ETAP

Project: Page: 1
12.6.0H
Location: Date: 19-12-2020
Contract: SN:
Engineer: Revision: Base
Study Case: LF
Filename: Ahmat Config.: Normal

LOAD FLOW REPORT

Bus Voltage Generation Load Load Flow XFMR

ID kV % Mag. Ang. MW Mvar MW Mvar ID MW Mvar Amp %PF %Tap

* BB 20 KV TRAFO 1 GI A 20.000 100.000 0.0 8.130 5.241 0 0 BB 150 KV GI A 8.130 5.241 279.2 84.1

BB 20 KV TRAFO 1 GI B 20.000 95.257 -4.1 0 0 8.100 5.020 BB 150 KV GI B -8.100 -5.020 288.8 85.0

BB 150 KV GI A 150.000 97.799 -2.0 0 0 0 0 BB 150 KV GI B 8.122 4.851 37.2 85.9

BB 20 KV TRAFO 1 GI A -8.122 -4.851 37.2 85.9

BB 150 KV GI B 150.000 97.594 -2.0 0 0 0 0 BB 150 KV GI A -8.109 -5.437 38.5 83.1

BB 20 KV TRAFO 1 GI B 8.109 5.437 38.5 83.1


* Indicates a voltage regulated bus (voltage controlled or swing type machine connected to it)
# Indicates a bus with a load mismatch of more than 0.1 MVA