SECTION 12

TRANSDUCER INSPECTION
FIELD INSPECTION AND TEST REPORT

TRANSDUCER

Plant : . Customer : .
Location : . Project : .
Unit : . Device No : .
Panel : . Feeder : .
TECHNICAL DATA
Manufacturer . Serial no. .
Type Amp . Scale .
Rated input . CT Ratio .
Rated Output . PT Ratio .
Accuracy class . Rated DC supply .
.
1. VISUAL INSPECTION CHECKED
1.1 Compare equipment Name plate data with drawing and specification .
1.2 Inspection of physical and mechanical damage .
1.3 On base fixing .
1.4 Cable connection .
1.5 Tightness of bolts/screws .
1.6 Verify the unit is clean .

2. TRANSDUCER TEST
Current Transducer
Phase A

Injected Should be AS Found


% Error
Current ( A ) ( mA ) ( mA )
0.00 4
0.25 8
0.50 12
0.75 16
1 20

Current Transducer
Phase B

Injected Should be AS Found


% Error
Current ( A ) ( mA ) ( mA )
0.00 4
0.25 8
0.50 12
0.75 16
1 20

Tested by Reviewed by Witnessed by

Date Date Date


FIELD INSPECTION AND TEST REPORT

TRANSDUCER

Plant : . Customer : .
Location : . Project : .
Unit : . Device No : .
Panel : . Feeder : .
TECHNICAL DATA
Manufacturer . Serial no. .
Type Amp . Scale .
Rated input . CT Ratio .
Rated Output . PT Ratio .
Accuracy class . Rated DC supply .
.
Current Transducer
Phase C

Injected Should be AS Found


% Error
Current ( A ) ( mA ) ( mA )
0.00 4
0.25 8
0.50 12
0.75 16
1 20

Test Equipment:

Comment: .
.
.

Tested by Reviewed by Witnessed by

Date Date Date


FIELD INSPECTION AND TEST REPORT

TRANSDUCER

Plant : . Customer : .
Location : . Project : .
Unit : . Device No : .
Panel : . Feeder : .
TECHNICAL DATA
Manufacturer . Serial no. .
Type Volt . Scale .
Rated input . CT Ratio .
Rated Output . PT Ratio .
Accuracy class . Rated DC supply .
.
1. VISUAL INSPECTION CHECKED
1.1 Compare equipment Name plate data with drawing and specification .
1.2 Inspection of physical and mechanical damage .
1.3 On base fixing .
1.4 Cable connection .
1.5 Tightness of bolts/screws .
1.6 Verify the unit is clean .

2. TRANSDUCER TEST
Voltage Transducer
Phase A-B

Injected Should be AS Found


% Error
Voltage ( V Ac ) ( mA ) ( mA )
0.00 4
25 8
50 12
75 16
100 20

Voltage Transducer
Phase B-C

Injected Should be AS Found


% Error
Voltage ( V Ac ) ( mA ) ( mA )
0.00 4
25 8
50 12
75 16
100 20

Tested by Reviewed by Witnessed by

Date Date Date


FIELD INSPECTION AND TEST REPORT

TRANSDUCER

Plant : . Customer : .
Location : . Project : .
Unit : . Device No : .
Panel : . Feeder : .
TECHNICAL DATA
Manufacturer . Serial no. .
Type Volt . Scale .
Rated input . CT Ratio .
Rated Output . PT Ratio .
Accuracy class . Rated DC supply .
.
Voltage Transducer
Phase C-A

Injected Should be AS Found


% Error
Voltage ( V Ac ) ( mA ) ( mA )
0.00 4
25 8
50 12
75 16
100 20

Test Equipment:

Comment: .
.
.

Tested by Reviewed by Witnessed by

Date Date Date


FIELD INSPECTION AND TEST REPORT

TRANSDUCER

Plant : . Customer : .
Location : . Project : .
Unit : . Device No : .
Panel : . Feeder : .
TECHNICAL DATA
Manufacturer . Serial no. .
Type MW . Scale .
Rated input . CT Ratio .
Rated Output . PT Ratio .
Accuracy class . Rated DC supply .
.
1. VISUAL INSPECTION CHECKED
1.1 Compare equipment Name plate data with drawing and specification .
1.2 Inspection of physical and mechanical damage .
1.3 On base fixing .
1.4 Cable connection .
1.5 Tightness of bolts/screws .
1.6 Verify the unit is clean .

2. TRANSDUCER TEST
Active Power Transducer

Injected Injected Injected Should be AS Found


% Error
Voltage ( V Ac ) Current ( A ) Angle ( A ) ( mA ) ( mA )
0.00 4
0.25 8
100V 0.50 12
0.75 16
1.00 20

Test Equipment:

Comment: .
.
.

Tested by Reviewed by Witnessed by

Date Date Date


FIELD INSPECTION AND TEST REPORT

TRANSDUCER

Plant : . Customer : .
Location : . Project : .
Unit : . Device No : .
Panel : . Feeder : .
TECHNICAL DATA
Manufacturer . Serial no. .
Type MVAr . Scale .
Rated input . CT Ratio .
Rated Output . PT Ratio .
Accuracy class . Rated DC supply .
.
1. VISUAL INSPECTION CHECKED
1.1 Compare equipment Name plate data with drawing and specification .
1.2 Inspection of physical and mechanical damage .
1.3 On base fixing .
1.4 Cable connection .
1.5 Tightness of bolts/screws .
1.6 Verify the unit is clean .

2. TRANSDUCER TEST
Reactive Power Transducer

Injected Injected Injected Should be AS Found


% Error
Voltage ( V Ac ) Current ( A ) Angle ( A ) ( mA ) ( mA )
0.00 4
0.25 8
100V 0.50 12
0.75 16
1.00 20

Test Equipment:

Comment: .
.
.

Tested by Reviewed by Witnessed by

Date Date Date