• Background
• Function Introduction of Gateway
• Detailed Introduction of Gateway
• Product Installation
Background
• Topology
Why you shall choose Modbus Gateway(Pro)
Why you shall choose Modbus Gateway(Pro)
• Appearance
• Function advantage
Appearance
Function advantage
Each gateway supports group inquiry and group control of all indoor
units
On/Off
Mode
Fan speed
Temperature
Remote locking
Topology
BMS system
Master
Modbus IDU IDU
gateway 1
ODU Slave ODU Slave ODU L3
...
L1
Master
ODU Slave ODU IDU IDU
CAN 2 network
L1 L3
CAN 1 bus
...
Ethernet interface
DO digital output
Power input
Power Supply
DI1...DI5
Digital inputs: 0/1 digital signals(binary system), applicable for those with
power supply
DI1: in CAN2 network, fire alarm signal, connect “1” to the power of 12V,
input fire alarm signal “1” in DI 1 port, then Modbus gateway(Pro) will give out
control, all units stop operation immediately;disconnect “1” or connect to “0”,
input signal “0” in DI 1 port,resume operation of all ODUs.
In CAN1 network, fire alarm signal, connect “1” to the power of 12V, input
fire alarm signal “1” in DI 1 port, then Modbus gateway(Pro) will give out
control, all units stop operation immediately;disconnect “1” or connect to “0”,
input signal “0” in DI 1 port,resume operation of IDUs manually.
DI2...DI5: Defined by the user.
DI/DO Digital Input/Output
CAN2 bus
CAN2 bus
Product Dimension
L × W × H:296×177×56(mm)
Installation Space of Electric Control Cabinet
50mm
98.5mm
Secure
it by four
screws
296mm
Wire groove
Wire groove
120mm 120mm 120mm 120mm 120mm 120mm
Comm
unicati Cable
Communica Material of Material
on diameter Remark
tion system cable standard
cable (mm2)
L(m)
When
Light/Ordi
communicati
Modbus Ga nary PVC
on distance
Communica sheathed
exceeds
tion twisted
IEC60227- 800m,
between pair L≤800 ≥2×0.75
5:2007 photoelectri
Modbus copper
c isolation
Gateway(Pr wire(60227
repeater
o) and BMS IEC52/6022
shall be
7 IEC53)
added
Light/Ordi
Communica nary PVC The length
tion sheathed of
between twisted communicati
IEC60227-
Modbus pair L≤500 ≥2×0.75 on cable
5:2007
Gateway(Pr copper shall not
o) and air wire(60227 exceed
conditioner IEC52/6022 500m
7 IEC53)
Communication Connection Way
BMS system
BMS system
Communication Connection Way
……
ODU system 3
Module 1
(master ODU)
……
……
ON ON
1 2
BMS
SA8
①
Slave
ODU
… Master
ODU
① ①
ON ON
1 2 Modbus Gateway(Pro) 1
SA8
Slave
… Master
① ①
ODU ODU
Modbus Gateway(Pro) 2
①
Q&A