SETTING LIGHT
MEASURING MODE > PM

Type “PM”

MODE 0-5mA 0-20mA 4-20mA ••• 0-10 V 0-40 V Er.4-20

  PM

MODE Selection of the instrument


  measuring range
Menu Range
0-5mA 0…5 mA
0-20mA 0…20 mA
4-20mA 4…20 mA
DEF = 4 - 20 mA

MODE
0-2 V ±2 V
0-5 V ±5 V
0-10 V ±10 V
0-40 V ±40 V
Er.4-20 4…20 mA, with error statement of
„underfl ow“ upon signal smaller
than 3,36 mA

Range 0…20 mA Example

4-20mA 0-20 mA MIN A

MIN A 0 Setting for minimum 


input signal

MIN A Setting display projection for


  minimum value of input signal

- range of the setting: -99999…999999 - the DP is automatically shifted after the value is
confirmed
- position of the DP does not affect display
projection DEF = 0

Projection for 0 mA > MIN A = -25 Example

0 1 2 3 4 5

05 -5 -05 -15 -25 MAX A