VOLTAGE DROP CALCULATION

Project: Proposed Globe Radio Room


Address: VISTA MALL NAGA

SOURCE OF DATA
- Load Schedule: Size of wire (mm2)
- Length of wire (m): Based on key plan
- Formula used was based on 1 & 3 Phase Voltage Drop

SIZE OF Z/30 V-LOAD


DESCRIPTION VA METERS AMP VD %VD REMARKS
WIRE 5 END
Source to Radio
26,280 190 30mm sq. 0.16 37.93 6.514 1.629 393.49 PASSED
Room
CIRCUIT 1 10,000 12 3.5mm sq. 1.7 43.48 5.816 2.529 224.18 PASSED
CIRCUIT 2 360 10 3.5mm sq. 1.7 1.57 0.174 0.076 229.83 PASSED
CIRCUIT 3 10,000 12 14mm sq. 0.45 43.48 1.540 0.669 228.46 PASSED
CIRCUIT 4 200 10 3.5mm sq. 1.7 0.87 0.097 0.042 229.90 PASSED
CIRCUIT 5 2,760 10 14mm sq. 0.45 12.00 0.354 0.154 229.65 PASSED
CIRCUIT 6 2,760 10 3.5mm sq. 1.7 12.00 1.338 0.582 228.66 PASSED
CIRCUIT 7 200 10 5.5mm sq. 1.1 0.87 0.063 0.027 229.94 PASSED
SPARE - - - - - - - - -
SPARE - - - - - - - - -
SPARE - - - - - - - - -

Note: Full Load Current is used in the calculation of voltage drop.

Findings: VD are acceptable


Recommendation(s): None

SHORT-CIRCUIT CURRENT CALCULATION


30kva Transformer
400V , 3Ø , Z(4.3%)

1 set – (3) 30mm2 Cu Wire in Magnetic Conduit


C = 5,907

Distribution Line 1:

At point 1.

kVA ( Transformer ) 30 kVA


IFL(TRANSFORMER) = = 1.732 x 400 = 43.30A
1.732 x V ( L−L)

IFL(Transformer) 43.30
I(SC1) = = 4.3 % x .9 = 1,118.86A
Z (.9)

At point 2 & 3

1.732 x L x I ( SC 1) 1.732 x 623.36' x 1,118.86


f= = = 0.511
C x n x V ( L−L) 5,907 x 1 x 400

1 1
M= = = 0.66
1+f 1+ 0.511

I(SC2) = M x I(SC1) = 0.66 x 1,118.86 = 738.45A = 5kaic