Manual 37615B SPM-D2-10 - Synchronizing Unit

Voltage Controller
The following screens are not found on the SPM-D2-10, SPM-D2-10/N. They utilize a three-position controller to
regulate the voltage. The SPM-D2-10/X & SPM-D2-10/XN have the option to utilize multiple methods of voltage
control. The following screens show the available methods of voltage regulation. The SPM-D2-10/X & SPM-D2-
10/XN will only display the screens related to the voltage controller type that is configured.

Parameter 6671 Voltage controller type THREESTEP/ANALOG


V contr. type
xxxxxxx THREESTEP The voltage controller operates as a three-position controller and out-
puts raise (V+) and lower pulses (V-) via the corresponding relays.
X & XN Packages only The frequency and voltage controller cannot output signals at the same
time.
ANALOG .... The voltage controller operates as a continuous controller with an ana-
log signal output (mA or V).

Note: Only the screens, which pertain to the selected output signal type, will be dis-
played.

Three-position controller (Standard; X & XN Packages: Setting 'THREESTEP')

Parameter 5607 Voltage controller ON/OFF


Volt. controller
ON ON................ Generator voltage control is performed by the SPM-D2. The generator
voltage is controlled in various manners depending on the task (no
X & XN Packages: load / isolated operation / synchronization). The subsequent screens of
with 'THREESTEP' setting
this function are displayed.
OFF.............. Voltage control is not performed by the SPM-D2, and the subsequent
screens of this function are not displayed.

Parameter 6657 Voltage controller isolated mode ON/OFF


Volt. controller
Isol. oper. ON ON................ In isolated operation the voltage controller is enabled.
OFF.............. In isolated operation the voltage controller is disabled.
X & XN Packages:
with 'THREESTEP' setting

Parameter 5603 Voltage controller set point ramp 1 to 99 V/s


Volt. controller
Ramp = 00V/s
The controller increases the voltage from the initial set point to the configured volt-
age via a ramp. The slope of the ramp is used to determine how quickly the controller
X & XN Packages: changes the voltage. The larger the value configured here, the more rapid the change
with 'THREESTEP' setting
in voltage.

Parameter 5650 Voltage controller dead band 0.5 to 60.0 V


Volt. controller
Dead band 00.0V No load/Isolated operation: The generator voltage is controlled in such a manner
that when in a steady state the actual voltage does not deviate from the
X & XN Packages: configured generator rated voltage by more than the value configured
only with 'THREESTEP' setting
in this screen.
Synchronization: The generator voltage is controlled in such a manner that, in a
steady state, the differential voltage does not deviate from the voltage
set point by more than the value configured in this screen.. The mains
or busbar voltage is used as the set point value.

© Woodward Page 47/68