designing and installation. Also, if you are looking finding the the exact
status of your electrical installation, then you can get the Electrical
Installation Condition Report quote from the Energy North Ltd.
For single-phase:
In other words, the fuse rating is equal to 1.25 times the full load
current.
For Three-phase:
For continuous operation, the fuse rating is less than the 125% is not
recommended since all the motor is designed to run 120% of the full
load rating. The under-capacity may lead to repeated tripping or
interruption of the operation.
Learn More: Cable Gland Size Chart & Double Compression Cable Gland Chart
We cannot size exact resultant rating of the fuse from the above
formula. Instead, we can choose nearest available standard fuse size.
They are 1, 2, 3, 4, 6, 10, 16, 32, 40, 63, 125, 150, 160, 200, 250,
315, 355, 450, 500, 560, 630, 710, 800, 1000, 1250, 1600, 2000,
2500, 3200, 4000, 5000, and 6000 amperes.
Also, note that the fuse size can be designed at any Amps rating
which is depending on the manufacturer. i.e if you need 900A rated
fuse means, they can design.
Let we calculate the fuse sizing for 5.5kW 415V three-phase induction
motor is planned to run at 0.86 power factor.
Here the standard IEC recommended fuse chart has been included.
But you can change the rated as per your load demand.
kW A A
0.25 0.8 4
0.37 1.1 4
0.55 1.5 6
0.75 2 6
1.1 30 10
1.5 3.6 16
2.2 5 16
3 6.5 20
4 8.4 20
5.5 11 25
7.5 15 40
11 20 50
15 27 63
18.5 33 80
22 38 80
30 54 100
37 66 125
45 79 160
55 98 160
75 135 250
90 155 250
For the transformer, the fuse rating is equal to the two times of the full
load current.
or in other words.,
Learn More: L&T Starter Types, Price List 2020 For Three phase motors
For single-phase:
Transformer fuse rating = 2000 x S(kVA) / V(V)
Example:
For the lighting circuit, the fuse current rating should be minimum 2
times the full load current of the total number of lighting.
For individual circuit, the fuse rating should be 1.5 times of the full
load current.
For example, let we calculate fuse rating for a 230 V, 0.8 pf light panel
and individual circuits and which contains 10 number of 400A mercury
vapour lighting.
Hence the fuse standard rating for the panel should be 40A.
Full load current for 400W lamp = 400 / (230 x 0.8) = 2.1
Hence the fuse standard rating for the individual lamp should be 4A.
For the capacitor circuit, the fuse rating is equal to 1.5 times of the full
load reactive current by considering staring inrush current, circuit
harmonics and capacitor tolerances. The formula will be
Or
0.5 HP Motor Price, Cable Size Chart, Contactor & Relay Size Chart
What is EFF1, EFF2, EFF3, IE1, IE2, IE3, IE4, IE5 Motor Efficiency Class
LEAVE A REPLY
Save my name, email, and website in this browser for the next time I comment.
Post Comment
Recent Posts
Alternator
app
Basic Relay
Calculator
Computer
Contactor
Definition
Difference
Electrical
Electrical Basic
Electrical Definition
Electrical License
Electronics
Energy calculation
Faults