST be fully inserted into NOTE: During Inspection, a black mark should be placed
the sensor tube to achieve accurate supply air temperature on the sensor harness. On subsequent Pretrip Inspections,
control. This is especially important when carrying chilled the black mark will indicate that the sensor position in the
cargo. sensor tube has been checked and is correct.
Failure to fully insert the sensor into the sensor tube can lower Tools Required:
the supply air temperature. Testing has shown that inserting • Black permanent marker
the sensor 10 mm (0.4 in.) short of the sensor tube end can • Ruler
lower the supply air temperature up to 0.3 C (0.5 F); inserting
the sensor 30 mm (1.2 in.) short of the tube end can lower the Supply (Discharge) Air Sensor Position Inspection
supply air temperature up to 1.2C (2.1 F). Procedure
Because it has been reported that the supply air sensor on 1. Loosen and unscrew the supply air sensor retaining cap.
some units has been found NOT to be fully inserted in the
sensor tube, Thermo King recommends that the following 2. Remove the supply air sensor from the sensor tube.
inspection be performed on all CSR-40, CRR-40, TNE 508
and TNE 508 SC1 units during the routine Pretrip Inspection: 3. Measure and place a black mark on the sensor harness
170 mm (6.75 inches) from the end of the sensor bulb.
Mark Sensor Lead
Here with Permanent 4. Firmly slide the sensor back into the sensor tube until the
Black Marker sensor bulb reaches the end of the sensor tube.
10-31
Section 10-Container Service Bulletins
SERVICE BULLETIN
The PCV valve that regulates the crankcase pressure of the If a new unit has a crankcase pressure significantly over 3
se 2.2 engine can develop excessive pressure in the engine inches W.C. positive, or has blow out of its oil level switch,
crankcase if the atmospheric vent in the cover of the valve is check the atmospheric vent on the PCV cover for blockage.
plugged. A few new units have been found with the vent
plugged with the epoxy clear coat applied to the power pack
at the factory.
10-32
Section 10-Container Service Bulletins
SERVICE BULLETIN
NOTE: To use the Tester/Amplifier to monitor SRMU or IRMU communications, see µP-A+ columns above (monitoring IRMU communications requires that
the unit be operating on 460/380V or 230/220V power).
10-33
Section 10-Container Service Bulletins
SERVICE BULLETIN
CSR and CRR refrigeration system diagrams are attached to Warranty Claim Form Reporting
this bulletin. The diagrams show all current connections for
CSR and CRR units. Use these diagrams to identify and Thermo King continuously monitors the performance and
report all component and joint repair work. reliability of unit components. Therefore it is important to
include the component and joint code number(s) that appear
All O-ring seal and solder connections (except coils) have on the attached refrigeration system schematic on warranty
been labeled. When repairing O-ring seals, apply compressor claim forms when describing any repair work. Forms include:
oil to new seals. When repairing solder connections, use the
same solder that was used in the manufacturing process: • CSR refrigeration system diagram with component and
joint identification tables
• Copper to copper, use 15% Silver Solder, • CRR refrigeration system diagram with component and
PN 203-364 joint identification tables
• Copper to brass or steel, use 35% Silver Solder,
PN 203-366
Use flux, PN 203-365, with both 15% and 35% silver solder.
Other types of leaks such as punctures in tubes and leaks in
coils can best be repaired using 15% silver solder, PN 203-
364 (with flux, PN 203-365).
10-34
Section 10-Container Service Bulletins
589
8 S
205
159
65
B
177
203 87
AZ 21
6
155
119
9 C
5
D 19 Y
4 106
E
155
W 52
66 19
E 161
W
265
64 P
63 18
49
62
2
105 1 A
154
114 277
266 156 AG
116 61
AC
605
BC
36
593
37
247 G
27
K
25
X 28
1
59
60 AJA524
10-35
Section 10-Container Service Bulletins
Warranty Claim Form Reporting Use flux, PN 203-365, with both 15% and 35% silver solder.
Other types of leaks such as punctures in tubes and leaks in
Thermo King continuously monitors the performance and coils can best be repaired using 15% silver solder, PN 203-
reliability of unit components. Therefore it is important to use 364 (with flux, PN 203-365).
this diagram to identify and report all component and joint
repair work. It is also important to include the component and
NOTE. It is important that your service procedures use the
joint code number(s) on warranty claim forms when describ-
same solder that was used in the manufacturing process We
ing any repair work.
therefore strongly recommend that you obtain solder and
All O-ring seal and solder connections (except coils) have flux from Thermo King and that only the recommended
been labeled. When repairing O-ring seals, apply compressor solder and flux be used on specific connections.
oil to new seals. When repairing solder connections, use the
same solder that was used in the manufacturing process:
10-36
Section 10-Container Service Bulletins
S
S
117
589
AV
118
205
105
116
62
5 BC
C P
6 247
52
114 640
605
B
159
BJ
177
636 W
Y
9
4 A
8 591 49 2
65
64
203
D BL
634
63 635
271 266
277
66
265
28
14
R
637
AG 243 1
235
99
155
639
19 100
156
G
106 59 1
E
BK
18
300
154 60
236 638
61 633
237 607
37
AJA525
AC 239
K
599
262
X
36 25
10-37
Section 10-Container Service Bulletins
10-38
Section 10-Container Service Bulletins
SERVICE BULLETIN
• Test 1: Uses controller keys to activate display segments • Down load a data log file from the controller.
and mode LEDs to verify keypad and display operation.
Connect POWER IN
Connector to Unit Wire
Harness Connector
Removed from
Connector “A” on AJA526
Back of Controller
Figure 1. Connecting a Tester, P/N 204-911, to a µP-D Controller That Has Been Disconnected
from the Unit Wire Harnesses
10-39
Section 10-Container Service Bulletins
10-40
Section 10-Container Service Bulletins
10-41
Section 10-Container Service Bulletins
SERVICE BULLETIN
When servicing Thermo King refrigeration systems that con- When servicing Thermo King refrigeration systems that con-
tain R-12, R-22 or R-401B refrigerants, use only those service tain R-134a or R-404A refrigerants, use only those service
tools certified for and dedicated to HCFC and CFC refriger- tools certified for and dedicated to HFC refrigerants. The
ants. The same gauge manifold set or recovery equipment can same gauge manifold set or recovery equipment can be used
be used on each of these refrigerants because R-12, R-22 and on each of these refrigerants because R-134a and R-404A
R-401B contain similar chemical compounds and require the contain similar chemical compounds and require the use of
use of mineral oil or alkyl benzene compressor oil. polyolester compressor oil.
CAUTION: Residual HFC refrigerants or ester based oils CAUTION: Residual HCFC/CFC refrigerants, or mineral
will contaminate HCFC and CFC systems or alkyl benzene oils will contaminate HFC systems.
Service tools that should be dedicated to HCFC/CFC systems Service tools that should be dedicated to HFC systems
include: include:
• Gauge Manifold Set
• Refrigerant Recovery Equipment • Gauge Manifold Set
• Vacuum Pump • Refrigerant Recovery Equipment
• System Cleanup devices including service hoses, valves, • Vacuum Pump
suction line filters. • System Cleanup devices including service hoses, valves,
suction line filters.
Recovery
Machine AJA527
10-42
Section 10-Container Service Bulletins
SERVICE BULLETIN
• If air is NOT blowing out from the center of the grille, Emergency Bypass Switch Assembly
place the Phase Rotation switch in the OFF position.
10-43
Section 10-Container Service Bulletins
Allow the motors and fans to come to a COMPLETE stop. NOTE: If emergency bypass procedures are used under
Then place the Phase Rotation switch in the CBA position. high ambient and high container (load) temperature
Check condenser airflow again to confirm that air is blowing conditions, a compressor motor shutdown may occur
out from the center of the grille. (indicating the compressor motor internal overload
protector has tripped). Wait a few minutes to allow the
8. Use the Mode Switch to set unit operation for Evaporator
overload protector to cool.
Fan Only or Full Cool operation.
The unit is equipped with a suction modulation capacity con-
CAUTION: The unit does not control to setpoint during trol system to control system cooling capacity and limit com-
emergency bypass switch use The unit must be cycled pressor motor current draw. If the unit shuts down due to the
manually to maintain the desired temperature Monitor the overload protector tripping during emergency bypass proce-
container temperature using the controller display (if dure operation, restrict refrigerant flow to the compressor
using the receiver tank outlet valve. Manually close the valve
working) or an external thermometer
and then open the valve 1/4 turn. Restart the unit. Check com-
9. High pressure cutout (HPCO) and 24 Vac LEDs on the pressor motor current draw. The motor should draw 14 to 15
Emergency Bypass Module turn ON to indicate normal amps. Adjust the receiver tank outlet valve slightly if neces-
operation. sary to raise or lower current draw to 14 to 15 amps.
• HPCO LED is ON when the HPCO switch is closed (nor-
mal). If the HPCO switch opens (high discharge pres-
sure), the LED will turn OFF.
• 24 VAC LED is ON when 24 volt ac control power is
supplied to the Emergency Bypass Switch.
10-44
Section 10-Container Service Bulletins
SERVICE BULLETIN
10-45
Section 10-Container Service Bulletins
SERVICE BULLETIN
10-46
Section 10-Container Service Bulletins
2. If the engine fails to start, press the ALARM key on 3. 3. To attempt another unit start-up, turn the On-Off switch
the controller keypad to view all alarm codes. Place the ON. Then clear all Alarm codes from the controller dis-
On-Off switch in the OFF position. Then determine and play to repeat starting procedure. To clear alarm codes:
correct the cause for not starting. • Press the DOWN key until all alarm codes have been
viewed and written down.
Alarm Codes: • When the last alarm code (ALM 1) appears in the con-
troller display, the display alternately flashes “ENTER”.
06 Water Temperature Sensor Failure • Press the ENTER key to clear all alarm codes from the
07 Engine RPM Sensor current display memory. The display briefly shows
15 Preheat Circuit Check “ALARM CLR”.
16 Digital Input Failure
17 Engine Failed to Crank NOTE: Clear the Alarm codes ONLY after the alarm codes
18 High Engine Water Temperature are documented and problems repaired Clearing the codes
erases them from the controller Alarm display memory.
19 Low Engine Oil Pressure
20 Engine Failed to Start NOTE: If the ENTER key is not pressed within 10 seconds,
25 Low Output Volts the controller will default (return) to the Standard Display.
31 Oil Pressure Sensor
Additional operating information about the µP-G controller
35 Run Relay Circuit
can be found in Container Bulletin C-014, µP-G Controller
37 Coolant Level Alarm Unit Operating Information for Generator Sets”.
41 Engine Water Temperature Check
43 Frequency Out of Range - Low
44 Fuel System Check
45 Frequency Out of Range - High
46 Check Air Filter
51 Alternator Overload Alarm
61 Low Battery Alarm, Low Battery Alarm during Crank,
or High Battery Alarm
63 Engine Stopped - Reason Unknown
66 Low Engine Oil Level
69 Field Relay (Exciter) Circuit Check
70 Any Hourmeter or Counter Exceeds Limits
71 Hourmeter 1 Exceeds Threshold
72 Hourmeter 2 Exceeds Threshold
74 Control Reverted to Default Settings
88 Microprocessor Internal Error
99 Restart Null
10-47
Section 10-Container Service Bulletins
SERVICE BULLETIN
AJA531
Sea-Land CSR Refrigerant Piping and Expansion Valve
10-48
Section 10-Container Service Bulletins
SERVICE BULLETIN
SUBJECT: New Dehydrator, P/N 66-9015, for ALL CF-II Series Units
BULLETIN NO. C 028
DATE: August 21,1998
A new dehydrator, P/N 66-9015, is now available for use on all CF-II refrigeration systems. The new dehydrator features a black,
double coat paint finish to improve corrosion resistance in marine applications.
Dehydrator 66-9015 replaces dehydrator 66-508. All Container Dealers should begin stocking this new dehydrator immediately.
10-49
Section 10-Container Service Bulletins
SERVICE BULLETIN
With thousands of CSR and CRR Smart Reefer(r) units now CSR units use advanced scroll compressor technology with
in service throughout the world, service technicians must R-404A refrigerant. With just 4 moving parts, scroll technol-
remember that CSR units have different service guidelines ogy maximizes pumping efficiency. Furthermore, radial and
and refrigeration system service procedures than CRR units. axial compliance combine with the centrifugal force of scroll
technology so scroll members maintain continuous contact to
CRR units use the Copeland 3DS reciprocating compressor actually “wear- in” rather than wear out. Consequently, per-
with R-134a refrigerant. Most technicians have years of expe- forming a compressor capacity and pump down test is not
rience with this package and probably received their basic necessary on a scroll compressor, and in fact may actually
refrigeration system service training on a unit using semi-her- damage the internal scroll set. Also, scroll compressors are
metic, reciprocating compressor technology. Technicians hermetically sealed, eliminating frequent replacement of the
learned that the pumping efficiency of the pistons and dis- dehydrator.
charge valves in the compressor could be periodically
checked using a compressor capacity (efficiency) and pump When dehydrator replacement is necessary, do NOT pump the
down test. Also, replacement of the dehydrator on systems system down below 0 psig (0 kPa, 0 bar).
with semi-hermetic reciprocating compressors allows the sys-
tem to be “pumped down” to 10” to 15” Hg vacuum (-35 to Refer to the charts below for more detailed information about
-50 kPa, -0.35 to -0.50 bar). the differences in service guidelines and repair procedures
between CSR and CRR Smart Reefer(r) units.
Procedure
CSR Unit CRR Unit Item or Repair/Service
Scroll Compressor Reciprocating Compressor Compressor Type
Reclaim Refrigerant Reclaim Refrigerant Open the high side of the refrigeration system.
Reclaim Refrigerant Low Side Pump Down Open the low side of the refrigeration system.
10-50
Section 10-Container Service Bulletins
SERVICE BULLETIN
This condition can be corrected by installing a new (shorter) 2. Remove the timing bolt from the end of the
the timing bolt. The timing bolt is located at the back of the injection pump. The timing bolt is located between the injec-
pump between the injection lines. The shorter bolt increases tion lines.
the volume in the plunger chamber, thereby reducing the fuel
pressure. 3. Install new BLACK timing bolt and COPPER lock
washer in injection pump. Tighten timing bolt to 17 ft-lb
This rework affects Generator Set units manufactured (23 N•m).
between 3/1/98 and 9/1/98. Units built after 9/1/98 have been
reworked at the factory. Check for a BLACK timing bolt and 4. Reconnect battery cables and start the unit.
COPPER washer to identify fuel pumps that has been modi-
fied to correct the fuel shutdown problem. 5. Check the engine speed setting. Loosen the jam nut on
the speed adjustment screw and set engine speed:
Tools Required: • 1800 +/- 10 rpm at Full Load (Alternator Output)
- Wrench and Socket Set • 1950 +/- 10 rpm at No Load
- New Timing Bolt and Copper Washer
10-51
Section 10-Container Service Bulletins
SERVICE BULLETIN
10-52
Section 10-Container Service Bulletins
Coil Support
Brackets (2)
AJA533
Unit Front 11 in. (279.4 mm) 1.5 in. (38.1 mm)
10-53
Section 10-Container Service Bulletins
SERVICE BULLETIN
It has been reported that some CRR units have been found 1
with an under-torqued suction flange connection. Units that
have been found with an undertorqued flange on the suction
side all have "291K" in the middle of the serial number:
"xxx29Kxxx". Thermo King recommends that the suction 2
flange bolts be checked and torqued during a Pretrip Inspec-
tion.
Mark or paint the suction flange bolts to indicate that the bolts have
been checked and torqued.
AJA583
10-54
Section 10-Container Service Bulletins
SERVICE BULLETIN
The following guidelines apply when adjusting the Adjusting Fan/Water Pump Belt Tension on Units
belt tension on Thermo King Gensets: with Sliding Pulley on Fan or Crankshaft Pulley
1. Remove bolts from adjustable pulley:
• All belt tensions should be checked using belt tension
gauge P/N 204-427. • Units with sliding pulley on crankshaft, remove bolts
from the crankshaft pulley.
• Belt tension should be checked when the belt is cold.
Fan Pulley
• To minimize time spent installing and removing shims on
adjustable pulleys, install the new belt using all the shims
Check Tension
provided with the unit (including any extra shims located
Here with Belt
on the outer face of the pulley). Check belt tension. If Gauge or Allow
necessary, remove shims to achieve correct tension. Place 0.75 to 1.0 inch
extra shims on outer face of the pulley. (19 to 25 mm)
Deflection
NOTE. When adjusting the belt tension using shims and
adjustable pulleys, the belt may still feet loose when the belt
Crankshaft Pulley AJA534
tension gauge indicates the correct tension. Allow 0.75 to
1.0 inch deflection with 6 to 9 lb (3 to 4 kg) of force. Fan/Water Pump Belt with Sliding Pulley on Fan or
• Do not attempt to remove or install belts without loosen- Crankshaft Pulley
ing adjustments. Belts that are installed by prying over
pulleys will fail prematurely due to internal cord damage.
Fan/Water Pump Belt Tension Adjustment Information
Belt Tension* Belt Deflection
Belt Adjustment Unit Date of Belt Stationary Sliding Shims
New or 6 - 9 lb (3 -4 kg)
Method Manufacture P/N Pulley P/N Pulley P/N P/N (Qty)
Field Reset of Force
Crankshaft Pulley After 2/96 78-1011 15 to 35 0.75 to 1.0 inch 77-2390 77-2385 77-2386 (6)
(19 to 25 mm) 77-2387 (1)
Crankshaft Pulley Before 2/96 78-943 15 to 35 0.75 to 1.0 inch 77-2260 77-263 77-2261 (6)
(19 to 25 mm) 77-2262 (1)
Fan Pulley -- 78-943 15 to 35 0.75 to 1.0 inch 77-2225 77-1187 77-1285 (5)
(19 to 25 mm) 77-2164 (1)
Idler Pulley -- 78-429 15 to 35 0.75 to 1.0 inch -- -- --
(19 to 25 mm)
10-55
Section 10-Container Service Bulletins
10-56
Section 10-Container Service Bulletins
SERVICE BULLETIN
NOTE. Documents on the EXTRANET are stored in a ".pdf" file format You must have Acrobat Reader Installed on your computer to
open and view these documents Acrobat Reader is required whether you view and print documents online, or download Me documents for
viewing and printing.
Additional regions of information on the Thermo King web site include:
• DEALERS: This region allows visitors to simply point and click on a geographical location for a directory of dealer addresses,
telephone numbers and hours of operation.
• PRODUCTS: This region details the features of Thermo King Truck, Trailer, Sea-going Container and Bus Transport Refrig-
eration units including heating and cooing capacity, as well as power consumption.
• FEATURES: This region select stories from Thermo King customer newsletters.
• ABOUT US: This region details the company history, manufacturing plant and parts warehouse locations and recent news
releases.
• CONTACT US: Use this region to
request product information from the
Thermo King Webmaster.
• CAREER OPPORTUNITIES: This
region fists Thermo King employment
opportunities.
Go to "wwwThermoking.corri". The
Thermo King home page will appear.
Click on "EXTRANET".
AJA537
10-57
Section 10-Container Service Bulletins
AJA538
AJA539
10-58
Section 10-Container Service Bulletins
AJA540
AJA541
10-59
Section 10-Container Service Bulletins
Go to "www.thermoking.com" again.
The Thermo King home page will appear.
Click on "EXTRANET".
AJA542
AJA543
10-60
Section 10-Container Service Bulletins
10-61
Section 10-Container Service Bulletins
Go to “www.thermoking.com”. The
Thermo King home page will appear.
2. Click on "EXTRANET".
AJA542
AJA543
10-62
Section 10-Container Service Bulletins
AJA557
10-63
Section 10-Container Service Bulletins
• Downloading a File:
AJA559
AJA562
10-64
Section 10-Container Service Bulletins
AJA563
10-65
Section 10-Container Service Bulletins
AJA564
AJA565
10-66
Section 10-Container Service Bulletins
SERVICE BULLETIN
PCPAC V3.2
Sensor names for supply and return
air sensors and setpoint can not be
changed.
Version 3.3 of PC-PAC software is fully
compatible with (and will handle all data
files produced by) previous versions of
PC-PAC. It is fully compatible with the NOTE. The PC-PAC V3.3 download
following Thermo King container micro- patch will NOT update PC-PAC V2.0 or
processor controllers and data logging
systems:
earlier. You must have PC-PAC V3.2
• µP-D Microprocessor Controllers installed on your computer to upgrade
• µP-A Microprocessor Controllers to PC-PAC V3.3.
• µP-A Microprocessor Controllers
• µP, Microprocessor Controllers
• SRMU Data Logging System
10-67
Section 10-Container Service Bulletins
Go to "www.thermoking.com" The
Thermo King home page will appear.
Click on "EXTRANET".
AJA537
AJA538
10-68
Section 10-Container Service Bulletins
AJA566
AJA567
10-69
Section 10-Container Service Bulletins
AJA568
AJA569
10-70
Section 10-Container Service Bulletins
AJA567
AJA568
10-71
Section 10-Container Service Bulletins
AJA570
AJA566
AJA565
10-72
Section 10-Container Service Bulletins
SERVICE BULLETIN
10-73
Section 10-Container Service Bulletins
d. Remove the controller and gasket from the door. Place the Setting the following information is optional:
old controller in the anti-static bag. • Compressor and On Time Hourmeters
e. Install the replacement controller and gasket in the door NOTE: See the Controller chapter of the unit maintenance
using the existing hardware. manual for instructions on: Menu Guard Functions to set
the Unit and Customer Configuration Numbers, Sensors
CAUTION. Do NOT over tighten the mounting hardware or Grades, Time and Date, Container Identification Number,
the controller may be damaged. Unit Serial Number, Compressor Hourmeter and On Time
f. Attach the wire harness connectors to the back of the con- Hourmeter
troller.
Step 4: Perform a Unit Pretrip Test
Perform a Pretrip Test to verify correct unit operation.
NOTE. Be certain that all connectors are fully seated until
the connector rings lock.
g. Plug the unit power cord into the proper power supply.
h. Turn the unit On/Off switch ON. The unit should start and
the Standard Display should appear on the controller.
10-74
Section 10-Container Service Bulletins
SERVICE BULLETIN
A replacement controller contains the most current software missing from the unit control box, refer to unit model list
version and default settings that allow it to function when below to obtain the correct unit configuration and customer
installed in a unit. However, CORRECT unit operation configuration settings.
REQUIRES that the Unit Configuration, Customer Configu- NOTE. See the Controller chapter of the unit maintenance
ration and programmable Sensor Grades be set to the UNIT manual for instructions on µP-D controller replacement.
specific features and sensors. If this information can not be
recovered from the previous controller and the Controller
Setup Decal is missing from the unit control box. Refer to
CF-II Units with µP-D Controller CRR Units with µP-D Controller
Unit Unit Customer
Model Configuration Configuration Unit Unit Customer
CF-II M37.8 5004 1 Model Configuration Configuration
CF-II M48.1 5008 1 CRR40-52 5015 10
CF-II M49 5008 7 CRR40-54 5013 9
CRR20-64 5013 9
CSR Units with µP-D Controller CRR20-794 5014 3
CRR40-100 5014 5
Unit Unit Customer CRR40-101 5014 3
Model Configuration Configuration CRR40-102 5009 6
CSR40-4 5009 5 CRR40-103 5013 9
CSR40-42 5009 8 CRR40SL-104 5014 2
CSR40-46 5010 7 CRR40-106 5014 2
CSR40-47 5010 7 CRR40-107 5014 8
CSR40-57 5009 4 CRR40-110 5013 9
CSR40-66 5010 7 CRR40-111 5013 9
CSR40-67 5010 4 CRR40-112 5014 8
CSR40-100 5011 7 CRR40-113 5014 14
CSR40-101 5010 7 CRR40-114 5014 4
CSR40-102 5009 6 CRR40-121 5014 5
CSR40-103 5013 9 CRR40-123 5014 14
CSR40-104 5010 2 CRR40-124 5014 2
CSR40-109 5009 7 CRR20SL-125 5014 3
CSR40-110 5009 6 CRR40-126 5014 3
CSR40SL-111 5017 9 CRR40-128 5014 1
CSR40-112 5009 10 CRR-40-133 5013 9
(Continued on next page)
(Continued on next page)
10-75
Section 10-Container Service Bulletins
CSR Units with µP-D Controller (Continued) CRR Units with µP-D Controller (Continued)
10-76
Section 10-Container Service Bulletins
SERVICE BULLETIN
CSR Hermetic units do not have service valves, fittings or To Check dT on Units with MP-3000 Controller:
sight glasses installed in the refrigeration system. Therefore, a a. Press F4 key to directly enter the Data menu. Read:
controller Pretrip Test is used to determine that a CSR Her- • Supply Air Temperature, Right Hand
metic refrigeration system contains an adequate charge of • Return Air Temperature
refrigerant for cooling. If the unit passes the Pretrip Test, the b. Subtract the supply air temperature (right hand) from the
refrigerant charge is generally OK. However, unit cooling return air temperature to determine dT.
performance may not be affected by a marginally low refrig-
erant charge (1 to 3 lbs [0.5 to 1.4 kg] low) under all ambient NO TE: Press the “5” key to lock a Data screen in the LCD
operating conditions. To accurately determine the cooling per- display for 5 minutes. Press any key to unlock the display.
formance and refrigerant charge level, operate the unit on Full
Cool for 15 minutes or more: NOTE. Controller returns to previous menu level or
1. Adjust setpoint well below the ambient temperature to Standard Display after 30 seconds.
force unit to Full Cool. The Modulation Cool and Power
Limit functions must be OFF. To Check dT on Units with P-D Controller:
2. After 15 minutes, check the temperature difference (dT) a. Press the SELECT key to enter controller menu (display
across the evaporator coil. shows “MENU < --- >”).
3. Compare the unit dT to the expected values in table b. Press DOWN key until display shows “MENU VIEW”.
below. If dT is less than the value in the “possible low c. Press the SELECT key to enter VIEW submenu (display
refrigerant charge” column, visually inspect the unit for shows “VIEW < --- >”).
signs of a frosted or iced evaporator coil, low side d. Press the DOWN key to view “TD” value (e.g.”TD -03.7
obstruction in the refrigeration system, plugged expan- C”) in display.
sion valve, or a loose or defective expansion valve feeler
bulb before concluding the unit is low on refrigerant. NO TE: To lock the current Hew Menu screen in the
controller display press the ENTER key. A colon flashes in
NOTE: A negative (-) dT indicates the unit is cooling. A the left display to indicate the screen is locked (the screen
positive (+) dT indicates the unit is heating. remains locked for 15 minutes). Press any key to unlock the
display
NOTE. Inspect the unit for refrigerant leaks with a reliable
leak detector If the unit is suspected of being low on R404A NO TE: The controller returns to the Standard Display from
charge. a View Menu screen after about 10 seconds.
10-77
Section 10-Container Service Bulletins
Table 1: Unit Health Check Table- Determining Possible Low R-404A Charge
10-78
Section 10-Container Service Bulletins
SERVICE BULLETIN
10-79
Section 10-Container Service Bulletins
10-80
Section 10-Container Service Bulletins
Set the µP-D COntroller’s Unit 6. If the Unit or Customer Configuration setting
COnfiguration, Customer Configuration, viewed in step 3 was incorrect, enter the
Container ID Number, Unit Serial Number, Configuration submenu (CNFIG <-->”). Then
Date and Time enter the correct Unit Configuration (“CFG U”)
Customer Configuration (“CFG C”) numbers.
1. Install the controller (or printed circuit board) in
the unit. NOTE: The Unit COnfiguration MUST always be
set first. Check the Setup Decal in the control box
2. Turn the Unit On/Off switch ON.
for the correct configuration numbers.
3. Verify the controller software version and
7. Return to the GUARD submenu and scroll until
configuration settings by pressing and holding
the display shows “CID11 XX”. ENter the
the ENTER key for 3 seconds. COmpare the
correct Container ID Number.
information that appears in the controller
display with the Setup decal located in the 8. From the GUARD submenu, scroll until the
control box. display shows “USN11 XXX”. ENter the
correct Unit Serial Number.
NOTE: If a Setup decal is not available, see
Container Service Bulletin C-010-4 or above (or 9. Return to the GUARD submenu and scroll until
consult a Thermo King factory representative) to the display shows “YEAR 1996”. Enter the
determine the correct software version and correct Year, Month, Hour and Minute.
configuration number for the unit.
NOTE: Setting the Compressor, On Time and
4. Enter the GUARD submenu (access is code User Hourmeters is optional when a new
“0007” or “0013”). controller or new software has been installed.
However, the Sensor Grades MUST be set. FOr
5. Press the DOWN or UP key to scroll through
detailed instructions, see “Setting the Sensor
the menu list to the desired submenu.
Grades” in the Controller chapter of the unit
maintenance manual.
10-81
Section 10-Container Service Bulletins
SERVICE BULLETIN
This is to remind all personnel that they Must Manual Emergency Mode Operation
Always disconnect the unit power cord from the
In the event of an emergency situation where a
power supply before attempting to disconnect or
failure of the controller occurs, a manual
replace a MP-3000 controller.
emergency mode function can be used to operate
WARNING: The unit will automatically start and
the unit. However, the unit must be manually
operate if 460/380V power is present at the main
cycled ON and OFF using the unit460/380V main
relay board and Cable No. 2 is disconnected from
circuit breaker. This is because manual control
the controller. TO prevent personal injury from
disconnects both the controller and Unit On/Off
rotating machinery or dangerous electrical shock
switch from the main relay board.
from high voltage controls, disconnect the supply
power to the unit. Then proceed to replace the NOTE: On CSR units, both the 460/380V main
controller or prepare the unit for manual circuit breaker and the Unit On/Off switch must
emergency mode operation. be used to cycle the unit ON and OFF. The unit
On/Off switch must be ON to operate the scroll
Remote
compressor.
Monitoring MP-3000
Modem
Manual control offers a selection of six operating
Controller
positions. Refer tot he Manual COntrol decal in the
unit control box or the unit Maintenance Manual to
set the J501 Jumper for the desired unit operating
mode.
NOTE: CRR units and CSR units use different
J501 Jumper positions to provide cooling on
emergency mode operation.
Cable No. 2
The unit must by cycled ON and OFF manually to
maintain the desired temperature. Use the 460/
380V main circuit breaker to start and stop the unit.
Monitor container temperature with an external
thermometer.
NOTE: The unit cooling capacity on Chill loads
can be reduced by almost closing the suction
service valve when Cool 1 is selected. If the
MP-3000 Controller compressor overheats, select Cool 2.
10-82
Section 10-Container Service Bulletins
10-83
Section 10-Container Service Bulletins
10-84
Section 10-Container Service Bulletins
SERVICE BULLETIN
10-85
Section 10-Container Service Bulletins
Replacing an Old Style Compressor NOTE: All visible grease residue should be
Power Cord removed.
When replacing an old style compressor power 8. Install the new sealing gasket (orange) on the
cord with a new style cord, follow this procedure: compressor receptacle.
1. Make sure the unit On/Off switch is OFF. 9. Cut open a corner of the grease packet.
Liberally coat the inner and outer surfaces of
2. Make sure the 460/230V unit power cord has the gasket with grease. Also coat the boot
been disconnected from the power supply. surfaces and terminal spades with grease.
WARNING: To prevent against personal injury
from dangerous electrical shock from high 10. place a small amount of grease in the connector
voltage controls, disconnect the supply power to terminal holes of the power cord.
the unit before working on the compressor power 11. Lightly push the power cord connector onto the
cord. terminal spades and into the gasket. then slide
3. Remove the terminal box cover. the connector into the terminal box slot.
4. Remove the ground screw and disconnect the 12. Connect the ground wire using the new screw
ground wire. Then unplug power plug from the and washer.
compressor receptacle. 13. Lightly coat the gasket on their terminal box
5. Remove the old sealing gasket (orange) and cover with grease.
discard. If a foam rubber gasket is present 14. Install the terminal box cover.
between the sealing gasket and the compressor
body, it must also be removed and discarded.
6. Wipe the old grease from compressor’s
electrical connections with a dry rag.
7. Wipe down the electrical connections again
using a rag and common cleaning solvent. Any
common solvent such as paint thinner, lacquer
thinner or mineral spirits is sufficient.
10-86
Section 10-Container Service Bulletins
SERVICE BULLETIN
This bulleting concerns the correct setting of the Setting Version 0200 Software for Use with
new “Engine Selection” screen in all units equipped an Isuzu or Yanmar Engine
µP-G controllers and EPROM chips with version NOTE: Version 0100 software does not contain
“0200” software.
the Engine Select screen and therefore should be
NOTE: The µP-G controller and EPROM chip only be used on a unit equipped with a di 2.2 or se
are sold separately by Service Parts. 2.2 (Isuzu) engine.
EPROM chip PN 40-751 (now available from 1. Make sure the unit On/Off switch is ON and the
Service Parts) is factory programmed with version LCD display shows the standard display
“0200” software. This software is factory set (voltage output).
(Engine Selection screen shows “YAnEN/YES”) to
2. Press SELECT key to access the Guard menu.
control Gensets equipped with a TK 486 (Yanmar)
engine. The Engine Selection screen MUST be set 3. Enter the current access code “0007” to access
to “YAnEN/No” when EPROM Chip No. 40-751 is the Guard menu.
installed on a Genset wit a di 2.2 or se 2.2 (Isuzu)
4. Enter the current access code “0007” to access
engine.
the Guard menu. The display will show
“GUArd/---”.
Viewing the Software Version
5. Press the DOWN key until the display shows
The software version is stored in the controller
“YAnEN/YES” (where “YES” means the
memory. To check the software version:
feature is set for a TK 486 (Yanmar) engine).
1. Make sure the unit On/Off switch is ON and the
LCD display shows the standard display
(voltage output).
2. Press the ENTER key for 3 seconds. The
display shows the software version (“0100/rEv”
or “0200/rEv”) for 3 seconds.
10-87
Section 10-Container Service Bulletins
6. Press the SELECT key to enter the load Engine 6. Press the SELECT key to enter the load
Select display. Bottom display flashes “YES”. Voltmeter Calibration display. Bottom display
flashes “CAL”
7. Press the UP or DOWN key to choose the
desired engine setting: 7. Press the UP or DOWN key to adjust the top
display reading to the average voltage reading
• nO=di 2.2 or se 2.2 (Isuzu) engine determined in Step 1.
• YES=TK 486 (Yanmar) engine 8. When the correct voltage reading shows in the
8. When the desired engine setting shows in the top display, press the ENTER key. The display
bottom display, press the ENTER key. The flashes “LOAd” and then shows “XXX/CAL”
display flashes “LOAd” and then shows (where “XXX” is the new voltage reading).
“YAnEN/XXX” (where “XXX” is the new
setting).
Voltmeter Calibration
The Voltmeter Calibration feature calibrates the
controller to the alternator output. The controller
voltmeter should be calibrated whenever a new
controller is installed in the unit or when the
controller is suspected of displaying inaccurate
readings.
NOTE: Version 0100 software does not contain
the Voltmeter Calibration screen.
10-88
Section 10-Container Service Bulletins
10-89
Section 10-Container Service Bulletins
SERVICE BULLETIN
Thermo King Corporation will phase in extended the EMI 3000 package do require regular
Maintenance Interval (EMI 3000) packages on new inspection in accordance with Thermo King pretrip
Gensets during the first quarter of 2001. Because inspection and maintenance recommendations.
maintenance intervals have an important impact on CAUTION: With both EMI 3000 and standard
unit operating costs, introduction of the EMI 3000 (non-EMI 3000) units operating in the field, there
package will result in lower total unit life cycle are several important rules to remember:
cost. The genset EMI 3000 package will be
• Extended Life Coolant (ELC) is RED in color
implemented on units with serial number
while conventional coolant is GREEN or
02136H8528 and later. The package includes:
BLUE-GREEN.
• New 5 year or 12,000 Hour Extended Life
• Do NOT add “RED” coolant to cooling systems
Coolant (ELC)
using “GREEN” or “BLUE-GREEN” coolant.
• New EMI 3000 Water Pump, P/N 11-9442
• Do NOT add “GREEN” or “BLUE-GREEN”
(includes HNBR elastomer seals and EPDM
coolant to cooling systems using “RED”
O-rings)
coolant.
• New EMI 3000 Dual Element Oil Filter, P/
• The EMI 3000 oil filter is NOT interchangeable
N 11-9182 (identified by black and gold
with previous oil filters.
colors)
• New EMI 3000 Dual Element Oil Filter EMI 3000 Components
Head, P/N 11-9354
Extended Life Coolant and EMI 3000 Water Pump
• New EMI 3000 API Rating CG-4 Mineral
A decal tag on the coolant expansion tank will
Oil
identify units with extended life coolant (ELC).
• New EMI 3000 Fuel Filter, p/N 11-9342 ELC extends the coolant change interval up to
(identified by black and gold colors) 12,000 hours or 5 years.
EMI 3000 equipped units are identified by a ELC requires a water pump with HNBR elastomer
“Texaco ELC” decal tag on the coolant expansion seal bellows and EPDM elastomer O-rings.
tank, and gold and black colored oil and fuel filters. therefore ELC should not be used on older units
The EMI 3000 package allows standard genset with standard water pumps. All Yanmar (TK 486)
maintenance intervals to be extended to 3000 engines with serial number L16553 and after
hours. However, please note that units equipped include a new EMI 3000 water pump for use with
with extended life coolant.
10-90
Section 10-Container Service Bulletins
10-91
Section 10-Container Service Bulletins
10-92
Section 10-Container Service Bulletins
5. Continue to flush and refill the entire cooling Converting a Storage Tank to Extended Life
system with HOT water until all traces of Coolant
previous coolant dye are gone and the discharge
Thermo King recommends that coolant storage
fluid (water) is clear.
tanks be thoroughly cleaned before using them to
6. Fill the cooling system with appropriate coolant hold extended life coolant. Use hot water as a
mixture. flushing agent. Any silicate get or deposits on the
NOTE: Thermo King recommends the use of 50/ bottom of the tank or associated piping must be
50% pre-mixed extended life coolant to assure physically removed with methods such as steam,
that de-ionized water is being used. 100% scraping or sand blasting. Flushing with hot water
concentrate extended life coolant must be mixed should continue until any traces of dye from
(50/50) with de-ionized or distilled water (NOT tap previous conventional coolants are gone, and the
water) to ensure cooling system integrity. discharge water is clear. Tanks and piping should be
inspected to assure they clean and dry. The storage
Retrofitting a Unit for Extended Life facility is then ready to be filled with Extended Life
Coolant Coolant (ELC), which is silicate free and can be
stored up to five years.
To retrofit a genset manufactured before serial
number 02136H8528 to extended life coolant. The use of soaps, commercial cleaners, solvents or
flushing agents to clean storage tanks or equipment
• Retrofit the water pump assembly on TK 486 cooling systems is NOT recommended. Cleaning
engines with serial number before L16553 to agents are corrosive by nature. Failure to remove
ELC compatible water pump P/N 11-9442 all of the agent will contaminate the coolant stored
• Thoroughly flush unit cooling system and in the tank. Coolant contaminated with a cleaning
convert to extended life coolant. See “Changing agent will likely cause corrosion in the cooling
a Unit to Extended Life Coolant” instructions system of a unit.
above.
10-93
Section 10-Container Service Bulletins
10-94
Section 11
Gen-Set
Configurations
Section 11-Gen-Set Configurations
THERMO KING
GENERATOR SETS
11-2
Section 12
Gen-Set
Control Systems
Section 12-Gen-Set Control Systems
‘CURRENT’ PRODUCTION
CONTROL SYSTEMS
AJA235
AJA572
‘PAST’ PRODUCTION
CONTROL SYSTEMS
Most CG-II / Early CG Series
AJA573
12-2
Section 12-Gen-Set Control Systems
µP-G CONTROLLER
Controller Features
AJA265
µP-G CONTROLLER
Controller Features
1. LCD display
2. Alarm Indicator Functions
3. Programming Keypad
AJA265
12-3
Section 12-Gen-Set Control Systems
µP-G CONTROLLER
Controller Features
1
2
3 1. LCD Fields
4 2. Alarm Icon
5 3. Select Key
6 4. Up Arrow Key
5. Down Arrow Key
7
6. Enter Key
7. Alarm Key
8 8. Unit On/Off Switch
9. Alarm Indicator Light
9 10. Unit On Indicator Light
AJA265
10
µP-G CONTROLLER
Controller Operation THERMOGUARD µP-G
THERMOGUARD µP-G
12-4
Section 12-Gen-Set Control Systems
STANDARD CONTROLLER
Features -- Controls & Instrumentation
1
4
1. Hourmeter
2 2. Ammeter
3. On/Off Switch
5
4. Engine Shutdown LED
3 5. Unit ON Indicator Light
6 6. Preheat-Start Switch
AJA235
1
2
1. Oil Pressure Gauge
2. Engine Coolant Gauge
AJA236
Standard (Original
Electro/Mechanical Style)
Control System
12-5
Section 12-Gen-Set Control Systems
TEST INSTRUMENTS
• AC-DC Voltmeter
• Ohmmeter
• Megohmmeter (Megger)
• Preliminary Checks
-- Engine Problems
-- Battery Conditions
-- Plug Connections
• Fault Categories
12-6
Section 12-Gen-Set Control Systems
‘THE TESTS’
• Test 1 - Determines Fault Area
-- Alternator or Excitation
LEAD
LEAD
Exciter
Main Rotor
Field
OHM
METER
F-1 Exciter F-2
Field
AJA575
12-7
Section 12-Gen-Set Control Systems
OHM
METER
F1 F2
Exciter
Field
Checking Main Field Winding
Main
• Rotation Field Field Exciter
Rotor
12-8
Section 13
µP-G ‘Smart’
Gen Set Controller
Section 13-µP-G ‘Smart” Gen Set Controller
µP-G Microprocessor Controller • Provides engine shutdown protection after unit shutdown
due to low engine oil pressure, low engine oil level, low
Description battery, low fuel, or run relay circuit failure.
The µP-G controller is a one-piece, self contained micropro-
cessor for diesel generator sets. This system automatically The Microprocessor contains the following basic features:
starts the generator set provides:
1. Two digital displays on front panel:
Automatic pre-trip test of the engine and alternator, provides • LARGE DATA DISPLAY: Five digits (numerical hun-
alarm and shutdown protection for the engine and alternator; dreds, tens, ones, tenths and hundredths position).
and restarts the generator set after a unit shutdown due to an • SMALL DATA DISPLAY: Three digits (numerical
unknown condition, high engine water temperature or 230/ tens, ones and tenths position).
460V alternator overload. 2. Alarm icon appears when the Microprocessor has
detected an alarm condition.
If a unit shutdown results from a low engine oil pressure or 4. Keypad:
low engine oil level condition, the Genset Control Module a. ALARM Key: Display fault code readout on digital
places the unit in a protection engine shutdown and does NOT display.
attempt to restart the unit. b. ENTER KEY: Enter menu information and
commands.
• Automatic unit preheat and engine startup during initial c. DOWN ARROW Key: Scroll down through MENU
startup or delayed restart display.
• Variable glow plug preheat time d. UP ARROW Key: Scroll up through MENU
• Automatic Pre-trip Test capability display.
• Automatic unit restart 20 minutes after unit shutdown e. SELECT Key: Places you in (enters) the MENU list
due to an unknown condition, high engine water tempera- and selects items for display, change or calibration.
ture, low engine oil pressure, engine failure to start,
check fuel alarm shutdown, or 230/460V alternator over-
load.
Display
Normally shows the Output Voltage. All segments and icons
are shown in the illustration. It will be blank when the unit
On/Off switch is OFF.
Mode Description
The Alarm description indicates alarms.
Icon
An alarm icon appears next to the Alarm description if an
alarm condition occurs.
Keypad
Alarm Key. Displays fault code readout.
Select Key. Places you in (enters) the MENU list and selects
AJA265
items for display or change.
13-2
Section 13-µP-G ‘Smart’ Gen Set Controller
13-3
Section 13-µP-G ‘Smart” Gen Set Controller
13-4
Section 13-µP-G ‘Smart’ Gen Set Controller
Alarm
Code Type Cause or Explanation
*06 Check Water Temperature Sensor Failure: This alarm indicates the water temp sensor has gone
out of range (below -40(C to 130(C) or is reading an open or shorted connection.
*Pretrip: During the pretrip test the above fault conditions for the water temp sensor occur.
*07 Check Engine RPM sensor: This alarm occurs if:
• The engine rpm was < 40 during crank, but the engine developed oil pressure > 5 psi 7
seconds after the starter de-energized.
• The engine is running, the rpm is < 800, the oil pressure is > 5 psi. This condition must
occur for one minute.
*Pretrip: During the pretrip test the RPM sensor either showed RPMs when the engine was
not running, or didn’t show RPMs when the engine should have been running.
*15 LOG/Check Preheat Circuit Check:
• If the glow plug preheat relay output is energized but the preheat digital input is low a
check alarm will be generated.
• If the preheat output is energized and the battery volts are
< 9.0V for 3 seconds a log alarm will be generated. If this occurs the unit will attempt to
start without the preheat.
*Pretrip: A check alarm will be produced if during the pretrip test the preheat circuit failed
with either condition.
16 Check Digital Input Failure: The digital inputs have been changing once a second for the last 100
seconds. This condition indicates noise on the line, a loose connection, or a bad sensor.
*17 Check/Shut- Engine Failed to Crank: If the engine failed to achieve 40 rpm within 3 seconds of starter
down energized and the oil pressure is < 5 psi 7 seconds after the starter is de-energized a check
alarm is generated. The unit will try and start 2 more times. If after a third attempt the unit
still doesn’t start the check alarm becomes a shutdown alarm.
*Pretrip: During the pretrip test the unit failed to crank by not reaching the above condi-
tions.
*18 Shutdown High Engine Water Temp: This alarm occurs with the engine running, the water temp sen-
sor not in the fail mode, and the water temp exceeds 225°F for 25 seconds. If the above con-
dition occurs the unit will generate a shutdown alarm and shutdown the unit until the water
temp drops < 190°F. The unit will then try to restart after 20 minutes.
*Pretrip: During the pretrip test the above fault conditions for the water temp occur.
13-5
Section 13-µP-G ‘Smart’ Gen Set Controller
Alarm
Code Type Cause or Explanation
*19 Check/Shut- Low Engine Oil Pressure: This alarm occurs when the engine is running, the oil level is
down high, and the oil pressure reading < 15 psi for water temps above 50F (10 C) or the oil pres-
sure hasn’t increase 5 psi from the non-running oil pressure for water temps below 50F (10
C). If the above conditions last for 30 seconds and the low oil pressure switch is high then a
check alarm will be produced. If the above condition occurs for 30 seconds and the low oil
pressure switch is low then a shutdown alarm will be produced and the unit will look at the
user programmable Low Oil Pressure Restart value. If this value is <OFF> then the unit will
remain off. If this value is <ON> then the unit will try to restart after 20 minutes.
*Pretrip: A shutdown alarm will be generated if during the pretrip test the above fault con-
ditions for oil pressure occur.
*20 Check/Shut- Engine Failed To Start: The rpm was > 40, but did not achieve 800 rpm within 30 seconds
down and did not develop oil pressure > 5 psi 7 seconds after the starter de-energized. If this con-
dition occurs the unit will generate a check level alarm and make two more attempts to
restart the unit. If the unit still does not start it will then try to restart after 20 minutes.
*Pretrip: A shutdown alarm will be generated if during the pretrip test the above fault con-
ditions occur.
*25 Check Low Output Voltage: The field relay is energized but the output voltage < 180 for 30
seconds.
*Pretrip: During the pretrip test the above fault conditions for output voltage occur.
*31 Check Oil Pressure Sensor: An alarm is generated if the engine is stopped and the oil pressure is >
10 psi. An alarm is also generated if the engine is running and the oil pressure is < 10 psi
and the oil pressure switch is high and oil level is high for 10 seconds.
*Pretrip: During the pretrip test the above fault conditions for the oil pressure sensor occur.
*35 Shutdown Run Relay Circuit:
• If after energizing the run relay but before the starter is activated, the run relay feedback
digital input is low. Three attempts 4 seconds on, 2 seconds off will be made to energize
the run relay and obtain a high run relay feedback digital input. An alarm is
generated after the third unsuccessful attempt.
• The run relay is not energized and the run relay feedback digital input is high indicating
a hot wire on the fuel solenoid.
• If running the run relay feedback drop out the unit will go into shutdown.
*Pretrip: During the pretrip test the run relay is energized and the run relay feedback
digital input is low.
*37 Check Coolant Level Alarm: The coolant level digital input is low for 30 seconds.
*Pretrip: During the pretrip test the above fault conditions for the coolant level sensor
occur.
41 Check Engine Water Temperature Check: Engine water temperature is 215 F (102 C) for 2 min-
utes while the unit is running.
13-6
Section 13-µP-G ‘Smart’ Gen Set Controller
Alarm
Code Type Cause or Explanation
*43 Check Frequency Out of Range-Low: The engine is running and the output frequency is < 45 Hz
(engine rpm < 1350) for 10 seconds.
*Pretrip: During the pretrip test the above fault conditions for output frequency occur.
44 Shutdown Fuel System Check: The engine rpm’s have dipped below 1050 and have stayed below
1075 for 80 seconds. This will generate an alarm and the unit will then try to restart after 20
minutes.
*45 Check Frequency Out of Range-High: The engine is running and the output frequency is > 70 Hz
(engine rpm > 2100) for 10 seconds.
*Pretrip: During the pretrip test the above fault conditions for output frequency occur.
46 Check Check Air Filter: Engine is running and the digital input AF is low for 10 seconds.
*51 Shutdown Alternator Overload Alarm: The unit is running and the field current exceeds 4 amps for
15 seconds or exceeds 6 amps for 5 seconds. This will generate an alarm and the unit will
then try to restart after 20 minutes.
*Pretrip: During the pretrip test the above fault conditions for the field current occur.
*61 Log/Check Low Battery Alarm:
• When the engine is in preheat the battery volts are < 9.0V for 3 seconds. This is a log
alarm and if it occurs the preheat output will de-energize and a start will be attempted
without preheat.
• The battery volts are < 12.2 for 3 minutes while the unit is not running, this is a check
alarm that may occur when in a restart null.
*Pretrip: During the pretrip test the above fault conditions for the battery occur.
*61 Shutdown Low Battery Alarm: The unit has attempted a start and the controller has reset itself before
the start could be completed.
*Pretrip: During the pretrip test the above fault conditions for the unit occur.
61 Check High Battery Check: When running the battery volts are > 16.0 V for 3 minutes.
63 Check Engine Stopped - Reason Unknown: The engine is not running, it used to be running and
it should still be running. This will generate an alarm and the unit will then make three
attempts to restart. If restart is unsuccessful the unit will again try to restart after 20 minutes.
*66 Shutdown Low Engine Oil Level: The engine is running and the oil level has been low for 3 minutes.
No restart attempts will be made.
*Pretrip: During the pretrip test engine oil level digital input is low.
*69 Check Field Relay Circuit: The field relay is energized and the field current is <.25 amps for 10
seconds.
*Pretrip: During the pretrip test the above fault conditions for the field relay occur.
70 Check Hour Meter Exceeds Limits: One or more of the hour meters has exceeded 99,999 hours
or one or both of the restart counters has exceeded 9999. The hourmeter or counter that
caused the alarm will be reset.
13-7
Section 13-µP-G ‘Smart’ Gen Set Controller
Alarm
Code Type Cause or Explanation
71 Check Hour Meter Exceeds Limits: Programmable hour meter 1 has exceeded set limit.
Clearing this code will also reset the hourmeter 1.
72 Check Hour Meter Exceeds Limits: Programmable hour meter 2 has exceeded set limit.
Clearing this code will also reset the hourmeter 2.
74 IM_Shutdown Control Reverted to Default Settings: The controller has reverted to factory
programmable settings. This will occur with a chip change in the controller or a controller
cold start was performed.
88 Log Shutdown Microprocessor Fault Alarm: The microprocessor has found a fault condition
with either its RAM or EEprom. If this alarm occurs twice the unit should be sent in for
repair.
99 Check Restart Null: The unit has been shutdown but the controller is monitoring conditions and
will try to restart after 20 minutes.
Notes:
* = Pretrip Alarm
1) The phrase “restart after 20 minutes” refers to the auto-restart mode where the unit will make up to three attempts every 20
minutes to restart the unit after a shutdown has occurred. This restart mode continues until the unit has been successfully
restarted or until a code 61 is generated due to low battery.
13-8
Section 13-µP-G ‘Smart’ Gen Set Controller
µP-G Acronyms
Acronym Definition
AC Alternating current or Volts A.C. (typically)
AL_01 Alarm 01
rEv Revision, software (typically)
MEnU Menu menu or submenu prompt
PtrIP Pretrip menu or submenu prompt
tESt Test menu or submenu prompt
GUArd Guard menu or submenu prompt
PrGrM Program menu or submenu prompt
vIEW View menu or submenu prompt
dEG Degree
F Fahrenheit
C Celsius
OIL Oil pressure
PSI Pounds per square inch
bArS Bars
kPa Kilo Pascals
HZ Hertz
Ent Engine temperature
rPM Revolutions per minute
bAt Battery volts D.C.
Fld Field current D.C. amps
rHr Run hourmeter
EntEr Prompt for key stroke
PrE Pretrip mode
LOAd Load of data into micro controller
OLS Oil level switch
OPS Oil pressure sensor
LOP Low oil pressure switch
UtS Water temperature sensor
FUS Flywheel sensor
Phr Preheat relay
rr Run relay
vr Voltage regulator
Sr Start relay
Fr Field relay
PASS Pass result after pretrip
FAIL Fail result during pretrip
13-9
Section 13-µP-G ‘Smart” Gen Set Controller
13-10
Section 14
Gen-Set
Schematic/Wiring Diagrams
Section 14-Gen-Set Schematic/Wiring Diagrams
14-2
Section 15
Gen-Set
Alternator Procedures
(Original Control System)
Section 15-Gen-Set Alternator Procedures (Original Control System)
This alternator consists of three principal components: the The build up continues until the voltage and amperage
main alternator, the integral direct connected exciter, and an reaches the rated amount at which the voltage regulator
externally mounted excitation control system. decreases field current, and the alternator maintains the
proper output voltage.
The main alternator may be subdivided into the 4-pole main
rotating field and the main stator winding. The exciter control system used with this generator differs
slightly from previous Thermo King control systems in that
The main rotating field, the rotating rectifier and the exciter only one booster bridge rectifier is used. This will not sub-
armature are all mounted on a common shaft. Output of the stantially alter test procedures that were utilized for previous
exciter is rectified by the shaft mounted rotating bridge recti- control systems.
fier to provide main alternator rotating field excitation.
Dual Voltage Alternator
The externally mounted excitation control system is energized The generator set is factory wired for 460V power output.
from the battery through a voltage regulator. The output from Alternator output can be changed to 230V by changing power
the main winding is stepped down by the power transformer cable wire connections at the terminal strips in the Exciter
and rectified by power bridge and added to the initial current Control Box.
supplied by the On-Off switch to build up alternator output.
Rotor Assembly
DC AC
Magnetic Magnetic
Coupling Coupling
Stator Assembly
Volts
Exciter Field
Alternator
(FLD)
Stator (ALT)
15-2
Section 15-Gen-Set Alternator Procedures (Original Control System)
AJA710
FUNCTION OF COMPONENTS IN
VR
EXCITER CONTROL SYSTEM The Voltage Regulator measures the power bridge output
voltage (RED terminal) and supplies exciter field current to
BR1 the GREEN (GRN) field circuit as required to maintain volt-
Bridge Rectifier I rectifies current from the power transformer age (and main generator output) at the desired level.
to charge the battery and supply exciter circuit.
15-3
Section 15-Gen-Set Alternator Procedures (Original Control System)
AJA711
DI D6
Diode I protects the Preheat/Start switch from negative tran- Diode 6 isolates alternator excitation system from the battery
sient voltages caused by arcing at the starter solenoid. when the unit is shut down (necessary to avoid drain on bat-
tery when -unit is OFF). Permits battery charging current to
D2 pass from power bridge to ammeter and then back to the bat-
Diode 2 protects the On-Off switch from negative transient tery.
voltages caused by arcing at the fuel shutoff solenoid.
D7
D3 Diode 7 isolates engine oil and water safety switch devices
Diode 3 diverts current bridge output into battery whenever from the exciter control.
the alternator reset circuit breaker opens, and suppresses
destructive voltage transients. D8
Diode 8 isolates and protects regulator from high voltages
D4 which are normally developed across field during motor starts
Diode 4 prevents the battery charging current from bypassing or under heavy overload. Also allows regulator to control
the positive temperature coefficient (PTC) charge limiting field voltage during normal operation.
resistors.
D9
D5 Diode 9 isolates the exciter circuitry from the 12 Vdc control
Diode 5 prevents feedback from power bridge output to voltage when the low oil pressure and high water temperature
engine controls, fuel solenoid, etc. (necessary in order to shut switches are open. Provides a path for field excitation to be
machine down). Permits flow of initial excitation current shunted to ground after the excitation circuit breaker opens
needed for building up normal alternator output voltage. and the silicon controlled rectifier (SCR) has been turned on.
D10
Diode 10 isolates the current bridge from the voltage regula-
tor output and from the transients generated in the field coils.
Allows current bridge output to control field voltage during
motor starts and overload conditions.
15-4
Section 15-Gen-Set Alternator Procedures (Original Control System)
CB1 BR2
Circuit Breaker 1 is located in the field circuit. When the gen- Current Bridge Rectifier (BR2) rectifies the ac output of the
erator set is overloaded, the field current increases to a point current transformer. This current is then used for dc excitation
that trips the circuit breaker. Field current is then diverted current through the orange wire, through diode D10 and into
through D3 to the battery charging circuit. When this hap- Fl. During an overload, this output increases greatly and is
pens, a voltage is present across resistors R4 and R5 which used to boost alternator output.
form a voltage divider for the gate of the SCR. This turns the
SCR on, allowing current to flow from the current bridge and TRF-2
the 20 circuit to ground. With current flowing in the 20 cir- Current transformer. Senses an abrupt increase in current
cuit, the resistor on the reset switch heats and trips the switch demand on the alternator. This in turn sends an increased cur-
shutting down the entire circuit. rent flow through the current rectifier by passing the voltage
regulator going directly to the alternator field winding.
CB2
Circuit Breaker 2 is electrically located between the reset RI &R2
switch normally closed contacts and On-Off switch. The cir- The Positive Temperature Coefficient (PTC) resistors are
cuit breaker trips open if the dc control circuits overload. charge rate control devices that prevents the charge demand of
a discharged unit battery from influencing the voltage output
of the main generator.
15-5
Section 15-Gen-Set Alternator Procedures (Original Control System)
ALTERNATOR FUNCTION The design of the current transformer limits the amount of
transformer current output to less than the field requirement to
A. Starting Excitation maintain normal alternator voltage. Therefore, the alternator
The initial excitation for the alternator is supplied by turning output voltage would tend to be low. The voltage regulator
the On-Off switch to the ON position. Current flows from the then senses a low alternator output voltage. It takes current
unit battery through the No. 2 wire, the ammeter, the fusible from the power transformer (TRF-1) and rectifier (BR1) and
link, diode D4, the safety switch (SSW), CB2, the On-Off adds to the field current to bring the alternator output voltage
switch, the 8-wire, and diode D5 to the RED lead of the volt- up to normal.
age regulator. The regulator sends the current out on the
GREEN wire through diode D8 to Fl. Fl sends the current to If the alternator output voltages rise above the predetermined
the exciter field to build voltage in the stator windings. The limit, the power transformer will reflect this rise in its output
current then travels through F2 and CB1 to ground. voltage. The voltage regulator sensing the higher voltage will
then reduce the exciter current to the field winding. This
B. Running Excitation and Control reduces exciter current to the main alternator field, reducing
Once the alternator is excited by the unit battery and the the alternator output.
engine is running, excitation is provided by the alternator
itself. In essence, a 12 Vdc automotive-type voltage regulator is
controlling a 15 KW ac alternator by taking a sample of the
The magnetic field that was formed in the exciter field stator alternator output, reducing the voltage, rectifying it and send-
winding, by battery current, induces a current in the exciter ing it to the field.
rotating winding. This current is changed from threephase ac
to dc by the rotating rectifier. The dc current is transferred to C. Temporary Overload
the main alternator field winding. The main alternator field For temporary overloads (such as refrigeration unit start up),
now becomes magnetic. the excitation control system utilizes the current (boost) trans-
former (TRF-2) and rectifier (BR2) to handle the overload.
The magnetic field formed in the main field winding now When the alternator output current is normal, the current
induces a voltage in the alternator stator windings. This volt- transformer is supplying a portion of the current used to excite
age is either 230 Vac or 460 Vac, 3-phase, depending on stator the alternator field. When an overload occurs, the increased
connections. current flow from the alternator through the current trans-
former causes an immediate increase in current transformer
It is sent out of the alternator stator leads to the power plug output. This increased output overrides the voltage regulator
and then to the load. The power transformer (TRF-1) is output and boosts the output of the alternator to handle the
tapped into the alternator stator leads. The transformer reads temporary overload.
the alternator output voltage and steps this voltage down to
D. Battery Charging
around 12 Vac (1/20th of output voltage). This current is fed
The unit battery is recharged using current from the power
through the power bridge rectifier (BRI), rectified to dc cur-
bridge rectifier. Current flows from the rectifier bridge
rent and is sent into the IA circuit, and some of it goes to the
through the IA wire and through diode D6.
voltage regulator.
The current is then divided between two wires, 2AI and 2A2
The voltage regulator RED lead is connected to the IA circuit,
and then through two RI and R2 resistors. These limit the
and it utilizes power bridge output to measure alternator volt-
amount of current that a battery, in a discharge state, can
age. It also uses the power bridge current output as a source of
receive from the system. If a battery will accept large amounts
exciter current rather than using the unit battery.
of current, the voltage from the power bridge rectifier will be
lowered, and the voltage regulator would sense the reduction
A portion of running excitation is actually supplied by the
and increase exciter current to the alternator field causing an
current transformer (TRF-2) and current rectifier (BR2). The
over-voltage condition in the alternator.
current transformer is designed to produce output current in
direct relation to the mount of current flowing from the alter-
Two wires are used in parallel (2AI-2A2) to reduce the
nator to the load. The output current is rectified by the current
amount of current transferred through the pin connector.
bridge (BR2) and then used as field current.
15-6
Section 15-Gen-Set Alternator Procedures (Original Control System)
E. Overload Shutdown If the overload breaker trips, it indicates one of the following:
The overload shutdown circuit utilizes a silicon-controlled
rectifier (SCR) in conjunction with the reset switch (SSW). 1. There is a malfunction in the load causing the load to fail
to start or to draw single phase current.
If an overload condition becomes more than temporary, the
reduction in alternator output voltage due to the overload 2. The engine speed or power is low due to improper speed
causes an increase in field current to a point (greater than 3.25 adjustment, fuel supply problems or other mechanical
amps) at -which the field circuit breaker (CB1) opens, discon- conditions while the generator is supplying -motor start-
necting the field circuit from ground. Field current is then ing current to the load.
diverted through D3 to the battery charging circuit.
3. Internal component failure in the excitation control sys-
When this happens, a voltage is present across resistors R4 tem, resulting in excessive field current. This includes
and R5 which form a voltage divider for the gate of the SCR. possible malfunction of protective elements in the excita-
This turns the SCR on. The SCR acting like a switch, allows tion control.
current to flow through the 20 circuit to ground. The resistor
on the reset switch heats up and trips the switches normally 4. Failure in the alternator rotating elements (exciter arma-
closed contacts open, de-energizing the fuel solenoid to stop ture, rotating diode assemblies or main field) can cause
the engine. the regulator to supply excessive exciter field current.
The SCR also provides a path to ground for the output of the
current bridge rectifier. This is done to prevent high voltages
building in and causing damage to the current transformer.
15-7
Section 15-Gen-Set Alternator Procedures (Original Control System)
NOTE: Further diagnosis is a waste of time until these items 3. DC ammeter (preferably induction type
are checked, since a problem in one of these areas will affect TK No. 204-449).
test results.
4. Ohmmeter.
1. If the generator malfunction is accompanied by excessive
black exhaust smoke and engine lugging, double check 5. Megohmmeter (Megger).
all possible engine problems such as fuel supply, injec-
tion timing, engine speed, restricted air cleaner, etc. 6. 1073 Light Bulb Assembly and Motorola Adapter.
2. Disconnect the refrigeration unit from the generator, and
check the output voltage at the plug. Voltage between the This can be built very quickly. It requires a No. 1073 light
three phases should be between 230 to 250 Vac or 460 to bulb and a matching socket, two alligator type clips and the
500 Vac depending on engine speed and whether the plug off of a discarded voltage regulator. See illustration for
alternator stator is wired for 230 or 460 volt operation. details.
All three phases should be within 3% of each other. If the
voltages appear normal, make sure the refrigeration unit
is not at fault. Reconnect refrigeration unit and run in
Cool mode. Check the amperage draw with an induction
type ammeter (amprobe), and compare it with the load
plate on the refrigeration unit.
3. Check the condition of the generator set battery. A dis-
charged unit battery can give a false signal to the voltage
regulator, causing the generator output voltage to be high.
The unit battery should have a minimum voltage of 12 V.
4. Check all push-in plugs on control circuit for loose pins
or sockets. Make sure all wire terminals are tight. Alternator Test Equipment
5. Check generator circuit breaker for proper operation. Use
an ohmmeter to make sure the circuit through the circuit ALTERNATOR MALFUNCTIONS
breaker is continuous.
Listed below are the categories in which most generator mal-
TEST INSTRUMENTS functions will fall. Following each category are a number of
If the preceding checks did not uncover the cause of the mal- possible component failures that may cause the malfunction.
function, more extensive diagnosis procedures will be Listed with each component is the test used to check the com-
required. The following tests will require various electrical ponent.
test instruments, and the technician performing the tests
should have a good working knowledge of their basic electri- NOTE. Always use Test 1 first to determine if the alternator
cal principles. or the exciter control package is at fault.
The tests are intended to determine whether the source of dif- 1. Generator set will not pick up the load (low or no output
ficulty lies in the generator itself or in the excitation control voltage).
system. Following the procedures carefully will, in many a. Diode D5 is open circuit (Test 2).
cases, avoid unnecessary dismantling and reassembly of the b. Voltage regulator is defective (Test 3).
generator when easily corrected problems may exist in the c. Diode D8 is open circuit (Test 2).
external circuitry. d. Exciter field circuit in alternator is open circuit
(Test 7).
e. Alternator circuit breaker (CBI) is defective (Test 7).
f. Alternator stator, main rotating field, rotating rectifier
or rotating exciter armature is defective (Test 8).
15-8
Section 15-Gen-Set Alternator Procedures (Original Control System)
2. Generator set tries to pick up the load but engine labors d.Exciter field circuit shorted or low resistance
excessively, eventually tripping the alternator circuit (Test 7).
breaker or stopping the engine. e. Defective rotating exciter armature, rotating rectifier,
a. Mechanical problems with engine (see preliminary exciter field circuit or main alternator stator (Test 8).
check 1). f. Engine speed too low. Reset injection pump/ governor
b. Excessive load from refrigeration unit malfunction speed to 1800 (10 rpm at Full Load (60 Hz alternator out-
(see preliminary check 2). put); 1950 ± 10 rpm No Load.
c. Current transformers or current bridge defective 4. Generator set output voltage too high.
(Test 4). a. Unit battery discharged (see preliminary check 3).
d. Diode D8 open circuit (Test 2). b. Voltage regulator defective (Test 2).
e. Defect in rotating field, rotating bridge, alternator main c. Power bridge not functioning (Test 3).
field or alternator stator (Test 8). d. Shorted exciter armature (Test 8).
3. Generator set trips the alternator circuit breaker without 5. Unit battery undercharged.
apparent overload. a. No output from power bridge (Test 3).
a. Power bridge inoperative (Test 3). b. Diode D6 open circuit (Test 5 and 6).
b. Circuit breaker defective (Test 7). c. PTC resistors open circuit (Test 6).
c. Voltage regulator failed in ON position (Test 2).
15-9
Section 15-Gen-Set Alternator Procedures (Original Control System)
TEST NO. 1 5. Attach the free lead of the bulb assembly to Fl. A slight
change in the sound of the engine should be evident as
This test will determine whether the alternator or the excita- alternator voltage and excitation builds up.
tion control system is causing the malfunction. The test
requires the use of the 1073 bulb assembly.
CAUTION: If the engine bogs down or produces black
smoke, there is a short circuit in the alternator or its output
CAUTION: Make sure the generator set is disconnected circuits. In this event, disconnect the light assembly and
from any load and the orange wire is jumpered to ground. shutdown the engine.
Severe damage to the current transformer will occur if the Refer to Tests 7 and 8.
load should attempt to start during this test.
6. Measure alternator output voltages on LI-L2, Ll-L3, and
1. Connect a jumper from orange to ground (CH) on circuit L2-L3. Voltage will normally be between 460 and 500
board during test. volts or 230 to 250 depending on engine s@ and whether
2. Disconnect Fl and F2 leads from the alternator. Using a the alternator stator is wired for 460 or 230 volt opera-
jumper wire, connect F2 to a known good ground. tion.
3. Connect one lead of the light assembly to a known good 7. Low or no output voltage indicates a problem in the
12 Vdc source such as the No. 2 wire at the ammeter. The exciter field coils or the alternator itself. To check alter-
other lead will be used later. nator or field coils, see Tests 7 and 8.
4. Start the engine and make sure speed is 1800 ± 10 rpm at 8. Normal output voltage indicates alternator is almost cer-
Full Load (60 Hz alternator output); 1950 ± 10 rpm No tainly in good condition. (Some machines may exhibit
Load. REMEMBER THAT HAZARDOUS ELECTRI- near normal output voltage with one defective rotating
CAL POTENTIALS will be present on alternator output diode. A defective rotating diode would impair the gener-
terminals on exciter control- The ground (negative) con- ator set motor-starting capabilities.) Ammeter should
nection bypasses all exciter control overload protection, indicate CHARGE. If not, power transformer, power
and CARE MUST BE EXERCISED TO AVOID DAM- bridge BR1 or diode D6 is defective (Tests 4, 6 and 7).
AGE TO THE ALTERNATOR IN THE EVENT THERE
IS AN INTERNAL OR EXTERNAL SHORT CIRCUIT.
15-10
Section 15-Gen-Set Alternator Procedures (Original Control System)
DIS-
CONNECT
CHECK
VOLT
CHECK
VOLT
CHECK
VOLT
TEST NO. 2
Test 2 checks the voltage regulator and also checks the initial 4. Using a dc voltmeter, check for voltage at the following
exciter circuit from the unit battery to the field circuit. locations:
1. Voltage Regulator Quick Test NOTE: Voltage readings may vary slightly depending on
The voltage regulator can be checked quickly by unplug- battery voltage.
ging it from the system and substituting the 1073 bulb
a. No. 8 wire at circuit board ó 12 Vdc
assembly and Motorola adapter plug. If there is at least 9
b. Red wire on circuit board after diode ó 10.5 Vdc
Vdc present, start the generator set engine, and connect
c. Green wire before diode D8 ó 9 Vdc
the light assembly from the red wire to the green wire at
the adapter plug. If the alternator picks up the load and
NOTE. No voltage here indicates open diode D8 (Test 6).
operates normally (alternator output voltage may be
slightly high), the voltage regulator is faulty. Higher voltage indicates the voltage regulator may have
2. Disconnect the No. 8A wire from the safety switch to failed in full-on position or field circuit is open (Test 7).
prevent tripping of the safety switch while the generator 5. Turn the unit switch OFF.
set switch is ON. 6. Reconnect the 20 circuit.
3. Turn the unit switch ON, but DO NOT start the engine. 7. Turn On-Off switch ON and start the generator set.
15-11
Section 15-Gen-Set Alternator Procedures (Original Control System)
8. Start the generator, but do not apply load. Voltages 10. The field circuit amperage can be checked with a dc
should be as follows: ammeter. Under normal load conditions, the field amper-
a. No. 8 wire at circuit board ó 13.5 Vdc age should be between 1.5 to 2.5 amps. If the amperage is
b. Red wire after diode D5 at circuit board ó 14 Vdc too high or too low, recheck the engine speed. If the
c. Green wire before diode D8 ó 5 Vdc speed is correct, replace the regulator. If the amperage is
d. F1 after diode D8 ó 4 Vdc still not correct, check the field circuit (see Test 7).
9. Turn the refrigeration unit on to apply load to alternator.
Voltages should be as follows: CAUTION. The voltage regulator used on the generator TK
a. No. 8 wire at circuit board ó 13Vdc Part No. 44-3345 is not the same as the voltage regulator
b. Red wire after diode D5 at circuit board ó 14Vdc used on 7hermo King over-the-road diesel transport
c. Green wire before diode D8 ó 8 Vdc refrigeration units. The voltage setting is lower on the
d. Fl after diode D8 ó 7.25 Vdc
refrigeration units.
Higher or lower than normal voltages at Fl indicate voltage
regulator failure. Replace the voltage regulator. If alternator
output still is too high or low, or if voltage at Fl is not correct,
check field circuit (see Test 7).
15-12
Section 15-Gen-Set Alternator Procedures (Original Control System)
CHECK
VOLT
CHECK
VOLT CHECK
VOLT
TEST NO. 3 3. Start the unit. The voltage should rise to approximately
14.5 volts (depending on batteries state of charge). This
indicates the power bridge and power transformer are
Test 3 checks the power bridge and power transformer. If the functioning.
power bridge fails completely, the voltage regulator will not 4. If the voltage does not rise, using an ac voltmeter, check
receive the normal voltage rise out of BRI. The low voltage the voltage across (XI-X2), (X2-X3), (X3-XI). The cor-
(battery voltage), in the 1A circuit keys the regulator to go to rect voltage is approximately 12 to 13 Vac. This ac read-
full field current and therefore high alternator output voltage, ing will be less than the dc output of the power bridge
eventually tripping the alternator circuit breaker from exces- rectifier. This is normal and is due to the fact that the ac
sive field current and thus shutting the generator set down. A voltmeter does not read the peak voltage of an ac sine
defective power bridge also causes the unit ammeter to show wave but reads an average figure (RMS factor). This phe-
a discharge condition, although the no charge condition can nomenon will usually only occur in a three-phase ac,
be caused by other malfunctions. bridge rectifier combination. If the ac voltage is correct
but the dc output was low or non-existent, replace the
To test the power bridge: power bridge rectifier.
1. Attach a dc voltmeter to the terminal that serves as the If the ac voltage from the power transformer is low or
connection of the two red wires, wire 1A and diode D6. non-existent, replace the power transformer. It is virtually
2. Turn the generator On-Off switch ON, but do not start the impossible to check the ac input to the power transform-
engine. The voltmeter should show a reading of 10 to 11 ers so if the alternator output is near normal or high,
volts (1.5 volts less than battery voltage). assume that the power transformer input is normal.
15-13
Section 15-Gen-Set Alternator Procedures (Original Control System)
CHECK
VOLT
CHECK
VOLT
CHECK
VOLT
TEST NO. 4 4. Attach the bulb assembly lead to the green wire on the
adapter and turn the generator set On-Off switch ON. The
This test checks the output of the booster circuit. The booster voltmeter should show 5 Vdc.
circuit is utilized when the generator starts up a load. 5. Start the generator set engine. The refrigeration unit
should start, and voltage should increase from 5 volts
1. Disconnect the voltage regulator and install the Motorola cranking to 10 to 12 or possibly higher, and then drop
adapter plug in its place. Attach one lead of the bulb back to approximately 7 Vdc as the alternator picks up
assembly to a known good 12 Vdc source (No. 2 wire on and starts the load. If field voltage does not rise as the
the ammeter). The other lead will eventually be con- generator set attempts to start the load or if the load will
nected to the green wire on the Motorola adapter plug. not start, the booster system is not functioning properly.
2. Hook up a dc voltmeter across the green and black wires 6. Turn the refrigeration unit On-Off switch OFF once the
on the adapter plug to measure exciter field voltage as refrigeration unit is running. Turn the refrigeration unit
shown. Voltmeter must have a range of at least 50 volts. back ON, and observe the voltmeter and alternator output
3. Hook up a load (refrigeration unit) to the generator and voltage. Field voltage should rise momentarily as the
turn the refrigeration unit On/Off switch ON. Make sure refrigeration unit starts, and the alternator output voltage
the refrigeration unit thermostat is set below box temper- should not drop below approximately 360 or 190 volts,
ature so the unit will start immediately. depending on how the alternator is wired. If the required
booster voltage is not present, check the current bridge
CAUTION: The generator set is not designed to start a rectifier (Test No. 6).
refrigeration unit from a dead stop, but for this test an 7. If the current bridge rectifier is ok, repeat the test check-
exception is made. ing for ac voltage on (XI-X2), (X2-X3), (X3-XI) at the
booster bridge. If the normal voltage rise (10 to 12 Vac) is
not present from the current transformer, replace the cur-
rent transformer.
15-14
Section 15-Gen-Set Alternator Procedures (Original Control System)
CHECK
VOLT
TEST NO. 5 3. 2AI and 2A2: There will be a small voltage drop across
the RI and R2 resistors (.5 volt). If the voltage reading at
Test 5 checks the battery charging circuit. this point is the same as battery voltage when the genera-
tor set is shut off, the resistors are probably open circuit.
NOTE: Before testing the battery charging circuit, run the The only reliable method of testing the resistors is to
generator set to bring all the components up to normal unsolder both of them from their connections and mea-
operating temperature. sure their resistance with an ohmmeter (.1 ohm at room
temperature).
If the unit ammeter indicates no charge or if the battery is
under charged, test the power bridge (Test 3) to make sure the
N0TE: Ambient temperature and battery charge rate will
bridge is providing adequate voltage to charge the battery
have an affect on the voltage drop across the R1 and R2
(14.6 ± .2 V). If the voltage from the power bridge is correct,
using a dc voltmeter, check the voltages at the following loca- resistors.
tions with the unit running. If the battery discharges while the generator set is not used,
check diode D6 (Test 6). It is probably short circuited. Over-
1. 1A at the junction of the two red wires, diode D6 and 1 charging of the battery is usually caused by a faulty voltage
A, 14.6 ± .2 V. regulator. The voltage regulator controls the ac alternator and
2. Between diode D6 and the R1 and R2 charging resistors, the battery charging voltage so an overcharged battery is usu-
it should be I to.8 volts less than the previous reading, ally accompanied by higher than normal output voltage. If
indicating the diode D6 is conductive. A larger difference this is the case, replace the regulator.
indicates the diode is open circuit.
15-15
Section 15-Gen-Set Alternator Procedures (Original Control System)
15-16
Section 15-Gen-Set Alternator Procedures (Original Control System)
OHM
METER
TEST NO. 7
Test 7 determines the condition of the exciter field circuit.
15-17
Section 15-Gen-Set Alternator Procedures (Original Control System)
TEST NO. 8
Test 8 includes testing the main alternator-stator, the rotating
field, the rotating rectifier, and the rotating field armature. All
tests must be made with reliable equipment.
Alternator Stator
2. Rotating Rectifier.
15-18
Section 15-Gen-Set Alternator Procedures (Original Control System)
15-19
Section 15-Gen-Set Alternator Procedures (Original Control System)
1 2
1. Bearing
2. Apply Grease Here
3. Shield
15-20
Section 15-Gen-Set Alternator Procedures (Original Control System)
1
8 9
2 10 11
3
4
5 12
13
25 6 7
8 14 15 17
16 18
9
19
10
11
12 20
25
23 24
22 21
Alternator Assembly
15-21
Section 15-Gen-Set Alternator Procedures (Original Control System)
15-22
Section 16
Gen-Set
Alternator Procedures
(New Control System)
Section 16-Gen-Set Alternator Procedures (New Control System)
This alternator consists of three principal components: the The build-up continues until the voltage and amperage
main alternator, the integral direct-connected exciter, and an reaches the rated amount at which the voltage regulator
externally mounted excitation control system. decreases field current, and the alternator maintains the
proper output voltage.
The main alternator may be subdivided into the 4-pole main
rotating field and the main stator winding. The exciter control system used with this generator differs
from previous Thermo King control systems in that the Genet
The main rotating field, the rotating rectifier and the exciter Control Module circuit board replaces the original safety
armature are all mounted on a common shaft. Output of the devices and the silicon controlled rectifier (SCR) that will
exciter is rectified by the shaft mounted rotating bridge recti- alter some test procedures that were utilized for previous con-
fier to provide main alternator rotating field excitation. trol systems.
The externally mounted excitation control system is energized Dual Voltage Alternator
from the battery through a voltage regulator. The output form The generator set is factory wired for 460V power output. The
the main winding is stepped down by the power transformer alternator output
and rectified by power bridge and added to the initial current can be changed to 230V by changing power cable wire con-
supplied by the On-Off switch to build up alternator output. nections at the terminal
strips in the control box.
Rotor Assembly
DC AC
Rotating Rotating
Rectifier Exciter
Main Field
Magnetic Magnetic
Coupling Coupling
Stator Assembly
Volts
Exciter Field
Alternator
(FLD)
Stator (ALT)
16-2
Section 16-Gen-Set Alternator Procedures (New Control System)
BR2 TRF-2
Current Bridge Rectifier (BR2) rectifies the ac output of the Current Transformer senses an abrupt increase m current
current transformer. This current is then used for dc excitation demand on the alternator. This in turn sends an increased cur-
current through the orange wire, through diode D3 and into rent flow through the current bridge rectifier by passing the
the exciter field. During an overload, this output increases voltage regulator and going directly to the alternator field
greatly and is used to boost alternator output. winding.
CBI VR
Circuit Breaker 1 is electrically located between the current The Voltage Regulator measures the power bridge output
limiter and On-Off switch. The circuit breaker trips open if voltage (RED wire) and supplies exciter field current (GRN
the dc control circuits overload. wire) to the field circuit as required to maintain voltage (and
main generator output) at the desired level.
16-3
Section 16-Gen-Set Alternator Procedures (New Control System)
D1 D5
Diode 1 protects the Preheat/Start switch from negative tran- Diode 5 prevents feedback from power bridge rectifier BRI to
sient voltages caused by arcing at the starter solenoid. engine controls, fuel solenoid, etc. (necessary m order to shut
machine down). Permits flow of initial excitation needed for
D2 building up normal alternator output voltage.
Diode 2 protects the On-Off switch from negative transient
voltages caused by arcing at the fuel shutoff solenoid. D6
Diode 6 isolates alternator excitation system from the battery
D3 when the unit is shut down (necessary to avoid drain on bat-
Diode 3 (part of bridge rectifier BR3) isolates the bridge recti- tery when unit is OFF). Permits battery charging current to
fier BR2 from the voltage regulator output and from the tran- pass from power bridge rectifier BRI to ammeter and then
sients generated in the field coils. Allows bridge rectifier to back to the battery.
control field voltage during motor starts and overload condi-
tions. D7
Diode 7 isolates and protects regulator from high voltages
D4 which are normally developed across field during motor starts
Diode 4 prevents the battery charging current from by passing or under heavy overload. Also allows regulator to control
the positive temperature coefficient (PTC) charge limiting field voltage during normal operation.
resistors RI and R2.
RI & R2
The Positive Temperature Coefficient (PTC) resistors are
charge rate control devices that prevent the charge demand of
a discharged unit battery from influencing the voltage output
of the main generator.
16-4
Section 16-Gen-Set Alternator Procedures (New Control System)
Once the alternator is excited by the unit battery, then excita- In essence, a 12 Vdc automotive-type voltage regulator is
tion is provided by the alternator itself. controlling a 15 KW ac alternator by taking a sample of the
alternator output, reducing the voltage and sending it to the
The magnetic field that was formed in the exciter field stator field.
winding by battery current induces a current in the exciter
rotating winding. This current is changed from three-phase ac C. Temporary Overload
to dc by the rotating rectifier. The dc current is transferred to
the main alternator field winding The main alternator field For temporary overloads (such as refrigeration unit start up),
now becomes magnetic. the excitation control system utilizes the current (boost) trans-
former (TRF-2) and rectifier (BR2) to handle the overload.
The magnetic field formed in the main field winding now
induces a voltage in the alternator stator windings. This volt- When the alternator output current is normal, the current
age is either 230 Vac or 460 Vac, 3-phase, depending on stator transformer is supplying a portion of the current used to excite
connections. the alternator field. When an overload occurs, the increased
current flow from the alternator through the current trans-
It is sent out of the a r stator leads to the power plug and then former causes an immediate increase in current transformer
to the load. The power transformer (TRF-1) is tapped into the output This increased output overrides the voltage regulator
alternator stator leads. The transformer reads the alternator output and boosts the output of the alternator to handle the
output volume and steps this voltage down to around 12 Vac temporary overload.
(1/20th of output voltage). This current is fed through the
power bridge rectifier (BR1), rectified to dc current and is
sent into the 1A circuit, and some of it goes to the voltage reg-
ulator.
16-5
Section 16-Gen-Set Alternator Procedures (New Control System)
D. Battery Charging If the Genset Control Module shuts down unit operation, it
indicates one of the following:
The unit battery is recharged using current from the power
bridge rectifier (BRI). Current flows from the rectifier bridge 1. There is a malfunction in the load causing the load to fail
through the 1A wire and through diode D6. to start or to draw single phase current
The current is then divided between two wires, 2A1 and 2A2 2. The engine speed or power is low due to improper speed
and then through two resistors R1 and R2 which have the adjustment, fuel supply problems or other mechanical
characteristics of their resistance increasing in proportion to conditions while the generator is supplying motor start-
temperature. This limits the amount of current that a battery, ing current to the load.
in a discharge state, can receive from the system. If a battery
will accept large amounts of current, the resistors heat up and 3. Internal component failure in the excitation control sys-
their resistance increases. This will limit the amount of bat- tem, resulting in excessive field current. This includes
tery charging current. possible malfunction of protective elements in the excita-
tion control.
E. Overload Shutdown
4. Failure in the alternator rotating elements (exciter arma-
The overload shutdown is provided by the Genset Control ture, rotating diode assemblies or main field) can cause
Module. the regulator to supply excessive exciter field current
If an overload condition becomes more than temporary, the 5. Engine shutdown on low engine oil level, low oil pres-
reduction in alternator output voltage due to the overload sure or high water temperature.
causes the Voltage Regulator (VR) to increase field current
through wire F2 to the Genset Control Module. The module
senses the overload current and then de-energizes the fuel
solenoid to stop the engine.
16-6
Section 16-Gen-Set Alternator Procedures (New Control System)
PRELIMINARY CHECKS If the preceding checks did not uncover the cause of the mal-
function, more extensive diagnosis procedures will be
Before attempting the more complicated diagnosis proce- required. The following tests will require various electrical
dures, check the following items to ensure a superficial prob- test instruments, and the technician performing the tests
lem is not overlooked. should have a good working knowledge of their basic electri-
cal principles.
NOTE: Further diagnosis is a waste of time until these item
are checked, since a problem in one of these areas will The tests are intended to determine whether the source of dif-
influence test results. ficulty lies in the generator itself or in the excitation control
system. Following the procedures carefully will, in many
1. If the generator malfunction is accompanied by excessive cases, avoid unnecessary dismantling and reassembly of the
black exhaust smoke and engine lugging, double check generator when easily corrected problems may exist in the
all possible engine problems such as fuel supply, injec- external circuitry.
tion timing, engine speed, restricted air cleaner, etc.
2. Disconnect the refrigeration unit from the generator and The test instruments required:
check the output voltage at the plug. Voltage between the
three phases should be between 230 to 250 Vac or 460 to 1. AC-DC voltmeter 2-5 V to 500 V ranges
500 Vac depending on engine speed and whether the (±2% max. error).
alternator stator is wired for 230 or 460 volt operation. 2. AC induction ammeter (amprobe).
All three phases should be within 3% of each other. If the 3. DC ammeter (preferably induction type
voltages appear normal, make sure the refrigeration unit TK No. 204-449).
is not at fault. Reconnect refrigeration unit and run in 4. Ohmmeter.
Cool mode. Check the amperage draw with an induction 5. Megohmmeter (Megger).
type ammeter (amprobe), and compare it with the load 6. 1073 Light Bulb Assembly and Motorola Adapter.
plate on the refrigeration unit.
3. Check the condition of the generator set battery. A dis- This can be built very quickly. It requires a No. 1073 light
charged unit battery can increase the voltage regulator bulb and a matching socket, two alligator type clips and the
output, causing the generator output voltage to be high. plug off of discarded voltage regulator. See illustration for
The unit battery should have a minimum voltage of 12 V. details.
4. Check all push-in plugs on control circuit for loose pins
or sockets. Make sure all wire terminals are tight.
16-7
Section 16-Gen-Set Alternator Procedures (New Control System)
ALTERNATOR MALFUNCTIONS 3. Generator set causes the Genset Control Module to shut-
down unit without apparent overload.
Listed below are the categories in which most generator mal- a.Power bridge (BR 1) inoperative (Test 2, 3, 6).
functions will fall. Following each category are a number of b.Voltage regulator (VR) failed in ON position
possible component failures that may cause the malfunction. (Test 2).
Listed with each component is the test used to check the com- c.Exciter field circuit shorted or low resistance
ponent. (Test 2, 7).
d.Defective rotating exciter armature, rotating rectifier,
NOTE: Always use Test 1 first to determine if the alternator exciter field circuit or main alternator stator (Test 8).
or the exciter control package is at fault e.Engine speed too low. Reset injection pump/governor
speed to 1800 (10 rpm at Full Load (60 Hz or output);
1. Generator set will not pick up the load (low or no output 1950 (10 rpm No Load.
voltage).
a. Diode D5 is open circuit (Test 2, 6). 4. Generator set output voltage too high.
b. Voltage regular (VR) is defective (Test 2). a.Unit battery discharged (see preliminary check 3).
c.Diode D7 (part of bridge rectifier BR3) is open circuit b.Voltage regulator (VR) defective (Test 2).
(Test 2, 6). c.Power bridge (BRI) not functioning (Test 2,3,6).
d.Exciter field circuit in alternator is open circuit d.Shorted exciter armature (Test 8).
(Test 2, 7).
e. Genset Control Module is defective (Test 2). 5. Unit battery undercharged.
f. Alternator stator, main rotating field, rotating rectifier a.No output from power bridge (BRI) (Test 2,3,6).
or rotating rectifier exciter armature is defective (Test 8). b.Diode D6 open circuit (Test 2, 3, 5, 6).
c.PTC resistors (RI, R2) open circuit (Test 5).
2. Generator set tries to pick up the load but engine labors
excessively, eventually causing an overload condition
and causing the Genset Control Module to shutdown unit
operation.
a.Mechanical problems with engine (see preliminary
check 1).
b.Excessive load from refrigeration unit malfunction (see
preliminary check 2).
c.Current transformer (TRF2) or current bridge (BR2)
defective (Test 4, 6).
d.Diode D7 open circuit (Test 2, 6).
e. Genset Control Module defective (Test 2).
f. Defect in rotating field, rotating bridge, alternator main
field or alternator stator (Test 8).
16-8
Section 16-Gen-Set Alternator Procedures (New Control System)
TEST NO. 1 3. Connect one lead of the light assembly to a known good
12 Vdc source such as the No. 2 wire at the ammeter. The
This test will determine whether the alternator or the excita- other lead will be used later.
tion control system is causing the malfunction. The test
requires the use of the 1073 bulb. 4. Start the engine and make sure speed is 1800 ± 10 rpm at
Full Load (60 Hz alternator output); 1950 ± 10 rpm No
CAUTION: Make sure the generator set is disconnected Load. REMEMBER THAT HAZARDOUS ELECTRI-
from any load and the orange wire is jumpered to ground. CAL POTENTIALS will be present on alternator output
Severe damage to the current transformer will occur if the terminals on exciter control. The ground (negative) con-
load should attempt to start during this test. nection bypasses all exciter control overload protection,
and CARE MUST BE EXERCISED TO AVOID DAM-
1. Connect a jumper from orange to ground (CH) on circuit
AGE TO THE ALTERNATOR IN THE EVENT THERE
board during test.
IS AN INTERNAL OR EXTERNAL SHORT CIRCUIT.
2. Disconnect F1 and F2 leads from the alternator. Using a
jumper wire, connect F2 to a known good ground.
16-9
Section 16-Gen-Set Alternator Procedures (New Control System)
5. Attach the free lead of the bulb assembly to Fl. A slight 7. Low or no output voltage indicates a problem in the
change in the sound of the engine should be evident as exciter field coils or the alternator itself To check alterna-
alternator voltage and excitation builds up. tor or field coils, see Tests 7 and 8.
CAUTION: If the engine bogs down or produces black 8. Normal output voltage indicates alternator is almost in
smoke, there is a short circuit in the alternator or its output good condition. (Some machines may exhibit near nor-
circuits. In this event, disconnect the light assembly and mal output voltage with one defective rotating diode. A
shutdown the engine. defective rotating diode would impair the generator set
Refer to Test 7 and 8. motor-starting capabilities.) Ammeter should indicate
CHARGE. If not, power transformer, power bridge BR1
6. Measure alternator output voltages on L1-L2, L1-L3 and or diode D6 is defective (Tests 4, 6 and 7).
L2-L3. Voltage will normally be between 460 and 500
volts or 230 to 250 volts depending on engine speed and
whether the alternator stator is wired for 460 or 230 volt
operation.
16-10
Section 16-Gen-Set Alternator Procedures (New Control System)
CHECK
VOLT
CHECK
VOLT
CHECK
VOLT
CHECK
VOLT
3. Turn the unit switch ON, but DO NOT start-t the engine. f. Wire F2 at connector CN1 of Genset Control
Module -- 1 Vdc
4. Wait at least 15 seconds then using.- a dc voltmeter, NOTE: No voltage here may indicate an open field coil
check for voltage at the following locations: winding within the alternator. Higher voltage indicates a de-
energized or faded Field Relay or a failed Genset Control
NOTE: Voltage readings may vary slightly depending on Module.
battery voltage.
16-11
Section 16-Gen-Set Alternator Procedures (New Control System)
5. Turn the unit switch OFF. 9. Turn the refrigeration unit on to apply load to alternator.
Voltages should be as follows:
6. Reconnect connector CN2 to the Genset Control Module. a.No. 8 wire at circuit board ó 13 Vdc
b.No. 1A wire on terminal board ó 14 Vdc
7. Turn On-Off switch ON and start the generator set. c.GRN wire at bridge rectifier BR3 ó 8 Vdc
d.Wire Fl at terminal board ó 7.25 Vdc
8. Start the generator, but do not apply load. Voltages
should be as follows: Higher or lower normal voltages at F1 indicate voltage regu-
a. No. 8 wire at Genset Control Module ó 13.5 Vdc lator failure. Replace the voltage regulator. If alternator output
b. No. 1A wire on terminal board ó 14 Vdc still is too high or low, or if voltage at Fl is not connect check
c.GRN wire at bridge rectifier BR3 ó 5 Vdc field circuit overload (see Test 7).
d. Wire F1 at terminal board ó 4 Vdc
NOTE: A voltage regulator failure in the full ON condition
NOTE: The above voltages indicate that the alternator will cause high alternator voltage and will cause the Genset
output voltage is stepped down by transformer TRF1 and Control Module to shut the unit down from field circuit
rectified by the power bridge rectifier (BR1) thus increasing overload.
the voltage on wire 1A and causing the voltage regulator
10. The field circuit amperage can be checked with a dc
(VR) output to correctly respond by decreasing its output at
ammeter. Under normal load conditions, the field amper-
the GRN wire. age should be between 1.5 to 2-5 amps. If the amperage
is too high or too low, recheck the engine speed. If the
speed is correct, replace the regulator. If the amperage is
still not correct check the field circuit (see Test 7).
16-12
Section 16-Gen-Set Alternator Procedures (New Control System)
CHECK
VOLT
CHECK
VOLT
TEST NO. 3 If the voltage does not rise, using an ac voltmeter, check
the voltage across (XI-X2), (X2-X3), (X3-XI). The correct
Test 3 checks the power bridge (BRI) and power transformer voltage is approximately 12 to 13 Vac. This ac reading will be
(TRF1). If the power bridge fails completely, the voltage reg- less than the dc output of the power bridge rectifier. This is
ulator will not receive the normal voltage rise out of BRI. The normal and is due to the fact that the ac voltmeter does not
low voltage (battery voltage), in the 1A circuit keys the regu- read the peak voltage of an ac sine wave but reads an average
lator to go to full field current and therefore high or output figure (RMS factor). This phenomenon will usually only
voltage, eventually tripping the Genset Control Module from occur in a three-phase ac, bridge rectifier combination. If the
excessive field current and thus shutting the generator set ac voltage is coma but the dc output was low or nonexistent,
down. A defective power bridge also causes the unit ammeter replace the power bridge rectifier (BR1). If the ac voltage
to show a discharge condition, although the no charge condi- from the power transformer is low or nonexistent, replace the
tion can be caused by other malfunctions. power transformer (TRF1). It is virtually impossible to check
the ac input to the power transformers so if the alternator out-
To test the power bridge (BRI): put is near normal or high, assume that the power transformer
1. Attach a dc voltmeter to terminal 1A of the terminal input is normal.
board.
2. Turn the generator On-Off switch ON, but do not start the
engine. The voltmeter should slow a reading of 10 to 11
volts. (1.5 volts less than battery voltage)
3. Start the unit. The voltage should rise to approximately
14.5 volts (depending on batteries state of charge). This
indicates the power bridge (BR1) and power transformer
(TRF1) are functioning.
16-13
Section 16-Gen-Set Alternator Procedures (New Control System)
CHECK
VOLT
CHECK
VOLT
CHECK
VOLT
TEST NO. 4 2. Hook up a dc voltmeter across the green and black wires
on the adapter plug to measure exciter field voltage as
Test checks the output of the booster circuit. The shown. Voltmeter must have a range of at least 50 volts.
booster circuit is utilized when the generator starts up a
load. 3. Hook up a load (refrigeration unit) to the generator and
turn the refrigeration unit On-Off switch ON. Make sure
1. Disconnect the voltage regulator and install the Motorola the refrigeration unit thermostat is set below box temper-
adapter plug in its place. Attach one lead of the bulb ature so the unit will start immediately.
assembly to a known good 12 Vdc source (No. 2 wire on
the ammeter). The other lead will eventually be con- CAUTION: The generator set is not designed to start a
nected to the green wire on the Motorola adapter plug. refrigeration unit from a dead stop, but for this test an
exception is made.
16-14
Section 16-Gen-Set Alternator Procedures (New Control System)
4. Attach the bulb assembly lead to the green wire on the 6. Turn the refrigeration unit On-Off switch OFF once the
adapter and turn the generator set On-Off switch ON. The refrigeration unit is running. Turn the refrigeration unit
voltmeter should show 5 Vdc. back ON, and observe the voltmeter and or output volt-
age. Field voltage should rise momentarily as the refrig-
5. Start the generator set engine. The refrigeration should eration unit starts, and the alternator output voltage
start, and voltage should increase from 5 volts cranking should not drop below approximately 360 or 190 volts,
to 10 to 12 or possibly higher, and then drop back to depending on how the rise. If the required booster voltage
approximately 7 Vdc as the alternator picks up and starts is not present, check the current bridge rectifier (BR2)
the load. If field volume does not rise as the generator set (Test No. 6).
attempts to start the load or if the load will not start, the
booster system is not functioning properly. 7. If the current bridge rectifier (BR2) is ok, repeat the test
checking for ac voltage on (XI-X2), (X2-X3), (X3-XI) at
the booster bridge (BR2). If the normal voltage rise (10 to
12 Vac) is not present from the current transformer
(TRF2), replace the current transformer.
16-15
Section 16-Gen-Set Alternator Procedures (New Control System)
CHECK
VOLT
16-16
Section 16-Gen-Set Alternator Procedures (New Control System)
Reject diodes that have excessive leakage (read less than Test B -- Diodes 1
100,000 ohms) reverse polarity. Reject diodes that read low in
both directions or operate in forward direction. Checking for For-
ward
Good diodes will have a high resistance reading in one on and Conductance
a low reading when ohmmeter leads are reversed.
Good diode reads
2. Testing Bridge Rectifiers: 1/2 to 2/3 up scale.
a.Unsolder wires from rectifier.
b. Place one ohmmeter lead on RED dot terminal the
other lead on each ac terminal in turn. The three ohmme-
2
ter readings should be similar to each other.
c. Reverse lead polarity, and repeat the test. Results
should be all similar to test “A” in one polarity direction,
test “B” in the other (ohmmeter leads reversed). 1. Ohmmeter
d. Place one ohmmeter lead on the case, the other lead on 2. Lead
each ac terminal in turn. Reverse lead polarity and repeat
Results should be all similar to test “A” in one instance,
test “B” in the other.
16-17
Section 16-Gen-Set Alternator Procedures (New Control System)
OHM
METER
AJA581
TEST NO. 7
Test 7 determines the condition of the exciter field circuit.
16-18
Section 16-Gen-Set Alternator Procedures (New Control System)
TEST NO. 8
Test 8 includes testing the main alternator-stator, the rotating
field, the rotating rectifier, and the rotating field armature. All
tests must be made with reliable
equipment.
Alternator Stator
F1 Exciter F2
b.Using a megohmmeter, check for down between each Field
pair of leads.
c.Remove the end bell for the remaining checks. 4. Main Alternator Field.
a. Measure the resistance of the main alternator field.
2. Rotating Rectifier. Standard value is 2.5 ohms.
Six rectifying diodes mount on the rotating rectifier, three are b. Measure the main field to rotor or ground with a
positive and three are negative. megohmmeter.
a.Unbolt each of the diode leads.
Main
Field Exciter
NOTE: The diodes must be disconnected for testing, or false Rotor
test readings may occur.
b.Disconnect main alternator field leads which connect to
exciter diode heat sinks.
c.Check each diode in the forward and reverse direction
Ohmmeter
(refer to Test 6). Exciter F2
F1
Field
16-19
Section 16-Gen-Set Alternator Procedures (New Control System)
EMERGENCY OPERATION One of the more popular megohmmeters used in the field
today is the “Megger” manufactured by:
Emergency operation of generator set which has a defective AVO Biddle Instruments
regulator can be obtained by removing the regulator and con- Bluebell, Pennsylvania 19422
necting a No. 1073, No. 1076 or a No. 1034 (with both ele- Area Code: (215) 646-9200
ments wired in parallel) automotive lamp between RED and
adjacent GRN terminals on excitation control connector. This They may be contacted for more information on how to use
connection will result in higher dm normal voltage when the megohmmeter for testing or about various types of mego-
loaded and will result in overcharged batteries if used for hmeters available.
more than 24 hours.
If there has been a complete failure of the exciter control MAINTENANCE PROCEDURES
package, the generator set can still be operated by using the The following paragraphs cover detailed maintenance proce-
1073 light bulb attached to a 12 V source and then to the Fl dures, including disassembly and assembly or equipment for
wire and shorting the F2 wire at the Genset Control Module to necessary component removal and replacement. Many repair
the “CH” ground stud. With no battery charging capabilities or replacement operations can be performed without exten-
from the exciter control package, the unit battery voltage will sive disassembly of the generator.
eventually drop to a point at which the engine fuel solenoid
will disengage and stop the engine (2 to 4 hours). WARNING: DO NOT attempt adjustments or changes in
wiring while a unit is in operation. The unit generates
CAUTI0N: This is a very dangerous procedure in that the sufficient voltage to cause severe and possible fatal shock.
engine has no safety protection from low oil pressure or low Use extreme caution when operating in wet or damp
oil level or overheat conditions, or overload locations.
16-20
Section 16-Gen-Set Alternator Procedures (New Control System)
1 8 9
2 10 11
3
4
5 12
13
25 6 7
8 14
15 17 18
16
9 19
10
11
20
12
25
23 24
22 21
16-21
Section 16-Gen-Set Alternator Procedures (New Control System)
1 2
1. Bearing
2. Apply Grease Here
3. Shield
16-22
Section 17
Notes
Section 18-Miscellaneous
17-2
Section 18-Miscellaneous
17-3
Section 18-Miscellaneous
17-4
Section 18-Miscellaneous
17-5
Section 18-Miscellaneous
17-6
Section 18-Miscellaneous
17-7
Section 18-Miscellaneous
17-8
Section 18-Miscellaneous
17-9
Section 18-Miscellaneous
17-10
Section 8-Refrigeration Unit Schematic/Wiring Diagrams
8-3
Section 8-Refrigeration Unit Schematic/Wiring Diagrams
8-10
Section 8-Refrigeration Unit Schematic/Wiring Diagrams
8-11
Standard Display
NOTE: The screens that display on the controller
are determined by the Unit Configuration setting. Keypad Operating Tips
All screens are NOT present on all units.
Text Input: Use F1, F2, F3 and F4 keys to enter text in information screens:
• To enter a number: Press the F1 key and the desired number key.
Setpoint Menu • To enter 1st letter on a key: Press the F2 key, the desired letter key.
• To enter 2nd letter on a key: Press the F3 key, the desired letter key.
— Setpoint Temperature • To enter 3rd letter on a key: Press the F4 key, the desired letter key.
Enter a Temperature or
— Economy Mode
Humidity Setpoint NOTE: When a function key (F1, F2, F3 or F4) is pressed to enter text,
— Airflow
• Press F4 key. the keypad remains on that “character level” until another function key
— Custom Airflow
• Type the new setpoint. is pressed.
— Bulb Mode
• Press and hold F4 key until
— Humidity Control
cursor stops flashing. To Enter a Controller Menu or Use Special Function Key:
— Humidity Setpoint
— AFAM Control • Press F4 key to directly enter the Data menu.
MAIN MENU Activate Humidity Control • Press F2 key to directly enter the Alarms menu.
— AFAM Delay
or Economy Mode • Press F1 key to directly enter the Main Menu.
— AFAM Rate
• Press F4 key.
9-1
— Battery Voltage
— ALARMS — Voltage Average LED display.
• View and write down all alarm
codes. — Voltage 1
• Press F2 key to view the next — Voltage 2 To Lock a LCD Data Screen Display:
alarm code. — Voltage 3 • Each time the “5” key is pressed, the display time of the current LCD screen
• Clear alarm code by correcting — Frequency increases by 5 minutes. Maximum display time is 30 minutes for data
problem and acknowledging — Zero Current screens and 100 minutes for manual tests. Press F1 (ESC) key to exit dis-
the alarm. — Current Phase 1 play.
• To acknowledge an alarm, — Current Phase 2
press F4 key with alarm code in — Current Phase 3
display. — O2
— CO2
— Fresh Air Exchange Rate
— Evaporator Fan Speed
— Supply Air Temp, LH
To Activate a Command
• Press F4 key to start a:
Commands Menu - Manual Defrost
— COMMANDS - Function Test
— Defrost - PTI (Pretrip) Test
— Function Test
Manual Function Test
— PTI (Pretrip) Test
Submenu
— Manual Function Test
— Power Management • First Component Test appears
Power Management Submenu in display.
• Press F2 or F3 key to scroll to
• Current Power Limit and Power to the desired component:
Time appear in display. - Condenser Fan
• Press F3 key to scroll to - Compressor
Misc. Functions Menu desired - Capacity 25%
— MISC FUNCTIONS — Date Time function. - Capacity 50%
— C/F Mode Misc. Functions Submenu • Press F4 key. - Capacity 100%
— Cargo Data - Power Limit: Press F2 or F3 - Injection Valve
• Current function setting appears key to scroll to new setting.
— Program Version - Dehumidify Valve
in display. - Power Time: Type the new
— Run Time - Evaporator High
• Press F3 key to scroll to desired time in hours. - Evaporator Low
function. • Press and hold F4 key until - Heat
• Press F4 key to change a cursor stops flashing. - Zero Current
setting.
- Sensor Checks
• Type new value; or press F3
• Press F4 key to start and stop
key to toggle value to desired
test (toggle component display
setting.
between ON and OFF).
• Press and hold F4 key until
• More than one component
cursor stops flashing.
can be turned ON at a time to
perform a functional test of
the unit.
Configuration Menu
— CONFIGURATION — In-Range
— Container ID
— Contrast
— Language
Configuration Submenu
— Economy Max.
— Economy Min. • Current function setting
— Humidity Option appears in display.
Datalogger Menu — Reefer Type • Press F4 key to change a
— DATALOGGER — Inspect Temp Log — Zero Current setting.
— Inspect event Log Datalogger Submenu — Supply LH • Press F2 key, “A” key (pass-
— Set Log Time • First function screen appears: — Controlled Atmosphere word), F4 key and EXIT key.
— Activate Tripstart - Inspect Temp Log: Press F4 Option • Type new value; or press F3
— Inspect PTI Log key to view next screen. — Evaporator Fans key to toggle value to desired
Press F3 key to scroll through — AFAM Setup setting.
previous logs of sensors. — Auto Configuration • Press and hold F4 key until
- Inspect Event Log: Press F3 — Serial Number cursor stops flashing.
key to scroll through previous
event logs.
RMM Status - Set Log Time: Press F3 key to
— RMM STATE scroll through log interval list.
Display shows current Press and hold F4 key until
status: cursor stops flashing.
• Offline - Activate Tripstart: Press F4
• Zombie key to enter trip start marker.
• On-line - Inspect PTI Log: Press F3 key
through test result screens.
3PAUSE screen indicates controller has stopped unit operation due to a shutdown
— ECON OFF display FLASHES.
alarm. Controller restarts unit if alarm condition is corrected.
— HUMID OFF • Set calibration for 4Screen shows ONLY if spare sensor is ON in program menu. If USDA option is ON,
Press to select
— BULB OFF USDA1, USDA2, ONLY View Menu shows USDA1, USDA2 and USDA3.
ON (or PWRED
— PWRED 0 USDA3 and PULP. 5PULP optional display.
value) in right display. 6PCVAL displays on modulation valve systems. PCCAP displays on KVQ valve systems.
• Set HUMSP for
7Access code is 0007.
Press to load HUMID.
8C/oF units shown on the controller display can also be changed by pressing and holding
option. • Set BDFTT and
the oC/oF key, and then pressing ENTER key.
BEFAN for BULB. 9When a unit configuration is entered, a customer configuration MUST also be entered.
— Battery Voltage
ALARMS • View and write down all alarm — Voltage Average
codes.
Electrical, Refrigeration and Controller Menu Flow Diagrams
— Voltage 1
• Press F2 key to view the next — Voltage 2
alarm code. — Voltage 3
• Clear alarm code by correcting — Frequency
problem and acknowledging — Zero Current
the alarm. — Current Phase 1
• To acknowledge an alarm, — Current Phase 2
press F4 key with alarm code in — Current Phase 3
display.
To Activate a Command
• Press F4 key to start a:
Commands Menu - Manual Defrost
— COMMANDS - Function Test
— Defrost - PTI (Pretrip) Test
— Function Test
Manual Function Test
— PTI (Pretrip) Test
Submenu
— Manual Function Test
• First Component Test appears
in display.
• Press F2 or F3 key to scroll to
to the desired component:
- Condenser Fan
- R-134a Compressor
- R-23 Compressor
Misc. Functions Menu
- Capacity 100%
— MISC FUNCTIONS — Date Time - Evaporator Fans
— C/F Mode Misc. Functions Submenu - Heat
— Cargo Data - Zero Current
• Current function setting appears
— Program Version • Press F4 key to start and stop
in display.
— Run Time test (toggle component display
• Press F3 key to scroll to desired
between ON and OFF).
function.
• More than one component
• Press F4 key to change a
can be turned ON at a time to
setting:
perform a functional test of
- Date Time: Type the new
the unit.
setting.
- C/F Mode: Press F2 key to
toggle setting.
- Cargo Data: Press F3 key to
scroll to desired function.
Press F4 key. Type new
setting.
- Program Version: Displays
current setting only.
- Run Time: Press F3 key to
scroll to desired function.
Press F4 key. Type new
setting.
• Press and hold F4 key until
cursor stops flashing.
Configuration Menu
— CONFIGURATION — In-Range
— Container ID Configuration Submenu
— Contrast • Current function setting appears
— Zero Current in display.
• Press F4 key to change a
setting.
• Press F2 key, “A” key (pass-
word), F4 key and EXIT key.
Datalogger Menu • Type new value; or press F3
— DATALOGGER — Inspect Temp Log key to toggle value to desired
— Inspect event Log Datalogger Submenu setting.
— Set Log Time • First function screen appears: • Press and hold F4 key until
— Inspect PTI Log - Inspect Temp Log: Press F4 cursor stops flashing.
key to view next screen.
Press F3 key to scroll through
previous logs of sensors.
- Inspect Event Log: Press F3
CRR DF MPC2000ID Menu Flow Diagram
9-4
Section 14-Gen-Set Schematic/Wiring Diagrams
14-1
Section 14-Gen-Set Schematic/Wiring Diagrams
14-2
Section 14-Gen-Set Schematic/Wiring Diagrams
14-3
Section 14-Gen-Set Schematic/Wiring Diagrams
14-4
Section 14-Gen-Set Schematic/Wiring Diagrams
14-5
Section 14-Gen-Set Schematic/Wiring Diagrams
14-6