Installation Manual
www.ias.net.au
Publisher
Innovative Air Systems Pty Ltd (ias)
Contents
1/49 Miller Street 1 INSTALLATION ..................................................1
Murarrie QLD 4172 1.1 Wiring ............................................................................ 1
Phone 1300 306 125 1.1.1 Device I/O Cabling Requirements........................................1
Fax 07 3870 8270
www.ias.net.au 1.2 Component Positioning ............................................... 1
info@ias.net.au 1.3 Controller Configuration .............................................. 2
Version 1.0 May 2005 1.4 Chrono technical specifications ................................. 3
This Install Guide documents the BlackBox Series Chrono 1.4.1 Inputs/Outputs......................................................................3
Copyright 1.4.2 Special Inputs ......................................................................4
This publication is Copyright © 2005 Innovative Air Systems Pty Ltd (IAS).
All rights reserved. No part of this publication may be reproduced, stored in 1.4.3 Message Library ..................................................................5
any retrieval system or transmitted, in any form or by any means, electronic, 1.4.4 Default Software Settings ....................................................6
mechanical, photocopying, recording or otherwise, without the prior written
1.4.5 Default Software Settings - Advanced Menu .......................7
permission of Innovative Air Systems Pty Ltd.
1.4.6 Default Hardware Settings ...................................................8
Disclaimer
IAS reserves the right to make changes and improvements to any of 1.5 133E - Economy Cycle Controller ............................... 9
the products described in this document without prior notice. Under no 1.6 TIME SW8 - 8 channel timeswitch.............................. 10
circumstances shall IAS be responsible for any loss of income or any
special, incidental, consequential or indirect damages howsoever caused. 1.6.1 Manually switching a channel ON or OFF .........................10
Page IV Page 1
1.3 Controller Configuration 1.4 Chrono technical specifications
The Chrono is capable of controlling many different A/C Power input to Controller ............... 240 volt ± 10%
configurations of up to 8 relay outputs. Line frequency ............................... 50 Hz
Power Consumption ...................... 7 VA (max)
The DIP switches on the face of the Chrono define the relay outputs.
Operating temperature .................. 0 °C to 50 °C
Relay outputs are assigned from 1 to 8 in the following order:
Altitude .......................................... 0 to 2000 meters
• fan outputs
Operating Relative Humidity ........... 10% to 80%
• cooling outputs
Unit Dimensions (mm) .................... 173 (L) x 116 (W) x 55 (H)
• heating outputs
Weight ............................................ 570 g
• auxiliary timers**
Avoid static electricity hazards
Select the appropriate configuration for your A/C unit from the table Avoid electromagnetic radiation sources
below and switch the corresponding DIP switch to the ON position. Avoid dust contamination
Avoid highly corrosive environments
Only one DIP switch may be ON at any time.
1.4.1 Inputs/Outputs
Table 1.3a
8 x relay outputs
Configuration DIP Switches • Max load through relay terminals is 2.5 A (inductive).
DIP Relay Relay Relay Relay Relay Relay Relay Relay • Green LED indicates normally open contact is energised.
Config
# 1 2 3 4 5 6 7 81
8 x digital inputs
Fan Fan Fan Timer Timer Timer
1 311 Cool Heat • linked to corresponding relay output.
Low Med High Ch6 Ch7 Ch8
Fan Fan Fan Timer • operation may be via momentary switch, or latched mode (short
2 322 Cool Cool Heat Heat
Low Med High Ch8
circuit to run: open circuit to stop)
Timer Timer Timer
3 122 Fan Cool Cool Heat Heat Ch6 Ch7 Ch8 2 x analogue outputs
4 133 Fan Cool Cool Cool Heat Heat Heat Timer • 1 x 0-10 VDC linked to cooling - V1
Ch8
• 1 x 0-10 VDC linked to heating - V2
Timer Timer Timer Timer
5 103 Fan Heat Heat Heat Ch5 Ch6 Ch7 Ch8
2 x analogue inputs
Timer Timer Timer Timer • 1 x NTC thermistor - 47 kΩ @ 25 °C
6 130 Fan Cool Cool Cool Ch5 Ch6 Ch7 Ch8
• 1 x Multi purpose
Timer
7 133E2 Fan Cool Cool Cool Heat Heat Heat Ch8
TIME Timer Timer Timer Timer Timer Timer Timer Timer
8 SW8 Ch1 Ch2 Ch3 Ch4 Ch5 Ch6 Ch7 Ch8
1. Relay 8 may be configured as a pump call relay by creating a short circuit at JP1 (refer to connection diagrams).
2. 133E features an economy cycle for the first stage of cooling using the 0-10V cooling ramp to drive an outside air
Page 2 Page 3
1.4.2 Special Inputs 1.4.3 Message Library
Analogue inputs S1 and S2 provide additional digital inputs in the The same message may be linked to more than one trigger.
following manner (voltage free clean contacts required):
Abbreviated version displayed on Message displayed on screen after
• S2 Closed Circuit = System Fault message selection screen trigger is activated
Close circuit analogue input 2 terminals (S2 and SC) to shutdown
<Blank>
all conditioning relays (compressors and electric duct heaters).
The fan relay will remain energised only if the system is On. SERVICER SERVICE
(Default Custom Message) REQUIRED
For 3 speed fan models in auto fan mode the controller will default
Door
to low fan speed. Manual changes to fan speed will be accepted. DoorOpen
Open
Vent
• S1 Closed Circuit = Remote On/Off VentMode
Mode
Close circuit analogue input 1 terminals (S1 and SC) to
Remote
RemoteOf
shutdown all relays. Off
Remote
• S1 Open Circuit = Forced Vent Mode RemoteSh
Shutdown
Open circuit analogue input 1 terminals (S1 and SC) to Clean
CleanFil
shutdown all conditioning relays (compressors and electric Filters
duct heaters), the fan and reversing valve relays will remain ServiceR Service
(Default Service Timer Message) Required
energised. If the system is Off, the relay for the currently
No Water
selected fan speed will be energised. NoWaterF
Flow
For 3 speed fan models in auto fan mode the controller will Fan
FanOverl
default to low fan speed. Manual changes to fan speed will be Overload
accepted. FireShut
Fire
Shutdown
Any connected LCD touchpad will display a message on the screen ACPlantF
AC Plant
Fault
for each digital input trigger and the service timer trigger.
If multiple trigger events occur at the same time the message HPFault
HP
Fault
displayed is based on the following priority.
LP
LPFault
1. SYSTEM FAULT Fault
S1Closed S1Closed
The factory default messages may be replaced by one from the (Default Remote On/Off Input Message) Circuit
message library via the Advanced Settings Menu. S2Closed S2Closed
The library contains one custom entry of 2x8 character lines. (Default System Fault Input Message) Circuit
Page 4 Page 5
1.4.4 Default Software Settings 1.4.5 Default Software Settings - Advanced Menu
Following is a list of adjustable settings from the main menu and Following is a list of advanced system settings and their factory
their factory default values. For details on altering these settings default values. For details on altering these settings refer to Section
refer to Section 3.5. 3.6.
During economy mode the controller shifts the cooling relay stages
Table 1.4.6a 1 degree away from their normal activation points and uses the V1
Main Processor Module DIP Switch Settings (0-10V) output to open an outside air damper.
DIP
Function
OFF
ON The controller will only enter economy mode if the outside air sensor
# (Factory Default)
is connected to the sensor 2 terminals (S2 & SC) and the outside air
Software Selectable 4 seconds max temperature will assist the cooling call (S2 temperature is 2 ºC lower
1 Compressor Delay
(4 minute default) (overrides software)
than S1 temperature).
Memory Lock Memory locked. Settings
2 Disabled
(Diagnostic Use Only) changes are discarded.
Restore Factory Restore factory defaults
3 Disabled
Defaults at next reboot.
Page 8 Page 9
1.6 TIME SW8 - 8 channel timeswitch • Press ENTER to define the days the program will be active. The
cursor will highlight the first letter on the bottom line, representing
The TIME SW8 personality provides 15 timer programs to switch the
Sunday.
eight relay outputs. When 8-channel timeswitch mode is selected,
• Press the UP ARROW to turn the program on, or the DOWN
only the timeswitch functions are displayed on the screen
ARROW to turn the program off for this day.
(HVAC functions – which are not available – are not shown).
• Press ENTER to save and move the cursor to the next day.
• Press MENU to go back one day if required.
Default Display Clock Display
• Repeat this procedure for each day of the week.
12345678 0 1 :31p Su • Press ENTER at Saturday to return the display to the program
tttttttt 0 6 M ar,0 5 selection screen and the cursor will highlight the last program
edited.
• Active programs (that is, programs with a start and/or stop time
AND active days) appear in upper case in the program list.
1.6.1 Manually switching a channel ON or OFF
Example: PROG 01 is active, prog 01 is inactive.
• While viewing the default display, press the ARROWs to move • To deactivate a program, select a start and stop time of ‘--:--’ or
the cursor to the channel you wish to switch ON or OFF. deactivate all seven days on that program.
• Press POWER to toggle the channel ON or OFF.
• Repeat for each additional channel. Refer to Section 3.7 for additional details on setting the clock and
• Press ENTER to accept the change(s). holiday functions.
Page 10 Page 11
1.7 Connection Diagrams 1.7.2 Configuration 322
Select the appropriate connection diagram from the following pages. Digital input terminals and IASnet Socket * Short Circuit JP1 to
configure relay output
8 as a pump call
or Proof of Flow*
Timer Ch8 Input
1.7.1 Configuration 311
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
LED indicates flow
Digital input terminals and IASnet RJ * Short Circuit JP1 to status.
configure relay output Flow must be proved
8 as a pump call before compressor
or Proof of Flow*
Timer Ch6 Input
Disabled
Disabled
Disabled
LED indicates flow IC I1 IC I2 IC I3 IC I4 IC I5 IC I6 IC I7 JC J8
status. IASNETIASNET �������� ����� JP1
ON Shield ������ ���
Flow must be proved RJ Terminals
before compressor
1 2 3 4 5 6 7 8 outputs are energised
IC I1 IC I2 IC I3 IC I4 IC I5 IC I6 IC I7 JC J8
IASNETIASNET �������� ����� JP1 Analogue input and output terminals, and IASnet Terminals
ON Shield ������ ���
RJ Terminals
Analogue input and output terminals, and IASnet Terminals D1 D2 V- V+ Analogue Output 1
Configuration 0-10V Cooling Ramp
DIP switches
Refer to
Return Air Analogue Output Analogue Output 2
Optional Table 1.4.6a
Sensor Common 0-10V Heating Ramp
Touchpad
D1 D2 V- V+ 1 2 3 4 5 6 7 8
Analogue Output 1
Configuration 0-10V Cooling Ramp IASNET
IASNET ON
DIP switches RJ
Terminals SH D1 D2 V- V+ SH S1 SC S2 VC V1 V2
Refer to
Analogue Output 2
Table 1.4.6a
0-10V Heating Ramp
Low Fan
Medium Fan
High Fan
Compressor 1
Compressor 2
240V Neutral
Timer Ch8 Output
or Pump Call**
Low Fan
Medium Fan
High Fan
Compressor
Earth
Page 12 Page 13
1.7.3 Configuration 122 1.7.4 Configuration 133
Digital input terminals and IASnet Socket * Short Circuit JP1 to Digital input terminals and IASnet Socket * Short Circuit JP1 to
configure relay output configure relay output
8 as a pump call 8 as a pump call
or Proof of Flow*
or Proof of Flow*
Timer Ch6 Input
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
LED indicates flow LED indicates flow
status. status.
Flow must be proved Flow must be proved
before compressor before compressor
1 2 3 4 5 6 7 8 outputs are energised 1 2 3 4 5 6 7 8 outputs are energised
IC I1 IC I2 IC I3 IC I4 IC I5 IC I6 IC I7 JC J8 IC I1 IC I2 IC I3 IC I4 IC I5 IC I6 IC I7 JC J8
IASNETIASNET �������� ����� JP1 IASNETIASNET �������� ����� JP1
ON Shield ������ ��� ON Shield ������ ���
RJ Terminals RJ Terminals
Analogue input and output terminals, and IASnet Terminals Analogue input and output terminals, and IASnet Terminals
Optional Return Air Analogue Output Optional Return Air Analogue Output
Touchpad Sensor Common Touchpad Sensor Common
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
IASNET
IASNET ON IASNET
IASNET ON
RJ
Terminals SH D1 D2 V- V+ SH S1 SC S2 VC V1 V2 RJ
Terminals SH D1 D2 V- V+ SH S1 SC S2 VC V1 V2
Relay output terminals and 240VAC Line in Relay output terminals and 240VAC Line in
Maximum load through each relay is 2.5 A (inductive) Maximum load through each relay is 2.5 A (inductive)
240V 240V
AC Green LEDs behind AC Green LEDs behind
terminals indicate terminals indicate
A1 N1 E1 C1 R1 C2 R2 C3 R3 C4 R4 C5 R5 C6 R6 C7 R7 C8 R8 relay is energised. A1 N1 E1 C1 R1 C2 R2 C3 R3 C4 R4 C5 R5 C6 R6 C7 R7 C8 R8 relay is energised.
Compressor 1
Compressor 2
Fan
Compressor 1
Compressor 2
Compressor 3
or Pump Call**
Rev. Valve / EDH 1
Earth Earth
Page 14 Page 15
1.7.5 Configuration 103 1.7.6 Configuration 130
Digital input terminals and IASnet Socket * Short Circuit JP1 to Digital input terminals and IASnet Socket * Short Circuit JP1 to
configure relay output configure relay output
8 as a pump call 8 as a pump call
or Proof of Flow*
or Proof of Flow*
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
LED indicates flow LED indicates flow
status. status.
Flow must be proved Flow must be proved
before compressor before compressor
1 2 3 4 5 6 7 8 outputs are energised 1 2 3 4 5 6 7 8 outputs are energised
IC I1 IC I2 IC I3 IC I4 IC I5 IC I6 IC I7 JC J8 IC I1 IC I2 IC I3 IC I4 IC I5 IC I6 IC I7 JC J8
�������� ����� JP1 IASNETIASNET �������� ����� JP1
IASNETIASNET ON Shield ������ ��� ON Shield ������ ���
RJ Terminals RJ Terminals
Analogue input and output terminals, and IASnet Terminals Analogue input and output terminals, and IASnet Terminals
Optional Return Air Analogue Output Optional Return Air Analogue Output
Touchpad Sensor Common Touchpad Sensor Common
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
IASNET
IASNET ON IASNET
IASNET ON
RJ
Terminals SH D1 D2 V- V+ SH S1 SC S2 VC V1 V2 RJ
Terminals SH D1 D2 V- V+ SH S1 SC S2 VC V1 V2
Relay output terminals and 240VAC Line in Relay output terminals and 240VAC Line in
Maximum load through each relay is 2.5 A (inductive) Maximum load through each relay is 2.5 A (inductive)
240V 240V
AC Green LEDs behind AC Green LEDs behind
terminals indicate terminals indicate
A1 N1 E1 C1 R1 C2 R2 C3 R3 C4 R4 C5 R5 C6 R6 C7 R7 C8 R8 relay is energised. A1 N1 E1 C1 R1 C2 R2 C3 R3 C4 R4 C5 R5 C6 R6 C7 R7 C8 R8 relay is energised.
Fan
Cooling Stage 1
Cooling Stage 2
Cooling Stage 3
EDH Stage 1
EDH Stage 2
EDH Stage 3
Earth Earth
Page 16 Page 17
1.7.7 Configuration 133E 1.7.8 Configuration TIME SW8
Digital input terminals and IASnet Socket * Short Circuit JP1 to Digital input terminals and IASnet RJ
configure relay output
8 as a pump call
or Proof of Flow*
Timer Ch8 Input
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
LED indicates flow
status.
Flow must be proved
before compressor
1 2 3 4 5 6 7 8 outputs are energised
1 2 3 4 5 6 7 8
IC I1 IC I2 IC I3 IC I4 IC I5 IC I6 IC I7 JC J8 IC I1 IC I2 IC I3 IC I4 IC I5 IC I6 IC I7 JC J8
IASNETIASNET �������� ����� JP1 JP1
ON Shield ������ ��� IASNETIASNET �������� �����
RJ Terminals ON Shield ������ ���
RJ Terminals
Analogue input and output terminals, and IASnet Terminals Analogue input and output terminals, and IASnet Terminals
Analogue Output
Optional Return Air Outside Air Common
Touchpad Sensor Sensor
Analogue Output 1
D1 D2 V- V+ 0-10V Outside Air
Configuration Damper
DIP switches
Refer to Analogue Output 2
Table 1.4.6a 0-10V Heating Ramp
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
IASNET
IASNET ON
RJ
Terminals SH D1 D2 V- V+ SH S1 SC S2 VC V1 V2 IASNET
IASNET ON
RJ
Terminals SH D1 D2 V- V+ SH S1 SC S2 VC V1 V2
240V Active
Compressor 1
Compressor 2
Compressor 3
240V Neutral
Page 18 Page 19
2 COMMISSIONING 3 USER GUIDE
If the clock module has been purchased and fitted, refer to Section
3.7 to configure the clock and automated on/off programs, holidays
and daylight savings.
2.3 Power on
Operate the controller in heat, cool and try each fan speed setting.
Page 20 Page 21
3.2 Default Display Screen 3.4 Quick Start Options
This controller provides a menu based user interface. The
Setpoint Operating Mode information that can be displayed at any given time is limited by the
Temperature T = Timer program screen area of 2 x 8 character lines. Additional options are viewed
R = Run Timer by using the ARROWs to scroll the information vertically across the
S = Setback screen.
M = Manual override The flashing cursor indicates the active area of the screen
O (generally the top line of the display). Pressing ENTER will activate
22 .5 c T C the selection highlighted by the flashing cursor.
FC c RRttT
• To change the setpoint, press the ARROWs. Once the required
temperature has been set the screen will revert to the default display
Relay Configuration Conditioning Mode after a short period.
Upper case indicates the A = Auto • Press CLOCK to switch between the default display screen and the
relay is energised. C = Cool clock display screen.
F = Fan H = Heat • All standard menu options are accessible by pressing MENU at
C = Compressor V = Vent the default display screen.
R = Rev. Valve • All clock menu options (clock module required) are accessible
H = Elect. Heat by pressing MENU at the clock display screen.
T = Timer Channel • While in the menu screens, pressing MENU takes you back one
P = Pump step.
• Pressing ENTER moves forward through the various screens,
selecting options and saving settings.
3.3 Clock Display Screen • The current active settings appear in CAPITALS.
• The ARROWs, when pressed in a menu will either cycle the
cursor and scroll the screen through the various options available,
Time Day or, alter the value of the selected variable.
• Press and hold the ARROW to quickly scroll the selected
variable.
0 1 :31 p S u
0 6 M ar,0 5
Date Year
Page 22 Page 23
3.5 Standard Menu Options 3.5.3 To Change the Heat Fan Setting
The default menus are accessible from the default display screen. Operation: Heat Fan controls the indoor fan operation in heating
mode. In ‘Contin’ mode the fan will run whenever the system is
Default Display On. In ‘Auto/Cyc’ mode the fan will cycle off between heating calls.
O
Electric Duct Heating is protected by 60 second fan run-on.
22.5 c T C
FCcRRttT • Select ‘Heat Fan’ from the standard menu screen and press
ENTER.
• Use the ARROWs to move the cursor to the required setting.
• Press MENU to gain access to the standard menu options.
• Press ENTER to save the new value and return to the default
• Use the ARROWs to cycle the cursor to the desired menu
display screen.
option, then press ENTER to select that option.
• Pressing MENU (or selecting ‘Exit’ then pressing ENTER) will NOTE: The fan can never cycle off in cool mode or during a cool or
exit the current selection if required. heat call.
3.5.1 To Change the Mode 3.5.4 To Set the Run Timer (After Hours Timer)
Operation: The Mode controls the operation of the A/C system. Operation: With the Run Timer enabled, and if the system is off
Available options are Cool, Heat, Vent or Auto (automatically (and outside any timer periods), pressing the On/Off button will start
switches between cooling and heating as required) the system in Run Timer Mode. The system will run for the duration
of time set in the Run Timer, after which the system will turn itself
• Select ‘Set Mode’ from the standard menu screen (see section
off.
3.5) and the mode selection screen will appear.
(Quick Tip: Press MENU, DOWN ARROW, ENTER) • Select ‘RunTimer’ from the standard menu screen and press
• Scroll down with the DOWN ARROW to select the required ENTER, the run timer edit screen will appear.
operating mode. • The cursor will highlight the minutes space.
• Press ENTER to save the new value and return to the default • Use the ARROWs to alter the hours shown (in ten minute
display screen. increments) to the required period (up to 24 hours).
• Press and hold the ARROWs to scroll numbers quickly.
3.5.2 To Set the Fan Speed • Press ENTER to save the new value and return to the default
display screen.
Operation: The Fan Speed enables the user to manually select
the fan speed or set the fan to Auto. In Auto mode the fan speed To disable the Run Timer, select the minimum value of “-----” and
decreases as the temperature approaches setpoint. press ENTER.
• Select ‘FanSpeed’ from the standard menu screen. NOTE: The Run Timer status can be determined from the standard
• Use the ARROWs to select the required fan speed setting. menu screen. If the Run Timer is enabled, ‘RUNTIMER’ will appear
• Press ENTER to save the new value and return to the default in CAPITAL letters in this screen.
display screen.
Page 24 Page 25
3.5.5 To Edit the Setback Temperatures 3.6 Advanced Settings (Service Personnel Only).
Operation: Setback is used to maintain temperature within preset � Changing these settings may adversely affect system operation
limits at all times. If the temperature moves outside these limits and in extreme cases may cause system damage.
the Controller will turn the system On and heat or cool as required
• Select ‘Advanced’ from the standard menu screen and press
to keep the temperature within the preset limits. These limits are
ENTER to access the advanced menu screen.
separate and distinct from the normal setpoint.
• The line ‘CAUTION!’ will alternate with ‘Service’ and ‘use only’.
CAUTION: When activated, Setback will cause the system to start • Press either ARROW to scroll the cursor from ‘Exit’ to ‘Proceed’
irrespective of any timer programs including holidays. Pressing the then press ENTER to access the advanced menu screen .
Off button WILL NOT stop the system if running in Setback Mode.
3.6.1 To Change the Compressor Delays
To disable Setback, select a minimum of “----” and a maximum of
“----”. These “----” settings are found by scrolling the minimum all the Operation: The compressor delays dictate the length of time that
way down, and the maximum all the way up. the compressor must remain on or off after cycling.
• Select ‘Setback’ from the standard menu screen and the setback • Select ‘Delays’ from the advanced menu screen, then press
edit screen will appear. ENTER to access the delay select screen.
• The cursor will highlight the minimum temperature value. • The current Delay setting is displayed in CAPITALS.
• Use the ARROWs to alter the value to the required temperature • Use the ARROWs to highlight the required Delay setting.
(in 1 °C increments). • Press ENTER to save and the display will return to the advanced
• Press ENTER to save and the cursor moves to the maximum menu screen.
temperature value.
The following options are available for Compressor Delays:
• Use the ARROWs alter the value to the required temperature (in
Safety = 4 minutes (minimum)
1 °C increments).
Extended = 40 seconds (minimum)
• Press ENTER to save and return to the default display screen.
Standard = 4 seconds (minimum)
NOTE: The Setback Range is from 5 - 50 °C. The setback function
is enabled whenever there is at least one valid limit set as detailed 3.6.2 To Set the Deadband
above. The setback temperatures values are to be linked to setpoint Operation: A deadband value other than 0 will create separate
in the following manner: Heating and Cooling setpoints (half of the deadband value either
Minimum setback temperature settings higher than setpoint minus 2 side of the displayed setpoint).
°C will cause the system to start at setpoint minus 2 °C.
Maximum setback temperature settings lower than setpoint plus 2 • Select ‘Deadband’ from the advanced menu screen, then press
°C will cause the system to start at setpoint plus 2 °C. ENTER to access the deadband edit screen .
• The cursor will highlight the deadband value.
• Use the ARROWs to alter the value in 1 °C increments from 0 to 3.
• Press ENTER to save and return to advanced menu screen.
Page 26 Page 27
3.6.3 To Set the Control Band • Select ‘SvcTimer’ from the advanced menu screen, then press
ENTER to access the service timer edit screen .
Operation: Control Band is a common variable covering both Stage
• Use the ARROWs to move the cursor to highlight ‘Set’. Press
Separation and Switching Differential. There is a separate control
ENTER and the cursor will highlight the number of hours. Use
band for Heating and Cooling working from the heating and cooling
the ARROW to change the hours shown in increments of 10
setpoints dictated by the DEADBAND.
hours.
• Highlight ‘CtrlBand’ from the advanced menu screen, then press • Press ENTER and the Service Timer will reset and the cursor
ENTER to access the control band edit screen. will move back to highlight ‘Set’.
• The cursor will highlight the Heating value. • Press menu to return to the advanced menu screen.
• Use the ARROWs to change the value. • To disable the service timer, select a set time of “----”.
• Press ENTER to save the value and move the cursor to the
NOTE: The Due value is the time remaining until the Service Timer
Cooling value. Now change this value by using the ARROWs.
message appears on the display. This value will revert to the Set
• Press ENTER to save and return to the advanced menu screen.
value when the above procedure is followed.
SINGLE STAGE CONTROLLERS: The control band for single stage
controllers is adjustable in 0.5 °C increments from 0.5 °C to 1.5 °C, 3.6.5 To Select the Forced Vent Input Message
resulting in a switching differential equal to the control band value
Refer to the message library table in Section 1.4.3 for the complete
and stage separation also equal to the control band value.
list of available messages and their abbreviations. Refer to Section
TWO STAGE CONTROLLERS: The control band for two stage 1.4.2 for information on input triggers.
controllers is adjustable in 1.0 °C increments from 1.0 °C to 3.0 °C,
• Select ‘Msg S1op’ from the advanced menu screen and press
resulting in a switching differential for each stage equal to half the
ENTER.
control band value and stage separation equal to half the control
• The screen will display the abbreviated message library, with the
band value.
cursor highlighting the current selection.
THREE STAGE CONTROLLERS: The control band for three stage • Press the ARROWs to scroll to the required selection then press
controllers can either be 1.5 °C or 3.0 °C, resulting in a switching ENTER.
differential for each stage equal to 1/3 the control band value and
stage separation equal to 1/3 the control band value. 3.6.6 To Select the Remote On/Off Input Message
• Select ‘Msg S1cl’ from the advanced menu screen and press
3.6.4 To Edit the Service Timer
ENTER.
Operation: The Service Timer monitors system run time and at the • The screen will display the abbreviated message library, with the
end of the timer period displays a message (see Section 1.4.2) and cursor highlighting the current selection.
gives an audible warning (2 beeps every 16 seconds). Press any • Press the ARROWs to scroll to the required selection then press
button to silence the audible warning. ENTER.
Page 28 Page 29
3.6.7 To Select the System Fault Message 3.7 Clock Menu Options
Operation: The input trigger for the System Fault Message (S2 The clock menus are accessible via the clock display screen.
closed circuit), when activated, displays the message and causes
the touchpad to emit an audible warning (2 beeps every 16 Clock Display
seconds). Press any button to silence the audible warning.
0 1 :31p Su
• Select ‘Msg S2cl’ from the advanced menu screen and press 0 6 M ar,0 5
ENTER.
• The screen will display the abbreviated message library, with the
• If the default display is showing on the screen, press CLOCK to
cursor highlighting the current selection.
access the clock display screen.
• Press the ARROWs to scroll to the required selection then press
• While the clock display screen is displayed press MENU to enter
ENTER.
the clock menu screen.
3.6.8 To Select the Service Timer Message • Use the ARROWs to cycle the cursor to the desired menu
option, then press ENTER to move to the edit screen for that
• Select ‘MsgTimer’ from the advanced menu screen and press menu option.
ENTER.
• The screen will display the abbreviated message library, with the 3.7.1 To Set the Clock
cursor highlighting the current selection.
• Select ‘SetClock’ from the clock menu screen (see Section 3.7)
• Press the ARROWs to scroll to the required selection then press
then press ENTER.
ENTER.
• The cursor will highlight the Hour value. Use the ARROWs to
3.6.9 To Edit the Custom Message select the correct hour (watch for am/pm), then press ENTER.
• Repeat this procedure for the Minutes, Day, Month and Year values.
• Highlight ‘Edit Msg’ and press ENTER. • After pressing ENTER on the Year, the display will return to the
• The display will show ‘SERVICE REQUIRED’ and the cursor clock display screen.
will highlight the first letter. Using the ARROWs, select the
alphanumeric symbol required then press ENTER to save and
move to the next letter. (Press menu to go back, if required.)
• Repeat until the both 8 character lines are complete.
• Press ENTER to save and return to the advanced settings
menu.
Page 30 Page 31
3.7.2 To Edit the Timer Programs 3.7.3 To Set Holidays
Each of the 15 timer programs may be assigned to any one of the NOTE: Active Holidays (i.e. ONLY holidays with a start AND stop
available relay channels. date) will appear in CAPITALS. Active Holidays will cause the
Active Programs will appear in CAPITALS system to ignore timer program signals (On or Off).
(“PROG 02” = active; “prog 02” = not active) Holidays may be set as single days, or as blocks.
To disable a timer program, select a start & stop time of “--:--”, or Dates are inclusive, and all holiday programs must have a start and
make all days inactive. stop date to be valid.
For a one day holiday, enter the same start and stop date.
• Select ‘SetProgs’ from the clock menu screen then press ENTER
To disable a holiday program, set it’s start or stop date to “----”.
to select a timer program to edit.
• Use the ARROWs to select the timer program to be edited, then • Select ‘Set Hols’ from the clock menu screen then press
press ENTER to edit the start time. ENTER.
• The cursor will highlight the minutes value. Use the ARROWs • Use the ARROWs to select the Holiday program to be edited,
to select the correct time in 10 minute increments, then press then press ENTER.
ENTER to edit the stop time. • The cursor will highlight the Month value. Use the ARROWs to
• Use the ARROWs to set the stop time then press ENTER. select the correct Month, then press ENTER.
• The display will show the channel and run day selection screen. • Repeat this procedure for the Day value which completes setting
• Use the ARROWs to select the relay channel controlled by this the start date for the holiday.
program. • The display will change to the set stop date screen.
NOTE: Channel 1 is always used for the air conditioning system (except for TIME • Repeat the procedure to set the stop date for the holiday.
SW8) and so it appears as “A/C” at this screen.
Other channels display as “Ch#” (# = Relay Number)
• The display will revert to the set holiday edit screen and the
• Press ENTER to define the days the program will be active. cursor will highlight the last holiday edited.
The cursor will highlight the first letter on the bottom line, • To return to the clock display screen, simply use the ARROWs to
representing Sunday. navigate back up to the ‘Exit’ options and press ENTER.
• Press the UP ARROW to turn the program on, or the DOWN • To enter more holidays, use the ARROWs to select another
ARROW to turn the program off for this day.
holiday entry and repeat the entire process.
• Press ENTER to save and move the cursor to the next day.
• Press menu to go back one day if required.
• Repeat this procedure for each day of the week.
• Press ENTER at Saturday to return the display to the program
selection screen and the cursor will highlight the last program
edited.
• To enter more programs, use the ARROWs to select another
program and repeat the process.
• To return to the clock display screen, simply use the ARROWs to
navigate back up to the exit options and press ENTER.
Page 32 Page 33
3.7.4 To Set Daylight Savings
Timer Program Record
Operation: The daylight savings function advances the clock’s time
by 1 hour whilst the current date and time are between the start
Program # Start Time Stop Time Channel Active Days
and stop dates set. (E.g. Southern Hemisphere = Oct 31...Mar 31;
Northern Hemisphere = Mar 31...Oct 31)
01
• Select ‘Day Save’ from the clock menu screen (see Section 3.7),
then press ENTER to select the start date for daylight savings. 02
• Use the ARROWs to select the correct Month , then press ENTER.
• Repeat this procedure for the Day value. 03
• The display will change to the set stop daylight savings screen.
• Repeat the steps detailed above to set the required stop date for 04
the daylight savings.
08
09
10
11
12
13
14
15