Академический Документы
Профессиональный Документы
Культура Документы
P
XFMR 4 P
XFMR 3
S 45000.0 kVA S 50000.0 kVA
230000 / 34500V 230000 / 34500V
10.56% Z 10.56% Z
CBL-0038 CBL-0039
BUS #5 BUS #6
34500V 34500V
CBL-0037 P
XFMR SUB B5 CBL-0035 P
XFMR SUB B6
3-#1000, 5ft S 20000.0 kVA 2-#4/0, 40ft S 20000.0 kVA
34500 / 13000V 34500 / 13000V
BUS C354 8.00% Z BUS C355 8.00% Z
34500V 34500V
SUB B6
13000V
C354 LD CAP F355-2 C355 LD
5.3 MVA 1200 KVAR 8.5 MVA
CAP B6-2
CAP F355-1 1800 KVAR
CAP F354-2 1200 KVAR
1200 KVAR SUB B5 CAP B6-1
13000V 4500 KVAR
CBL-0048
1-#1/0, 5ft
CAP B5-3 SUB B5 LD
CAP F354-1 1800 KVAR 5.4 MVA
1200 KVAR
CAP B5-2
600 KVAR CAP B5-5
CBL-DOM PCC 2700 KVAR
3-#1000, 2006ft CAP B5-1
600 KVAR CAP B5-4
TO T HE BLEACH 4950 KVAR
PRODUCTION PLANT
MV SWGR
34500V
MCC 3
480V
ATS1 ATS2
480V 480V
CBL-0023 CBL-0024
5-#500, 25ft 5-#500, 25ft
MCC 1 MCC 2
480V 480V
2
TABLE I
SUMMARY OF SIMULATED CASES
The following twelve (12) cases were analyzed in the Case 11: Similar to Case 10, except that the 9600 kVAR
harmonic analysis study. The conditions for each of the cases capacitor at the utility substation 34.5 kV bus is online and the
are summarized in Table I. utility substation B6-1 capacitor (4500 kVAR at 13 kV) is
online.
Case 1: This is considered the base case, which is the normal
operating scenario at the utility substation and bleach Case 12: Similar to Case 11, except that only 2 rectifiers are
production facility. All three (3) rectifiers are online with online, XFMR U2303A is offline.
balanced load and the entire facility is supplied by the utility
substation XFMR 4. B. Harmonic Case Results
Case 2: When performing maintenance on a single
electrolyzer, the facility will operate with 2 rectifiers at 100% 1) Total Harmonic Distortion at the PCC: Twelve (12)
for approximately 8-10 hours. study cases considering five (5) different utility substation
conditions as well as three (3) different facility conditions
Case 3: Similar to Case 1, except that 5-stage filters (see filter were analyzed to ensure satisfactory performance of the
design specifications in Section III) are added on the front-end filters. The study results are summarized in Table II. The
of each rectifier transformer. study cases allow for a variety of operating conditions for
the facility rectifiers/filters in addition to likely combinations
Case 4: 2 rectifiers online, XFMR U2303A offline. The same
of the many capacitors at the utility substation. Since the
5-stage filter in Case 3 is added on the front-end of rectifier
utility capacitors are electrically near the facility filters, it
transformers XFMR U2303B and XFMR U2303C.
was important to consider them in the harmonic analysis
Case 5: Similar to Case 4, except that the 7200 kVAR study. Based on the harmonic analysis results, voltage and
capacitor at the utility substation 34.5 kV bus is online. current total harmonic distortion (THD) at the PCC were
within the IEEE Std 519-1992 limits [2] for all study cases.
Case 6: Similar to Case 3, except that the 7200 kVAR The voltage distortion gives a clear representation of the
capacitor at the utility substation 34.5 kV bus is online. impact of harmonics on the electrical distribution system.
Case 7: Similar to Case 3, except that the 7200 kVAR The harmonic voltage distortion from an individual
capacitor at the utility substation 34.5 kV bus is online and the customer is evaluated at the PCC where the utility can
utility substation B5 capacitors (2700 kVAR and 4950 kVAR at supply other customers. The voltage THD limit is 5% for
13 kV) are online. customers supplied by 69 kV or less. The harmonic
currents from an individual customer are likewise evaluated
Case 8: Similar to Case 4, except that the 7200 kVAR at the PCC. The current THD limits depend upon the
capacitor at the utility substation 34.5 kV bus is online and the customer’s load with respect to the available fault current
utility substation B5 capacitors (2700 kVAR and 4950 kVAR at (ISC/IL) at the PCC, which explains why the current
13 kV) are online. distortion limit for Cases 1, 3, and 6 is 5% compared to 8%
Case 9: Similar to Case 3, except that the rectifiers are only for all other cases.
50% loaded.
3
TABLE II TABLE III
SUMMARY OF DISTORTION AND POWER FACTOR AT SUMMARY OF INDIVIDUAL HARMONIC VOLTAGE AT
PCC THE PCC
4
Fig. 3 Case 1, PCC Voltage and Current Waveforms for Fig. 5 Case 4, PCC Voltage and Current Waveforms for
Three Rectifiers with Balanced Load Two Rectifiers with Balanced Load
Fig. 4 Case 1, PCC Voltage and Current Harmonic Fig. 6 Case 4, PCC Voltage and Current Harmonic
Spectrum for Three Rectifiers with Balanced Load Spectrum for Two Rectifiers with Balanced Load
4) Effect of One Rectifier Offline: Operating with just two which lie on the harmonic order corresponding to a
(2) rectifiers fails to achieve the full benefit of the phase characteristic harmonic current of the rectifier. The number
shifting transformers. As expected, the resulting waveform of rectifiers online and their load balance will result in either
th th th th
is quasi 12-pulse with more 5 , 7 , 11 , and 13 harmonic an 18-pulse or quasi 12-pulse system and determine which
current content compared to the scenarios with all three (3) of the parallel resonance points is excited. This variability
rectifiers online with balanced load. For example, consider in both the parallel resonance points as well as the exciting
Case 4 with filtering and one rectifier offline (2 rectifiers harmonic currents required the installation of the power
with balanced load). The result is a quasi 12-pulse system factor correction in the form of filters rather than capacitors.
as shown in the current waveform of Fig. 5 and the current
harmonic spectrum of Fig. 6. See similar results for other 7) Avoiding Parallel Resonance Through Harmonic
cases with two (2) rectifiers with balanced loads as shown Filter Design: To avoid the issues of parallel resonance,
for Cases 2, 5, 8 and 12 in Table IV. and variable parallel resonance, the power factor correction
for the rectifiers was designed in the form of 5-stage
5) Effect of Unbalanced Rectifier Load: Operating with harmonic filters. The details of the 5-stage harmonic filter
two (2) or three (3) rectifiers online with unbalanced loads design are described in Section III. Of interest at this point
will result in quasi 12-pulse (for 2 rectifiers) or 18-pulse (for is the impact of the filter design on controlling the parallel
3 rectifiers) current waveforms. As the load unbalance resonance points and avoiding the characteristic harmonic
th th
increases, there will be more 5 , 7 , 11 , and 13
th th currents of the rectifiers. For Case 4 with the application of
harmonic currents flowing in the system. the harmonic filters, the parallel and series resonance
points are shown in the frequency scan of Fig. 8 as well as
6) Series and Parallel Resonance Due to Utility in Table V. By proper selection of the series resonance
Capacitor Combinations: Series and parallel resonance through filter design as explained in [3], the parallel
points are caused by the LC combination of the 45 MVA resonance points no longer lie on the harmonic order of
transformer and feeder capacitors (34.5 kV), and the 20 characteristic harmonic currents of the rectifier. In this way,
MVA transformer and feeder capacitors (13 kV) as shown the filter design controls the parallel resonance points and
for Case 1 in Fig. 7. As more capacitors are connected on avoids parallel resonance for the variety of capacitor
the 34.5 kV and 13 kV busses (i.e. CAP B5, B6, B5-4, B5- combinations possible.
5, and B6-1), the series and parallel resonance points will
shift to the left (lower harmonic order). When the parallel 8) IEEE Std 18 Evaluation of Harmonic Filter Design:
resonance points lie on or near the harmonic order of the Although the primary purpose of the 5-stage harmonic filter
characteristic harmonic currents of the rectifier, parallel design was to control parallel resonance, the filter will be a
th
resonance will be excited. For Case 1, the parallel low impedance path for the 5, 7, 11, 13 and 17 harmonics
resonance points of concern are shown in Table V, most of and must be designed to handle these currents
5
continuously. For this reason, the 5-stage harmonic filter TABLE VI
was evaluated on the basis of IEEE Std 18 for both normal CASE 4, SERIES AND PARALLEL RESONANCE
and contingency situations. For all cases studied, the 5- (FILTERS IN THE FACILITY)
stage harmonic filters are applied within the IEEE Std 18
limits [4] for voltage, current, and apparent power with Parallel Resonance Series Resonance
sufficient margin to allow for the contingencies considered. Frequency Frequency
The filter currents are less than 100% rated for all cases
Order (h) (Hz) Order (h) (Hz)
except when only 2 of 3 filters/rectifiers are in service
(Cases 4, 8, and 12). As expected, when one (1) 4.4 264 4.7 282
filter/rectifier is offline, the remaining two (2) filters see 6.2 372 6.8 408
elevated levels of harmonic current. In Case 4, stage-2 8.2 492 10.7 642
th
(tuned to 7 harmonic) sees 123% of rated current. Case 4 11.5 690 12.6 756
results are shown in Table VII. In Case 8, stage-1 (tuned 13.4 804 16.8 1008
th
to 5 harmonic) sees 126% of rated current. In Case 12, 20.0 1200 31.7 1902
stage-1 sees 129% of rated current, and stage-2 sees
123% of rated current. The overcurrent protection is set for TABLE VII
135% of rated current, and the capacitors are designed for CASE 4, IEEE STD 18 EVALUATION OF HARMONIC
180% of rated current, so these contingencies do not FILTER CAPACITORS
present a problem.
Study Capacitor Voltage Current kVA
Case Location V Rated % I Rated % kVA Rated %
U2303A-5 0 39490 0.0% 0.0 6.59 0.0% 0.0 450.0 0.0%
U2303A-7 0 39490 0.0% 0.0 4.39 0.0% 0.0 300.0 0.0%
U2303A-11 0 39490 0.0% 0.0 6.59 0.0% 0.0 450.0 0.0%
U2303A-13 0 39490 0.0% 0.0 4.39 0.0% 0.0 300.0 0.0%
U2303A-17 0 39490 0.0% 0.0 6.59 0.0% 0.0 450.0 0.0%
U2303B-5 37764 39490 95.6% 6.9 6.59 104.6% 425.2 450.0 94.5%
U2303B-7 36990 39490 93.7% 5.4 4.39 123.2% 287.5 300.0 95.8%
Case 4 U2303B-11 36272 39490 91.9% 6.9 6.59 105.1% 389.9 450.0 86.6%
U2303B-13 36160 39490 91.6% 4.5 4.39 101.8% 256.1 300.0 85.4%
U2303B-17 36054 39490 91.3% 6.7 6.59 101.0% 380.0 450.0 84.4%
U2303C-5 37764 39490 95.6% 6.9 6.59 104.6% 425.2 450.0 94.5%
U2303C-7 36989 39490 93.7% 5.4 4.39 123.0% 287.4 300.0 95.8%
U2303C-11 36272 39490 91.9% 6.9 6.59 105.4% 390.1 450.0 86.7%
U2303C-13 36160 39490 91.6% 4.5 4.39 102.0% 256.2 300.0 85.4%
U2303C-17 36054 39490 91.3% 6.7 6.59 101.0% 380.0 450.0 84.4%
IEEE Limit 110% 180% 135%
A. Filter Specifications
6
TABLE VIII B. Selection of Capacitors
5-STAGE HARMONIC FILTER SPECIFICATIONS
The capacitor sizes were selected based on standard
5th Harmonic Filter Harmonic I (Amps) kVAR sizes displayed in IEEE Std 18 [4], Standard for Shunt
Capacitor VLL 39,490 Volts 1 7.18
Total capacitor kVAR 450 kVAr 3 1.08 Power Capacitors, Table 1. The suggested reactor rated
System frequency 60 Hertz 5 5.39 fundamental and harmonic current are also shown in Table
Harmonic tuning 4.7 Order 7 2.51 VIII. The higher VLL rating of 39,490 V versus the system
Capacitor rated current 6.6 Amps 11 2.87
135% of Capacitor rated current 8.9 Amps X 1.35 13 2.51
voltage of 34,500 V allows for voltage rise when the capacitor
Harmonic frequency 282 Hertz 17 0.72 is applied as a filter. The selection of the appropriate voltage
Reactance per phase 156.879 Ohms 19 0.72 rating for capacitors in a filter bank and advantages of such a
Capacitance per phase 0.765 uF 23 0.36
Inductance per phase 416.136 mH/phase 25 0.36
selection is discussed in [5]. The capacitor sizes were also
Taps ±5 Percent selected to allow for two (2) standard capacitor can sizes (i.e.
System VLL 34,500 Volts 100 kVAR and 150 kVAR both rated 22,800 V). These are
Winding Material Copper Winding
standard capacitor can sizes and should simplify
7th Harmonic Filter Harmonic I (Amps) maintenance. The site electricians will only have to maintain
Capacitor VLL 39,490 Volts 1 4.79 an inventory of 100 kVAR and 150 kVAR capacitors.
Total capacitor kVAR 300 kVAr 3 0.72
System frequency 60 Hertz 5 1.68
Harmonic tuning 6.8 Order 7 3.59 TABLE IX
Capacitor rated current 4.4 Amps 11 1.68 RECOMMENDED CAPACITOR SIZES
135% of Capacitor rated current 5.9 Amps X 1.35 13 0.72
Harmonic frequency 408 Hertz 17 0.24
Reactance per phase 112.418 Ohms 19 0.24 Harmonic Number of Capacitor Size Total
Capacitance per phase 0.510 uF 23 0.24 Filter Stage Capacitors (kVAR) (kVAR)
Inductance per phase 298.198 mH/phase 25 0.24
Taps ±5 Percent 5 3 150 450
System VLL 34,500 Volts 7 3 100 300
Winding Material Copper Winding 11 3 150 450
11th Harmonic Filter Harmonic I (Amps)
13 3 100 300
Capacitor VLL 39,490 Volts 1 7.18 17 3 150 450
Total capacitor kVAR 450 kVAr 3 1.08
System frequency 60 Hertz 5 1.08
Harmonic tuning 10.8 Order 7 1.08 C. Overcurrent and Unbalance Protection
Capacitor rated current 6.6 Amps 11 5.39
135% of Capacitor rated current 8.9 Amps X 1.35 13 2.51 The capacitors must be connected wye-ungrounded.
Harmonic frequency 648 Hertz 17 1.08
Reactance per phase 29.711 Ohms 19 1.08 Unbalance protection (59N) must be installed in the neutral of
Capacitance per phase 0.765 uF 23 1.08 the ungrounded-wye of each filter bank stage. The unbalance
Inductance per phase 78.810 mH/phase 25 1.08 protection can be set to alarm on the loss of one capacitor
Taps ±5 Percent
System VLL 34,500 Volts
can, and trip the filter bank on the loss of 2 or more capacitor
Winding Material Copper Winding cans [6].
13th Harmonic Filter Harmonic I (Amps)
Capacitor VLL 39,490 Volts 1 4.79
D. Surge Protection for Reactors and Capacitors
Total capacitor kVAR 300 kVAr 3 0.72
System frequency 60 Hertz 5 0.72 Surge protection must be applied at the Main 34.5 kV Bus,
Harmonic tuning 12.8 Order 7 0.72
Capacitor rated current 4.4 Amps 11 1.68
reactor and capacitor bank for the 5-stage harmonic filter,
135% of Capacitor rated current 5.9 Amps X 1.35 13 3.59 primary side of the rectifier transformers, and unit
Harmonic frequency 768 Hertz 17 0.72 transformers, 480 V switchgears and MCCs in order to
Reactance per phase 31.727 Ohms 19 0.72
Capacitance per phase 0.510 uF 23 0.72
minimize the effect of the transient overvoltages during any
Inductance per phase 84.159 mH/phase 25 0.72 circuit switching.
Taps ±5 Percent
System VLL 34,500 Volts
Winding Material Copper Winding IV. CONCLUSION
17th Harmonic Filter Harmonic I (Amps)
Capacitor VLL 39,490 Volts 1 7.18
Total capacitor kVAR 450 kVAr 3 1.08
The paper has shown that the size, number, and possible
System frequency 60 Hertz 5 1.08 combinations of capacitors at the utility substation result in a
Harmonic tuning 16.8 Order 7 1.08 variety of series and parallel resonance points at the PCC.
Capacitor rated current 6.6 Amps 11 1.08
135% of Capacitor rated current 8.9 Amps X 1.35 13 1.08
These series and parallel resonance points are of concern due
Harmonic frequency 1008 Hertz 17 5.39 to the harmonic current sources at the bleach producing
Reactance per phase 12.278 Ohms 19 2.51 facility which vary with rectifier combinations and loadings.
Capacitance per phase 0.765 uF 23 1.08
Harmonic resonance results in very high harmonic currents
Inductance per phase 32.570 mH/phase 25 1.08
Taps ±5 Percent and voltages at the resonant frequency. It is important to
System VLL 34,500 Volts analyze the system when major changes or upgrades (i.e.
Winding Material Copper Winding
new transformer, feeders, capacitor banks, etc.) are made at
the facility and the utility substation. To avoid the issues of
parallel resonance, power factor correction for the rectifiers
was designed in the form of 5-stage harmonic filters, one at
7
each rectifier. Although the harmonic filter was not required to power quality investigations, harmonic analysis and harmonic
comply with IEEE Std 519 harmonic distortion limits, it was filter design for electric arc furnaces, rectifiers, and VFD
required to correct the power factor from 85% to above the applications. Mr. Dionise is the Chair of the Metal Industry
utility target of 90% and avoid harmonic resonance and Committee and a member of the Generator Grounding
potential equipment damage. Finally, the 5-stage harmonic Working Group. He has served in local IEEE positions and
filter was evaluated on the basis of IEEE Std 18 proving the had an active role in the committee that planned the IAS 2002
design had adequate margin for both normal and contingency Annual Meeting in Pittsburgh, PA. He is a Licensed
situations. Professional Engineer in Pennsylvania
VII. VITAE