Академический Документы
Профессиональный Документы
Культура Документы
O&M Documentation
Procedural Handbook
Status RELEASED
Contents
Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1 Safety Rules and Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.1 Safety Rules for Equipment Under Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
1.2 Electrostatic Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2 BTS A910 RITs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.1 Adjust the MSUM (CGU) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2.2 Before You Start to Replace the BTS A910 or SSC RITs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.3 Replace BTS A910 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
2.4 Replace COBO RITs (Fuses and Abis Lightning Protection) . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
2.5 Replace ACCO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
2.6 Replace ABISCO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
2.7 Replace Fan Cassette . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
2.8 Replace Top of Cover with Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
2.9 Replace Integrated Antenna . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
2.10 Replace VSWR detector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
2.11 Replace SSC RITs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
2.11.1 Replace SSCB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
2.11.2 Replace SSCPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
2.11.3 Replace SSCFH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
2.11.4 Replace SSCF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
2.11.5 Replace SSCCF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
2.11.6 Replace SSC Lightning Protector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
3 BTS A9100 RITs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
3.1 Open and Close BTS A9100 Cabinets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
3.1.1 Before You Start to Open and Close BTS A9100 Cabinets . . . . . . . . . . . . . . . . . . 44
3.1.2 Open and Close BTS A9100 and External Battery Indoor Cabinets . . . . . . . . . 45
3.1.3 Open and Close BTS A9100 and External Battery Outdoor Cabinets . . . . . . . . 46
3.2 Adjust the Clock of the SUM (CGU) in the BTS A9100 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
3.3 Before You Start to Replace BTS A9100 RITs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
3.4 Physical RIT Positions in STASR/ACSR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
3.5 Replace ABAC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
3.6 Replace ACIB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
3.7 Replace AC Link Lightning Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
3.8 Replace ACRI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
3.9 Replace ADAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
3.10 Replace ADAM4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
3.11 Replace Air-Conditioner in External Outdoor Battery Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . 69
3.12 Replace ANX, ANY, ANC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
3.13 Replace ANX and ANY by ANC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
3.14 Replace APOD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
3.15 Replace BACO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
3.16 Replace BAC2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
3.17 Replace BATS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
3.18 Replace BCU1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
3.19 Replace BCU2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
3.20 Replace BU41 in Combination with PM08/PM11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
3.21 Replace BU100 in Combination with PM08/PM11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
3.22 Replace BU41/BU100 in Combination with PM12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
3.22.1 Replace BU41 in Combination with PM12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
3.22.2 Replace BU100 in Combination with PM12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
3.23 Replace BU101 in External Battery Cabinets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
3.24 Replace BU101 in MBO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
3.25 Replace External Diplexer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Figures
Figure 1: BTS A910 Installed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Figure 2: COBO Internal Layout - RITs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Figure 3: COBO Internal Layout - ACCO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Figure 4: COBO Internal Layout - ABISCO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Figure 5: BTS A910 with Two VSWR Detectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Figure 6: SSC, Position of RITs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Figure 7: SSC, Battery Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Figure 8: SSC, Installation of Battery Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Figure 9: SSCPS, LEDs Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Figure 10: SSCFH, Front View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Figure 11: SSCFH, Internal View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Figure 12: SSCCF, Detailed View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Figure 13: SSC, AC Connection Field . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Figure 14: CIMI/CIDI and CIMA/CIDE Front External Views . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Figure 15: MBI3/MBI5 Front External Views . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Figure 16: External Indoor Battery Cabinet Front View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Figure 17: COME/COMI/COEP Module Positions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Figure 18: CODE/CODI/COEP Module Positions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Figure 19: CPT2 Module Positions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Figure 20: MBO1 Module Positions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Figure 21: MBO2 Module Positions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Figure 22: Module Positions of External Outdoor Battery Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Figure 23: STASR/ACSR, Physical RIT Positions and Slot Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Figure 24: BU41 Battery Branches and Terminal Connections in Combination with PM08/PM11 . . . . . . . . 88
Figure 25: BU100 Battery Branch and Terminal Connections in Combination with PM08/PM11 . . . . . . . . . 90
Figure 26: BU41/BU100 Battery Branches and Terminal Connections (top view) in Combination with
PM12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Figure 27: BU101 Battery Unit and Terminal Connections in External Battery Cabinets . . . . . . . . . . . . . . . . . 96
Figure 28: BU101 Battery Branches and Terminal Connections (front view) . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Figure 29: LPFU Internal View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Tables
Table 1: BTS A910 variants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Table 2: VSWR detector variants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Table 3: BTS A9100 Antenna Network Module RIT Part Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Table 4: TMA Part Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
Table 5: BTS A9100 TRE Module RIT Part Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
Preface
Purpose The EVOLIUM BTS A9100/A910 Corrective Maintenance Handbook describes
how to perform EVOLIUM BTS maintenance. It breaks down each maintenance
task into a series of step-by-step instructions, and tells you what tools and
materials are required.
The handbook covers the following equipment configurations:
BTS A910, BTS A9100
CPT2
MBO1, MBO2
Note: Your network may not have some of the hardware included in the handbook.
For more information about these configurations, refer to the functional
description documents.
The Alcatel EVOLIUM TM Radio Solutions include the EVOLIUM BTS
A910/A9100 equipment described in this document.
Network technicians
Network operators.
MS-DOS
Telecommunications engineering
Anti-static procedures
Electrostatic precautions.
Ensure that work benches, stools, and floor mats have a conducting surface
connected to ground. Before handling static-sensitive components and
assemblies, ground yourself to the conducting surface using an anti-static
wrist strap.
Do not mark a PBA with a lead pencil or any other writing instrument.
Do not use synthetic brushes to clean equipment, and do not use dry
cleaning methods.
Transportation and Pack all containers used to transport and store static-sensitive components,
Storage and use aluminium container tubes if possible. If not, insert the component
terminations into electrically conductive foam.
Store spare PBAs in their appropriate polyethylene boxes. Keep the boxes
closed except when access to their contents is required.
Do not store PBAs in an area where the air is polluted with smoke, dust,
dangerous gases or other air-borne particles that may cause damage.
Do not stack PBAs side-by-side or on top of each other with the board
surfaces or components in contact with one another.
Components and PBAs Components and PBAs not in protective containers, must only be handled
by trained personnel in static-controlled work areas.
Do not handle a PBA by the gold-plated contact terminals and do not apply
direct pressure to the components.
Do not touch PBA connection pins or conductor paths.
Place PBAs that have been removed during maintenance with the soldered
side downwards on a conductive surface.
Do not scratch or rub the soldered side of a PBA with a sharp or rough
object.
This chapter tells you how to adjust the CGU and how to remove and replace
BTS A910 and SSC RITs.
It contains procedures for replacing the following RITs:
BTS A910
COBO
ACCO
ABISCO
Fan Cassette
Top of Cover with Fan
Integrated Antenna
VSWR detector
SSC RITs.
Have read Safety Rules and Precautions (Chapter 1) before performing any
maintenance procedures.
Be familiar with electrostatic precautions. Refer to Electrostatic Precautions
(Section 1.2) for more information.
Ensure that the MSUM (CGU) has had power continuously supplied for
the previous 15 minutes.
Ensure that the frequency counter has had the warm-up period specified by
the manufacturer.
Loss of Calls
Failure to comply with the prerequisites can result in the BTS being locked
(disabled) and all calls being lost.
5. Use the BTS terminal (see BTS Terminal User Guide chapter “Adjust the
OCXO”) to adjust the BTS clock for a frequency between 2 166 666.55
Hz and 2 166 666.77 Hz.
2.2 Before You Start to Replace the BTS A910 or SSC RITs
Read this section before starting the replacement procedures in this chapter.
Have read Safety Rules and Precautions (Chapter 1) before performing any
maintenance procedures.
Be familiar with electrostatic precautions. Refer to Electrostatic Precautions
(Section 1.2) for more information.
Know how to use the BTS terminal software.
Establish an efficient means of communication with an OMC-R operator in
order to lock (disable) and unlock (initialize) the BTS when required.
Impact on System This depends on the nature of the RIT and its position in the system. Refer to
the specific replacement procedures in this chapter.
Restrictions None.
Heavy Equipment
The BTS weighs 25 kg. Injury to personnel and damage to equipment may
result if it is dropped or otherwise mishandled.
Use suitable equipment to lift the BTS. Do NOT lift it from the mounting frame
until it is properly supported.
6. Using the BTS terminal, display the current transmission settings on the
BTS, and note them down for use in Step 22.
7. If applicable, remove the RJ45 slave connectors from the bottom of the BTS,
carefully noting their positions for re-connection.
Protective Cover Protective Cover
Fully in Place Partly Removed
Rear section
of protective
cover
BTS A910
COBO
21. Using the BTS terminal, update the Remote Inventory EEPROM with:
Commissioning (current installation) date
Network identity
22. Using the BTS terminal, set the transmission parameters (Q1 address) on
the BTS according to the removed BTS, as noted in Step 6.
23. Wait for 15 minutes for the OCXO to warm up and the oven alarm to
disappear.
24. Adjust the frequency of the CGU in the BTS. Refer toAdjust the MSUM
(CGU) (Section 2.1) for more information.
25. Using the BTS terminal, initialize BTS_TEL.
26. Using the BTS terminal, check that there are no outstanding alarms on the
BTS, and that all SBLs are in traffic.
27. Disconnect the BTS terminal.
28. Replace the COBO front cover in position over the base, and then tighten
the retaining bolts.
29. If applicable, re-connect the power and alarm cables to the fan from the
COBO.
30. Replace the front protective cover in position over the BTS.
Locating
Pin
BTS
BTS Calib Fuses
Abis Lightning
Protection
MMI
Fan ACCO
Fuses
ABISCO
5. Remove the appropriate faulty RIT and replace it with a new one. The
following items are replaceable:
Locating
Pin
BTS Calib
L
E AC Fan
N L E N
MMI
AC In
L E N L E N
Ac Slave2 Ac Slave1
ACCO
ABISCO
4. Connect the BTS terminal to the MMI port inside the COBO.
5. Using the BTS terminal, display antenna mapping, external alarm mapping,
additional modules (e. g. cover , fan, SSC, VSWR), BTS site name and
note them down for use in Step 13.
6. Switch OFF the AC power supply to the COBO.
Locating
Pin
BTS Calib
Alarm
Alarm
MMI
Abis 1 Abis 2
Alarm
Alarm ACCO
ABISCO
7. Disconnect the Abis cable from the Abis 1 and Abis 2 clamp strips, carefully
noting the position of each wire for re-connection.
8. Disconnect the Alarm cables from the Alarm clamp strips, carefully noting
the position of each wire for re-connection.
9. Disengage the ABISCO from the BTS connector at the top edge of the
board, and remove it from the COBO.
10. Insert the replacement ABISCO into the COBO and plug it in to the BTS
connector.
11. Re-connect the Abis and Alarm cables to the clamp strips according to
Step 5 and 8
12. Switch ON the AC power supply to the COBO.
13. Using the BTS terminal, update antenna mapping, external alarm mapping,
additional modules (e. g. cover , fan, SSC, VSWR), BTS site name as
noted in Step 5.
14. Using the BTS terminal, update the Remote Inventory EEPROM with:
Note: If the BTSs A910 installed in the field may have different colours of the cover,
it is important to select a top of cover to be replaced with the correct colour
before starting the replace procedure.
14. Close the bottom section of the front protective cover on the BTS, and lock it.
Prerequisites To avoid or to minimize telecom outage time during the replacement procedure
ask the operator to move the BCCH to a TRX with an undisturbed antenna
connection. That is possible when one of the following configurations is used.
The VSWR detector is a discrete module which is fixed to the antenna output
connector of the BTS A910. A VSWR RF jumper cable connects the VSWR
detector and the antenna cable. The ALARM/VCC cable of the VSWR detector
is connected with the ABISCO clamp field inside the COBO. The following
figure shows a BTS A910 with two VSWR detectors.
Rear section
of protective
cover
BTS A910
COBO
VSWR detector 2
VSWR detector 1
Antenna
connection 1
Antenna
connection 2
ALARM/VCC cable 1
ALARM/VCC cable 2
Figure 5: BTS A910 with Two VSWR Detectors
Tools and Materials You must have:
A medium flathead screwdriver.
Prerequisites To avoid or to minimize telecom outage time during the replacement procedure
ask the operator to move the BCCH to a TRX with an undisturbed antenna
connection.
That is possible when following configurations are used:
A two antenna A910 DB4x
15. Using the BTS terminal, check that there are no outstanding alarms on the
BTS, and that all SBLs are in traffic.
16. Disconnect the BTS terminal.
17. Replace the COBO front cover in position over the base, and then tighten
the retaining bolts.
18. Close the bottom section of the front protective cover on the BTS, and lock it.
AC Connection Field
X8 and X9 cables
Temperature sensor cable from its coupling
Ground cable.
6−pole Mate−N−Locks
Fuse box cover Temperature sensor
Retaining screws
cable coupling
Distribution clamp
Heavy Equipment
The battery unit weighs 32 kg. Injury to personnel and damage to equipment
may result if it is dropped or otherwise mishandled.
Be careful when moving or lifting the battery unit.
The battery unit must be handled by two persons on the right and on the left
with each one hand on the lower side and one hand on the front panel handle.
8. Slide out the battery unit on the rails and then lift it off.
9. Make sure that the back holding clamps are in position. If they are not, the
battery cannot be correctly inserted.
10. Slide in a new charged battery unit on the rails at a 20 angle (see the
following figure).
The two 6-pole Mate-N-Locks (can be used in any order, false polarity is
protected by mechanical code)
Feed the ventilation valve in the cable entry area through a PG gland on
the bottom and into the the free cable screw joint on the battery unit.
Then fix the screw joint.
16. Press the button[ Back up ] in the Connector Field. The red LED on the
right will go OUT.
17. Close and lock the door.
Tools and Materials You must have a small pointed flathead screwdriver.
Fan test
POWER CHARGER
SUPPLY 1
POWER MAIN
SUPPLY 2
Back up
3. Support the SSCFH before removing the two retaining screws (and washers)
and then pull it out.
4. Disconnect the outer fan cable wires from the clamps, carefully noting the
position of each for re-connection (see Figure SSCFH, Internal View (11)).
5. Replace the SSCFH by a new one and re-connect the outer fan cable
wires to the clamps as noted before.
6. Put the new SSCFH in the correct position and fix it with the two retaining
screws.
7. Re-connect the power supply cable and the inner and outer fan cables as
noted before.
8. On the Connector Field press [ FAN-Test ] and check acoustically that the
new fan is running.
9. Press the button again to stop the check.
10. Close and lock the door.
A M4 single-ended spanner
4. Support the SSCFH before removing the two retaining screws (and washers)
and then pull it out. Figure SSCFH, Internal View (11) shows the internal
composition.
5. Disconnect the outer fan cable wires from the clamps, carefully noting the
position of each for re-connection the new cable (see Figure SSCFH,
Internal View (11)).
6. Feed the outer fan cable through the rubber nozzle at the top of the SSC so
that it can be removed when removing the outer fan.
7. Unscrew the four M4 retaining nuts fixing the outer fan.
8. Remove the outer fan (and cable), replace it by a new one and fix the new
one with nuts and washers from the old one.
9. Feed the new outer fan cable through the rubber nozzle at the top of the SSC.
10. Take the SSCFH and connect the new outer fan cable wires to the clamps as
noted before.
11. Put the SSCFH in the correct position and fix it with the two retaining screws.
12. Re-connect the power supply cable and the inner and outer fan cables as
noted before.
13. On the Connector Field press[ FAN-Test ]and check that the new fan is
running.
Impact on System All telecommunications resources are lost when BTS_TEL is locked (disabled).
6. Disconnect all cables connected with the clamps X5, X6, X7, X8, X12 by
disconnecting each discrete wire, carefully noting the position of each wire
and each cable for re-connection (see the following figure).
Connector Group
Retaining screw
X10 X11 X9
Fan−test
X1
POWER
CHARGER KRONE
SUPPLY 1
CONNECTOR
POWER X2 X3 X4
MAIN
SUPPLY 2
Back up
OFF
X12 X5 X6 X7 X8
Clamp Group
Figure 12: SSCCF, Detailed View
7. Remove the six retaining screws at the front plate. Support the front plate
and tip it over forward.
8. Disconnect the two cables connected at the back of the front plate and
remove the front plate.
9. Pull out the electronic part of the SSCCF and replace it by a new one. Make
sure that all boards are in their guide rails, then push it fully into the slot.
10. Re-connect the cables of the electronic part of the SSCCF to the back of the
front plate and fix the front plate with the six retaining screws.
11. Re-connect all cables and wires to the clamps and connectors as
disconnected and noted in step 5 and step 6.
12. Turn on the main power switch (position ’1’, see Figure SSC, Position of
RITs (6)).
13. If the red back up LED ’OFF’ is activated, press [ Back up ] to activate the
back up function (LED ’OFF’ is deactivated).
14. Ask the OMC-R operator to unlock (initialize) BTS_TEL and BTS_O&M MOs
(SBLs) and to check that there are no outstanding alarms on the BTS, and
that all MOs (SBLs) are in traffic.
15. Close and lock the door.
PE
L1
This chapter tells you how to open and close doors, to adjust SUM(CGU) and
to remove and replace BTS A9100 RITs.
It contains procedures to replace the following RITs:
Battery Units
Transceiver Equipment
Water Detection Float Switch.
Prerequisites You must have read Safety Rules and Precautions (Chapter 1) before
performing any maintenance tasks or procedures.
Tools and Materials You must have the key(s) for the cabinet(s).
Required
Impact on System None.
Environmental Impact To comply with EMC regulations, ensure that all doors and side panels are
correctly closed.
To reduce the emission of RFI, doors and panels must be correctly fitted. Also,
gaskets must not be broken. The BTS hardware complies with EMC regulations
when operated with the doors, panels and casings in place.
Restrictions None.
3.1.2 Open and Close BTS A9100 and External Battery Indoor Cabinets
To open and close the CIMI/CIDI, CIMA/CIDE, MBI3/MBI5 or external indoor
battery cabinet front door:
1. Insert the key in the door lock and turn it clockwise to unlock the door. Pull
the door knob from the door recess, turn it to the release position, and then
pull the door open. The following figures show the cabinet external views.
CIMA/CIDE
Door Lock
CIMI/CIDI
Door Lock
MBI3 MBI5
Door Lock
Door Lock
Door Lock
2. When you have finished working on the equipment, close the cabinet door.
Turn the door knob to the lock position and push it into the door recess.
Then turn the key counter-clockwise in the door lock to lock the door.
3.1.3 Open and Close BTS A9100 and External Battery Outdoor Cabinets
Procedure To open and close the COMI/COEP/COME, CODI/COEP/CODE, CPT2,
MBO1/MBO2, or external outdoor battery cabinet front doors:
1. Insert the key in the door lock and turn it clockwise to unlock the door. Pull
the door knob from the door recess, turn it to the release position, and then
pull the door open. Figures COME/COMI/COEP Module Positions (17) to
MBO2 Module Positions (21) show the front and top internal views of
the cabinets.
Note: There can be two types of keys. Keys marked ’Side’ can only unlock the Side
Compartment door. Keys marked ’Side+BTS’ can unlock all compartment
doors.
2. Open the door fully so that the latch bar at the back drops into position
keeping it open.
3. Insert the key in the door alarm override key switch (not available in
external outdoor battery cabinet) and turn it clockwise (not necessary in
CPT2/MBO1/MBO2 cabinets) to prevent door alarms being generated. For
module positions see the following figures.
In the external outdoor battery cabinet pull the door switch to prevent
door alarm being generated.
4. When you have finished working on the equipment, reactivate the door alarm
override key switch (not available in external outdoor battery cabinet ) by
turning the key counter-clockwise (if necessary) and drawing the key.
5. Lift the door latch and close the door. Turn the door knob to the lock position,
and then push it into the door recess. Turn the key counter-clockwise
in the door lock to lock the door.
COME
COMI COEP
DCDP
Interconnection
Panel
STASR 2 STASR 4 Not neces−
SRACDC or sarily
ACSR equipped
Document
Holder
Door Alarm
Switch
BTSRIOUT STASR 1 STASR 3 (installation
on upper or
Battery (2 BU41 s lower position)
or BU100)
Flood De−
tector
(installation
on left or Front View
right posi−
tion)
Top View
CODE
CODI COEP
Equipment
Labels
ACSU
Door Alarms
Override STASR 3 STASR 6
Key Switch STASR 7
(Bus−bar)
Interconnection
Panel
Door Alarm
LPFU Switch
Flood
Detector BTSRIOUT
Front View
HEAT2 HEAT2
HEAT2
Top View
Equipment
Labels
ACSU
Door Alarms
STASR 6
Override
STASR 3
Key Switch
(Bus−bar)
OUTC
Document STASR 5
Holder STASR 2
Door Alarm
Switch
Battery STASR 4
LPFU
Flood
Detector
Front View
HEAT2
HEAT2
HEX2 HEX2
Top View
Service Light
Smoke Detektor
AC Switch Unit
(ACMU)
LPFM
ADAM4
STASR 7
HEX Breaker
Options Area
(e.g. Microwaves)
Door Alarms
STASR 3 Override
Key Switch
Batteries
Document
Holder
OUTC
STASR 2
Battery Cover
Batteries
Door Alarm
STASR 1
Switch
Flood
Detector
Front View
HEAT2
HEX4
Top View
MBO2
Service Light
MBO1 MBOE
Smoke Detektor
AC Switch Unit
(ACMU)
LPFM Normally
ADAM4 not equipped
HEX Breaker
STASR 7 STASR 0
Options Area
Door Alarms
(e.g. Microwaves)
Override
Key Switch
STASR 3 STASR 6
Batteries
OUTC
Document
Holder
STASR 2 STASR 5
Battery Cover
Batteries
Door Alarm
Switch
STASR 1 STASR 4
Flood
Detector
Front View
HEAT2
HEAT2
HEX4
HEX3
Top View
Smoke Detector
DC Breaker Box
Battery Units
A
Transmission
Blocks
External
Airconditioner Cable Entry
with integrated heater
Front View
AC Box
(behind frame)
Battery Unit
Jumper
Internal Internal
Cable Entry Cable Entry
Top View A
(Bottom Floor)
3.2 Adjust the Clock of the SUM (CGU) in the BTS A9100
Prerequisites Note the following conditions. You must:
Have read Safety Rules and Precautions (Chapter 1) before performing any
maintenance procedures.
Be familiar with electrostatic precautions. Refer to Electrostatic Precautions
(Section 1.2) for more information.
Ensure that the SUM (CGU) has had power continuously supplied for
the previous 15 minutes.
Ensure that the frequency counter has had the warm-up period specified by
the manufacturer.
Loss of Calls
Failure to comply with the prerequisites can result in the BTS being locked
(disabled) and all calls being lost.
A specific cable (ref. 3BK 08066 AB) for connecting the frequency counter
to the BTS.
5. Use the BTS terminal (see BTS Terminal User Guide chapter “Adjust the
OCXO”) to adjust the BTS clock for a frequency between 2 166 666.55
Hz and 2 166 666.77 Hz.
Impact on System This depends on the nature of the RIT and its position in the system. Refer to
the specific replacement procedures in this chapter.
Restrictions None.
Subrack
backpanel
connectors
Backplane
Slot No. 1 2 3 4 5 7 9 10 11
Backplane
Slot No. 1 3 5 7 9 11
Impact on System If there is a mains power failure during the replacement procedure, the BTS is
powered down and all telecommunications resources are lost.
Backplane Damage
Do not use excessive force when inserting the ABAC.
9. Push the replacement ABAC fully into the empty slot ensuring that pins
and sockets are correctly aligned.
10. Tighten the quarter-turn Camloc fasteners on the front panel of the ABAC.
11. Use the M6 nuts to re-connect the ABAC cables removed from the battery
terminals in Step 5.
12. Using a torque wrench fitted with an M6 adaptor, tighten the terminal
connections to a torque of 3.9 Nm and then replace the rubber insulation
(BU41) or the terminal caps (BU100).
13. Re-connect the D-type cable to the front panel of the ABAC.
14. Switch ON (up) the circuit breaker F3 on the front panel of the ABAC.
15. Disconnect the anti-static wrist strap.
16. Connect the BTS terminal to the MMI port on the SUM in the STASR.
17. Using the BTS terminal, set the part number into BTSRI remote inventory
additional module field.
18. Using the BTS terminal, check that there are no outstanding alarms on the
BTS, and that all SBLs are in traffic.
19. Disconnect the BTS terminal.
20. Close the front door of the BTS.
Backplane Damage
Do not use excessive force when inserting the ACIB.
7. Push the replacement ACIB fully into the empty slot ensuring that pins
and sockets are correctly aligned.
8. Tighten the quarter-turn Camloc fasteners on the front panel of the ACIB.
9. Re-connect the AC IN cable and the AC OUT cables to the front panel of the
ACIB and tighten the locknuts, according to Step 4.
10. Switch ON (up) all the circuit breakers (Fi, F1, L1, L2, L3) on the front
panel of the ACSB.
11. Verify that the green On LED on the front panel of the BCU1 is ON and that
the red Batt and yellow Test LEDs are OFF.
12. Connect the BTS terminal to the MMI port on the SUM in the STASR.
13. Using the BTS terminal, set the part number into BTSRI remote inventory
additional module field.
14. Using the BTS terminal, check that there are no outstanding alarms on the
BTS, and that all SBLs are in traffic.
15. Disconnect the BTS terminal.
16. Close the front doors of the BTS.
AC handling
Be careful when handling AC circuits and components!
2. Remove the L1, L2 and L3 plug-in phase protectors on the front of the
ACSB or ACSP.
3. Insert the new protectors on the front of the ACSB or ACSP.
4. Verify that the L1, L2 and L3 phase protection indicators on the front of the
ACSB or ACSP are green.
5. Verify that the status of the LEDs on the BCU1/BCU2 front panel is as follows:
For the BCU1:
Green On LED - ON
Red Batt LED - OFF
Yellow Test LED - OFF.
6. Connect the BTS terminal to the MMI port on the SUM in the STASR.
7. Using the BTS terminal, check that there are no outstanding alarms on the
BTS, and that all SBLs are in traffic.
8. Disconnect the BTS terminal.
9. Close the front doors of the BTS.
Backplane Damage
Do not use excessive force when inserting the ACRI.
8. Push the replacement ACRI fully into the empty slot ensuring that pins
and sockets are correctly aligned.
9. Tighten the quarter-turn Camloc fasteners on the front panel of the ACRI.
10. Re-connect the D-type cable to the front panel of the ACRI.
11. Verify that both green POWER ON LEDs on the front panel are ON.
12. Disconnect the anti-static wrist strap.
13. Using the BTS terminal, check that there are no outstanding alarms on the
BTS, and that all SBLs are in traffic.
14. If you were able to upload the remote inventory file from the old ACRI
in Step 3, go directly to Step 16.
If you were unable to upload the remote inventory file from the old ACRI in
Step 3, use the BTS terminal to upload the file to the new ACRI.
15. Using the BTS terminal, update the remote inventory file with the following
information:
Network identity
16. Using the BTS terminal, update the remote inventory file with the
Commissioning Date (current installation date).
17. Using the BTS terminal, download the remote inventory file to the new
ACRI in the BTS.
18. Disconnect the BTS terminal.
19. Close the front door of the BTS.
Impact on System There is a main power failure during the replacement procedure, so that the
BTS is powered down and all telecommunications resources are lost.
Backplane Damage
Do not use excessive force when inserting the PM12s.
14. Push each PM12 into its empty slot as noted in step 9, ensuring that pins
and sockets are correctly aligned.
15. Tighten the retaining screws on the front panels of all PM12s.
16. Connect the cables disconnected in step 6 to the connector on the front
panel of the PM12s.
17. Connect the cables disconnected in step 7 to the connectors on the front
panel of ADAM.
18. Switch ON the circuit breakers F5, F6, and F7 on the front panel of the
ACSU or in case of an indoor cabinet the external circuit breakers to
connect AC power.
19. Switch ON (up) the circuit breakers BR1 (branch 1) and BR2 (if optional
branch is available).
20. Verify that the green On LED on the front panel of each PM12 is ON.
21. Use the BTS terminal to set the part number into BTSRI remote inventory
additional module field.
22. Use the BTS terminal to initialize BTS_TEL.
23. Use the BTS terminal to check that there are no outstanding alarms on the
BTS, and that all SBLs are in traffic.
24. Disconnect the BTS terminal.
25. Close the front door(s) of the BTS.
Impact on System There is a main power failure during the replacement procedure, so that the
BTS is powered down and all telecommunications resources are lost.
Backplane Damage
Do not use excessive force when inserting the PM12s.
15. Push each PM12 into its empty slot as noted in step 10, ensuring that pins
and sockets are correctly aligned.
16. Tighten the retaining screws on the front panels of all PM12s.
17. Replace dummy panel(s) (if necessary) and tighten the retaining screws.
18. Connect the cables disconnected in step 6 to the connector on the front
panel of the PM12s.
19. Connect the cables disconnected in step 7 to the connectors on the front
panel of ADAM4.
20. Switch ON circuit breakers F3, F4 and F5 on the front panel of ACMU to
connect AC power.
21. Switch ON (up) the battery circuit breaker which is positioned on the
righthand side of the ACMU to connect the battery.
22. Verify that the green On LED on the front panel of each PM12 is ON.
23. Use the BTS terminal to set the part number into BTSRI remote inventory
additional module field.
24. Use the BTS terminal to initialize BTS_TEL.
25. Use the BTS terminal to check that there are no outstanding alarms on the
BTS, and that all SBLs are in traffic.
26. Disconnect the BTS terminal.
27. Close the front door(s) of the BTS.
Heavy Equipment
The air-conditioner weighs 30 kg and there is no handle. Injury to personnel
and damage to equipment may result if it is dropped or otherwise mishandled.
Be careful when removing the air-conditioner. Do NOT remove the nuts that
secure it to the door until it is properly supported.
Gasket Damage
While placing the replacement air-conditioner against the door in the next step,
take care not to damage the gasket between air-conditioner and door.
7. Place the replacement air-conditioner against the door and replace the fixing
nuts. Support the air-conditioner until the nuts are fully tightened.
8. Re-connect the AC power supply cable to the AC connector at the left side of
the AC distribution box.
9. Re-assemble the alarm cable and re-connect it to the terminal blocks as
noted before.
10. Switch ON (up) the air-conditioner circuit breaker on the front panel of
the AC distribution box.
11. Open the front door(s) of the BTS (Refer toOpen and Close BTS A9100
Cabinets (Section 3.1) for more information.)
12. Connect the BTS terminal to the MMI port on the SUM in the STASR.
13. Using the BTS terminal, set the part number into BTSRI remote inventory
additional module field.
14. Using the BTS terminal, check that there are no outstanding alarms on the
BTS, and that all SBLs are in traffic.
15. Disconnect the BTS terminal.
16. Close the front doors of the BTS and the external outdoor battery cabinet.
Impact on System All telecommunications resources are lost when BTS_TEL is locked (disabled).
Procedure To replace an ANxx RIT:
1. Open the front door(s) of the BTS. (Refer toOpen and Close BTS A9100
Cabinets (Section 3.1) for more information.)
2. Connect the BTS terminal to the MMI port on the SUM in the STASR.
3. Use the BTS terminal to disable BTS_TEL. Enter a WTC = 3 minutes
to ensure an orderly shutdown of the BTS. Wait three minutes before
continuing to the next step.
4. Using the BTS terminal, disable the RAn SBL where n corresponds to the
rotary switch setting on the front panel of one of the ANXx RITs. The
particular ANX x is either the faulty ANXx to be replaced, or the ANX in the
same radio sector as the faulty ANYx to be replaced.
For ANCx use the BTS terminal (Monitoring, BTS Modules) to get the faulty
RAn SBL (FOS/FLT). Use the UT_ANX_BCB yy to identify the module inside
the BTS (e.g UT_ANX_BCB 43 = ANC in Subrack 2, Slot 11).
Backplane Damage
Do not use excessive force when inserting the RIT.
9. If you are replacing an ANXx RIT, use a screwdriver to set the rotary
switch on the front panel of the replacement to the same position as that
on the faulty one.
10. Push the replacement RIT fully into the empty slot ensuring that pins and
sockets are correctly aligned, and then tighten the quarter-turn Camloc
fasteners on the front panel.
11. Re-connect the coaxial RF cables to the front panel.
12. Disconnect the anti-static wrist strap.
13. Unlock (initialize) RAn and then BTS_TEL.
14. Using the BTS terminal, check that there are no outstanding alarms on the
BTS, and that all SBLs are in traffic.
15. Using the BTS terminal, upload from the BTS the ANXx/ANCx remote
inventory file UT_ANX_BCB yy or the ANYx remote inventory file
UT_ANY_BCB yy , as appropriate, where yy is the ANxx number.
16. Using the BTS terminal, update the remote inventory file with the following
information:
Network identity.
17. Using the BTS terminal, download the remote inventory file to the BTS.
18. Disconnect the BTS terminal.
19. Close the front door(s) of the BTS.
SUMP/SUMA Installation
Before starting to replace ANX and ANY by ANC, check which SUMP/SUMA
variant is installed on site.
Subrack Variants
Before starting to replace ANX and ANY by ANC check the subrack variant
which is installed on site. ANC module implementation to former subrack
variants requires following steps:
Variant ABAA: if additional guide rails are available, add one or two pairs
of guide rails at ANC guide rails positions (details see appropriate step
during replace procedure). If no additional guide rails are available change
ANX guide rails to ANC guide rails positons (details see appropriate step
during replace procedure).
Table BTS A9100 Antenna Network Module RIT Part Numbers (3) shows the
Antenna Network Module RIT part numbers.
Impact on System All telecommunications resources are lost when BTS_TEL is locked (disabled).
Perform Initial Checks 1. On OMC-R site: perform an Audit Alarm/State for the BSS.
2. Check Status of MOs and Alarms for the impacted BTS.
3. Make a report containing the status of MOs and alarms.
Install ANC 1. If the subrack variant ABAA is installed and additional guide rails are
available, add following guide rails:
ANC left position: add a pair of guide rails (bottom and top) at 82 mm
(counting from left side of subrack) position
ANC middle position: add a pair of guide rails (bottom and top) at 153.1
mm (counting from left side of subrack) position
ANC right position: add two pairs of guide rails (bottom and top) at 295.4
mm and 366.5 mm (counting from left side of subrack) position
If SUM module must move, it goes from slot 1 to slot 7 (physical RIT
position seePhysical RIT Positions in STASR/ACSR (Section 3.4)).
ANC left position: move left pair of ANX guide rails (bottom and top)
towards right on 1 step (at 82 mm, counting from left side of subrack)
ANC middle position: move left pair of ANX guide rails (bottom and top)
towards left on 1 step (at 153.1 mm, counting from left side of subrack)
ANC right position: : move the two pairs of ANX guide rails (bottom
and top) towards left on 1 step (at 295.4 mm and 366.5 mm, counting
from left side of subrack).
If SUM module must move, it goes from slot 1 to slot 7 (physical RIT
position see Physical RIT Positions in STASR/ACSR (Section 3.4)).
3. Insert the ANC module (for more information of rack layouts and module
positions refer to the EVOLIUM BTS A9100 Hardware Description).
Backplane Damage
Do not use excessive force when inserting the RIT.
4. Push the replacement RIT fully into the empty slot ensuring that pins and
sockets are correctly aligned, and then tighten the quarter-turn Camloc
fasteners on the front panel.
5. Connect all coaxial RF cables to ANC (and ANY if available) front panel(s).
On ANC: use bridges if necessary). For rack layouts refer to the EVOLIUM
BTS A9100 Hardware Description.
ANC Bridges
In each sector: If no more than 4 TREs, no ANY required. TRE1 to TRE4
are then cabled on ANC.
On each ANC: If no more than 2 TREs, no bridges are used.
If bridges are not used, keep them on ANC (screwed on TXxOUT connectors)
for future use.
Number of sector
Perform Final Checks 1. The ’BSSUSM Main View’ (equipment view) still displays removed modules.
at the OMC-R 2. Use ’Display USD Detailed Cell Information’ to check if calls are made
on changed cells.
3. Perform an ’Audit/Alarm State’ for the BSS.
4. Perform ’Check Status of MOs and Alarms’ for the impacted BTS.
Impact on System All telecommunications resources are lost when BTS_TEL is locked (disabled).
13. Ensure that the AC INPUT circuit breaker and the six DC OUTPUT circuit
breakers INT, SR1-4, and EXT on the front panel of the replacement APOD
are all OFF (down).
14. Hold the replacement APOD next to the empty slot and feed the AC cable at
the back into the slot for connection to the AFIP.
15. Carefully push the APOD fully into the slot ensuring that the AC cable at
the back is allowed to hang free.
16. Tighten the quarter-turn Camloc fasteners on the front panel of the APOD.
17. Re-connect the AC cable from the APOD to the back of the two filters on the
AFIP and replace the M3 nuts and the protective rubber caps.
18. Carefully push the AFIP back against the subrack without trapping the
AC cable, and replace the six crosshead screws to secure the AFIP to
the subrack.
19. Replace the filter cover on the AFIP and secure it with the two crosshead
screws.
20. Plug in the cables from the APOD to AC IN on the front panels of the PM08s
according to Step 7.
21. Switch ON the external AC power supply to the BTS cabinet.
22. Switch ON (up) the AC INPUT circuit breaker on the front panel of the APOD.
23. Switch ON (up) the six DC OUTPUT circuit breakers INT, SR1-4, and EXT
on the front panel of the APOD.
24. Switch ON (up) the circuit breaker F3 on the front panel of the ABAC.
25. Verify that the green On LED on the front panel of the BCU1 is ON and that
the red Batt and yellow Test LEDs are OFF.
26. Using the BTS terminal, set the part number into BTSRI remote inventory
additional module field.
27. Using the BTS terminal, initialize BTS_TEL.
28. Using the BTS terminal, check that there are no outstanding alarms on the
BTS, and that all SBLs are in traffic.
29. Disconnect the BTS terminal.
30. Close the front doors of the BTS.
Impact on System If there is a mains power failure during the replacement procedure, the BTS is
powered down and all telecommunications resources are lost.
Procedure To replace a BACO RIT:
1. Open the front doors of the BTS. (Refer toOpen and Close BTS A9100
Cabinets (Section 3.1) for more information.)
2. Connect the anti-static wrist strap.
3. Switch OFF (down) the circuit breakers P1 and P2 on the front panel
of the BACO.
4. Disconnect the D-type cable on the front panel of the BACO.
5. At the batteries, pull back the rubber insulation on the four terminals
connected to the BACO and loosen the M6 nuts.
6. Remove the M6 nuts from the terminals and disconnect the cables to the
BACO, carefully noting their positions for re-connection.
7. Loosen the quarter-turn Camloc fasteners on the front panel of the BACO.
8. Carefully disengage the BACO from the backplane and fully withdraw it
from the slot.
Backplane Damage
Do not use excessive force when inserting the BACO.
9. Push the replacement BACO fully into the empty slot ensuring that pins
and sockets are correctly aligned.
10. Tighten the quarter-turn Camloc fasteners on the front panel of the BACO.
11. Use the M6 nuts to re-connect the BACO cables removed from the battery
terminals in Step 6.
12. Using a torque wrench fitted with an M6 adaptor, tighten the terminal
connections to a torque of 3.9 Nm and then replace the rubber insulation.
13. Re-connect the D-type cable to the front panel of the BACO.
14. Switch ON (up) the circuit breakers P1 and P2 on the front panel of the BACO.
15. Disconnect the anti-static wrist strap.
16. Connect the BTS terminal to the MMI port on the SUM in the STASR.
17. Using the BTS terminal, set the part number into BTSRI remote inventory
additional module field.
18. Using the BTS terminal, check that there are no outstanding alarms on the
BTS, and that all SBLs are in traffic.
19. Disconnect the BTS terminal.
20. Close the front door(s) of the BTS.
Impact on System If there is a mains power failure during the replacement procedure, the BTS is
powered down and all telecommunications resources are lost.
Backplane Damage
Do not use excessive force when inserting the BAC2.
6. Push the replacement BAC2 fully into the empty slot, ensuring that pins
and sockets are correctly aligned.
7. Tighten the retaining screws on the front panel of the BAC2.
8. Re-connect the cables removed from the front panel of the BAC2 in Step 3.
9. Switch ON (up) the circuit breakers F1 and F2 on the front panel of the BAC2.
10. Connect the BTS terminal to the MMI port on the SUM in the STASR.
11. Using the BTS terminal, set the part number into BTSRI remote inventory
additional module field.
12. Using the BTS terminal, check that there are no outstanding alarms on the
BTS, and that all SBLs are in traffic.
13. Disconnect the BTS terminal.
14. Close the front doors of the BTS.
Heavy Equipment
The BATS weighs 15 kg. Injury to personnel and damage to equipment may
result if it is dropped or otherwise mishandled.
Be careful when moving or lifting the BATS.
6. Carefully disengage the BATS from the backplane and fully withdraw it
from the slot.
Backplane Damage
Do not use excessive force when inserting the BATS.
7. Push the replacement BATS fully into the empty slot ensuring that that pins
and sockets are correctly aligned.
8. Tighten all retaining screws at the front panel of the BATS.
9. Re-connect both battery cables disconnected in step 4 to the connectors at
the front panel of the BATS.
10. Re-connect the ’BATT -48 V’ battery cable at ADAM.
11. Switch ON (up) the circuit breaker at the BATS.
12. Close the front door of the BTS.
Impact on System If there is a mains power failure during the replacement procedure, the BTS is
powered down and all telecommunications resources are lost.
Backplane Damage
Do not use excessive force when inserting the BCU1.
5. Push the replacement BCU1 fully into the empty slot ensuring that pins
and sockets are correctly aligned.
6. Tighten the quarter-turn Camloc fasteners on the front panel of the BCU1.
7. Verify that the green On LED on the front panel is ON and that the red
Batt and yellow Test LEDs are OFF.
8. Disconnect the anti-static wrist strap.
9. Press the Status button on the front panel of the BCU1 repeatedly until the
battery configuration is displayed, for example BU41 2B. This is displayed
for a BU41 with two branches.
If the configuration is incorrect, use the Special Menu function of the BCU1
to set it to the configuration currently in use in the cabinet.
The procedure for setting the configuration is defined in Steps 10 to 19. If
the configuration is correct, go directly to Step 20.
10. Press the Function and Status buttons on the front panel of the BCU1
simultaneously for five seconds to access the Special Menu and display
"SpecFunc".
11. Press the Function button to display "BatEquip".
12. Press the Status button to display "BatType".
13. Press the Status button to display "BU15", the default.
14. Press the Function button to display "BU41".
15. Press the Status button to select BU41 or the Function button followed by the
Status button to select BU61 if a BU100 is being used.
16. Press the Status button to display "1 Branch", the default.
17. Press the Status button to select one branch or the Function button followed
by the Status button to select two branches.
18. Press the Function button to display "SpecFunc".
19. Press the Status button to leave the Special Menu (and to return to the
information mode).
20. Press the Status button on the front panel of the BCU1 repeatedly until
the Rectif status is displayed and verify that the status of the PM08s is
"Y Y Y Y Y".
The following character designations are used:
21. Press the Status button on the front panel of the BCU1 repeatedly until the
Alarm status is displayed and verify that the status of the PM08s is "- - - - -".
A "-" in any display position indicates that the PM08 in the corresponding
slot is not in an alarm condition. Any other character in the display indicates
an alarm condition.
22. Connect the BTS terminal to the MMI port on the SUM in the STASR.
23. Using the BTS terminal, check that there are no outstanding alarms on the
BTS, and that all SBLs are in traffic.
24. Using the BTS terminal, upload the ACRI remote inventory file
UT_ACDC_BCB 136 from the BTS.
25. Using the BTS terminal, update the remote inventory file with the following
information:
26. Using the BTS terminal, download the remote inventory file to the ACRI in
the BTS.
27. Disconnect the BTS terminal.
28. Close the front door of the BTS.
Impact on System If there is a mains power failure during the replacement procedure, the BTS is
powered down and all telecommunications resources are lost.
Backplane Damage
Do not use excessive force when inserting the BCU2.
7. Disconnect the XBCB and the TEMPERATURE cables from the front panel
of the BCU2.
8. Push the replacement BCU2 fully into the empty slot, ensuring that pins
and sockets are correctly aligned.
9. Tighten the retaining screws on the front panel of the BCU2.
10. Re-connect the XBCB and the TEMPERATURE cables to the front panel
of the BCU2.
11. Verify that the green On and Power On LEDs on the front panel are ON and
that the red Alarm and yellow Test LEDs are OFF.
12. Disconnect the anti-static wrist strap.
13. Press the Status button on the front panel of the BCU2 repeatedly until the
battery configuration is displayed, for example BU41 2B. This is displayed
for a BU41 with two branches.
If the configuration is incorrect, use the Special Menu function of the BCU2
to set it to the configuration currently in use in the cabinet.
The procedure for setting the configuration is defined in Steps 14 to 23. If
the configuration is correct, go directly to Step 24.
14. Press the Function and Status buttons on the front panel of the BCU2
simultaneously for five seconds to access the Special Menu and display
"SpecFunc".
For only one branch installed, press the Status button to select one
branch. "CapTest" is displayed.
For two branches installed, press the Function button and "2 Branch" is
displayed. Press the Status button to select two branches. "CapTest"
is displayed.
26. Press the Status button on the front panel of the BCU2 repeatedly until the
Alarm status is displayed. Verify that the status is "ALM".
Any other character in the display, for instance "ALM M", indicates an alarm
condition. The following character designations are used:
27. Using the BTS terminal, check that there are no outstanding alarms on the
BTS, and that all SBLs are in traffic.
28. Using the BTS terminal, upload the BCU2 remote inventory file
UT_ACDC_BCB 136 from the BTS.
29. Using the BTS terminal, update the remote inventory file with the following
information:
Network identity
30. Using the BTS terminal, download the remote inventory file to the BCU2 in
the BTS.
31. Disconnect the BTS terminal.
32. Close the front doors of the BTS.
Short-Circuiting Batteries
Short-circuiting of battery terminals can cause injury to personnel and damage
to equipment.
Be careful when handling batteries.
Each cabinet contains one or optionally two (outdoor BTS A9100 only) BU41
battery branches. The batteries are connected as shown in the following
figure (top view).
BU41 Optional BU41
Battery Branch Battery Branch
Fixing Belt
To BACO/BAC2
To BACO/BAC2 − + − + Batt 2−
Batt 1−
− + − +
Jumper
− + − + To BACO/BAC2
Batt 2+
− + − +
To BACO/BAC2 Batt 1+
Each battery branch is fitted with an exhaust hose which expels the gasses
produced during battery charging to the external environment.
A temperature sensor is connected to the positive (+) battery terminal of
branch 1.
Once a year, you must inspect it for corrosion and damage and measure
the battery voltage and temperature.
Heavy Equipment
The BU41 comprises four blocks of 12.5 kg. Injury to personnel and damage to
equipment may result if it is dropped or otherwise mishandled.
Be careful when moving or lifting the BU41.
7. Release the fixing belt securing the BU41 to the battery compartment and
then remove the individual battery blocks from the compartment.
8. Inspect the batteries and terminals of the replacement BU41 for corrosion
or cracks.
9. Install the charged replacement battery blocks in the battery compartment
and secure using the fixing belt.
10. Use the M6 nuts to re-connect all the battery cables to the battery terminals,
as shown in Figure BU41 Battery Branches and Terminal Connections in
Combination with PM08/PM11 (24).
11. Using a torque wrench with an M6 adaptor, tighten all the terminal
connections to a torque of 3.9 Nm and then replace the rubber insulation.
12. Re-connect the exhaust hose to the nipple on top of each battery block.
13. Switch ON (up) the circuit breakers P1 and P2 on the front panel of the
BACO or BAC2.
14. Connect the BTS terminal to the MMI port on the SUM in the STASR.
15. Using the BTS terminal, set the part number into BTSRI remote inventory
additional module field.
16. Using the BTS terminal, check that there are no outstanding alarms on the
BTS, and that all SBLs are in traffic.
17. Disconnect the BTS terminal.
18. Close the front door of the BTS.
Short-Circuiting Batteries
Short-circuiting of battery terminals can cause injury to personnel and damage
to equipment.
Be careful when handling batteries.
The batteries are connected as shown in the following figure (top view).
To BACO/BAC2
To BACO/BAC2 Batt 1+
Batt 1−
+ − + − + −
The battery branch is fitted with exhausting hoses which expel the gasses
produced during battery charging to the external environment.
A temperature sensor is connected to one of the battery terminals.
Once a year, you must inspect it for corrosion and damage and measure
the battery voltage and temperature.
Impact on System If there is a mains power failure during the replacement procedure, the BTS is
powered down and all telecommunications resources are lost.
6. Pull off the cap on the positive (+) terminal on the rightmost battery, remove
the M6 nut and then disconnect the cable that goes to the BACO or BAC2.
7. Pull off the other six caps on the remaining battery terminals, and remove
the six M8 screws.
8. Remove the three jumpers linking the four batteries.
Heavy Equipment
The BU100 comprises four blocks of 30 kg. Injury to personnel and damage to
equipment may result if it is dropped or otherwise mishandled.
Be careful when moving or lifting the BU100.
9. Release the fixing belt securing the BU100 to the battery compartment and
then remove the individual batteries from the compartment.
10. Inspect the batteries and terminals of the replacement BU100 for corrosion
or cracks.
11. Place two self-adhesive spacers on the top of one of the side walls of three
of the four battery blocks (same side wall in order to insure distance to
the next battery).
12. Install the charged replacement batteries in the battery compartment and
secure using the fixing belt.
13. Replace the three jumpers linking the four batteries, as shown in Figure
BU100 Battery Branch and Terminal Connections in Combination with
PM08/PM11 (25).
14. Replace the six M8 screws on the three jumpers, and tighten each nut to a
torque of 5 Nm using a torque wrench with an M8 adaptor.
15. Replace the terminal caps on the six M8 screws.
16. Re-connect the battery cable removed in Step 4 to the negative (-) terminal
on the leftmost battery, and replace the M6 nut.
17. Using a torque wrench with an M6 adaptor, tighten the nut to a torque of
3.9 Nm and then replace the terminal cap.
18. Re-connect the battery cable removed in Step 5 to the positive (+) terminal
on the rightmost battery, and replace the M6 nut.
19. Using a torque wrench with an M6 adaptor, tighten the nut to a torque of
3.9 Nm and then replace the terminal cap.
20. Re-connect the exhausting hoses to the nipple on top of each battery.
21. Switch ON (up) the circuit breakers P1 and P2 on the front panel of the
BACO or BAC2.
22. Connect the BTS terminal to the MMI port on the SUM in the STASR.
23. Using the BTS terminal, set the part number into BTSRI remote inventory
additional module field.
24. Using the BTS terminal, check that there are no outstanding alarms on the
BTS, and that all SBLs are in traffic.
25. Disconnect the BTS terminal.
26. Close the front door of the BTS.
Short-Circuiting Batteries
Short-circuiting of battery terminals can cause injury to personnel and damage
to equipment.
Be careful when handling batteries.
To Circuit Breaker
BR1 or BR2
1234567890123456789
1234567890123456789
Fixing Belt
Jumper
12345678901234567890123
12345678901234567890123 To Circuit Breaker
To Circuit Breaker
BR1 or BR2
BR1 or BR2
Each battery branch is fitted with an exhaust hose which expels the gasses
produced during battery charging to the external environment.
A temperature sensor is connected to the positive (+) battery terminal.
Once a year, you must inspect the batteries for corrosion and damage and
measure the battery voltage and temperature.
Impact on System If there is a mains power failure during the replacement procedure, the BTS is
powered down and all telecommunications resources are lost.
Heavy Equipment
The BU41 comprise four blocks of 12.5 kg. Injury to personnel and damage to
equipment may result if it is dropped or otherwise mishandled.
Be careful when moving or lifting the BU41.
7. Release the fixing belt securing the BU41 to the battery compartment and
then remove the individual battery blocks from the compartment. (It is
recommended to start with the interior blocks)
8. Inspect the batteries and terminals of the replacement BU41 for corrosion
or cracks.
9. Install the charged replacement battery blocks in the battery compartment
and secure using the fixing belt.
10. Re-connect the exhausting hoses to the nipple on top of each battery block.
11. Use the M6 nuts to re-connect all the battery cables to the battery terminals,
as shown in Figure BU41/BU100 Battery Branches and Terminal
Connections (top view) in Combination with PM12 (26).
12. Using a torque wrench with an M6 adaptor, tighten all the terminal
connections to a torque of 3.9 Nm and then replace the rubber insulation.
13. Switch ON (up) the circuit breakers BR1 (branch 1) or BR2 (optional branch).
14. Connect the BTS terminal to the MMI port on the SUM in the STASR.
15. Using the BTS terminal, update the remote inventory of the RIBAT with
the following information:
Heavy Equipment
The BU100 comprises four blocks of 30 kg. Injury to personnel and damage to
equipment may result if it is dropped or otherwise mishandled.
Be careful when moving or lifting the BU100.
9. Release the fixing belt securing the BU100 to the battery compartment
and then remove the individual batteries from the compartment (It is
recommended to start with the interior blocks).
10. Inspect the batteries and terminals of the replacement BU100 for corrosion
or cracks.
11. Place two self-adhesive spacers on the top of one of the side walls of three
of the four battery blocks (same side wall in order to insure distance to
the next battery).
12. Install the charged replacement batteries in the battery compartment and
secure using the fixing belt.
13. Replace the three jumpers linking the four batteries, as shown in Figure
BU100 Battery Branch and Terminal Connections in Combination with
PM08/PM11 (25).
14. Replace the six M8 screws on the three connector bars, and tighten each nut
to a torque of 5 Nm using a torque wrench with an M8 adaptor.
Short-Circuiting Batteries
Short-circuiting of battery terminals can cause injury to personnel and damage
to equipment.
Be careful when handling batteries.
Temperature
Sensor Cable
(to RIBAT)
Front View
Jumper
Exhausting
Hoses
Top View
Figure 27: BU101 Battery Unit and Terminal Connections in External Battery
Cabinets
Heavy Equipment
Each battery block of the BU101 weighs 30 – 35 kg. Injury to personnel and
damage to equipment may result if it is dropped or otherwise mishandled.
Be careful when moving or lifting the BU101.
10. Loosen the retaining nuts of the fixing straps securing the BU101 to the
battery compartment, remove the fixing straps and then remove the
individual battery blocks from the compartment.
Short-Circuiting Batteries
Short-circuiting of battery terminals can cause injury to personnel and damage
to equipment.
Be careful when handling batteries.
Battery Box
Battery Battery
Connection Cable
Upper Block
To Circuit Breaker
Jumper
Battery Battery
Figure 28: BU101 Battery Branches and Terminal Connections (front view)
Each battery branch is fitted with exhausting hoses which expel the gasses
produced during battery charging to the external environment.
A temperature sensor is connected to the positive (+) battery terminal.
Heavy Equipment
Each battery block of the BU101 weighs 30 – 35 kg. Injury to personnel and
damage to equipment may result if it is dropped or otherwise mishandled.
Be careful when moving or lifting the BU101.
10. Remove the individual batteries from the battery box (It is recommended to
start with the right blocks).
4. Replace the two jumpers and the “connection” cable linking the four
batteries, as shown in Figure BU101 Battery Branches and Terminal
Connections (front view) (28).
5. Replace the six M8 screws on the two jumpers and the “connection” cable,
and tighten each nut to a torque of 5 Nm using a torque wrench with an
M8 adaptor.
6. Replace the terminal caps on the six M8 screws.
7. Re-connect the battery cable removed in Step 5 (Remove the Batteries) to
the negative (-) terminal on the left upper battery, and replace the M6 nut.
8. Using a torque wrench with an M6 adaptor, tighten the nut to a torque of 5
Nm and then replace the terminal cap.
9. Re-connect first the battery cable and then the temperature cable removed
in Step 6 (Remove the Batteries) to the positive (+) terminal on the right
lower battery, and replace the M6 nut.
10. Using a torque wrench with an M6 adaptor, tighten the nut to a torque of
5 Nm and then replace the terminal cap.
11. Re-connect the exhausting hoses to the nipple on top of each battery.
12. Replace the cover of battery box and tighten the retaining screws.
13. Switch ON (up) the battery circuit breaker.
14. Connect the BTS terminal to the MMI port on the SUM in the STASR.
15. Using the BTS terminal, update the remote inventory of the RIBAT with
the following information:
Location of Diplexer
One external diplexer is installed near the BTS and MBS, another diplexer is
installed near the antennas. Make sure that the diplexer to be removed is
accessable by existing equipment.
Impact on System All telecommunications resources of GSM and UMTS equipment are lost when
BTS_TEL and Node B are locked (disabled).
Remove Diplexer To remove an external diplexer:
1. Open front door(s) of the BTS (refer toOpen and Close BTS A9100 Cabinets
(Section 3.1) for more information) and the MBS.
2. Connect BTS terminal to MMI port on SUM in the BTS STASR.
3. Use BTS terminal to disable BTS_TEL. Enter a WTC = 3 minutes to ensure
an orderly shutdown of the BTS. Wait three minutes before continuing
to next step.
4. Connect MBS terminal to MMI port on SUMU in the MBS STASR.
5. Use MBS terminal to lock Node B.
6. If available, remove the vinyl plastic electrical tape at all RF connectors
and disconnect RF jumper cables at diplexer, carefully noting down their
positions for re-connection.
7. Disconnect ground cable which is fixed at ground rod of diplexer.
8. Secure diplexer, loosen mounting and remove diplexer.
A TORX screwdriver M3
A BTS terminal and an RS-232 asynchronous communication link cable
to connect it to the MMI port. The MMI port is located on the front panel
of the SUM. Refer to the BTS Terminal User Guide for information on
how to use the terminal.
Impact on System All telecommunications resources are lost when BTS_TEL is locked (disabled).
Backplane Damage
Do not use excessive force when inserting the modules.
13. Push the module removed from the subrack earlier, back into the empty slot
ensuring that pins and sockets are correctly aligned. Then tighten the
quarter-turn Camloc fasteners on the front panel of the module.
14. Re-connect all the cables to the module.
15. Disconnect the anti-static wrist strap.
16. Using the BTS terminal, initialize the CCFn and RA SBLs and then BTS_TEL.
17. Using the BTS terminal, check that there are no outstanding alarms on the
BTS, and that all SBLs are in traffic.
18. Using the BTS terminal, update the remote inventory file uploaded in Step 3
with the following information:
Commissioning (current installation) date
Network identity
19. Using the BTS terminal, download the remote inventory file to the new
FACB in the BTS.
20. Disconnect the BTS terminal.
21. Close the front door of the BTS.
Tools and Materials You must have a BTS terminal and an RS-232 asynchronous communication
link cable to connect it to the MMI port. The MMI port is located on the front
panel of the SUM. Refer to the BTS Terminal User Guide for information
on how to use the terminal.
Impact on System The FANU can be replaced by hot-swapping (no power supply switched off),
and there is no loss of telecommunications resources.
Procedure To replace an FANU RIT:
1. Open the front door of the BTS. (Refer toOpen and Close BTS A9100
Cabinets (Section 3.1) for more information.)
2. Connect the BTS terminal to the MMI port on the SUM in the STASR.
3. Using the BTS terminal, disable the CCFn SBL, where n = the SBL number
between 1 and 23. If n is unknown, use the Display Hardware Configuration
screen of the BTS terminal to find it.
4. Locate the faulty FANU at the top of the cabinet or the bottom of the
appropriate subrack. Lift the latch underneath the handle at the front to
release the FANU, and then pull it out from the backplane.
Note: To access a top FANU, you must remove the cabinet top cover and the
FANU front panel.
Backplane Damage
Do not use excessive force when inserting the FANU.
5. Push the replacement FANU fully into the empty slot ensuring that pins and
sockets are correctly aligned. Check that the latch snaps into the locked
position.
6. Using the BTS terminal, set the part number into FACB remote inventory
additional module field.
7. Using the BTS terminal, initialize the CCFn SBL.
8. Using the BTS terminal, check that there are no outstanding alarms on the
BTS, and that all SBLs are in traffic.
9. Disconnect the BTS terminal.
10. Close the front door of the BTS.
2. Locate the appropriate HEAT2 inside the compartment (for module position
see Figures COME/COMI/COEP Module Positions (17) to MBO2 Module
Positions (21)) and disconnect the one (or optionally two) AC power
connectors.
The HEAT2 is located on the floor or side wall of the compartment or
directly underneath the HEX4 at the back of the front door of MBO1. The
power connectors are mounted on the front plate of the HEAT2, next
to the thermostat.
3. Remove the four screws securing the HEAT2 plate to the floor or side wall of
the compartment or to the door and remove the HEAT2.
4. Place the replacement HEAT2 in position and replace the four screws.
5. Re-connect the AC power connectors to the new HEAT2.
6. Connect the BTS terminal to the MMI port on the SUM in the STASR.
7. Using the BTS terminal, set the part number into BTSRI remote inventory
additional module field.
8. Using the BTS terminal, check that there are no outstanding alarms on the
BTS, and that all SBLs are in traffic.
9. Disconnect the BTS terminal.
10. Close the front doors of the BTS.
Heavy Equipment
The HEX2 weighs 24 kg and there is no handle. Injury to personnel and
damage to equipment may result if it is dropped or otherwise mishandled.
Be careful when removing the HEX2. Do NOT remove the bolts that secure it to
the door until it is properly supported.
Gasket Damage
While placing the replacement HEX2 against the door in the next step, take
care not to damage the gasket between the HEX2 and the door.
7. Place the replacement HEX2 against the door and replace the four bolts.
Support the HEX2 until the bolts are fully tightened.
8. Re-connect the two D-type connector cables to the left side of the Control
Box at the bottom of the HEX2.
9. Secure the cables to the HEX2 using three cable ties.
10. Depending on the BTS variant, switch ON (up) the circuit breaker F2 on the
front panel of the DCDP or the HEX breaker on the busbar.
11. Verify that the red ALARM LED above the temperature readout on the
Control Box is OFF.
12. Connect the BTS terminal to the MMI port on the SUM in the STASR.
13. Using the BTS terminal, set the part number into BTSRI remote inventory
additional module field.
14. Using the BTS terminal, check that there are no outstanding alarms on the
BTS, and that all SBLs are in traffic.
15. Disconnect the BTS terminal.
16. Close the front doors of the BTS.
Heavy Equipment
The HEX3 weighs 24 kg, the HEX4 weighs 28 kg, and not all HEX variants
have handles. Injury to personnel and damage to equipment may result if it is
dropped or otherwise mishandled.
Be careful when removing the HEX. Do NOT remove the bolts that secure it to
the door until it is properly supported.
Gasket Damage
While placing the replacement HEX against the door in the next step, take care
not to damage the gasket between the HEX and the door.
7. Place the replacement HEX3 or HEX4 against the door and replace the four
bolts. Support the HEX3 or HEX4 until the bolts are fully tightened.
8. Re-connect the D-type connector cable to the Control Box at the upper
part of the HEX3 or HEX4.
9. If necessary secure the cable to the HEX3 or HEX4 using the cable tie(s).
10. Switch ON (up) the HEX breaker on the busbar.
11. Verify that the red ALARM LED above the temperature readout on the
Control Box (to the right of the D-type connector) is OFF.
12. Close the front door(s) of the BTS.
AC handling
Be careful when handling AC circuits and components!
2. Detect the defective lightning protector (for DEHN supplier a red indication
field and for PHOENIXCONTACT supplier a green indication field indicates
that the lightning detector has to be replaced) at the top cover of the AC
distribution box.
3. Unscrew the retaining screws of the top cover and put it aside.
4. Remove the defective lightning protector and insert a new one.
5. Replace the top cover of the AC distribution box and tighten the retaining
screws.
6. Close the front door of the external outdoor battery cabinet.
AC handling
Be careful when handling AC circuits and components!
2. Detect the defective lightning protector (for DEHN supplier a red indication
field and for PHOENIXCONTACT supplier a green indication field indicates
that the lightning detector has to be replaced) at the top cover of the LPFM.
3. Unscrew the four retaining nuts (TORX, M4) of the LPFM top cover and put
it aside.
4. Remove the defective lightning protector and insert a new one.
5. Replace the top cover of the LPFM and tighten the retaining screws.
6. Close the front door of the MBO1.
AC handling
Be careful when handling AC circuits and components!
2. Unscrew the retaining screw (TORX, M4) in the middle of the LPFU top
cover, if available. Open the LPFU by pulling off the top cover. The following
figure shows an internal view of the LPFU.
Retaining Thread
(not necessarily equipped)
Lightning Protector
3. Remove the lightning protector (for DEHN supplier a red indication field and
for PHOENIXCONTACT supplier a green indication field indicates that the
lightning detector has to be replaced) and insert a new one.
4. Replace the top cover of the LPFU, press the cover down until it locks and
tighten the retaining screw (if available).
5. Close the front doors of the BTS.
Backplane Damage
Do not use excessive force when inserting the PM08.
6. Push the replacement PM08 fully into the empty slot ensuring that pins
and sockets are correctly aligned.
7. Tighten the quarter-turn Camloc fasteners on the front panel of the PM08.
8. Re-connect the power cable to the front panel of the PM08 and verify that
the green On LED on the front panel is ON.
9. Disconnect the anti-static wrist strap.
10. Press the Status button on the front panel of the BCU1 repeatedly until
the Rectif status is displayed and verify that the status of the PM08s is
"Y Y Y Y Y".
The following character designations are used:
11. Press the Status button on the front panel of the BCU1 repeatedly until the
Alarm status is displayed and verify that the status of the PM08s is "- - - - -".
A "-" in any display position indicates that the PM08 in the corresponding
slot is not in an alarm condition. Any other character in the display indicates
an alarm condition.
12. Connect the BTS terminal to the MMI port on the SUM in the STASR.
13. Using the BTS terminal, set the part number into BTSRI remote inventory
additional module field.
14. Using the BTS terminal, check that there are no outstanding alarms on the
BTS, and that all SBLs are in traffic.
15. Disconnect the BTS terminal.
16. Close the front door of the BTS.
Backplane Damage
Do not use excessive force when inserting the PM11.
4. Push the replacement PM11 fully into the empty slot, ensuring that pins
and sockets are correctly aligned.
5. Tighten the retaining screws on the front panel of the PM11.
6. Verify that the green On LED on the front panel of the PM11 is ON.
7. Press the Status button on the front panel of the BCU2 repeatedly until the
power module status is displayed. Verify that the status is "PM Y Y Y Y".
The following character designations are used:
8. Press the Status button on the front panel of the BCU2 repeatedly until the
Alarm status is displayed. Verify that the alarm status is "ALM".
Any other character in the display, for instance "ALM M", indicates an alarm
condition. The following character designations are used:
9. Connect the BTS terminal to the MMI port on the SUM in the STASR.
10. Using the BTS terminal, set the part number into BTSRI remote inventory
additional module field.
11. Using the BTS terminal, check that there are no outstanding alarms on the
BTS, and that all SBLs are in traffic.
12. Disconnect the BTS terminal.
13. Close the front doors of the BTS.
Backplane Damage
Do not use excessive force when inserting the PM11.
7. Push the replacement PM11 fully into the empty slot, ensuring that pins
and sockets are correctly aligned.
8. Tighten the retaining screws on the front panel of the PM11.
9. For each of the other three PM11s, repeat Steps 5to 8.
10. Switch ON (up) the circuit breakers F3, F4 and F5 on the front panel
of the ACSP.
11. Verify that the green On LED on the front panel of each of the PM11s is ON.
12. Press the Status button on the front panel of the BCU2 repeatedly until the
power module status is displayed. Verify that the status is "PM Y Y Y Y".
The following character designations are used:
13. Press the Status button on the front panel of the BCU2 repeatedly until the
Alarm status is displayed. Verify that the alarm status is "ALM".
Any other character in the display, for instance "ALM M", indicates an alarm
condition. The following character designations are used:
14. Connect the BTS terminal to the MMI port on the SUM in the STASR.
15. Using the BTS terminal, set the part number into BTSRI remote inventory
additional module field.
16. Using the BTS terminal, check that there are no outstanding alarms on the
BTS, and that all SBLs are in traffic.
17. Disconnect the BTS terminal.
18. Close the front doors of the BTS.
Backplane Damage
Do not use excessive force when inserting the PM12.
5. Push the replacement PM12 fully into the empty slot, ensuring that pins
and sockets are correctly aligned.
6. Tighten the retaining screws on the front panel of the PM12.
7. Connect the cable disconnected in step 2 to the connector on the front
panel of the new PM12.
8. Verify that the green On LED on the front panel of the PM12 is ON.
9. Connect the BTS terminal to the MMI port on the SUM in the STASR.
10. Using the BTS terminal, update the remote inventory file with the following
information:
Network identity
Logical site name
11. Using the BTS terminal, download the remote inventory file to the PM12 in
the BTS.
12. Disconnect the BTS terminal.
13. Close the front door(s) of the BTS.
A wrench (M6)
A vinyl plastic electrical tape (for MAB; part of the installation kit for MAB:
3BK 08840 AAAA)
Impact on System All telecommunications resources are lost when BTS_TEL is locked (disabled).
13. Put the new MAB and the fixation band in their installation position, secure it
and tighten up the retaining screws of the fixation band.
14. Re-connect the RF cables and the ground cable as noted down before. Use
the vinyl plastic electrical tape to cover the RF connectors.
15. Re-connect the power supply cable to the front panel of the PDU.
Alarm Indication
The power cable must not be connected to the PDU before a complete
installation of all other cables has been set correctly!
Otherwise alarm reports will appear, hence, one or more red LEDs will be
activated. A resetting of the PDU will be required. This resetting can be carried
out by pressing the ’TRX 1 RESET’ and ’TRX 2 RESET’ buttons with a pencil.
Alarm Indication
The power cable must not be connected to the PDU before a complete
installation of all other cables have been set correctly!
Otherwise alarm reports will appear, hence, one or more red LEDs will be
activated. A resetting of the PDU will be required. This resetting can be carried
out by pressing the ’TRX 1 RESET’ and ’TRX 2 RESET’ buttons with a pencil.
On the ACSB/ACMU the Residual Current Device is the first block from
the left in the block of circuit breakers.
On the ACSB/ACMU the Residual Current Device is the first block from
the left in the block of circuit breakers.
On the ACSP or ACSU (versions AA or AB) the Residual Current Device
is the first block from the right in the block of circuit breakers.
The SUMA RIT part number is 3BK 08925 AA or 3BK 08925 DA (inclusive
GPS receiver).
Impact on System All telecommunications resources are lost when BTS_TEL is locked (disabled).
Procedure To replace a SUMP/SUMA RIT:
1. Open the front door of the BTS. (Refer toOpen and Close BTS A9100
Cabinets (Section 3.1) for more information.)
2. Connect the BTS terminal to the MMI port on the SUMP/SUMA in the
STASR.
3. Using the BTS terminal, display the following information and write it down
for use later in the procedure:
SUMP/SUMA Q1 address
Backplane Damage
Do not use excessive force when inserting the SUMP/SUMA.
12. Push the replacement SUMP/SUMA fully into the empty slot ensuring that
pins and sockets are correctly aligned.
13. Tighten the quarter-turn Camloc fasteners on the front panel of the
SUMP/SUMA.
14. Disconnect the anti-static wrist strap.
15. Re-connect the BTS terminal cable to the MMI port on the front panel
of the SUMP/SUMA. Do NOT re-connect the other cables to the front
panel at this time.
16. Use the BTS terminal to set the SUMP/SUMA Q1 address as noted in
Step 3.
17. Using the BTS terminal, download to the BTS the transmission settings
from the file uploaded in Step 4.
18. Re-connect the BTS Connection “Area Flat cable” to the front panel of the
SUMP/SUMA, and then the Abis Si cable.
19. If the SUMA contains a GPS receiver connect the GPS cable on the front
panel of the SUMA.
20. Wait for the OMU LED on the front panel of the SUMP/SUMA to start
flashing (after 5 to 10 minutes), and then stop flashing (when the software
has been downloaded).
21. Use the BTS terminal to initialize the RAx SBLs for each cell (x = 1 to
6 sectors, as applicable).
Ensure that all the RAx SBLs are IT before continuing to the next step.
22. Use the BTS terminal to initialize the BTS_TELx SBLs for each cell (x
= 1 to 6 sectors, as applicable).
Ensure that all the BTS_TELx SBLs for each cell are IT before continuing to
the next step.
23. Using the BTS terminal, display the states of all the SBLs and all the
outstanding alarms and ensure they are the same as in Step 3
24. Using the BTS terminal, update the remote inventory on the new
SUMP/SUMA with the following information:
Commissioning (installation) date
Network identity
Impact on System All telecommunications resources are lost when BTS_TEL is locked (disabled).
SUMP Q1 address
4. Using the BTS terminal, from the Online Mode menu bar, select:
Show —> Remote Inventory —> Manufacturing Part —> Application
Part —> Sector MappingWrite down the following information for later use
in the procedure:
Sector Mapping
Position of Rotary Switches
VSWR.
Ensure that all the BTS_TELx SBLs for each cell are OPR before continuing
to the next step.
7. Use the BTS terminal to disable the RAx SBLs for each cell (x = 1 to
6 sectors, as applicable).
Ensure that all the RAx SBLs for each cell are OPR before continuing to
the next step.
8. Disconnect the Abis Si cable on the front panel of the SUMP and then the
BTS Connection Area flat cable and the BTS terminal cable.
9. Connect the anti-static wrist strap.
10. Loosen the quarter-turn Camloc fasteners on the front panel of the SUMP.
11. Carefully disengage the SUMP from the backplane and fully withdraw it
from the slot.
Backplane Damage
Do not use excessive force when inserting the SUMA.
12. Push the replacement SUMA fully into the empty slot ensuring that pins
and sockets are correctly aligned.
13. Tighten the quarter-turn Camloc fasteners on the front panel of the SUMA.
14. Disconnect the anti-static wrist strap.
15. Re-connect the BTS terminal cable to the MMI port on the front panel of the
SUMA. Do NOT re-connect the other cables to the front panel at this time.
16. Use the BTS terminal to set the SUMA Q1 address as noted in Step 3.
17. Using the BTS terminal, download to the BTS the transmission settings
from the file uploaded in Step 5.
18. Re-connect the BTS Connection Area cable to the front panel of the SUMA,
and then the Abis Si cable.
19. Wait for the OMU LED on the front panel of the SUMA to start flashing
(after 5 to 10 minutes), and then stop flashing (when the software has
been downloaded).
20. Use the BTS terminal to set sector mapping and VSWR as noted in Step 4.
From the Online Mode menu bar, select
Commissioning —> Edit Remote Inventory —> Manufacturing Part —>
Application Part —> Sector Mapping
Then select ’Add antenna-sector mapping (TLV386) to RI’.
21. Use the BTS terminal to restart the OMU. From the Online Mode menu
bar, select
CMDS —> SBL Management
Then check ’SBL Modul States’; all RAs have to be in state ’OPR’.
22. Use the BTS terminal to initialize the RAx SBLs for each cell (x = 1 to
6 sectors, as applicable).
Ensure that all the RAx SBLs are IT before continuing to the next step.
23. Use the BTS terminal to initialize the BTS_TELx SBLs for each cell (x
= 1 to 6 sectors, as applicable).
Ensure that all the BTS_TELx SBLs for each cell are IT before continuing to
the next step.
24. Using the BTS terminal, display the states of all the SBLs and all the
outstanding alarms and ensure they are the same as in Step 3
25. Use the BTS terminal to update the remote inventory on the new SUMA with
the following information:
Commissioning (installation) date
Network identity
Part number
A wrench (M6)
Insulating tape (1AC 01595 0001) and vinyl adhesive tape (1AC 01556
0001) for watertightness connections
Impact on System All telecommunications resources are lost when BTS_TEL is locked (disabled).
Thermal Restrictions
In addition to replace a faulty module by an identical one, a faulty non-EDGE
TRE module can be replaced by an EDGE TRE module, i.e. TRxM by TRAx
and TRDH by TADH.
Before using EDGE TRE modules please check in the rack configurations
shown in the EVOLIUM BTS A9100 Hardware Description that your equipment,
after replacement, does not exceed the possible thermal restrictions (especially
for the medium power TRAP modules which have a power consumption and a
thermal dissipation comparable to high power GSM modules.
Impact on System All telecommunications resources are lost when BTS_TEL is locked (disabled).
Backplane Damage
Do not use excessive force when inserting the TRE.
10. Push the replacement TRE fully into the empty slot ensuring that pins
and sockets are correctly aligned.
11. Tighten the quarter-turn Camloc fasteners on the front panel of the TRE.
12. Re-connect the cables to the front panel of the TRE.
13. Disconnect the anti-static wrist strap.
14. Switch on the power switch on the front panel.
15. Using the BTS terminal, initialize the TRE SBL and then BTS_TEL, if it
was disabled.
16. Using the BTS terminal, check that there are no outstanding alarms on the
BTS, and that all SBLs are in traffic.
17. Using the BTS terminal, upload from the BTS the TRE remote inventory
file UT_TRE xx, where xx is the TRE number.
18. Using the BTS terminal, update the remote inventory file with the following
information:
Commissioning (installation) date
Network identity
19. Using the BTS terminal, download the remote inventory file to the new
TRE in the BTS.
20. Disconnect the BTS terminal.
21. Close the front door of the BTS.
Tools and Materials You must have a torque wrench with an M6 adaptor.
Impact on System All telecommunications resources are lost when BTS_TEL is locked (disabled).
Procedure To replace an XIOB RIT:
1. Open the front door(s) of the BTS. (Refer toOpen and Close BTS A9100
Cabinets (Section 3.1) for more information.)
2. Connect the BTS terminal to the MMI port on the SUM in the STASR.
3. Use the BTS terminal to disable BTS_TEL and BTS_OM SBL. Enter a
WTC = 3 minutes to ensure an orderly shutdown of the BTS. Wait three
minutes before continuing to the next step.
4. Using the BTS terminal, disable the EACB 1 SBL.
5. Connect the anti-static wrist strap.
6. Disconnect the power cable from the bottom of the XIOB. The XIOB is
located behind the COAR on the right side of the Side Compartment, but is
accessed through the left side of BTS Compartment 1.
7. A flat ribbon cable is connected to the back of the COAR through a slot in
the XIOB. Loosen the retaining screws and remove the connector from
the COAR.
8. Remove the five TORX screws securing the XIOB to the back of the COAR,
and then remove the XIOB.
9. Install the new XIOB and secure it to the back of the COAR with the
TORX screws.
10. Re-connect the flat ribbon cable to the COAR through the slot in the XIOB
and tighten the retaining screws.
11. Re-connect the power cable to the bottom of the XIOB.
12. Disconnect the anti-static wrist strap.
13. Using the BTS terminal, initialize the EACB 1 and BTS_OM SBLs and
then BTS_TEL.
14. Using the BTS terminal, check that there are no outstanding alarms on the
BTS, and that all SBLs are in traffic.
15. Using the BTS terminal, upload the XIOB remote inventory file
UT_XIOB_BCB from the BTS.
16. Using the BTS terminal, update the remote inventory file with the following
information:
Network identity
17. Using the BTS terminal, download the remote inventory file to the XIOB in
the BTS.
18. Disconnect the BTS terminal.
19. Close the front door(s) of the BTS.
A TORX screwdriver
A BTS terminal and an RS-232 asynchronous communication link cable
to connect it to the MMI port. The MMI port is located on the front panel
of the SUM. Refer to the BTS Terminal User Guide for information on
how to use the terminal.
7. Using the BTS terminal, check that there are no outstanding alarms on the
BTS, and that all SBLs are in traffic.
8. Using the BTS terminal, upload the XIBM remote inventory file
UT_XIOB_BCB from the BTS.
9. Using the BTS terminal, update the remote inventory file with the help of the
information noted before for the following data:
Network identity
This chapter tells you how to reload the OMU software in a BTS.
It contains a procedure for reloading the software via a BTS, BSC or OMC-R
terminal.
Prerequisites You must have read Safety Rules and Precautions (Chapter 1) before
performing any reloading procedures.
The BTS is still available during the reset and subsequent reload of OMU
software. Although the OMU is not available, calls can be set up and
cleared in normal operating conditions.
Restrictions None.