≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ WARNING The following values must be entered correctly to ensure proper monitoring of the generator. Failure to do so may lead to incorrect measuring of parameters resulting in damage to or destruction of the gen- erator and/or personal injury or death!
Parameter 1750 System rated frequency 48.0 to 62.0 Hz
Rated Frequency fn = 00.0Hz The system rated frequency, which in most cases is 50 Hz or 60 Hz, is entered in this screen.
Parameter 5500 Generator frequency set point 48.0 to 62.0 Hz
Generator freq. Setpoint= 00.0Hz The generator (variable system) frequency set point is entered in this screen. The fre- quency controller will reference this value for no-load and isolated operations.
Parameter 1800 Secondary generator voltage (measuring transducer) 50 to 440 V
Gen. voltage secondary 000V The secondary voltage for the generator (variable system) potential transformers is configured here in Volts. This entry is the reference voltage for displaying the system or primary voltage. If potential transformers are not used, the system voltage must be entered here. Example: if a generator rated for 400v is used without PTs, then 400v must be entered for this parameter.
Parameter 1803 Secondary mains voltage (measuring transducer) 50 to 440 V
Mains voltage secondary 000V Secondary voltage for the mains (reference system) potential transformers is config- ured here in Volts. This entry is the reference voltage for displaying the system or primary voltage. If potential transformers are not used, the system voltage must be entered here. Example: if a main rated for 400v is used without PTs, then 400v must be entered for this parameter.
Parameter 1801 Primary generator voltage (measuring transducer) 0.1 to 65.0 kV
Gen. voltage primary 00.000kV The primary voltage for the generator (variable system) is configured here in kV. This entry is the generator voltage to be displaying on the controller. If potential transformers are not used, the generator voltage must be entered here. Example: if a generator rated for 400v is used without PTs, then 00.400kV must be entered for this parameter.
Parameter 1804 Primary mains voltage (measuring transducer) 0.1 to 65.0 kV
Mains voltage primary 00.000kV The primary voltage for the mains (reference voltage) is configured here in kV. This entry is the generator (variable system) voltage to be displaying on the controller. If potential transformers are not used, the generator voltage must be entered here. Ex- ample: if a generator rated for 400v is used without PTs, then 00.400kV must be en- tered for this parameter.
Parameter 1767 System rated voltage 70 to 420 V
Rated voltage ......Vn = 000V The system rated voltage is entered in this screen. The controller references this val- ue to determine the permissible voltage range for synchronization. This setting affects the synchronization limits (refer to Table 5-3 on page 23).