Modbus Gateway(Pro) Promotion

Applicable for multi VRF which supports CAN protocol

ALWAYS BETTER CAC SOLUTION FROM GREE


Modbus Gateway(Pro)

• Background
• Function Introduction of Gateway
• Detailed Introduction of Gateway
• Product Installation
Background

• Why you shall choose Modbus Gateway(Pro)

• Topology
Why you shall choose Modbus Gateway(Pro)
Why you shall choose Modbus Gateway(Pro)

• Have CE ETL certification

• Linux operation system, stable and high-efficiency


operation

• Support 16 systems and 255 indoor units


Why you shall choose Modbus Gateway(Pro)

Contrast Modbus Gateway Modbus Gateway(Pro)


Certification × CE ETL
Mode 、Fan speed 、Temperature 、
Group control On/Off
On/Off 、Remote locking
Operation
uCOS-II Linux
system
Supports indoor
128 255
units
Function Introduction of Gateway

• Appearance

• Function advantage
Appearance
Function advantage

• Support more units

Each Modbus Gateway(Pro) supports 16 systems and 255 indoor units

Each BMS network can connect with 16 Modbus Gateways(Pro)


Function advantage

• Group inquiry and group control

Each gateway supports group inquiry and group control of all indoor
units

On/Off
Mode
Fan speed
Temperature
Remote locking
Topology
BMS system

Other devices Fire control Elevator


Lighting Ventilation Electricity
L1
L2 L3
...
CAN 2 bus

Master
Modbus IDU IDU
gateway 1
ODU Slave ODU Slave ODU L3
...
L1
Master
ODU Slave ODU IDU IDU
CAN 2 network

L1 L3
CAN 1 bus
...

IDU IDU ODU


Modbus
gateway n CAN 1 network
Topology Introduction

Modbus bus: L1 shown in the figure is the Modbus bus.


CAN1 network: which is consist of Modbus Gateway(Pro) and all IDUs and
ODUs of the system. One CAN1 network can be connected to maximum 80
IDUs.
CAN2 network: which is consist of Modbus Gateway(Pro) and main control
ODU of the system. One CAN2 network can be connected to maximum 16
systems and 255 IDUs.
System: One system consists of one set of outdoor unit (one set of outdoor
unit is a module group consisting of 1~4 modules, that is 1~4 outdoor units)
and it’s connected indoor units.
Connectable unit quantity of Modbus Gateway(Pro): one Modbus
Gateway(Pro) can be connected with 16 systems and 255 indoor units in
maximum.
Detailed Introduction of Gateway

• Interface Function Drawing


• Power Supply
• Communication Interfaces
• DI/DO Digital Input/Output
• LED Display
• DIP Switches
Interface Function Drawing
CAN
communication
interface
RS485-1
communication
interface

RS485-2 DI Digital input


communication
interface
RS232
USB interface communication
SD card interface interface

Ethernet interface
DO digital output

Power input
Power Supply

Power supply should be 100VAC-240VAC, 50/60Hz


Warning! Protective grounding of power input must be connected,
otherwise a hazard may happen; in addition, do not touch the power
input when the gateway is energized.
Notice: Power cord should be secured with the equipped wire clip,
as shown in the figure.
Communication Interfaces

CAN communication interface: It is connected to air conditioner through two-


core connection wire, to realize communication between Modbus Gateway(Pro) and air
conditioner.
RS485-1 communication interface: It is connected to BMS through two-core
connection wire, to realize communication between Modbus Gateway(Pro) and BMS.
RS485-2 communication interface: This device doesn’t use this
communication interface currently.
Interface of USB or SD card: This device doesn’t use this interface currently.
Ethernet interface: This device doesn’t use this interface currently.
DI/DO Digital Input/Output

This gateway supports 5 DIs(digital inputs) and 5


DOs(digital outputs); DO6 is reserved.
DI/DO Digital Input/Output

DI1...DI5
Digital inputs: 0/1 digital signals(binary system), applicable for those with
power supply
DI1: in CAN2 network, fire alarm signal, connect “1” to the power of 12V,
input fire alarm signal “1” in DI 1 port, then Modbus gateway(Pro) will give out
control, all units stop operation immediately;disconnect “1” or connect to “0”,
input signal “0” in DI 1 port,resume operation of all ODUs.
In CAN1 network, fire alarm signal, connect “1” to the power of 12V, input
fire alarm signal “1” in DI 1 port, then Modbus gateway(Pro) will give out
control, all units stop operation immediately;disconnect “1” or connect to “0”,
input signal “0” in DI 1 port,resume operation of IDUs manually.
DI2...DI5: Defined by the user.
DI/DO Digital Input/Output

DO1...DO5 digital outputs: Relay output, normally-open contact


Max admissible power: 250VAC, 3A; 30VDC, 3A
Example: write “1” into DO5 of Modbus protocol and the two
contacts of DO5 relay will be closed; write “0” into DO5 of Modbus
protocol and the two contacts of DO5 relay will be cut off.
LED Display

LED indicators shown in the above figure are divided


into two parts: status indicators (operation, alarm,
power) and communication indicators(CAN, RS485,
RS232).
LED Display

Operation status of each indicator is shown in the following table.

When the data from the equipment (e.g. air conditioner)


CAN RX connected with Modbus Gateway(Pro) is received, it will
flash.

When the data is transferred to the equipment (e.g. air


CAN TX conditioner) connected with Modbus Gateway(Pro), it will
flash.

When the data from the Modbus bus is received, it will


RS485-1 RX
flash.

When the data is transferred to the Modbus bus, it will


RS485-1 TX
flash.

RS232 RX This device does not use this LED indicator.


RS232 TX This device does not use this LED indicator.
RS485-2 RX This device does not use this LED indicator.
RS485-2 TX This device does not use this LED indicator.

When power supply of Modbus Gateway(Pro) is normal, it


Power
will be always on..

Run When Modbus Gateway(Pro) works normally, it will blink.

Alarm This device doesn’t use this LED indicator.


DIP Switches

This gateway includes two kinds of DIP switches,


address DIP switch and function DIP switch.
DIP Switches

Function DIP Switch


The seventh switch of function DIP switch is used for setting the Modbus bus
matched resistance of this gateway.
The eighth switch of function DIP switch is used for setting the CAN2 bus
matched resistance of this gateway.

Address DIP Switch


Address DIP switch is used for setting the device address of Modbus
Gateway(Pro).
Address setting range: 1~255.
DIP Switches

CAN2 bus

Master Master Master


control unit control unit control unit Set as with
of ODU of ODU of ODU
system 1 system 2 system n matched
resistance
Set as Set as
Set as with
without without
matched
matched matched
resistance
resistance resistance
DIP Switches

CAN2 bus

Master Master Master


control unit control unit Set as control unit
of ODU of ODU of ODU
system 1 system 2
without system n
matched
Set as Set as with
Set as with resistance
without matched
matched
matched resistance
resistance
resistance
Installation

Product Dimension

Installation Space of Electric Control Cabinet

Material Selection of Communication Cable

Communication Connection Way

Setting of Communication Connection


Product Dimension

L × W × H:296×177×56(mm)
Installation Space of Electric Control Cabinet

Modbus Gateway(Pro) shall be installed in the electric


control cabinet. The front side of gateway shall be hung
upwards and secured by four screws. Required
installation space is shown as below (only for reference).

50mm
98.5mm
Secure
it by four
screws

296mm
Wire groove

Wire groove
120mm 120mm 120mm 120mm 120mm 120mm

With the front side


177mm hung upwards Electric control
cabinet
Material Selection of Communication Cable

Comm
unicati Cable
Communica Material of Material
on diameter Remark
tion system cable standard
cable (mm2)
L(m)
When
Light/Ordi
communicati
Modbus Ga nary PVC
on distance
Communica sheathed
exceeds
tion twisted
IEC60227- 800m,
between pair L≤800 ≥2×0.75
5:2007 photoelectri
Modbus copper
c isolation
Gateway(Pr wire(60227
repeater
o) and BMS IEC52/6022
shall be
7 IEC53)
added

Light/Ordi
Communica nary PVC The length
tion sheathed of
between twisted communicati
IEC60227-
Modbus pair L≤500 ≥2×0.75 on cable
5:2007
Gateway(Pr copper shall not
o) and air wire(60227 exceed
conditioner IEC52/6022 500m
7 IEC53)
Communication Connection Way

Notice! All communication cables of Modbus


Gateway(Pro) must be connected in series instead
of in star mode.
Communication Connection Way

BMS system

BMS system
Communication Connection Way

……

ODU system 1 ODU system 2 ODU system n


Module 1 Module 1 Module 1
(master ODU) (master ODU) (master ODU)

ODU system 3
Module 1
(master ODU)

……

ODU system 1 ODU system 2 ODU system n


Module 1 Module 1 Module 1
(master ODU) (master ODU) (master ODU)

……

ODU system 1 ODU system 2 ODU system n


Module 1 Module 1 Module 1
(master ODU) (master ODU) (master ODU)
Communication Connection Way

ON ON

1 2
BMS
SA8


Slave
ODU
… Master
ODU
① ①
ON ON

1 2 Modbus Gateway(Pro) 1
SA8

Slave
… Master
① ①
ODU ODU

Modbus Gateway(Pro) 2


Q&A

• Q: Modbus Gateway(Pro) is applicable for what kinds


of unit?
• A: Gree Modbus Gateway(Pro) is applicable for all
Gree multi VRFs which adopt CAN protocol.

• Q: Modbus Gateway(Pro) supports how many


systems in maximum?
• A: Each BMS network can be connected with 16
Modbus Gateways(Pro). Each Modbus Gateway(Pro)
can be connected with 16 systems and 255 indoor
unit.
ALWAYS BETTER CAC SOLUTION FROM GREE