Вы находитесь на странице: 1из 2

Checked By:_____________

SUEZ
Drawing Checklist Date:_____________

Project Name:______________________________________________________

Drawing Scale and orientation


Yes No N/A
Drawing Scale 1"=100'
(1"=50' will be accepted in certain instances but will be handled on a case by case basis)
Drawing oriented so north is to the top of the page and north arrow present

Title Block
Yes No N/A
SUEZ title block
Correct title Block size
Correct Notes
Correct symbols and size
Title block filled out correctly
Map number assigned
Reference number assigned

Drawing
Yes No N/A
Mains
Appropriate line weight (bold water line, existing and other utilities faded back or thin line)
Water main in correct location ( ACHD assigned corridor - N & E side of road, not under curb & gutter)
Does a main front or new main need to front the property?
Air vac installed at the high points if applicable
Joint restraint listed when applicable
Call out all instances where a main lowering or water class pipe by other utilities may be required
Show angle in pipe but do not call out (no pipe deflection around corners)
Pipe footages rounded to nearest five feet
Show enough existing facilities to complete work (shut downs and tie-ins)
Ductile Iron (DI) pipe required in foothills and pipe larger than 12-inch
Does project require a PRV or Special Facilities
If yes, a Preliminary Engineering Report (PER) and DEQ review will be required
Call out connection points
Label existing main with CEA number, material type and diameter
Crossing detail provided when necessary

Services
Common services on north and east of lot line
Alternating lot line used whenever possible
Irrigation services labeled (all irrigation services to be single 1-inch or larger)
Call out fire service size (in notes or as call-out on drawing)
On commercial and multifamily developments, call out domestic service size (in notes or as call-out on drawing)
(For combination services or services larger than 2-inch, a building flow will be required)

Lots
Lot and Block numbers clearly visible
Pad elevations for each lot
Lot square footage for each lot
Lots larger than 12,000 have single service
Lot and Block present for all lots requiring a service
Building numbers present (Commercial developments)
Drawing cont.
Yes No N/A
Regulatory Requirements
Pressurized Irrigation system on drawing and Irrigation district indicated
"NO PI" on drawing if no alternate irrigation system present
DEQ separation requirements marked where appropriate
(10' min. and 25' min. callouts from not potable and sub serface drainage, 20' min. from buildings)

System Operation
Confirm valve locations for optimal operation
Main size meets requested fire flow demand

Miscellaneous
Easement required?
If yes, indicate 30' wide SUEZ easement on drawing or include the easement on the subdivision plat
and provide plat for review by SUEZ
Existing street names on drawing
Proposed street names on drawing
Can easily determine project location (Vicinity Map required/present and legible?)
Engineering firm name and contact information (name, address, phone number and contact name)
Developer name and contact information (name, address, phone number and contact name)
Phased Plan?
If yes, request full build out to determine overall line size and layout
Drawing on acceptable sheet size
8 1/2"x11", 11"x17", 18"x24", 24"x36"
Show curb line and sidewalk on commercial projects
Offsites required?

Comments: