1. A protective device used for limiting surge voltages by discharging surge current and that prevents continued flow of follow
current while still remaining capable of repeating these functions is considered which of the following:
a.) Circuit breaker c.) Disconnect switch
b.) Fuse d.) Surge arrestor

2. Rod and pipe grounding electrodes must not be less than which of the following lengths:
a.) 1500 mm c.) 2400 mm
b.) 1800 mm d.) 3000 mm

3. A multi-wire branch circuit protected by fuses may supply which of the following:
a.) Only one load c.) Both of the above
b.) Only line-to-neutral loads d.) Neither of the above

4. Rigid nonmetallic conduit shall be permitted to have a total number of quarter bends in one run that does not exceed which of the
following:
a.) 2 c.) 4
b.) 3 d.) None of the above

5. Which of the following shall be used to connect the grounding terminal of a grounding receptacle to a grounded box:
a.) A junction box c.) A neutral conductor
b.) A main bonding jumper d.) An equipment bonding jumper

6. The residual voltage of a capacitor must be reduced to which of the following voltage levels within one minute after the capacitor is
disconnected from the power source:
a.) 50 volts or less c.) 120 volts or less
b.) 60 volts or less d.) Zero volts

7. If an installation has two 2-wire branch circuits then the service disconnecting means must be rated at not less than which of the
following:
a.) 15 amps c.) 50 volts
b.) 30 amps d.) 110 volts

8. The required distance between outlets along the floor line of any wall space in the living room of a dwelling unit is which of the
following:
a.) No more than 1800 mm measured horizontally from one outlet to another
b.) Every 3000 mm
c.) Only one outlet is required per wall
d.) None of the above

9. An auxiliary gutter is not permitted to extend for more than which of the following distances:
a.) 1800 mm c.) 6000 mm
b.) 3000 mm d.) none of the above 9100 mm

10. Single phase loads connected on the load side of a phase converter shall be permitted to be connected to which of the following:
a.) Grounded phase c.) High leg
b.) Neutral d.) All of the above

11. Heavy duty lamps are used on which of the following circuit sizes:
a.) 25 amps or larger c.) 15 amps or larger
b.) 20 amps or larger d.) None of the above

12. Low torque, low speed synchronous motors used to drive such equipment as reciprocating compressors or pumps that start
unloaded do not require a fuse rating greater than which of the following:
a.) 100 percent of the continuous load c.) 200 percent of the full load current
b.) 150 percent of the volt-amperes d.) 185 percent of the run voltage
HABILIS EE TRAINING CENTER, INC.
61st Isabel Ramiro Road, Purok 6A, Tambo-Hinaplanon,
Iligan City, 9200 Tel No. (063) 2250809 Refresher Day 9

13. The definition of a pool includes wading, swimming and therapeutic pools, and the term fountain includes
which of the following:
I. Reflection pools II. Drinking fountain III. Display pool IV. Ornamental pool
a.) II only c.) I, III and IV
b.) IV only d.) all of the above

14. A light fixture installed under a canopy in front of a delicatessen is considered to be in which of the following locations:
a.) Commercial Class II c.) Wet
b.) Dry d.) Damp

15. Solid dielectric insulated conductors in permanent installations operating over 2000 volts shall meet
which of the following requirements:
a.) Be shielded c.) Both A & B
b.) Have ozone-resistant insulation d.) Neither of the above

16. The separation distance from non-current-carrying metal parts of electrical equipment and lightning protection conductors is
which of the following:
a.) 6 feet through air c.) 3 feet through concrete
b.) 3 feet through dense materials d.) All of the above

17. In electrical construction, mica is most commonly used for which of the following:
a.) In switchboard panels c.) Conductor insulators
b.) Communicator bus separators d.) None of the above

18. Edges that are invisible in an electrical drawing should be represented by which of the following line type:
a.) Solid c.) Broken
b.) Dotted d.) All of the above

19. Taps and splices shall not be located within which of the following fixture components:
a.) Stems and arms c.) Ring assembly
b.) Splice boxes d.) None of the above

20. If a single-family dwelling with 190 square meter of living space includes a kitchen, two bedrooms, a living room, dining room,
and a bathroom with 2100 mm of counter space including the sink, then the total number of receptacles required to serve the
bathroom area is which of the following:
a.) 4 c.) 2
b.) 3 d.) 1

21. When installed in a ventilated channel cable tray with a 10 cm inside width, the sum of the diameters of all of the single
conductors shall meet which of the following demands:
a.) Shall be less than the width of the channel c.) Shall not exceed 10 cm
b.) Shall be permitted to total 20 cm or less d.) None of the above

22. Concealed knob – and – tube wiring shall be permitted to be used only for extensions of existing installations and elsewhere
only by special permission under the following conditions _____.
I. In unfinished attic and roof spaces when such spaces are insulated by loose or rolled insulating material
II. In the hollow spaces of walls and ceilings
III. In unfinished attic and roof spaces as provided in section 324 – 11
a. I only b. I and II only c. II and III only d. I, II and III

23. Raceways shall be installed _____ between outlet, junction or splicing points prior to the installation of conductors.
a. Partially b. complete c. straight d. tightly

24. Flexible cords to portable electrically heated appliances rated at more than ____ watts shall be approved for heating cords.
a. 50 b. 100 c. 300 d. 500

25. A single grounding electrode is permitted when the resistance to ground does not exceed _____ ohms.
a. 5 b. 10 c. 15 d. 25
HABILIS EE TRAINING CENTER, INC.
61st Isabel Ramiro Road, Purok 6A, Tambo-Hinaplanon,
Iligan City, 9200 Tel No. (063) 2250809 Refresher Day 9

26. Unfinished basements are defined as portions or areas of basements not intended as habitable rooms and ____.
I. Work areas II. storage areas III. tool storage area
a. I only b. II only c. I and II only d. I, II and III

27. The _____, or other descriptive marking by which the organization responsible for the product may be identified, shall be
placed on all electric equipment.
I. Trademark II. cost III. manufacturer’s name
a. I only b. I and II only c. I and III only d. I, II and III

28. The interior metal water piping system shall be bonded to the ______.
a. Grounded conductor at the service
b. Grounding electrode conductor
c. Service equipment enclosure
d. All of these

29. Which of the following statements about FCC cable is not true?
a. A bottom shield be installed beneath all type FCC cable, connectors, and insulating ends.
b. FCC cable can cross over or under flat telephone cable
c. An FCC system with a height above floor level exceeding 0.090 inches shall be tapered
d. Receptacles and connections need not to be polarized

30. Type AC cable shall be permitted for branch circuits and feeders in _____.
I. Concealed work II. exposed work III hazardous locations
a. I, II and III b. II and III only c. I and III only d. I and II only

31. Except by special permission, no conductor larger than ____ shall be installed in cellular metal floor raceways.
a. 50sq mm b. 60 sq mm c. 125 sq mm d. 250 sq mm

32. The principal determinants of operating temperature are _____.


I. Threadless coupling and connectors made up tight for rigid metal conduit, IMC and EMT
II. Threaded coupling and threaded bosses on enclosures with joints shall be made up wrench tight where rigid metal
conduit and IMC are involved
III. Ambient temperature
a. I or III only b. II or III only c. I or II only d. I, II or III

33. The first floor of a building shall be that floor which is designed for human habitation and which has _____ percent or more
of its perimeter level with or above finished grade of the exterior wall line.
I. Heat generated internally in the conductor as the result of load current flow.
II. The rate at which generated heat dissipates into the ambient medium
III. Adjacent load – carrying conductors
IV. Ambient temperature
a. II and IV only b. I and IV only c. I, II and IV d. I, II, III and IV

34. The first floor of a building shall be that floor which is designed for human habitation and which has _____ percent or more
of its perimeter level with or above finished grade of the exterior wall line.
a. 10 b. 15 c. 25 d. 50

35. Circuit breakers shall be so located or shielded so that persons _____.


a. Will not burned or otherwise injured by their operation
b. Other than the authority cannot locate them
c. Cannot operate them without a key
d. Other than the authority cannot remove them

36. Electrical equipment such as a panelboard, shall include an exclusively dedicated space extending from the floor to a height
of 6 feet or to the _____ whichever is lower. No piping, ducts, or equipment foreign to the electrical equipment shall be
permitted in this dedicated space.
a. Floor to suspended ceiling c. wall to wall
b. Structural ceiling d. basement to ceiling
HABILIS EE TRAINING CENTER, INC.
61st Isabel Ramiro Road, Purok 6A, Tambo-Hinaplanon,
Iligan City, 9200 Tel No. (063) 2250809 Refresher Day 9

37. The ampacity of a device to open under short circuit or ground fault is based on its _______ rating.
a. Operating b. interrupting c. ampacity d. temperature

38. Heavy – duty lampholders shall have a rating not less than ____ watts of the admedium type, and not less than _____ watts
of any other type.
a. 750 … 750 b. 1000 … 750 c. 660 … 750 d. 660 … 1000

39. The minimum feeder – circuit conductor size, before the application of any adjustment or correction factors, shall an
allowable ampacity equal to a greater than the noncontinuous load plus ____ percent of the continuous load.
a. 100 b. 125 c. 80 d. 75

40. Conductive materials enclosing electrical conductors are grounded to ______.


I. Prevent surges of voltage
II. Prevent surges of lightning
III. To facilitate overcurrent device operation in case of ground faults
a. I only b. II only c. III only d. all of these

41. ____ cable shall be flame – retardant, moisture – resistant, fungus resistant, and corrosion – resistant.
a. MI b. USE c. NMC d. NM

42. Circuit breakers shall not be located in the vicinity of easily ignitable material such as in ______.
a. Hallways b. laundry rooms c. clothes closets d. basements

43. In dwelling units and guests rooms of hotel, motels, and similar occupancies, the voltage shall not exceed _______, nominal.
a. 440 V b. 600 V c. 230 V d. 5000 V

44. Receptacles installed in __________ amperes branch circuits shall be of the grounding type.
a. 15 – 20 b. 25 – 40 c. 30 – 60 d. 20

45. Grounding type receptacles shall be installed only on circuits of the voltage class and the current for which they are _____.
a. grounded b. rated c. permitted d. classified

46. A non-grounding type receptacle _________ permitted to be replaced with another non-grounding type receptacles.
a. shall not be b. shall be c. are sometimes d. NOT

47. For ranges of 8 ¾ kW or more rating , the minimum branch circuit shall be _________ amperes.
a. 40 b. 60 c. 30 d. 15

48. The rating of the overcurrent device shall not be less than the non-continuous load plus _______ % of the continuous load.
a. 100 b. 80 c. 125 d. 90

49. The rating of any cord and plug connected utilization equipment shall not exceed _______ % of the branch circuit ampere
rating.
a. 100 b. 80 c. 125 d. 90