Академический Документы
Профессиональный Документы
Культура Документы
com
Email: oilwatersales@recoveredenergy.com
OPERATIONS
&
MAINTENANCE
MANUAL
1. SYSTEM DESCRIPTION:................................................................................................3
1.1. Components by System.................................................................................................3
a. Pre-filter system.............................................................................................................3
b. Oil water separator system...........................................................................................3
c. Filter/Polishing System..................................................................................................4
d. Filter Backwash System................................................................................................4
e. OCM/turbidity Monitoring...........................................................................................4
f. Electrical/Controls.........................................................................................................5
1.2 Process Description........................................................................................................5
1.2.1 Pre-Filtration System:............................................................................................5
1.2.2 Oil Water Separator System..................................................................................5
1.2.3 Filter/Polishing System:..........................................................................................6
1.2.4 Filter Backwash/Blowdown System......................................................................7
1.2.5 OCM and Turbidity Monitoring System..............................................................8
1.2.6 Ultraviolet Sanitizing..............................................................................................8
1.2.7 Area Classification (Class I, Div II).......................................................................9
1.3 System Specifications.....................................................................................................9
1.4 Fault Alarms and Remote Monitoring Capabilities...................................................9
2. STARTUP..........................................................................................................................11
2.1 Factory Testing/Delivery.............................................................................................11
2.2 Installation....................................................................................................................11
2.3 Power Test....................................................................................................................11
2.4 pH Probe Installation..................................................................................................12
2.5 UV bulb Installation....................................................................................................12
2.6 Initial Water Filling.....................................................................................................13
2.7 OCM and Turbidity Test............................................................................................13
3. OPERATION.....................................................................................................................15
3.1. Normal Operation........................................................................................................15
3.2. Alarm and Action Conditions.....................................................................................15
3.3. Backwash Mode...........................................................................................................16
4. CONTROL SYSTEM DESCRIPTION...........................................................................17
5 TROUBLE SHOOTING:.................................................................................................29
6 MAINTENANCE..............................................................................................................31
7. SPARE PARTS..................................................................................................................32
7.1 Pumps............................................................................................................................32
7.2 Valves............................................................................................................................32
7.3 Monitoring Equipment................................................................................................33
7.4 PLC...............................................................................................................................34
7.5 Miscellaneous...............................................................................................................35
ATTACHMENT 1 - P&ID DRAWING..............................................................................36
ATTACHMENT 1 – ELECTRICAL SCHEMATICS.......................................................37
ATTACHMENT 3 - CALIBRATION SHEETS.................................................................46
ATTACHMENT 4 - CALCULATIONS..............................................................................47
The BOSS Platform oil water separation system includes the following basic components:
a. Pre-filter system
MOV-102 Inlet shutoff valve
F-101 Inlet filter Y strainer
F-104 Hydrocyclone particulate filter
V-102 System isolation valve
G-103 Inlet pressure
V-105 Sample valve
V-104 Vent valve
CV-101 F-104 return check valve
V-103 F-104 effluent isolation valve
c. Filter/Polishing System
(See Arrangement Photo—Attachment 2d)
e. OCM/turbidity Monitoring
(see Arrangement Photo—Attachment 2g)
f. Electrical/Controls
(see Arrangement Photo—Attachment 2h)
P1 Power disconnect
P2 Electrical panel
P3 PLC and Panel View display
AI-103 Turbidity meter and display
AI-101 OCM monitor
Process water is pumped to the system from the sump at a pressure of at least 2.3
bars. A shutoff valve (V102) is provided for system isolation. A Y strainer (F-101)
removes particulates larger than 1/20th of an inch in any dimension. The pre-filter
system also includes a differential pressure transmitter to determine when F-101
needs cleaning and a blow down valve (MOV-101) to blow down the Y strainer
when it is full. The process water goes through a control valve MOV-102 to
prevent water from back flowing from the system when the unit is off or in the
fill/oil discharge mode. The customer is responsible to determine what to do with
the blow down.
The pressure drop across F-101 starts out at 0 and will go up to whatever it is set at
before it causes the blowdown function to trigger. The pressure drop allowed will
depend on the inlet pressure available. F-104 needs at least 2 bar so the amount of
pressure drop available for F-101 is the difference between the inlet pressure and
the pressure drop required for F-104. The blowdown can be controlled either by the
pressure drop or time. A more complete description of how the blowdown works is
included in the discussion of the control system.
The water goes through a hydrocyclone (F-104) to remove smaller sediment down
to about 30 micron particle size. The sediment slurry comes out the bottom of the
hydrocyclone through an isolation valve (V-103) and must be handled in some way
by the customer. Any water going through the hydrocyclone that is more than the
capacity of the system will go back to the oily water storage tank or sump. The
pressure drop across F-104 is about 2 bar. The hydrocyclone will work better if
there is excess flow going through it.
The separator has an inner and outer section. The water comes up through the
center section of the separator through an oleophilic media (polyethylene or
polypropylene). The media facilitates the separation of the oil from the water by
providing a surface area that attracts droplets of oil and holds them until they
coalesce into larger droplets which rise rapidly to the surface of the water in the
separator. As oil collects in the top of the separator it displaces the water and forces
The water level in the separator downward. Any gas vapor or air that enters the
separator will rise rapidly to the top of the separator where it collects with the oil.
Air or vapor that collects in the separator will be discharged with the oil. A level
sensor (LS-101) in the top of the separator detects the water level in the separator.
When the oil in the top of the separator reaches the full level set point the process
pump (P-101 or P-102) shuts off, the discharge valves (SOV 101 or SOV 102) close
and Pump 103 or P-104 turns on until the oil level reaches the empty level set point
at which time the level switch automatically switches all the valves and pumps back
into the process mode. While the oil is being discharged the separator is not
operating. As the oil is evacuated the water level rises in the separator until the oil
reservoir is empty and the oil discharge valve shuts.
During normal operation oily water entering the system flows up through the center
section of the separator and over the top of the inner section weir where most of the
oil is separated from the water. The water then flows down through the outer
section of the separator, which contains additional media. The pass through the
second stage of coalescing media helps remove any residual oil and provides
discharge water from the primary separator in most cases with less than 15-PPM oil
content. Separated water exiting the separator comes out the bottom of the outer
section and is pumped to the sand filter (F-102) by P-101 or P-102. The suction of
the pump is continuously flooded with a positive head so there is no need to prime
the pump. The duplex pumps are progressive cavity pumps and share a common
safety relief valve. The process pumps are capable of pumping the design flow at 3
bar. The system is not designed for much turn down. As the flow is restricted the
pumps will go up in pressure to compensate. The system will operate best at design
flow. Depending on suction and head requirements for a given installation, the
process pump will be capable of pumping slightly more than the design flow rate
through the system. The flow rate is controlled by the flow meter (FM-102) and
control valve (FCV-101).
The water leaving the separator goes to a sand filter (F-102) to remove turbidity
from the water. The sand filter has a differential pressure transmitter (DPT-102)
and backwash feature that is discussed below.
The water then goes to a polishing filter (F-103) that can contain several different
types of bulk media. The initial charge of media is organoclay. The primary types
The filter has an inlet distributor at the top and an outlet distributor at the bottom.
The filter vessels are rated for 4.5 barg pressure. The pumps are sized to give no
more than 3.4 barg under normal operating conditions. A relief valve on the
process pumps is set at 3.4 barg.
The organoclay media will need to be replaced when the system will no longer keep
the oil content within acceptable limits. Before deciding that the media is spent,
clean the OCM cell and make sure the oil content reading is accurate. The media
can either be vacuumed out or dumped out through the side manway. Each filter
has an inlet nozzle on top that can be used to loan new media and an outlet nozzle at
the bottom that can be used to remove spent media. The used media can generally
be thrown away in the same manner a spent oil filter is discarded or with the other
municipal waste from the vessel or facility. It is generally best to add coarse sand
(40 mesh or coarser--#20) in the bottom of F-103 to a level a few inches above the
top of the bottom distributor. This helps keep the distributor from plugging up with
fines. Fill the rest of the filter with media up to a few inches below the top
distributor.
New organoclay will generally remove free oil to a non-detect level. If emulsions
are present it will require a combination of carbon and organoclay to achieve non-
detect levels. This can sometimes be done by combining carbon and organoclay in
the same filter. To do this load sand in the filter first, then carbon and then
organoclay on top.
When the Y strainer (F-101) needs to be cleaned MOV-102 closes, P-101 or P-102
shuts off, MOV-101 opens and P-105 or P-106 turns on. This forces the sediment
out of the Y strainer to wherever the customer sends the blowdown. It will only
take a few seconds to blow down the Y strainer. The blowdown can be set to come
on either based on the differential pressure or based on a timer. When the control
system calls for a blowdown of F-101 it will wait to blow down until the system
goes into the fill mode. This way the system will not be shutting down for the
blowdown. For more explanation of how the settings are adjusted for the
blowdown process see the discussion on the control system.
When the sand filter needs to be backwashed, the process pump (P-101 or P-102)
shuts off, the discharge valve (SOV-102) or recycle valve (SOV-101) shut off, the
backwash control valve (SOV-103) opens, MOV 102 closes and the backwash
pump (P-105 or P-106) turns on and runs for a pre set time that is adjustable by the
customer. The backwash can be set to come on either based on the differential
pressure or based on a timer or based on loss of flow. For more explanation of how
the settings are adjusted for the backwash process see the discussion on the control
system.
This system includes a NE Controls Oil Content Monitor (OCM), also referred to as
a The Oil Content Monitor (“OCM”) also called the Total Petroleum Hydrocarbon
meter (“TPH”) that has been certified to meet MEPC 60(33) regulations. The OCM
monitor has the ability to automatically return non-conforming discharge water
back to the sump or oily water storage tank. The recycle and discharge solenoid
valves (SOV-101 and SOV-102) are controlled by the oil content monitor (OCM).
The OCM unit, which has been tested and approved in accordance with IMO
Resolution MEPC 60(33), is set from the factory to alarm at 15 PPM. Through
the PLC, the monitor can be set to alarm down to 1 ppm.
Turbidity to the monitor should not be an issue if the sand filter is used because the
sand filter will remove the turbidity from the water.
The water goes from the organoclay filter to an ultraviolet disinfecting system
(UV-101) as it enters into the water storage tank (T-101). The UV unit disinfects
The system has been designed to meet a hazard area classification for Class I, Div
II, groups B,C and D. The pump motors are explosion proof. The solenoid valves,
motorized ball valves and level controller are rated for Class I, Div II. The
electrical panels are aluminum NEMA 7/4X enclosures. The PLC panel is NEMA
4X with a type Z purge control. The external wiring is armored cable with the
appropriate connectors. The Oil Content Monitor is enclosed in a NEMA 7/4X
enclosure. The PLC system included a PanelView Plus touch screen. All other
instruments or controls are properly protected and rated.
a. Dimensions
Length 157” –62.3 cm
Width 126” – 49.6 cm
Height 102” – 40.2 cm
Weight approx. 15,000 lbs. (6800 kg) dry
b. Flow rate—32 gpm (7.2 m³/hr.)
c. S-101 operating pressure— vacuum to 2.8 barg
d. F-102 operating pressure— < 4.5 barg
e. F-103 operating pressure— < 4.5 barg
f. T-101 operating pressure— atmospheric vessel
g. System test pressure – 6.3 barg
h. Operating temperature range—5 to 60 C
i. Maximum oil concentration—35%
j. Maximum specific gravity of oil to achieve design separation—0.95
k. Oil in water discharge-- <15 ppm
l. Maximum turbidity for accurate OCM reading—35 NTU
m. IMO MEPC Compliance—60(33)
n. Voltage—440 V 3 phase, 60 Hz.
o. Hazardous area classification—Class I, Div II group B,C,D
The OCM monitor is designed to alarm if the oil content exceeds the set limit or if the
OCM system fails. If the oil content exceeds the set limit the OCM alarms internally
and causes the system to go into recycle mode until the alarm condition no longer
exists. The alarm will show on the PLC display. Any OCM alarm or fault condition
will automatically put the system into the recycle mode. Potential causes of the OCM
system fault include:
a. loose or improperly inserted data card
b. loss of communication between the display and the detector (loose cable)
c. internal board or power supply failure
The customer can connect directly to the control system and obtain the following
information at a remote location:
a. 4-20 mA signal showing the ppm oil content in the water (0-20 ppm)
b. Voltage free contact for the OCM alarm
c. Voltage free contact for the OCM system fault
The customer can connect to the main control panel and obtain the following:
a. 120 V signal showing whether the system is in normal operation mode
(pump is running and either discharging water or recycling water)
b. 120 V signal showing whether the system is in fill mode (pump is not
running, the system is filling and oil is being discharged)
c. The customer can remotely start or stop the system with an external voltage
free contact.
Prior to delivery the system is tested in the manufacturers shop to verify that the
system is watertight and that all the pumps, instrumentation and controls are
operational. A FAT report is completed and included in the information provided
with the system. When the system arrives at it final destination it should be
carefully checked for damage that may have been sustained during shipping. All
damage should be noted and reported to the shipping company and to the
manufacturer. If replacement parts or components are needed the manufacturer
should be informed immediately.
2.2 Installation
The system is a self-contained package system that has been tested and operated
under test conditions at the factory. Within the system battery limits no
installation will be necessary except to mount the system, make the necessary
connections, bring power to the main disconnect, install the UV tubes and install
the pH probes.
After the system is placed in the location where it will operate, it will be necessary
to connect power and piping connections. The power connections to the main
power disconnect are shown on the electrical schematics attached as Attachment
3. All piping connections to the system are listed in Attachment 4. We would
advise the customer to install an isolation valve on any line where there is not one
from the factory EXCEPT the water discharge from T-101. It is important that
there not be any restrictions in this line. T-101 is designed to gravity flow to the
ocean. This is clean water that has been tested and the system will not allow water
into this tank that does not meet the ppm requirement. Any restrictions in this line
will plug up the whole system.
After the installation of power and before any water is put in the system the pumps
should be checked for proper direction of rotation. They will come from the
factory all tested so if you test the rotation of 1 pump (either P-101 or P-102) you
will know that the rotation is correct for all pumps.
Check that power has been connected and verified to the Main Disconnect. Turn
on the main disconnect. The PLC panel should power up. Go to either the PID or
Main Console screens. The system can be started from either of these screens.
Turn the system switch to Manual and bump any one of the pumps. Have someone
watch the blower end of the pump motors to verify the direction of pump rotation.
P-101, P-102, P-105 and P-106 rotate clockwise. P-103 and P-104 rotate counter
clockwise when looking at the blower end. If necessary correct the wiring for the
proper pump rotation. Switch the main system switch to off. Do not make any
The water tank (T-101) needs to be filled with clean water before the system can
start up. This will provide the water to fill up the rest of the system and to test the
system before introducing oily water. To fill up the tank connect a hose to the T-
101 drain and fill until water comes out the overflow. Once the water tank is
filled the system will be filled automatically from the water tank. The control
system includes an INITIAL FILL sequence. The instructions for this sequence
are built into the control system. It will take you through the process step by step.
The INITIAL FILL is only used when the system is empty at the initial startup or
when the system is emptied for maintenance. It should not be used in normal
operation.
Zero the OCM meter by doing the following. Open the top of the OCM cell and
fill with clean water. Open the plug on the bottom fitting to drain the OCM cell if
necessary. Replace the top plug. Set the display switch to the OCM position.
Adjust the potentiometer on the right side of the OCM electrical enclosure until
the display meter reads 0.00. This sets the zero for the OCM. All other
adjustments are factory adjustments and cannot be done in the field.
The OCM meter will likely read 15 ppm when the turbidity is greater the 35 NTU.
After all of the specified testing has been completed and the system has run
satisfactorily with clean water then the system can be put in operation with oily
water. Turn the system switch to automatic. This can be done either at the PID
screen or the Main Console screen. From this point everything should be
automatic. After the system has been put into operation care should be taken to
not allow the separator tank to be emptied. The system is designed to operate
without operator interface except in certain conditions as described below. :
There is 1 alarm condition and 4 action conditions that require operator response.
d. Short-cycle condition—If the inlet pump is pulling air into the system,
gas will collect in the top of the separator and force the oil down. This
will cause the level sensor to read high oil level and will short cycle the
oil discharge pump. This is a possible indicator that the external sump
low-level switch is faulty or the system is pulling more water than the
platform is generating. Check the sump level switch or adjust the
system flow rate. If the inlet line is plugged, or the pre-filter is
plugged, the separator will likely short cycle. Remove the restriction.
The control system is a redundant Allen Bradley ControlLogics PLC system that has been pre
programmed for easy operator interface. For questions regarding the programming or control
system itself refer to the Allen Bradley manual and instructions. The following section will
explain how the screens have been set up for operator interface. The screen shots that are shown
below do not necessarily represent an actual state of the machine.
The system will automatically boot up to the main screen when powered. The PanelView
screen is a touch screen. If it goes blank just touch the screen anywhere to bring it back up.
The following screen will come up whenever the system is turned on. The buttons give the
operator various screen options for controlling and setting the system parameters. The
system can be controlled either from the P&ID screen or the Console screen. The remaining
screens are used to set the operating parameters or to display the status of key operating
parameters. The button in the bottom right hand corner is exit out of this screen. If this
screen is exited it will shut off the PanelView. You will find this same button on all of the
screens. In the case of all other screens, pushing this button will exit to the previous screen
or the main screen.
The P&ID Screen shows a picture of the system components and their status at any given
time. You cannot change the settings for the pumps, valves, blowdowns, TPH or UV from
this screen. However, it will show the status of all of these components during normal
operations and during the Initial Fill procedure.
The system can be operated from this screen either in a manual or automatic mode. The
manual mode would generally be used only for maintenance purposes to test individual
components or sequences. The AUTO mode will turn on the system’s normal operating
sequences.
The E-STOP is an emergency stop button that will shut the system down regardless of what
is happening. This should only be used in emergency situations.
The INITIAL FILL button is used to initially fill up the system with water. Do not operate
the system in AUTO mode without filling the system up with water first.
Manual valves are shown smaller than solenoid (SOV) or motorized (MOV) valves and they
do not change color. They are shown for training purposes only. The indicators for LS102
and LS103 turn green when the PLC is receiving a signal from them. The actual state of the
liquid inside the tank is shown by the light blue indicators inside the tank. Same with the
separator tank level LS101.
The CONSOLE SCREEN, shown below, provides the ability to start the entire system, either
in manual or automatic mode. The system can be started or stopped either from the P&ID
SCREEN or the CONSOLE SCREEN. This screen also includes an emergency stop button.
The primary purpose of this screen is to enable or disable various backwash and pump
options.
This screen will also display a log of various alarm conditions and messages and allows you
to silence the alarms.
The INITIAL FILL screen is used ONLY during initial startup or after a major maintenance
process to fill the system with water prior to operating the system. This screen has a series of
instructions that will walk the operator through the initial fill procedure. After each
instruction is completed push the NEXT button to go to the next step or push the PREV
button to go back to an earlier step. This is a function that is done only when the system does
not have water, such as initial startup or after a major maintenance function. The INITIAL
FILL is not used in normal operations to fill the system up after an oil discharge.
The INITIAL FILL procedure can only be started from the P&ID screen. Once the INITIAL
FILL button is pushed on the P&ID screen the INITIAL FILL SEQUENCE screen will come
up and provide the instructions for how to proceed. The P&ID screen will show orange
rectangles around the tanks, valves or pumps that are affected in each step.
(Note: This screen shot does not represent an actual state of the machine.)
This screen shows the status of the valves. You cannot control the valves from this screen.
The pump screen shows the status of the pumps and is also used to select the pump that will
be running. The system will not switch back and forth between pumps. If you want to
switch pumps it has to be done from this screen.
(Note: This screen shot does not represent an actual state of the machine.)
This screen is used to set the parameters for the Y strainer (F-101) blowdown. The first line
shows the amount of time that the blowdown will be running. Normally the blowdown
should not be more than 1 minute. There is a counter on this clock showing the number of
seconds remaining for the blowdown.
The “Time Based” method allows the operator to set the number of days or hours between
each blowdown. This time should be set based on the experience of the operator about the
normal operating conditions.
The “Pressure drop Based” method allows the operator to set the differential pressure that
should be allowed. It also allows for the operator to set a delay so that the pressure has to
reach the set point for a fixed amount of time. This prevents the blowdown from happening
based on normal fluctuations in the differential pressure.
(Note: This screen shot does not represent an actual state of the machine.)
This screen is used to set the parameters for the sand filter (F-102) backwash. The first line
shows the amount of time that the backwash will be running. Normally the backwash should
not be more than 10 minutes. There is a counter on this clock showing the number of
seconds remaining for the backwash.
The “Time Based” method allows the operator to set the number of days or hours between
each backwash. This time should be set based on the experience of the operator about the
normal operating conditions.
The “Pressure drop Based” method allows the operator to set the differential pressure that
should be allowed. It also allows for the operator to set a delay so that the pressure has to
reach the set point for a fixed amount of time. This prevents the blowdown from happening
based on normal fluctuations in the differential pressure.
The “Flow loss Based” method allows the operator to set the allowed flow loss before the
system goes into backwash.
The operator can choose from any of these methods. Experience will determine which
option is better.
(Note: This screen shot does not represent an actual state of the machine.)
The FLOW CONTROL screen is used to control the flow control valve. The setpoint will
generally be the design flow of 7.2 m³/hr. The system is not designed to deviate much from
The gain and reset allow the operator to adjust the reaction time and speed for how the valve
opens and closes. The flow control loop is extremely fast by nature. In the BOSS 32 TPX oil
separator system, the distances between the pressurized tank, the control valve and the
volumetric flow transmitter are small. Therefore, the dead band (the time between the
moment the valve changes position and the transmitter sees a change in flow) and the lag (the
capacity of the pipe and flow transmitter internals) are very small. We estimate them at 1
second each.
With those values in mind, good start values for the PID controller are:
Gain = 0.6
Reset = 60 repeats/minute
Those values should provide a quick reaction time and a 1/4 amplitude response (the second
overshoot after a set-point change should less than 1/4 of the first one).
If the process is slower than 1 second you will see oscillations. In that case, reduce the reset
value to 30 repeats/minute and try again. If the process is faster than 1 second the original
values should work as well. When the system is in MANUAL mode (selected from the
P&ID or Overview screens, you can enter a desired control valve opening by touching the
“Manual CV” button.
(Note: This screen shot does not represent an actual state of the machine.)
This screen allows the operator to set the alarm level for the OCM. It shows the set point
limit and the actual measured oil content. The delay allows for minor fluctuations without
alarming the system. The maximum delay is programmed into the computer and is set by
IMO.
The UV Light screen allows the operator to set the number of hours of runtime before the
UV light needs to be changed. The maximum runtime is 3000 hours. This is a maintenance
feature to inform the operator when the UV light should be changed.
The oil pump delay allows the operator to set a delay before the oil pump comes on so that
the oil pump will never be pumping dry.
(Note: This screen shot does not represent an actual state of the machine.)
The Allen-Bradley ControLogix system supplied includes two identical chassis that host a
processor card, a redundant module, an Ethernet card and a ControlNet card each. A
separate chassis includes two ControlNet cards and the I/O modules. There is a single
ControlNet network that links all four ControlNet cards.
The two Ethernet cards share the same IP address and the two ControlNet cards (in the
processor chassis) share the same ControlNet node number. When the Primary processor
At the time of commissioning of this system (December 2009), Allen-Bradley does not offer
firmware revision 17 for the redundant modules. For that reason, the processors and
ControlLogix program are set at revision 16.xx. please do not upgrade the firmware or the
ControlLogix program to revision 17.
The following suggestions are provided for situations that have been encountered in the past:
If a solenoid valve does not work the most likely cause is a failure of the coil or a loose wire.
You can verify the electrical continuity from the control panel. To replace the coil, turn off the
power to the system, disconnect the wiring, remove the cover and replace the coil.
NEVER remove the coil with the power still connected. You will destroy the coil instantly if
the coil is separated from the valve and the power somehow is either left on or gets turned on.
If the valve needs a new gasket or O ring turn off the power and make sure there is no power to
the coil. Then loosen the nut just above the valve and remove the coil section. Replace the
gasket/Oring and reassemble the valve. Do not turn the power back on until the valve is fully
reassembled.
5.2 MOV
If an MOV is not functioning properly the first thing to check is the internal limit switch. Most
of the problems with the MOV are with the internal limit switch. The normal symptom is that
the MOV opens but fails to make full contract. The MOV opens but the other related valve(s)
do not perform their normal function. If this happens you likely have a bad switch on the
MOV and need to replace the switch.
5.3 Filters
There are a number of situations that can occur with the filters:
a. If there is turbidity in the water the OCM monitor can give a false oil content
reading. The sand filter should prevent this from happening.
b. If you have high levels of emulsions and the organoclay is not removing the oil
adequately, you may need to use carbon instead of organoclay or you can use a
combination of carbon and organoclay. Carbon will work better for emulsions and
organoclay will work better for free oil. If you use the combination you should
load a bed of sand first, then carbon and then organoclay. The water goes down
through the media. It is best to go through the organoclay first and then the carbon.
c. If you are running high concentrations of oil the primary separator may pass more
than 15 ppm oil. The system will handle up to 100% slugs of oil and will handle
25% or more on a continuous basis. However, the water coming out of the
separator will also go up in oil content. This is generally not a problem because the
organoclay filter will remove the oil. However, the organoclay media will fill up
faster and the media will need to be changed more often.
d. The organoclay works best in a downflow configuration, where the water goes
down through the media. The oil content will be at least 5 ppm lower in a
downflow configuration.
You can also hire a local filter company (such as US Filter) to change the media.
They will come out and vacuum out the filter and replace the media.
h. Sometimes a high OCM reading has nothing to do with the filter and is simply
caused by a dirty OCM cell. The glass in the cell should be cleaned on a regular
basis. This should be the first thing checked when the monitor is in alarm mode.
B. Valves—The solenoid valves installed on the system are high quality marine grade
valves and do not require lubrication. If sand particles get into the solenoid valves it can
cause them to leak and they will need to be cleaned. The coils and gasket may need to be
replaced periodically. NEVER remove the solenoid from the valve with the power on.
This will IMMEDIATELY destroy the coil and will void any warranty on the valve.
The most common maintenance on the motorized ball valves is the replacement of the
switch. On rare occasions the switch will open or close but not make full contact.
C. OCM Monitor—The OCM will need a periodic check of zero against clean water,
and frequent cleaning of the glass sample cell. Any maintenance on the OCM will require
the unit to be sent back to the factory for repair.
D. Coalescing Media—The coalescing media in the separator should last for several
years. It does not require specific maintenance or replacement under normal operating
conditions. If the media is damaged by adding chemicals to the water or for some unusual
reason you should do the following in order to change out the media:
1. Remove the old media. This is easier if you make a hook using a small
diameter rod. Shove the rod down the side of the media. Turn 90 degrees so
the hook part is under the media and use the hooked rod to pull the media up.
2. The replacement media should come packaged with an inner section and an
outer section. The inner section should come partially shoved inside the outer
section. Remove the inner section.
3. It doesn’t matter which section you install first. Place the media in the proper
section and get it started, making sure not to damage the edge of the media
trying to force it in place. The media should be tight but not too tight. If the
section is too large you may need to trim a small amount off the roll. To do
this just cut off the excess with a utility knife.
4. It is easier to push the media into the vessel with 2 people. Both people can
help get the media started about 1/3 of the way. Then use the round piece of
wood to put on top of the media and push down uniformly.
5. Repeat the same process for the other section of media. The inner section
should be pushed down about 1-2 inches below the weir. The outer section
should be pushed down just below the weir.
7. SPARE PARTS
The following list shows the available spare parts that could be needed for routine
maintenance and repair of the Recovered Energy platform oil/water separation system. In the
case of valves, OCM, turbidity, UV and pH, we recommend that the customer spare a
complete assembly plus rebuild components. That way if a component breaks down the spare
assembly can be installed and the rebuild kit can be used to repair the component that failed
and the customer will always have a functioning spare.
7.1 Pumps
7.2 Valves
a. Complete units:
7.4 PLC
7.5 Miscellaneous
Calculation Data
The separator vessel is designed for a 7.8 minute retention time. The normal design is a 5
minute retention time but the system design does not fit a standard certified size so the
system is sized for the next size up standard certified size. The time is divided between
the inside and outside compartments.
The sand filter is designed for no more than 12 gpm per square feet of surface area.
The backwash pump for the sand filter is designed for at least 15 gpm per sq. ft surface
area.