SIEMENS TEST CERTIFICATE

Generated
Generated automatically,
automatically
valid without
valid without
and therefore
signature
signature

MLFB code : 7SR1587-5HA87-1CA0/CC date of test: 19.12.2019 08:53:19


serial no.: BF1912501686 test equip. : UPS-07 / 2.0.5.1937
firmware : 2436H80011R4e-2a tested by : 1016
order no. : 38525033/20 page no. : 1 / 2

Shorting contacts test


Test result: PASS

Program USB identifier


Test result: PASS

Auxiliary voltage / Hilfsspannung


| setpoint |meas. value| unit | deviation| phase | remarks / communication | stat.|

| 110.000 | 110.000 | V | -- | | permissible aux. voltage | PASS |


| 68.000 | 60.218 | mA | -- | | dc current | PASS |
| 7.500 | 6.614 | W | -- | | power consumption | PASS |

Test result: PASS

HWT internal DC voltages / interne Versorgungsspannungen


Supply count= 3
Supply test: OK
Test result: PASS

HWT LED - Display


Max. Relay count= 8
present HWT Build Date: 11:53:52 Oct 19 2016
Configuration info written to device OK
LED test: OK
Display test: OK
Set Clock Date: 19/12/2019 08:54:54
Device clock: Date=19.12.2019 Time=08:54:56
Test result: PASS

HWT keyboard test / Folien-Tastatur


Test result: PASS

MLFB-Compare / MLFB-Vergleich
DEV-MLFBNr=7SR1587-5HA87-1CA0
Test result: PASS

Test of Communication Interfaces / Schnittstellen


Location Rear of PSU: System-Interface = RS485-Half Duplex : OK
Location LHS Enclosure Extension: System EN100 = V04.37.01
Location LHS Enclosure Extension: System EN100-Interface = EN100 Ch1 : OK
Location LHS Enclosure Extension: System EN100 = BF1910054192 - MAC:B4B15A0AE5BE
Location LHS Enclosure Extension: System EN100-Interface = EN100 Ch2 : OK
Test result: PASS

HWT binary inputs / Binär-Eingänge


Max. Bin-Input count= 6
Test result: PASS

HWT relay outputs / Relais-Ausgänge


Max. Relay count= 8
Test result: PASS

Calibration of the analog Channels


| Remark | Ch.1 | Ch.2 | Ch.3 | Stat.|

|Dead Band | 2| 4| 4| PASS |


|DC Off HI | -2| -1| -1| PASS |
|DC Off Lo | -2| -2| -1| PASS |
|Hi Gain Ma| 71709| 71310| 71609| PASS |
|Lo Gain Ma| 71709| 71310| 71609| PASS |
|Phase | 0| 19| 76| PASS |

Test result: PASS


SIEMENS TEST CERTIFICATE
Generated
Generated automatically,
automatically
valid without
valid without
and therefore
signature
signature

MLFB code : 7SR1587-5HA87-1CA0/CC date of test: 19.12.2019 08:53:19


serial no.: BF1912501686 test equip. : UPS-07 / 2.0.5.1937
firmware : 2436H80011R4e-2a tested by : 1016
order no. : 38525033/20 page no. : 2 / 2

Voltage analog inputs / Spannung analoge Eingänge


| setpoint |meas. value| unit | deviation| phase | remarks / communication | stat.|

| 60.000 | 60.050 | V | 0.08 % | UL1 | 50Hz: A. R21-22 | PASS |


| 60.000 | 60.023 | V | 0.04 % | UL2 | 50Hz: A. R23-24 | PASS |
| 60.000 | 60.030 | V | 0.05 % | UL3 | 50Hz: A. R25-26 | PASS |
| 30.000 | 30.003 | V | 0.01 % | UL1 | 50Hz: A. R21-22 | PASS |
| 30.000 | 30.027 | V | 0.09 % | UL2 | 50Hz: A. R23-24 | PASS |
| 30.000 | 30.014 | V | 0.05 % | UL3 | 50Hz: A. R25-26 | PASS |

Test result: PASS

Firmware download
Firmware: 2436H80011R4e-2a-38_7SR1587-5[GHJ]A[178][27]-[12][CD]A0.exe
Test result: PASS

Undervoltage, Overvoltage / Unter-, Über-Spannungsschutz


| setpoint |meas. value| unit | deviation| phase | remarks / communication | stat.|

| 50.000 | 49.898 | V | -0.20 % | L123E | Undervoltage | PASS |


| 0.058 | 0.052 | sec | -- | L123E | Trip Time | PASS |
| 80.000 | 80.024 | V | 0.03 % | L123E | Overvoltage | PASS |
| 0.073 | 0.071 | sec | -- | L123E | Trip Time | PASS |

Test result: PASS

Send default settings


Test result: PASS