Sprinkler System
Piping Support
© Fire Smarts LLC. All rights reserved.
Welcome
Russell B. Leavitt SET, CFPS
Executive Chairman
Russ is the Executive Chairman of Telgian Corporation. He is a
graduate of the University of Nevada, Las Vegas, holds a Level
IV certification from NICET in Fire Sprinkler Layout, and is a
Certified Fire Protection Specialist. He is a licensed contractor
with 38 years of experience in the design, installation, and
testing of fire protection systems. Russ is a member of the
board of directors and serves as 2nd Vice‐Chair for the
National Fire Protection Association (NFPA). He is currently
the chair for the NFPA 13 Technical Committee on Sprinkler
System Discharge Criteria as well as a member of the NFPA 13
Sprinkler System Installation Technical Committee, the NFPA
25 Technical Committee and several other NFPA technical
committees. Russ is a senior instructor for NFPA, AFSA and
Fire Smarts and has authored a number of articles and
training materials used throughout the industry.
© Fire Smarts LLC. All rights reserved.
DISCLAIMER
This seminar and its content is not a formal interpretation issued pursuant to
NFPA regulations. Any opinion expressed is the personal opinion of the
author and presenter and does not necessarily present the official position of
the NFPA and its Technical Committees. Furthermore, this presentation is
neither intended, nor should be relied upon, to provide professional
consultation or services.
© Fire Smarts LLC. All rights reserved.
Seminar Basis
Advisory information:
All NFPA 13 references are to the 2019 Edition
© Fire Smarts LLC. All rights reserved.
Hanging and Support of Piping
Chapter 17 ‐ NFPA 13 2019 edition
General Requirements
Hanger Components
Trapeze Hangers
Installation of Pipe Hangers
Pipe Stands
© Fire Smarts LLC. All rights reserved.
General Requirements
Alternate hangers that are certified by a
registered professional engineer are
permitted.
© Fire Smarts LLC. All rights reserved.
General Requirements
Certification must demonstrate the following:
Hangers can support 5 times the weight of the
water filled pipe plus 250 lbs
The points of support are adequate to support the
system
Spacing must not exceed specified limits in
chapter 17
Components must be ferrous
Detailed calculations must be submitted when
required by AHJ
© Fire Smarts LLC. All rights reserved.
General Requirements
Support of Non‐System Components
© Fire Smarts LLC. All rights reserved.
General Requirements
Shared Supports are permitted
Piping is permitted to share support structures
as long as they are certified by a registered
professional engineer. [17.1.3.2 and 17.1.4]
Criteria is found in 17.1.4.1.1 and 17.1.4.1.2
© Fire Smarts LLC. All rights reserved.
General Requirements
Shared Supports are permitted
© Fire Smarts LLC. All rights reserved.
General Requirements
Listed
© Fire Smarts LLC. All rights reserved.
General Requirements
N ot
Listed
© Fire Smarts LLC. All rights reserved.
General Requirements
Listed
Not‐Listed
© Fire Smarts LLC. All rights reserved.
General Requirements
Ferrous metals
(or proven adequate)
© Fire Smarts LLC. All rights reserved.
General Requirements
© Fire Smarts LLC. All rights reserved.
Hanger Components
Hanger rod size
Table 17.2.1.1
© Fire Smarts LLC. All rights reserved.
Hanger Components
© Fire Smarts LLC. All rights reserved.
Hanger Components
U‐Hooks
Table 17.2.1.4
Eye Rods
Table 17.2.1.5.1
© Fire Smarts LLC. All rights reserved.
Hanger Components
© Fire Smarts LLC. All rights reserved.
Hanger Components
Fasteners in Concrete
Post‐installed anchors
Listed
Cannot be used in cinder concrete for mains
Can be used with branch lines where alternated with
thru‐bolds or hangers attached to beams
Cannot be used in gypsum or similar soft materials
Installed horizontally unless certain conditions are met
Holes must be above the center line of the beam
© Fire Smarts LLC. All rights reserved.
Hanger Components
Fasteners in Concrete
Powder‐driven studs
Listed
Increaser couplings connected directly to the stud
Representative samples of concrete tested
750 lbs for 2 in. and smaller pipe
1000 lbs for 2.5 in. to 3.5 in. pipe
1200 lbs for 4 and 5 in. pipe
Table 17.2.2.10.1 Bolt and Rod Sizes
© Fire Smarts LLC. All rights reserved.
Hanger Components
Fasteners in Steel
Listed
Cannot be welded to steel less than 12 gauge
Table 17.2.3.5.1 Bolt and Rod Sizes
© Fire Smarts LLC. All rights reserved.
Hanger Components
Fasteners in Wood
Drive screws can only be use horizontally
2 in diameter pipe maximum
Must 2 points of connection
© Fire Smarts LLC. All rights reserved.
Hanger Components
Ceiling Flanges and U‐Hooks
Table 17.2.4.2.1
© Fire Smarts LLC. All rights reserved.
Hanger Components
Bolts, Rods, and Lag Screws
Table 17.2.4.1 sizes
Installed in the side of beam
All holes must be pre‐drilled
Bolts and rods must have washers and nuts
Wood screws must be installed with a screwdriver
Nails are not permitted
Must maintain minimum distances above bottom
of beam
© Fire Smarts LLC. All rights reserved.
Hanger Components
Table 17.2.4.7.1 Coach Screw Rod Sizes
Table 17.2.4.7.2 Plank Thickness and Beam or Joist
Widths
© Fire Smarts LLC. All rights reserved.
Trapeze Hangers
Must be secured to prevent slippage
All components must be sized to support the
suspended pipe
Rings and straps must be sized to fit the pipe
size of the trapeze member
Holes for bolts and rods cannot exceed 1/16th
in. greater than the diameter of the bolt or
rod
© Fire Smarts LLC. All rights reserved.
Trapeze Hangers
Table 17.3.1(a) Section Modulus for Trapeze
Members
Table 17.3.1(b) and (c) Available Section
Modulus for Common Trapeze Hangers
© Fire Smarts LLC. All rights reserved.
Trapeze Hangers
Table 17.3.1(a)
Span 1 1.25 1.1.5 2 2 2.5 3 3.5 4 5 6 8 10
1.5 0.08 0.08 0.09 0.09 0.10 0.11 0.12 0.13 0.15 0.18 0.26 0.34
2 0.11 0.11 0.12 0.13 0.14 0.15 0.16 0.17 0.20 0.24 0.34 0.45
2.5 0.14 0.14 0.15 0.16 0.18 0.21 0.23 0.25 0.30 0.36 0.50 0.69
3 0.16 0.17 0.18 0.19 0.20 0.22 0.24 0.26 0.31 0.36 0.51 0.67
3.5 0.19 0.20 0.21 0.22 0.24 0.26 0.28 0.30 0.36 0.42 0.60 0.78
© Fire Smarts LLC. All rights reserved.
Trapeze Hangers
Table 17.3.1(b)
© Fire Smarts LLC. All rights reserved.
Trapeze Hangers
A trapeze hanger is supporting 8 in. diameter
sch 10 pipe. The span between I‐beams is 8 ft
and the pipe will be located 2 ft from one beam.
What is the minimum diameter Sch. 40 pipe that can
be used for the trapeze member?
For Sch. 10?
For angle iron?
© Fire Smarts LLC. All rights reserved.
Trapeze Hangers
L = equivalent Length
a = distance from one support to the load
b = distance from the other support to the load
© Fire Smarts LLC. All rights reserved.
Trapeze Hangers
© Fire Smarts LLC. All rights reserved.
Trapeze Hangers
6.0 0.33 0.34 0.35 0.38 0.41 0.44 0.48 0.51 0.61 0.71 1.02 1.34
8 0.43 0.45 0.47 0.50 0.54 0.59 0.63 0.68 0.82 0.95 1.36 1.79
© Fire Smarts LLC. All rights reserved.
Trapeze Hangers
Pipe Modulus Angles Modulus
In. mm (in.³) (in.) (in.³)
Schedule 40
2 50 0.56 3 x 3 x 7/16 0.95
2.5 65 1.06 4 x 4 x 1/4 1.05
Pipe Modulus
In. mm (in.³)
Schedule 10
2.5 0.69
3 1.04
© Fire Smarts LLC. All rights reserved.
Trapeze Hangers
A trapeze hanger is supporting 8 in. diameter
sch 10 pipe. The span between I‐beams is 8 ft
and the pipe will be located 2 ft from one beam.
What is the minimum diameter Sch. 40 pipe that can
be used for the trapeze member? 2.5 in.
For Sch. 10? 3 in.
For angle iron? 4 x 4 x 1/4
© Fire Smarts LLC. All rights reserved.
Installation of Hangers
Supported substantially from building
structure
Toggle hangers are permitted for 1.5 in. pipe
or smaller under hollow tile or metal lath and
plaster
Supported by rack structure
Metal deck for 1 in. or smaller pipe
© Fire Smarts LLC. All rights reserved.
Installation of Hangers
© Fire Smarts LLC. All rights reserved.
Installation of Hangers
© Fire Smarts LLC. All rights reserved.
Installation of Hangers
Clearance to sprinklers
© Fire Smarts LLC. All rights reserved.
Installation of Hangers
Unsupported Lengths
© Fire Smarts LLC. All rights reserved.
Installation of Hangers
Unsupported Arm‐overs
© Fire Smarts LLC. All rights reserved.
Installation of Hangers
Hangers on Mains
© Fire Smarts LLC. All rights reserved.
Installation of Hangers
Multi‐story Buildings
© Fire Smarts LLC. All rights reserved.
Installation of Hangers
Pipe Stands
© Fire Smarts LLC. All rights reserved.
Installation of Hangers
Pipe Stands
5 times weight of water‐filled pipe plus 250
lbs
Components must be ferrous
Spacing limits apply
Calculations must be submitted when
requested
© Fire Smarts LLC. All rights reserved.