EPM 6000

POWER METER

High Accuracy Power and


Energy Measurement
KEY BENEFITS

Digital Metering
• High accuracy multifunction power meter • Large 3 line .56” bright LED display for better visibility and
• Superior performance at competitive pricing longer life
• Ultra compact, easy to install, program and use • User programmable for different system voltages and
current measurements
• 0.2% class revenue certifiable energy and demand metering
• Standard Modbus and DNP communications
• Total harmonic distortion (%THD)
• Optional Ethernet port for simplified integration into onto new
• Fits both ANSI and DIN cutout or existing LAN infrastructures and multi-point connectivity.

APPLICATIONS
• Continuous metering of electrical loads such as generator • Low and medium voltage applications
panels, feeders, switchgear etc. • Replaces multiple analog meters saving space and
• Provides remote status when used with EnerVista suite of installation costs
software

FEATURES
FEATURES
Monitoring and Metering Communications
• True RMS multifunction measurements including voltage, • RS485 Modbus and DNP 3.0 Protocol up to 57.6K Baud
current, power, freq., energy, etc. (Serial Option)
• Meets ANSI C12.20 (0.2%) and IEC 687 (0.2%) accuracy • Modbus TCP Protocol through 10/100BaseTX via RJ45
classes (Ethernet Option)
• Future field upgradeable for added functionality without • 3 Line .56” Bright Red LED Display
removing installed meter • Front IrDA Port laptop communication
• Load percentage graphical bar for instant load visualization • Pulse output for accuracy testing and energy

g Digital Energy
Multilin
589
EPM 6000 Power Meter

Features Current Input Connections


EPM 6000 is one of the industry’s highest Method One Method Two
performance revenue grade panel meters.
Based on the latest technology and an Nickel Plated Brass
all-new platform, EPM 6000 has a superior Current “Gill”
cost to performance ratio and significantly
outperforms other metering products
many times its price.

Revenue Grade Certifiable with


built-in Accuracy Verification
EPM 6000 is a traceable revenue class
meter. It contains a utility grade test pulse
allowing power providers to verify and Inherently
CT wires CT wires terminate
confirm that the meter is performing to its Safe Design
pass through meter to meter
rated accuracy. To be certified for revenue (dia. 0.77” / 4.5mm)
metering, power providers and utility
companies need to know that the billing over the user selectable averaging period. Through a built-in infra-red (IrDA)
energy meter will perform to the stated Voltage provides an instantaneous max port , the meter can be programmed
accuracy. This features allows instant and min reading displaying the highest through a lap top computer without a
verification of accuracy by third parties as surge and lowest sag seen by the meter. physical wire connection to the meter,
Digital Metering

well as utilities for billing purposes. making programming or data download


Universal Voltage and Current
The EPM 6000 excels in metering energy convenient and safe. Using standard high
Inputs
accurately exceeding ANSI C12.20 (0.2%) speed Modbus communications, the meter
and IEC 687 (0.2%) energy measurement The meter allows voltage inputs
can also provide data to RTUs, PLCs and
standards. The unit utilizes high speed measurements up to 416 Volts Line to
other control devices. When used with the
DSP technology with high resolution A/D Neutral and 721 Volts Line to Line. This
EnerVista suite of software, the meter can
conversion to provide revenue certifiable insures proper meter safety when wiring
be remotely monitored.
accuracy for utility billing, substation directly to high voltage systems. The unit
metering, sub-metering and critical will perform to specification on 69 Volt,
metering applications. 120 Volt, 230 Volt, 277 Volt and 347 Volt Unique Current Input Connections
power systems. The EPM 6000 provides two independent
Measured Values communication ports with advanced
Unique Current Input Connections
Standard EPM 6000 measures the features.
EPM 6000 meter uses a two current input
following values:
wiring methods.
Measured Real Avg Max Min
• IrDA port – Uniquely the unit has an
Values -Time optical IrDA port allowing the unit
• Method One - CT pass through. Directly
Voltage L-N n n n to be set up and programmed using
Voltage L-L n n n pass the CT through the meter without
Current Per Phase n n n n a remote laptop without needing a
Watts n n n any physical termination on the meter.
n
communication cable. Just point at
VAr n n n n
This insures that the meter cannot be a
VA n n n n the meter with an IrDA equipped PC
PF n n n n point of failure on the CT circuit. This is
+Watt-hr n computer and configure it.
-Watt hr n preferable to utility users when sharing
Watt-hr net n
relay class CTs. No Burden is added to
+VAr-hr n The second port is factory selectable to
-VAr-hr n the secondary CT circuit.
VAr-hr net n be either a RS485 port or an Ethernet
VA-hr n • Method Two - Current “Gills.” The meter port with features as follows:
Frequency n n n
Voltage Angles n additionally provides ultra-rugged
Current Angles n
termination pass through bars allowing
%THD n n n
• RS485 Port – This port provides RS485
% of Load Bar n the CT leads to be terminated on the
meter. This also eliminates any possible communication using Modbus ASCII or
Utility Peak Demand point of failure at the meter. This Modbus RTU or DNP 3.0 protocol. Baud
method is also a preferred technique rates are from 9600 to 57.6 kbaud
The EPM 6000 provides user configurable
fixed window or rolling window demand. for ensuring relay class CT integrity
KW, kVAR, kVA and PF are calculated does not get compromised. No terminal • Ethernet Port – This port provides
using utility demand structures. All other blocks are required and this stud based connectivity via a 10/100BaseT RJ45
parameters offer min and max capability design ensures that CTs will not open connection. Modbus TCP protocol is
under a fault condition. supported

590 www.GEDigitalEnergy.com
EPM 6000 Power Meter

Simultaneous Dual Communications Paths

Wireless Communication

Direct PC Interface
Serial or Ethernet
Options Available

Modbus Master
Serial RS485 Host

Master Host
or
Ethernet
Multiple Masters
TCP/IP

Solid Construction with Mounting Future Upgrade Packs Additionally, using the PC, a technician
Versatility The EPM 6000 is equipped with a virtual or electrician can see a visual phasor
firmware based switch that allows feature diagram of the vectors ensuring that the
The EPM 6000 has a rugged design for
CT and voltage polarities are correct. All
harsh environment . This is especially upgrades through communications

Digital Metering
wiring inputs are color coded with clear
important in power generation, utility even after installation. This allows you to
labeling to avoid cross wiring mistakes
substation, and critical user applications. optimize your metering investment. Begin by installers. The meter has built in
The structural and electrical design of with a standard meter and upgrade it programmable auto scroll features to
this meter was developed based on the to more functionality as new features display multiple values without having to
recommendations and approvals of many are added, such as %THD Monitoring for press keys.
of our utility customers. identifying power quality problems and
EPM 6000 can easily be mounted in a limit exceeded alarms for notification of out
panel for generator monitoring, substation of limit conditions. EnerVistaTM Software
automation and more. The unique dual
Simple Installation and EnerVistaTM Launchpad
design combines ANSI and DIN mounting
Programming
structure and allows easy installation for EnerVista TM Launchpad is a powerful
EPM 6000 is intuitive so that a new user
both new metering applications and retrofit software package that provides users
can easily program and set-up the meter.
of existing analog meters. a platform to access all of the setup and
The unit can be programmed using a PC
The unit mounts directly in an ANSI C39.1 or through a simple keypad interface. support tools needed for configuring
(4” Round form) or an IEC 92 mm DIN and maintaining GE Multilin Products.
square form.

EnerVista Viewpoint Monitoring Data Recording and Real-Time Status

Create graphical trending reports of usage overtime Real-time metering values and phasors to verify device connection

www.GEDigitalEnergy.com 591
EPM 6000 Power Meter

Launchpad allows configuration of devices Viewpoint Monitoring • Automatic Event Retrieval


in real-time by communicating using RS232, Viewpoint Monitoring is a simple-to-use, • Automatic Waveform Retrieval
RS485, Ethernet, or modem connections. full-featured monitoring and data recording
Using Launchpad as the single interface software package for small systems. EnerVistaTM Integrator
to the setup and analysis software makes Viewpoint Monitoring provides a complete EnerVistaTM Integrator is a toolkit that
it simple to enter setpoints, read metered HMI package that instantly puts critical allows seamless integration of GE Multilin
values, monitor status and evaluate power real-time device data on your PC through devices into new or existing automation
quality. pre-configured graphical screens with the systems by sending GE device data to
Included in Launchpad is a document following functionality. HMI, DCS, and SCADA systems. Included in
archiving and management system EnerVistaTM Integrator is:
that ensures critical documentation is
• Plug-&-Play Device Monitoring • OPC/DDE Server
up-to-date and available when needed
by automatically checking for and • System Single-Line Monitoring & Control • GE Multilin Drivers
downloading new versions of manuals, • Annunciator Alarm Screens • Automatic Event Retrieval
applications nates, specifications, and • Trending Reports • Automatic Waveform Retrieval
service bulletins.

EnerVista Viewpoint Monitoring Data Recording and Real-Time Status


Digital Metering

Create tabular trending reports


of usage data

Historical minimum and maximum


values to understand fluctuations on
the network

Real-time power values to instantly analyze system capacity

592 www.GEDigitalEnergy.com
EPM 6000 Power Meter

RS485 COM Port and Pulse Counter

To M
aste
r de
vice

To o
ther
Slav
e de
vice

EPM6000 with RS485 Comm Port EPM6000 THD Option with RS485 and KYZ pulse output

Dimensions and Mounting

Digital Metering
User Interface
Large .56” LEDs
Only 3.25”
Reading Type
Designator Tx Rx Indicator LEDs

Screen
Selectors

RS 485
IRDA Communication
Port

Vh Pulse

% Load
Bar

Universal
Voltage Inputs

Auto Scale Indicator Current


“Gills”

www.GEDigitalEnergy.com 593
EPM 6000 Power Meter

Technical Specifications
VOLTAGE INPUTS POWER SUPPLY PULSE OUTPUT
Universal Voltage Input • Universal AC/DC Supply • Front panel Wh infared test pulse
• 0-416 Volts Line To Neutral, - 90 to 265 Volts AC and • Back panel Wh pulse output
0-721 Volts Line to Line - 100 to 370 Volts DC.
• Input withstand capability – Meets IEEE C37.90.1 • Optional 24 to 48 Volts DC Supply. DIMENSIONS & SHIPPING
(surge withstand Capability) Burden: 10VA max.
• Programmable voltage range to any PT ratio • Weight: 2 lbs
COMMUNICATIONS • Basic Unit: H4.85 x W4.82 x L4.25
• Supports: 3 element WYE, 2.5 element WYE,
2 Element Delta, 4 Wire Delta Systems • 2 Com Ports: IrDA and either RS485 or Ethernet • Mounts in 92mm DIN and ANSI C39.1 Round Cut-outs
• Burden: 0.36VA per phase max at 600V, 0.014VA • IrDA (Through Faceplate) • Shipping Container Dimensions:
at 120 Volts - Protocol Modbus ASCII 6” cube
• Input wire gauge max (AWG 12 / 2.5mm2 ) - Com Port Baud Rate: 56.7k
- Address: 1
• RS485 Output (Back Plate) ENVIRONMENTAL
CURRENT INPUTS - Protocol Modbus RTU, Modbus ASCII or DNP 3.0 Storage: -40° C to +85° C
- Com Port Baud Rate: 9600 to 57.6K Operating: -30° C to +70° C
• Class 10: 0 to 11 Amps Secondary / 5 Amps Nominal Humidity: to 95% RH Non-Condensing
/ 10Amps Max - Com Port Address: 0-247
- 8 Bit, No Parity Faceplate Rating: NEMA 12 (Water Resistant) Mounting
• Class 2: 0 to 2 Amps Secondary / 1 Amp Nominal Gasket Included
/ 2 Amps max • Ethernet (Back Panel)
• Fault Current Withstand: - 10/100BaseT via RJ45 connector
100 Amps for 10 Seconds - Protocol Modbus TCP COMPLIANCE
300 Amps for 3 Seconds • IEC 687 (0.2% Accuracy)
500 Amps for 1 Second. METERING ACCURACY
• ANSI C12.20 (0.2% Accuracy)
• Programmable Current to Any CT Ratio • ANSI (IEEE) C37.90.1 Surge Withstand
• Burden 0.005VA per phase Max at 11Amps Measured Accuracy%
Parameters of Reading Display Range • ANSI C62.41 (Burst)
• 5mA Pickup Current • IEC1000-4-2 – ESD
• Frequency 50 Hz or 60 Hz+/- 3Hz above and below • IEC1000-4-3 – Radiated Immunity
nominal range Voltage L-N 0.1% 0-9999 Scalable V or kV
Voltage L-L 0.1% 0-9999 V or kV Scalable • IEC 1000-4-4 – Fast Transient
• Pass through wire gauge dimension: 0.177” / 4.5mm • IEC 1000-4-5 – Surge Immunity
Current 0.1% 0-9999 Amps or kAmps
ISOLATION +/- Watts 0.2% 0-9999 Watts, kWatts,
MWatts APPROVALS
• All Inputs and Outputs are galvanically isolated to
2500 Volts AC. +/-Wh 0.2% 5 to 8 Digits ISO: Manufactured to an ISO9001 registered program
Programmable UL/cUL: Listed under E250818
+/-VARs 0.2% 0-9999 VARs, kVARs, CE: Conforms to European CE standards
SENSING METHOD MVARs
+/-VARh 0.2% 5 to 8 Digits
• True RMS Programmable
Digital Metering

• Sampling at 400+ Samples per Cycle on all channels VA 0.2% 0-9999 VA, kVA, MVA
measured readings simultaneously VAh 0.2% 5 to 8 Digits
• Harmonic % THD (% of total harmonic distoration) Programmable
PF 0.2% +/- 0.5 to 1.0
UPDATE RATE Frequency 0.01 Hz 45 to 65 Hz
%THD 5% 0-200%
• Watts, VAr and VA-100msec %Load Bar 1-120% 10 Digit Resolution
• All other parameters-1second Scalable

Ordering
PL 6000 * * * * * Description
Standard unit with display, all current/voltage/power/frequency/energy counters measurement,
% load bar, RS 485 and IRDA communication ports and one front test pulse output.

Hz 5 50 Hz AC frequency system
6 60 Hz AC frequency system
Amps 5A 5 Amps
1A 1 Amp
Pulse 0 No THD option
THD THD, limit alarms & one pulse Output
Power Supply LDC 24 to 48 V DC power supply to substitute standard AC/DC power supply
Communications S RS485 Communications Port (Modbus and DNP)
E Ethernet 10/100BaseT via RJ45 (Modbus TCP)

Example - EPM 6000 for 60Hz system with 1 Amp secondary current with THD, Limit Alarms & one additional pulse output. PL600061ATHD

Visit www.GEMultilin.com/EPM6000 to:


  •  View Guideform Specifications
  •  Download the instruction manual
  •  Review applications notes and support documents
  •  Buy a EPM 6000 online