Fire 

Sprinkler System 
Piping Support

© Fire Smarts LLC.  All rights reserved.  
Welcome
Russell B. Leavitt  SET, CFPS
Executive Chairman
Russ is the Executive Chairman of Telgian Corporation. He is a 
graduate of the University of Nevada, Las Vegas, holds a Level 
IV certification from NICET in Fire Sprinkler Layout, and is a 
Certified Fire Protection Specialist.  He is a licensed contractor 
with 38 years of experience in the design, installation, and 
testing of fire protection systems.  Russ is a member of the 
board of directors and serves as 2nd Vice‐Chair for the 
National Fire Protection Association (NFPA).  He is currently 
the chair for the NFPA 13 Technical Committee on Sprinkler 
System Discharge Criteria as well as a member of the NFPA 13 
Sprinkler System Installation Technical Committee, the NFPA 
25 Technical Committee and several other NFPA technical 
committees.  Russ is a senior instructor for NFPA, AFSA and 
Fire Smarts and has authored a number of articles and 
training materials used throughout the industry. 

© Fire Smarts LLC.  All rights reserved.  
DISCLAIMER
This seminar and its content is not a formal interpretation issued pursuant to
NFPA regulations. Any opinion expressed is the personal opinion of the
author and presenter and does not necessarily present the official position of
the NFPA and its Technical Committees. Furthermore, this presentation is
neither intended, nor should be relied upon, to provide professional
consultation or services.

© Fire Smarts LLC.  All rights reserved.  
Seminar Basis
Advisory information:
 All NFPA 13 references are to the 2019 Edition

© Fire Smarts LLC.  All rights reserved.  
Hanging and Support of Piping

 Chapter 17 ‐ NFPA 13 2019 edition
 General Requirements
 Hanger Components
 Trapeze Hangers
 Installation of Pipe Hangers
 Pipe Stands

© Fire Smarts LLC.  All rights reserved.  
General Requirements

 Alternate hangers that are certified by a 
registered professional engineer are 
permitted. 

© Fire Smarts LLC.  All rights reserved.  
General Requirements

 Certification must demonstrate the following:
 Hangers can support 5 times the weight of the 
water filled pipe plus 250 lbs
 The points of support are adequate to support the 
system
 Spacing must not exceed specified limits in 
chapter 17
 Components must be ferrous
 Detailed calculations must be submitted when 
required by AHJ
© Fire Smarts LLC.  All rights reserved.  
General Requirements

Support of Non‐System Components

© Fire Smarts LLC.  All rights reserved.  
General Requirements

Shared Supports are permitted

Piping is permitted to share support structures 
as long as they are certified by a registered 
professional engineer.  [17.1.3.2 and 17.1.4]

Criteria is found in 17.1.4.1.1 and 17.1.4.1.2

© Fire Smarts LLC.  All rights reserved.  
General Requirements

Shared Supports are permitted

© Fire Smarts LLC.  All rights reserved.  
General Requirements

Listed

© Fire Smarts LLC.  All rights reserved.  
General Requirements

N ot
Listed

© Fire Smarts LLC.  All rights reserved.  
General Requirements

Listed

Not‐Listed

© Fire Smarts LLC.  All rights reserved.  
General Requirements

Ferrous metals
(or proven adequate)

© Fire Smarts LLC.  All rights reserved.  
General Requirements

© Fire Smarts LLC.  All rights reserved.  
Hanger Components

Hanger rod size
Table 17.2.1.1

© Fire Smarts LLC.  All rights reserved.  
Hanger Components

© Fire Smarts LLC.  All rights reserved.  
Hanger Components

U‐Hooks
 Table 17.2.1.4

Eye Rods
 Table 17.2.1.5.1

© Fire Smarts LLC.  All rights reserved.  
Hanger Components

© Fire Smarts LLC.  All rights reserved.  
Hanger Components

 Fasteners in Concrete
 Post‐installed anchors
 Listed
 Cannot be used in cinder concrete for mains
 Can be used with branch lines where alternated with 
thru‐bolds or hangers attached to beams
 Cannot be used in gypsum or similar soft materials
 Installed horizontally unless certain conditions are met
 Holes must be above the center line of the beam

© Fire Smarts LLC.  All rights reserved.  
Hanger Components

 Fasteners in Concrete
 Powder‐driven studs
 Listed
 Increaser couplings connected directly to the stud
 Representative samples of concrete tested 
 750 lbs for 2 in. and smaller pipe
 1000 lbs for 2.5 in. to 3.5 in. pipe
 1200 lbs for 4 and 5 in. pipe
 Table 17.2.2.10.1  Bolt and Rod Sizes

© Fire Smarts LLC.  All rights reserved.  
Hanger Components

 Fasteners in Steel
 Listed
 Cannot be welded to steel less than 12 gauge
 Table 17.2.3.5.1  Bolt and Rod Sizes

© Fire Smarts LLC.  All rights reserved.  
Hanger Components

 Fasteners in Wood
 Drive screws can only be use horizontally
 2 in diameter pipe maximum
 Must 2 points of connection

© Fire Smarts LLC.  All rights reserved.  
Hanger Components

 Ceiling Flanges and U‐Hooks
 Table 17.2.4.2.1

© Fire Smarts LLC.  All rights reserved.  
Hanger Components

 Bolts, Rods, and Lag Screws
 Table 17.2.4.1 sizes
 Installed in the side of beam
 All holes must be pre‐drilled
 Bolts and rods must have washers and nuts
 Wood screws must be installed with a screwdriver
 Nails are not permitted
 Must maintain minimum distances above bottom 
of beam 

© Fire Smarts LLC.  All rights reserved.  
Hanger Components

 Table 17.2.4.7.1 Coach Screw Rod Sizes
 Table 17.2.4.7.2 Plank Thickness and Beam or Joist 
Widths

© Fire Smarts LLC.  All rights reserved.  
Trapeze Hangers

 Must be secured to prevent slippage
 All components must be sized to support the 
suspended pipe
 Rings and straps must be sized to fit the pipe 
size of the trapeze member
 Holes for bolts and rods cannot exceed 1/16th
in. greater than the diameter of the bolt or 
rod

© Fire Smarts LLC.  All rights reserved.  
Trapeze Hangers

 Table 17.3.1(a) Section Modulus for Trapeze 
Members
 Table 17.3.1(b) and (c) Available Section 
Modulus for Common Trapeze Hangers

© Fire Smarts LLC.  All rights reserved.  
Trapeze Hangers

Table 17.3.1(a)
Span 1 1.25 1.1.5 2 2 2.5 3 3.5 4 5 6 8 10

1.5 0.08 0.08 0.09 0.09 0.10 0.11 0.12 0.13 0.15 0.18 0.26 0.34

2 0.11 0.11 0.12 0.13 0.14 0.15 0.16 0.17 0.20 0.24 0.34 0.45

2.5 0.14 0.14 0.15 0.16 0.18 0.21 0.23 0.25 0.30 0.36 0.50 0.69

3 0.16 0.17 0.18 0.19 0.20 0.22 0.24 0.26 0.31 0.36 0.51 0.67

3.5 0.19 0.20 0.21 0.22 0.24 0.26 0.28 0.30 0.36 0.42 0.60 0.78

© Fire Smarts LLC.  All rights reserved.  
Trapeze Hangers

Table 17.3.1(b)

Pipe Modulus Angle Modulus


in. mm (in.³) in. (in.³)
Schedule 10
1 25 0.12 1.5 x 1.5 x 3/16 0.10
1.25 32 0.19 2 x 2 x 1/8 0.13

1.5 40 0.26 2 x 1.5 x 3/16 0.18

2 50 0.42 2 x 2 x 3/16 0.19

2.5 65 0.69 2 x 2 x 1/4 0.25

© Fire Smarts LLC.  All rights reserved.  
Trapeze Hangers

A trapeze hanger is supporting 8 in. diameter 
sch 10 pipe.  The span between I‐beams is 8 ft 
and the pipe will be located 2 ft from one beam.
 What is the minimum diameter Sch. 40 pipe that can 
be used for the trapeze member?
 For Sch. 10?
 For angle iron?

© Fire Smarts LLC.  All rights reserved.  
Trapeze Hangers

L = equivalent Length
a = distance from one support to the load
b = distance from the other support to the load

© Fire Smarts LLC.  All rights reserved.  
Trapeze Hangers

© Fire Smarts LLC.  All rights reserved.  
Trapeze Hangers

Span 1 1.25 1.5 2 2.5 3 3.5 4 5 6 18 10

6.0 0.33 0.34 0.35 0.38 0.41 0.44 0.48 0.51 0.61 0.71 1.02 1.34

8 0.43 0.45 0.47 0.50 0.54 0.59 0.63 0.68 0.82 0.95 1.36 1.79

© Fire Smarts LLC.  All rights reserved.  
Trapeze Hangers
Pipe Modulus Angles Modulus
In. mm (in.³) (in.) (in.³)
Schedule 40
2 50 0.56 3 x 3 x 7/16 0.95
2.5 65 1.06 4 x 4 x 1/4 1.05

Pipe Modulus
In. mm (in.³)
Schedule 10
2.5 0.69
3 1.04

© Fire Smarts LLC.  All rights reserved.  
Trapeze Hangers

A trapeze hanger is supporting 8 in. diameter 
sch 10 pipe.  The span between I‐beams is 8 ft 
and the pipe will be located 2 ft from one beam.
 What is the minimum diameter Sch. 40 pipe that can 
be used for the trapeze member?   2.5 in.
 For Sch. 10?   3 in.
 For angle iron?   4 x 4 x 1/4

© Fire Smarts LLC.  All rights reserved.  
Installation of Hangers

 Supported substantially from building 
structure
 Toggle hangers are permitted for 1.5 in. pipe 
or smaller under hollow tile or metal lath and 
plaster
 Supported by rack structure
 Metal deck for 1 in. or smaller pipe

© Fire Smarts LLC.  All rights reserved.  
Installation of Hangers

© Fire Smarts LLC.  All rights reserved.  
Installation of Hangers

© Fire Smarts LLC.  All rights reserved.  
Installation of Hangers

Clearance to sprinklers

© Fire Smarts LLC.  All rights reserved.  
Installation of Hangers

Unsupported Lengths

© Fire Smarts LLC.  All rights reserved.  
Installation of Hangers

Unsupported Arm‐overs

© Fire Smarts LLC.  All rights reserved.  
Installation of Hangers

Hangers on Mains

© Fire Smarts LLC.  All rights reserved.  
Installation of Hangers

Multi‐story Buildings

© Fire Smarts LLC.  All rights reserved.  
Installation of Hangers

Pipe Stands

© Fire Smarts LLC.  All rights reserved.  
Installation of Hangers

Pipe Stands
 5 times weight of water‐filled pipe plus 250 
lbs
 Components must be ferrous
 Spacing limits apply
 Calculations must be submitted when 
requested

© Fire Smarts LLC.  All rights reserved.  
Questions and Comments

© Fire Smarts LLC.  All rights reserved.  