Академический Документы
Профессиональный Документы
Культура Документы
L/M/P/311 Series
3. Specifications......................................................................................................... 5
4. Application Information......................................................................................... 13
Operating Range........................................................................................ 13
Controllers................................................................................................. 13
5. Installations........................................................................................................... 18
6. Wiring Diagrams................................................................................................... 33
8. Troubleshooting.................................................................................................... 40
9. Dimensional Data................................................................................................. 41
Note : Installation and maintenance are to be performed only by qualified personnel who are
familiar with local codes and regulations, and experienced with this type of equipment.
Caution : Sharp edges and coil surfaces are a potential injury hazard. Avoid contact with them.
Warning : Moving machinery and electrical power hazard. May cause severe personnel
injury or death. Disconnect and lock off power before servicing equipment.
FT 10 L V1 L
Controller
L/I : Wireless Controller
M/J : Wired Controller
Power Supply
V1 : Single Phase, 220-240V, 50Hz
Series
L : L Series
M : M Series
P : P Series
Capacity Index
10 : Based on Btu/hr
Refrigerant
Blank : R22
N : R410A
Type of Air-Conditioner
FT : Wall Mounted
TM-FT-0415-B
R 18 C V1
Power Supply
V1 : Single Phase, 220-240V, 50Hz
Series
C : C Series
F : F Series
Capacity Index
18 : Based on Btu/hr
Refrigerant
Blank : R22
N : R410A
Type of Air-Conditioner
R : Single Split Condensing Unit
TM-FT-0415-B
Stylish Flat-Panel
Ideal blend of style and function. Regular cleaning is easier by just wiping the flat front panel. This
ensures the air-conditioner will always look brand new all the time.
Self Diagnosis
The microprocessor provides the possibility to detect and diagnose any fault or malfunction that occurs
in the system. The error will be reflected by the blinking of the LED lights.
10%
in
tF
Sli
Heat Transfer Efficiency
ic
p hil
ro
yd
in 15%
H
it F
Sl
F in
in
la
P
Rotary Compressor
The ever popular rotary compressor is more energy efficient and has a higher output to weight ratio.
TM-FT-0415-B
Space Saving
No space is required on either floor or ceiling. This newly developed super slim design for wall mounting
maximizes floor space usage and enhances ceiling appearance where ceilings are low.
1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.
3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER
AS A RESULT OF AMBIENT CONDITION.
1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.
3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER
AS A RESULT OF AMBIENT CONDITION.
TM-FT-0415-B
1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.
3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER
AS A RESULT OF AMBIENT CONDITION.
TM-FT-0415-B
1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.
3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER
AS A RESULT OF AMBIENT CONDITION.
1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.
3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER
AS A RESULT OF AMBIENT CONDITION.
TM-FT-0415-B
10
DRIVE DIRECT
DIAMETER mm/ in 106 / 4.17
LENGTH mm/ in 950 / 37.4
TYPE INDUCTION
QUANTITY 1
INDEX OF PROTECTION (IP) IP24
INSULATION GRADE CLASS B
POWER SOURCE V / Ph / Hz 220 - 240 / 1 / 50
FAN MOTOR RATED INPUT POWER W 71
RATED RUNNING CURRENT A 0.3
MOTOR OUTPUT W 40
POLES 4
HIGH 1300
SPEED MEDIUM RPM 1200
LOW 1080
MATERIAL SEAMLESS INNER GROOVE COPPER
TUBE DIAMETER mm / in 7.0 / 0.276
THICKNESS mm / in 0.28 / 0.011
MATERIAL ALUMINIUM
COIL
THICKNESS mm/ in 0.11 / 0.0043
FIN FACE AREA m² / ft² 0.30 / 3.23
ROW 2
FIN PER INCH 18
TYPE SARANET
QUANTITY pc 3
AIR QUALITY FILTER LENGTH mm / in 330 / 13.0
SIZE WIDTH mm / in 317 / 12.4
THICKNESS mm / in 1.8 / 0.07
TM-FT-0415-B
1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.
3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER
AS A RESULT OF AMBIENT CONDITION.
11
1) DUE TO OUR POLICY OF INNOVATION, ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO INTERNATIONAL STANDARDS SUCH AS ISO 5151 AND AHRI 210/240.
3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE MEASURED IN OYLM R&D SOUND ROOM. SOMEHOW DURING ACTUAL OPERATION, THE RESULT WILL BE HIGHER
AS A RESULT OF AMBIENT CONDITION.
TM-FT-0415-B
12
Cooling
50
46
43
40
OUTDOOR TEMP. DB (˚C)
Caution :
30
20
The use of your air conditioner
10
outside the range of working
temperature and humidity can
0 result in serious failure.
10 14 15 19 20 23 25
Controller
DGS01
1
TURBO QUIET
13
7 8
3
4 6
12 5
SLEEP MODE
TIMER
9 ON OFF 10
CANCEL CLOCK CANCEL
11
Operating Guide
1 Transmission Source
• The source where the signal will be transmitted.
3 “ON/OFF” Button
• Press once to start the air conditioner unit.
• Press again to stop the unit.
5 Operation mode
• Press the MODE button to select the type of operating mode.
• For cooling only unit, the available modes are: COOL ( ), DRY ( ) and FAN ( ).
7 Turbo function
• Press for fast cooling operation.
• Fan speed turn to maximum speed.
• Press again to deactivate the function.
• Available under COOL and DRY modes only.
• Any change of fan speed will deactivate this function.
8 Quiet function
• Press for quiet operation.
• Fan speed turn to minimum speed.
• Press again to deactivate the function.
• Any change of fan speed will deactivate this function.
9 ON timer setting
• Press the ON TIMER button will activate the on timer function.
• Set the desired on time by pressing the ON TIMER button continuously. If the timer is set to
7.30am, the air conditioner will turn on at 7.30am sharp.
• Press the CANCEL button to cancel the on timer setting.
13 Temperature setting
• To set the desired room temperature, press the or button to increase or decrease the
set temperature.
• The temperature setting range is from 16°C to 30°C.
• Press both buttons and simultaneously to toggle from °C to °F setting.
TM-FT-0415-B
14
3
2 4
1 MODE
TURBO SWING QUIET
5
8 TIMER
OVERRIDE
TIMER
ON
TIMER
OFF SLEEP
7 6
9 10
11
Operating Guide
1 MODE Button
Press the MODE button to switch operation from COOL, AUTO*, DRY*, FAN. Check the display to
see in which mode the control is set. *AUTO and DRY are available for selected models only.
3 SWING Function
Press SWING button to activate the swing function. Press it again to deactivate it.
6 SLEEP Function
Press the SLEEP button to activate the sleep mode. DRY MODE and FAN MODE are not valid
during sleep function.
TM-FT-0415-B
15
All timers are event-triggered timers and can be overridden by the ON/OFF button and Override function.
Set Event 1 and Event 2 Timers
Process for Timer ON and Timer OFF is the same.
1. Press and hold Timer ON/OFF key for 3 seconds to go into timer setting mode. (Icon ON 1 or
OFF 1 will blink)
2. Press UP or DOWN to select Timer 1 or Timer 2 to set. (‘1’ blinking indicate that Timer 1 is
currently selected, ‘2’ blinking indicate that Timer 2 is currently selected)
3. Press Timer ON/OFF key again to confirm. (Day will blink next)
4. Press UP or DOWN to select the day.
5. Press Timer ON/OFF key again to confirm the day. (Hour will blink next)
4. Press UP or DOWN to change the hour.
5. Press Timer ON/OFF key again to confirm the hour. (Minute will blink next)
6. Press UP or DOWN to change the minute.
7. Press Timer ON/OFF key again to confirm the minute.
Each timer (Timer 1 ON or Timer 1 OFF or Timer 2 ON or Timer 2 OFF) will only be set separately
after all 7 steps, if there is no key operation for 5 seconds during setting the timer, it will
automatically exits from setting mode and no changes will be made.
ON/OFF timer will be checked every 1 minute.
It is not advisable to set ON TIMER and OFF TIMER to have same values. Shall these occur, the
effective timer will be treated with priority as stated in Table 1.2.
Example:
ON TMR 2 settings: DAY – TUE, TIMER – 5.00pm
OFF TMR 1 settings: DAY – TUE, TIMER – 5.00pm
Outcome when RTC reaches 5.00pm on TUE:
- when unit is on, no respond.
- when unit is off, unit will trigger to on.
16
10 ON/OFF Button
Starting Operation:
- Press the ON/OFF button, the LCD will show full display and the unit is turned on.
Stopping Operation:
- Press the ON/OFF button, the LCD will show real time clock only and the unit is turn off.
12 Hardware Setting
The unit has 4 jumpers option to control the board function.
Table 2.0: Summary of Hardware Settings
Blink E4
short/Outdoor coil sensor short
Blink E5 Gas leak
Blink E6 Pump faulty
17
WARNING
• Installation and maintenance should be performed by qualified persons who are familiar with local code
and regulation, and experienced with this type of appliance.
• All field wiring must be installed in accordance with the national wiring regulation.
• Ensure that the rated voltage of the unit corresponds to that of the name plate before commencing wiring
work according to the wiring diagram.
• The unit must be GROUNDED to prevent possible hazard due to insulation failure.
• All electrical wiring must not touch the refrigerant piping or any moving parts of the fan motors.
• Confirm that the unit has been switched OFF before installing or servicing the unit.
• Disconnect from the main power supply before servicing the air conditioner unit.
• DO NOT pull out the power cord when the power is ON. This may cause serious electrical shocks which
may result in fire hazards.
• Keep the indoor and outdoor units, power cable and transmission wiring, at least 1m from TVs and radios,
to prevent distorted pictures and static. {Depending on the type and source of the electrical waves, static
may be heard even when more than 1m away}.
CAUTION
Please take note of the following important points when installing.
• Do not install the unit where leakage of flammable gas may occur.
If gas leaks and accumulates around the unit, it may cause fire ignition.
• Sharp edges and coil surfaces are potential locations which may cause injury hazards.
Avoid from being in contact with these places.
• Before turning off the power supply, set the remote controller’s ON/OFF switch to the “OFF” position
to prevent the nuisance tripping of the unit. If this is not done, the unit’s fans will start turning
automatically when power resumes, posing a hazard to service personnel or the user.
• Do not operate any heating apparatus too close to the air conditioner unit. This may cause the plastic
panel to melt or deform as a result of the excessive heat.
• Ensure the color of wires of the outdoor unit and the terminal markings are same to the indoors respectively.
• IMPORTANT : DO NOT INSTALL OR USE THE AIR CONDITIONER UNIT IN A LAUNDRY ROOM.
• Do not use joined and twisted wires for incoming power supply.
NOTICE
Disposal requirements
Your air conditioning product is marked with this symbol. This means that electrical and electronic
products shall not be mixed with unsorted household waste.
Do not try to dismantle the system yourself: the dismantling of the air conditioning system, treatment
of the refrigerant, of oil and of other parts must be done by a qualified installer in accordance with
relevant local and national legislation. Air conditioners must be treated at a specialized treatment
facility for re-use, recycling and recovery. By ensuring this product is disposed of correctly, you will
TM-FT-0415-B
help to prevent potential negative consequences for the environment and human health. Please
contact the installer or local authority for more information.
Batteries must be removed from the remote controller and disposed of separately in accordance with
relevant local and national legislation.
18
Indoor unit
Caulk pipe Cut thermal insulation pipe
75mm or more from ceiling hole gap to an appropriate length and
with putty. wrap it with tape, making
Front panel sure that no gap is left in the
insulation pipe’s cut line.
500mm from
Outdoor unit wall
Caution
• Before installing the unit, ensure that the power supply matches the power requirement of the air conditioner.
Installation Clearances
C D
Dimension A B C D
Service access
Return air
Obstacle
obstruction at the upper part of the unit, please allow more space than
the figure indicated in the above table.
19
min. 75
the hot return air. Please follow the installation
clearance shown in the figure. Do not place the indoor
unit where there could be direct sunlight shining on it. min. 50 min. 50
Also, this location must be suitable for piping and (Space for
Required space
(Space for
drainage, and be away from doors or windows. maintenance) maintenance)
All dimensions are in mm
The refrigerant piping can be routed to the unit in a number of ways (left or right from the back of the unit), by
using the cut-out holes on the casing of the unit (see figure). Bend the pipes carefully to the required position
in order to align it with the holes. For the side and bottom out, hold the bottom of the piping and then position
it to the required direction (see figure). The condensation drain hose can be taped to the pipes.
Remove pipe
port cover here
for left-side
Right-side piping
piping
Right-back piping Left-side
Remove pipe port cover
piping
here for right-side piping Right-bottom
piping Remove pipe port cover here Left-back
Bind coolant pipe for left-bottom piping piping
Remove pipe port cover here and drain hose
for right-bottom piping Left-bottom piping
together with
insulating tape.
Marking-offline
Mounting plate
TM-FT-0415-B
fixing screw
Thread
20
42.2
61
61
Through
288
the wall
310
hole Through the
Ø 65mm wall hole
45.9
Ø 65mm
45.9
40
40
54.5 153.8 263 181.7 55.5
51.9 Drain Liquid pipe end Gas pipe end Drain hose
800 45 91 219 48
hose 580 45
1065
position
Liquid pipe end Gas pipe end position
Inside Outside
Wall embedded pipe
(Field supply) Caulking
When stripping Mounting plate
the ends of
interconnecting
wires in advance,
Ø 65 bind right ends Interconnecting
Wall hole cover
(Field supply) of wires with wires
insulating tape.
Wall embedded pipe Wire guide
(Field supply)
with the upper edge of the installation plate). Ensure that the
hooks are properly seated on the installation plate by moving it
to the left and right. Clip
Water Drainage
Water
retention End
dipped
CAUTION
Water Water Water into • Do not install the unit at altitude over 2000m
leaking leaking leaking water for both indoor and outdoor.
TM-FT-0415-B
Drain
Correct Wrong Wrong Wrong
21
Indoor Unit
L E
Outdoor Unit
For R22:
Indoor FT10LV1L/M FT15LV1L/M FT20LV1L/M FT25LV1L/M
FT311V1L/M
Model FT10MV1I/J FT15MV1I/J FT20MV1I/J FT25MV1I/J
Outdoor R09CV1 R15CV1 R18CV1 R20CV1 R25CV1 R31CV1
Min. Allowable Length (L), m 3
Max. Allowable Length (L), m 12 15 25
Additional Charge of Refrigerant (g/m) 20 37
Max. Allowable Elevation (E), m 5 8
Gas Pipe Size, mm / (in) 9.50 (3/8”) 12.70 (1/2”) 15.88 (5/8”)
Liquid Pipe Size, mm / (in) 6.35 (1/4”) 6.35 (1/4”) 9.50 (3/8”)
For R410A :
Example:
TM-FT-0415-B
FT10LV1L & R09CV1 with 12m piping length, additional piping length is 4.5m. Thus,
Additional charge = 4.5m x [20g/m]
= 90 [g]
* Be sure to add the proper amount of additional refrigerant. Failure to do so may result in reduced performance.
Remark: The refrigerant pre-charged in the outdoor unit is for piping length up to 7.5m.
22
A
position and burr remover at lower position to
prevent metal chips from entering the pipe. This
will avoid unevenness on the flare faces which
will cause gas leak.
• Insert the flare nuts, mounted on the connection
parts of both the indoor unit and outdoor unit, Ø Tube, D A (mm)
into the copper pipes.
Inch mm Imperial Rigid
• The exact length of pipe protruding from the top (Wing-nut Type) (Clutch Type)
surface of the swaging block is determined by
the flaring tool. See Figure C. 1/4" 6.35 1.3 0.7
• Fix the pipe firmly on the swaging block. Match the 3/8" 9.52 1.6 1.0
centers of both the swaging block and the flaring 1/2" 12.70 1.9 1.3
punch, then tighten the flaring punch fully.
5/8" 15.88 2.2 1.7
Piping Connection To The Units 3/4" 19.05 2.5 2.0
• Align the center of the piping and tighten the
flare nut sufficiently with fingers. See Figure D.
Figure D
• Finally, tighten the flare nut with torque wrench Flare joint Flared tube
until the wrench clicks.
• When tightening the flare nut with the torque
wrench, ensure that the tightening direction
follows the arrow indicated on the wrench.
Indoor piping Flare nut
• The refrigerant pipe connection are insulated by
closed cell polyurethane.
23
FT311V1L/R31CV1 FT311V1L
Indoor
FT311V1M/R31CV1 Outdoor Unit Model FT311V1M
Indoor Unit Terminal Block
Outdoor R31CV1
Terminal Block L
Voltage range** 220-240V/1Ph/50Hz +
COMP N
Power supply cable size* mm² 4
N2 Number of conductors 3
L
Power Supply Cable
N
FTN311V1L/RN28CV1 FTN311V1L
Indoor
FTN311V1M/RN28CV1 Model FTN311V1M
Indoor Unit Outdoor Unit Outdoor RN28CV1
Terminal Block Terminal Block
Voltage range** 220-240V/1Ph/50Hz +
COMP COMP
Power supply cable size* mm² 2.5
N2 N
Number of conductors 3
Interconnection cable size* mm² 2.5
N1 Number of conductors 3
Recommended time delay fuse A 20
L
24
Electric wire
Round crimp-style terminal
• Used the correct screwdriver for terminal screws tightening. Unsuitable screwdrivers can damage the
screw head.
• Over tightening can damage the terminal screws.
• Do not connect wire of different gauge to same terminal.
• Keep wiring in an orderly manner. Prevent the wiring from obstructing other parts and the terminal
box cover.
Connect wires of the same Do not connect wires of the Do not connect wires of
gauge to both side. same gauge to one side. different gauges.
TM-FT-0415-B
25
• If the gauge needle does not move to HANDLE LO HANDLE HI (ALWAYS CLOSED)
-760mmHg, be sure to check for gas leaks CHARGE HOSE
(using the refrigerant detector) at fl are type CHARGE HOSE VACUUM PUMP
ADAPTER FOR
connection of the indoor and outdoor unit and COUNTER FLOW
repair the leak before proceeding to the next PREVENTION
LIQUID
step. VALVE
CHECK
• Close the valve of the changing gauge and GAS VALVE VALVE
(3-WAY)
stop the vacuum pump.
• On the outdoor unit, open the suction valve (3 CONFIGURATION OF AIR PURGE
BY CHARGING
way) and liquid valve (2 way) (in anti-clockwise
direction) with 4mm key for hexagon sacked
screw. LOW PRESSURE GAUGE HIGH PRESSURE GAUGE
26
Indicator Lights
IR Signal Receiver
When an infrared remote control operating signal has been transmitted, the signal receiver on the indoor
unit will respond as below to confirm acceptance of the signal transmission.
IR Receiver
Cooling Unit
The table shows the LED indicator lights for the air conditioner unit under normal operation and fault
conditions. The LED indicator lights are located at the right-bottom of the air conditioner unit.
LED Indicator Lights for Cooling Unit
IR Receiver
Cool
Timer
Sleep
ON/OFF ON/OFF switch
TM-FT-0415-B
27
Cool Mode – –
Green
Timer on – –
Sl eep m ode on – –
Fan m ode on – –
D r y m ode on – –
Compressor overload /
Indoor coil sensor short / Call your dealer Blink E4
1 time
outdoor coil sensor short
D ef r ost oper at i on – –
Red
Hardware error (tact switch pin short) Call your dealer Blink E8
6 times
4 times
No feedback from indoor fan Call your dealer Blink E9
ON ON or OFF Blinking
TM-FT-0415-B
28
Timer on -
Sleep mode on -
Dry mode on -
- ON / - ON or OFF - Blinking
TM-FT-0415-B
29
Frost Prevention
• When the air filter is dirty, the evaporating temperature will decrease and eventually cause frosting.
• If the evaporating temperature reaches -1°C/33.8°F, the unit will trip.
ATTENTION
• Always use a remote controller to adjust the flaps angle. If you attempt to move it forcibly with hand
when it is swinging, the mechanism may be broken.
• Be careful when adjusting the louvers. Inside the air outlet, a fan is rotating at a high speed.
When stop
operation
Upper limit 55˚
Lower limit 85˚
30
(2) Components
Mixture weight composition R32(50%) and R125(50%)
(3) Characteristic
• R410A liquid and vapour components have different compositions when the fluid
evaporates of condenses. Hence, when leak occurs and only vapor leaks out, the composition
of the refrigerang mixture left in the system will change and subsequently affect the system
performance. DO NOT add new refrigerant to leaked system. It is recommended that the system
should be evacuated thoroughly before recharging with R410A.
• When refrigerant R410A is used, the composition will differ depending on whether it is in
gaseous or liquid phase. Hence when charging R410A, ensure that only liquid is being withdrawn
from the cylinder or can. This is to make certain that only original composition of R410A is being
charged into the system.
• PVE oil is used as lubricant for R410A compressor, which is different from the mineral oil used for
R22 compressor. Extra precaution must be taken not to expose the R410A system too long to
moist air.
(4) Check List Before Installation / Servicing
• Tubing
Refrigerant R410A is more easily affected by dust of moisture compared with R22, make
sure to temporarily cover the ends of the tubing prior to installation.
• Compressor oil
No additional charge of compressor oil is permitted.
• Refrigerant
No other refrigerant other that R410A
• Tools (size of service port is different from R22 system)
Tools specifically for R410A only (must not be used for R22 or other refrigerant)
i) Gauge manifold and charging hose
ii) Gas leak detector
iii) Refrigerant cylinder/charging cylinder
iv) Vacuum pump c/w adapter
v) Flare tools
vi) Refrigerant recovery machine
31
(e) Normally, the R410A cylinder or can is being equipped with a dip pipe for liquid withdrawal.
However, if the dip pipe is not available, invert the cylinder or can so as to withdraw liquid from the
valve at the bottom.
TM-FT-0415-B
32
Outdoor Unit
Model : R09/15CV1
RN10/15FV1
WHITE WHITE
TM-FT-0415-B
33
Outdoor Unit
Model : R18/20/25CV1, RN20/25CV1
WHITE
TM-FT-0415-B
34
Outdoor Unit
Model : R09/15CV1
RN10/15FV1
WHITE WHITE
TM-FT-0415-B
35
Outdoor Unit
Model : R18/20/25CV1
RN20/25CV1
WHITE
TM-FT-0415-B
36
TM-FT-0415-B
Outdoor Unit
Model : R31CV1, RN28CV1
37
! CAUTION
• Don’t touch the metal parts of the indoor unit. It may cause an injury.
• When removing or attaching the front panel, use a robust and stable stool and watch your steps carefully.
• When removing or attaching the front panel, support the panel securely with hand to prevent from it falling.
• For cleansing, do no use hot water above 40°C, benzene, gasoline, thinner, nor other volatile oils, polishing
compound, scrubbing brushes, nor other hand stuff.
• After cleaning, make sure that the front panel is securely fixed
TM-FT-0415-B
38
The design of the outdoor series allows servicing to be carried out easily. The removal of the top, front
and side panels makes almost every part accessible.
Under normal circumstances, these outdoor units only require a check and cleaning of air intake coil
surface once every 3 months. However, if a unit is installed in areas subjected to much oil mist and dust,
the coils must be regularly cleaned by qualified Air Conditioner Service Technicians to ensure sufficient
heat exchange and proper operation. Otherwise, the systems life span may be shortened.
! Caution
Do not charge OXYGEN, ACETYLENE OR OTHER FLAMMABLE and poisonous gases into the unit when
performing a leakage test or an airtight test. These gases could cause severe explosion and damage if
exposed to high temperature and pressure.It is recommended that only nitrogen or refrigerant be charged
when performing the leakage or airtight test.
TM-FT-0415-B
39
No Fau l t c o n d i t i o n s Po s s i b l e c au s es / c o r r ec t i v e ac t i o n s
1 The air conditioner unit will not resume after • The auto restart function is not functioning. Please
power failure. turn on the unit with the wireless / wired controller.
2 The compressor does not operate 3 minutes • Protection against frequent starting.
after the air conditioner unit is started. • Wait for 3 or 4 minutes for the compressor to start
operating by it self.
3 The airflow is too slow or room cannot be • The air filter is dirty.
cooled sufficiently. • The doors and windows are opened.
• The air suction and discharge of both indoor and
outdoor units are clogged or blocked.
• The regulated temperature or temperature setting
is not low enough.
4 Discharge airflow has bad odor. • Cigarettes, smoke particles, perfume and others,
which might have adhered onto the coil, may
cause odor.
• Contact your nearest dealer.
5 Condensation on the front air grille of the indoor • This is caused by air humidity after an extended
unit. period of operation.
• The set temperature is too low. Increase the
temperature setting and operate the unit at high
fan speed.
6 Water flowing out from the air conditioner. • Switch off the unit and contact your nearest
dealer. This might be due to tilted installation.
7 Hissing airflow sound from the air conditioner • Liquid refrigerant flowing into the evaporator coil.
unit during operation.
9 Compressor operates continuously. • Dirty air filter. Clean the air filter.
• Temperature setting too low (cooling). Use higher
temperature setting.
10 No cool air comes out during cooling cycle. • Temperature setting too high (cooling). Use lower
temperature setting.
TM-FT-0415-B
40
REAR REAR
LEFT RIGHT
C
TOP VIEW
NAME PLATE
B
SIGNAL RECEIVER
B
TERMINAL
INDOOR UNIT BLOCK WITH
ON/OFF SWITCH EARTH
BOTTOM BOTTOM SIDE VIEW TERMINAL
ROOM TEMPERATURE
LOUVER FRONT GRILLE FIXED SCREWS THERMISTOR (INSIDE)
(INSIDE)
FRONT VIEW
D E
F
F
B
G
G
H J K I
L M Drain hose position
A
FT10/15MV1I
TM-FT-0415-B
FT10/15MV1J
FTN10/15MV1I9 800 288 216 166 184 42 46 55 56 154 182 263 52
FTN10/15MV1J9
41
F
F
hole Ø 65mm
G
G
H J Drain hose position
L M K I
A
FT10/15MV1I
FT10/15MV1J
FTN10/15MV1I9 800 288 216 104 141 30 46 55 56 153 181 207 52
FTN10/15MV1J9
TM-FT-0415-B
42
D E
F
F
B
G
H J Liquid pipe end Gas pipe end K I Drain hose position
L M
A
FT20/25MV1I
FT20/25MV1J
1065 310 233 190 173 61 40 45 48 91 219 580 45
FTN20/25MV1I9
FTN20/25MV1J9
Indoor Unit
Model : FT311V1L, FT311V1M
FTN311V1L, FTN311V1M
200.0
360.0
TM-FT-0415-B
327.0
347.0
Note : Dimension in mm
43
L K L
N
M
C
N
30
A C
O D G H
3
F
E
B
65
80
I J
19
Dimension
Model A B C D E F G H I J K L M N O
44
H I
G
P
N
J
O
E F
D B C
A
L
M K All dimensions are in mm
Dimension
Model A B C D E F G H I J K L M N O P
TM-FT-0415-B
45
N
M
C
P
N
C
A
O D G H
Q
F
E
B
T
S
I J
R
Dimension
Model A B C D E F G H I J K L M N O
R18/20CV1
855 628 328 520 179 46 93 149 101 113 603 126 164 17 34
RN20/25CV1
R25/31CV1
855 730 328 533 182 44 93 149 101 113 603 126 164 17 47
RN28CV1
Dimension
Model P Q R S T
R18/20CV1
32 3 23 73 75
RN20/25CV1
R25/31CV1 3
32 23 73 75
RN28CV1
TM-FT-0415-B
46
NO DESCRIPTION NO DESCRIPTION
1 ASSY., FRONT GRILLE 12 ASSY, INSTALLATION PLATE
2 PANEL 13 RIGHT SIDE PANEL
3 AIR FILTER 14 DRIP PROOF COVER
4 FRONT GRILLE 15 CLIP, COIL SENSOR
5 ASSY, CONTROL BOX 16 ASSY, HEAT EXCHANGER
6 ASSY, SERVICE COVER 17 ASSY, DRAIN HOSE
7 ASSY, PIPING FIXTURE 18 FAN BEARING VIBRATION ABSORBER SET
8 MOTOR 19 ASSY, DISCH, GRILLE HOR. BLADE
9 MOTOR MOUNTING PLATE (1) 20 ASSY BOTTOM FRAME
10 MOTOR MOUNTING PLATE (2) 21 ASSY, PCB (WITH LAMP COVER)
11 BLOWER, CROSS FLOW
TM-FT-0415-B
* DUE TO OUR POLICY OF INNOVATION, SOME SPECIFICATIONS MAY BE CHANGED WITHOUT NOTIFICATION.
47
NO DESCRIPTION NO DESCRIPTION
1 ASSY., FRONT GRILLE 12 ASSY, INSTALLATION PLATE
2 PANEL 13 RIGHT SIDE PANEL
3 AIR FILTER 14 DRIP PROOF COVER
4 FRONT GRILLE 15 CLIP, COIL SENSOR
5 ASSY, CONTROL BOX 16 ASSY, HEAT EXCHANGER
6 ASSY, SERVICE COVER 17 ASSY, DRAIN HOSE
7 ASSY, PIPING FIXTURE 18 FAN BEARING VIBRATION ABSORBER SET
8 MOTOR 19 ASSY, DISCH, GRILLE HOR. BLADE
9 MOTOR MOUNTING PLATE (1) 20 ASSY BOTTOM FRAME
10 MOTOR MOUNTING PLATE (2) 21 ASSY, PCB (WITH LAMP COVER)
11 BLOWER, CROSS FLOW
TM-FT-0415-B
* DUE TO OUR POLICY OF INNOVATION, SOME SPECIFICATIONS MAY BE CHANGED WITHOUT NOTIFICATION.
48
NO DESCRIPTION NO DESCRIPTION
1 ASSY., FRONT GRILLE 12 ASSY, INSTALLATION PLATE
2 PANEL 13 RIGHT SIDE PANEL
3 AIR FILTER 14 DRIP PROOF COVER
4 FRONT GRILLE 15 CLIP, COIL SENSOR
5 ASSY, CONTROL BOX 16 ASSY, HEAT EXCHANGER
6 ASSY, SERVICE COVER 17 ASSY, DRAIN HOSE
7 ASSY, PIPING FIXTURE 18 FAN BEARING VIBRATION ABSORBER SET
8 MOTOR 19 ASSY, DISCH, GRILLE HOR. BLADE
9 MOTOR MOUNTING PLATE (1) 20 ASSY BOTTOM FRAME
10 MOTOR MOUNTING PLATE (2) 21 ASSY, PCB (WITH LAMP COVER)
11 BLOWER, CROSS FLOW 22 PLASMA GENERATOR
TM-FT-0415-B
* DUE TO OUR POLICY OF INNOVATION, SOME SPECIFICATIONS MAY BE CHANGED WITHOUT NOTIFICATION.
49
NO DESCRIPTION NO DESCRIPTION
1 ASSY., CHASSIS 10 ASSY., CONTROL BOX
2 MOTOR 11 ASSY., PCB (WITH LAMP COVER)
3 BLOWER, CROSS FLOW 12 CONTROL BOX COVER
4 FAN BUSH 13 SERVICE COVER
5 MOTOR COVER 14 ASSY., MOUNTING PLATE
6 ASSY., INDOOR COIL 15 ASSY., FRONT COVER
7 ASSY., AIR DISCHARGE HOUSING 16 FRONT COVER
8 ASSY., LOUVER 17 PANEL
9 PVC HOSE 18 FILTER
* DUE TO OUR POLICY OF INNOVATION, SOME SPECIFICATIONS MAY BE CHANGED WITHOUT NOTIFICATION.
TM-FT-0415-B
50
NO DESCRIPTION NO DESCRIPTION
1 ASSY., CHASSIS 10 ASSY., CONTROL BOX
2 MOTOR 11 ASSY., PCB (WITH LAMP COVER)
3 BLOWER, CROSS FLOW 12 CONTROL BOX COVER
4 FAN BUSH 13 SERVICE COVER
5 MOTOR COVER 14 ASSY., MOUNTING PLATE
6 ASSY., INDOOR COIL 15 ASSY., FRONT COVER
7 ASSY., AIR DISCHARGE HOUSING 16 FRONT COVER
8 ASSY., LOUVER 17 PANEL
9 PVC HOSE 18 FILTER
* DUE TO OUR POLICY OF INNOVATION, SOME SPECIFICATIONS MAY BE CHANGED WITHOUT NOTIFICATION.
TM-FT-0415-B
51
19
NO DESCRIPTION NO DESCRIPTION
1 ASSY., CHASSIS 11 ASSY., PCB (WITH LAMP COVER)
2 MOTOR 12 CONTROL BOX COVER
3 BLOWER, CROSS FLOW 13 SERVICE COVER
4 FAN BUSH 14 ASSY., MOUNTING PLATE
5 MOTOR COVER 15 ASSY., FRONT COVER
6 ASSY., INDOOR COIL 16 FRONT COVER
7 ASSY., AIR DISCHARGE HOUSING 17 PANEL
8 ASSY., LOUVER 18 FILTER
9 PVC HOSE 19 PLASMA GENERATOR
10 ASSY., CONTROL BOX
* DUE TO OUR POLICY OF INNOVATION, SOME SPECIFICATIONS MAY BE CHANGED WITHOUT NOTIFICATION.
TM-FT-0415-B
52
21
20 19 18 17 16 15 14 13
NO DESCRIPTION NO DESCRIPTION
1 ASSY. INSTALLATION BRACKET 12 LED LIGHT BRACKET
2 ASSY. CHASSIS 13 CONTROL BOX COVER
3 PIPING CLAMP 14 ASSY. DRAIN HOSE
4 FAN BUSH BRACKET 15 AIR SWING MOTOR
5 CROSS FLOW FAN 16 AIR LOUVER
6 FAN BUSH 17 ASSY. AIR DISCHARGE HOUSING
7 ASSY., INDOOR COIL 18 COIL SENSOR CLIP
8 SERVICE PANEL 19 ASSY. FRONT COVER
9 CONTROL MODULE 20 SARANET FILTER
10 FAN MOTOR 21 THERMISTOR HOLDER
11 ASSY, CONTROL BOX
* DUE TO OUR POLICY OF INNOVATION, SOME SPECIFICATIONS MAY BE CHANGED WITHOUT NOTIFICATION.
TM-FT-0415-B
53
* DUE TO OUR POLICY OF INNOVATION, SOME SPECIFICATIONS MAY BE CHANGED WITHOUT NOTIFICATION.
TM-FT-0415-B
54
2 1
3
17
6
16
15
7 8 9 10 11 12 13 14
* DUE TO OUR POLICY OF INNOVATION, SOME SPECIFICATIONS MAY BE CHANGED WITHOUT NOTIFICATION.
TM-FT-0415-B
55
* DUE TO OUR POLICY OF INNOVATION, SOME SPECIFICATIONS MAY BE CHANGED WITHOUT NOTIFICATION.
TM-FT-0415-B
56
NO DESCRIPTION NO DESCRIPTION
1 ASSY. BASE PAN 11 FRONT PANEL, LEFT
2 ASSY. OUTDOOR COIL 12 TOP PANEL
3 MOTOR BRACKET 13 ASSY. CONTROL PANEL
4 FAN MOTOR 14 TERMINAL CONTROL PANEL
5 FAN BLADE 15 ASSY. VALVE COVER
6 VALVE BRACKET 16 ASSY. FRONT GRILLE
7 PARTITION 17 PLASTIC HANDLE, SIDE
8 COMPRESSOR 18 DISCHARGE PIPE
9 BACK PANEL, RIGHT 19 SUCTION PIPE
10 SERVICE PANEL 20 ASSY. CAP TUBE
* DUE TO OUR POLICY OF INNOVATION, SOME SPECIFICATIONS MAY BE CHANGED WITHOUT NOTIFICATION.
TM-FT-0415-B
57
21
NO DESCRIPTION NO DESCRIPTION
1 ASSY. BASE PAN 12 ASSY., PANEL FRONT LEFT
2 ASSY. OUTDOOR COIL 13 ASSY, FRONT GRILLE
3 MOTOR BRACKET 14 ASSY , PANEL TOP
4 MOTOR 15 PLASTIC, HANDLE FRONT
5 FAN BLADE 16 PLASTIC HANDLE
6 ASSY. VALVE BRACKET 17 PIPE, SUCTION
7 COMPRESSOR 18 PIPE, DISCHARGE
8 PANEL, SERVICE 19 ASSY. CAP TUBE
9 PANEL, PARTITION 20 FELT, COMPRESSOR
10 ASSY., VALVE COVER 21 ASSY., CONTROL PANEL
11 PANEL, RIGHT BACK
* DUE TO OUR POLICY OF INNOVATION, SOME SPECIFICATIONS MAY BE CHANGED WITHOUT NOTIFICATION.
TM-FT-0415-B
58