Transformer Protection Relay

TR-7570
(FOR RESIN CAST / DRY TYPE TRANSFORMERS)

Transformer Protection Relay TR-7570

Channel Temperature

Set

Max.
C secs.
Press RESET for more than 3 s
to RESET Max. Temp

Func. Set
Fault High V. High Fan Esc. Reset

Auto Max.
R
Manual Enter
PECON Power Electronics & Control,
electronics Ahmedabad-382 330..

RTD 1 RTD 2 RTD 3 RTD 4 Fault High Very High Fan Remote Aux. Supply
o/p.

230V
110V
~
~
-
N
+

Transformer Protection Relay TR-7570


R

PECON
electronics

Power Electronics & Control


Ahmedabad : 382 330 Max. Temp. Reset

Standard Features:
* Single scanner unit for three windings and fan Control.
* Four output relays for Alarm (High), Trip (V.High), Fan on/off (Fan) &
to warn against sensor open or wrong sensor connection (Fault).
* Bright digital display offers accurate and unambiguous reading.
* Better vibration withstanding capability.
* µC and solid state design offers high reliability.
* IP-52 Enclosure
* Memorizes max. temperature.
* Low power requirement.
* Extremely high noise immunity.
Doc no. : 0 7 0 5 1 1 0 1

The model TR-7570 is designed for safe operation of medium voltage cast resin / dry type transformer. It
is suitable for control room as well as marshalling box installation and is built for long and trouble-free
operation under extreme conditions of service associated with transformer.
Three numbers of user settable set-points can be used to control the cooling fan, to warn the user of high
temperature and to shut down the transformer in case of excessive heating. Four numbers of Pt-100 RTD
sensors allows the user to monitor the temperature of all the three phase windings plus one other critical
point on the transformer like core. Alternatively, it can be used to check the ambient temperature or can
be left for use as spare.

Power Electronics & Control


R
145/2, G.I.D.C. Estate, Naroda, Ahmedabad - 382 330 INDIA
Tel: + 91 (79) 2281 3432, 2281 7892 Fax: +91 (79) 2282 1397
email: pecon@vsnl.com W e b s i t e : www. p e c o n - i n d i a . c o m
TR-7570 is programmed to note and store maximum temperature of the winding. Facility extends to recall
this information and to clear it for fresh recording. The maximum Temperature is saved such that it can
be recalled even after the power for the unit fails. It also has a facility to keep displaying only the
maximum temperature of all the channels thereby facilitating easy supervision.
Technical Specifications
Inputs : 4 RTDs (Pt-100, IEC 751)
No. of Set-points : Three (High, V.High & Cooling Fan On.)
Temperature indication range: - 50 OC to 300 OC
Set point range : 0 to 299 OC
Accuracy : ± 1 OC
Dead Band (relay differential) : User settable (range: 1 - 25 OC)
Display Speed : User Settable (range 1 - 60 secs)
Display : 3 Seven Segment 1/2" red LEDs for displaying temperature
1 Seven segment 1/2" red LED for displaying channel no.
Mechanical
Overall Dimensions : 215 (H) x 265 (W) x 130 (D) mm
Mounting : Wall mounting by 3 nos. M6 Screws
Weight : 3.5 kg approx. (unpacked)
Enclosure : M.S. Sheet Box. with acrylic viewing window
Electrical
Supply Voltage : 90-270 VAC/DC OR 20-50 VAC/DC
Outputs : Four (1 C/O) Relays & 1 analog output (4 - 20 mA for 0 – 300 OC,
Linearity ± 0.5%, Max. resistance load 300 ohms).
Contact Racting : for res. load 5A/250VAC, 250W at 125VDC
for L/R = 7 msecs, 5A/250V AC, 125W at 125VDC
Relay operations : Fault : When power is applied to TR-7570, this relay energizes.
The relay will de-energize if any of the rtd is open or short
or if any of the rtd is out of temperature indication range.
High : To energize if any one Channel has crossed High set point
V.High : To energize if any one Channel has crossed V.High set point
Fan : To energize to start the cooling fan.
Terminals : Screwed Caged suitable for 0.2 - 4 sq. mm solid conductors.
Insulation : Insulation resistance shall be 100 Mohm or more when 500VDC
is applied between each terminal in turn and enclosure.
Controller will withstand 2 KV rms at 50 Hz. for 1 min., applied
between all relay & supply terminals shorted together and enclosure.
Power consumption : Max. 10VA
Operating conditions : Ambient Temp. : -20 OC to 50 OC.
R.H. : 95% Max non-condensing.
Storage Temp. : -20 OC to 85 OC.
Test conditions : 60% ±20% R.H., Amb. Temp. 27 ±5 oC.